The Micolift M3P Operating Manual provides detailed information on the lift control system, including its features, control functions, and interface connections. It emphasizes the system's security, ease of use, and advanced technology for lift operation and management. The manual includes diagrams and descriptions for terminal connections, input and output units, and error handling procedures.

Uploaded by

kajoladust9387
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
5 views

null

The Micolift M3P Operating Manual provides detailed information on the lift control system, including its features, control functions, and interface connections. It emphasizes the system's security, ease of use, and advanced technology for lift operation and management. The manual includes diagrams and descriptions for terminal connections, input and output units, and error handling procedures.

Uploaded by

kajoladust9387
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 33

Operating Manual Micolift M3P

Catalog
Chapter 1 Introduction
1.1 Foreword……..…………….……………………………………….……..3
1.2 Features……………………………………………………………………3
1.3 Lift control functions………………………………………………………5

Chapter 2 Interface
2.1 Terminal connection with dual speed………………………………...…..7
2.2 Terminal connection with VVVF………………………………………..12
Drawing 1: Terminal diagram for Micolift M3P with dual speed……..…19
Drawing 2: Terminal diagram for Micolift M3P with VVVF…………….20
Drawing 3: Dimension for Micolift M3P micro controller……………….21

Chapter 3 Parameter menu for M3P debugger


3.1 Screen and the menu..….…………...…………………………………… 22
3.2 Menu description..………………………………………………..……….23
3.2.1 Main menu……………………………….………………………24
3.2.2 Config menu…………………………….……………………….24
3.2.3 Time menu……………………………….………………………29
3.2.4 Station menu…………………………….……………………….30
3.2.5 Call menu……………………………….………………………..32
3.2.6 IO menu……………………………….…………………………34
3.2.7 Door menu…………………………….…………………………36
3.2.8 Error history menu……………………….………………………37
3.2.9 Password menu………………………….……………………….37
3.2.10 Pulse monitor menu………..………………………….………….37
3.2.11 Input select………..………………………….…….…….……….40
3.2.12 Times2 menu……..………………………….…….…….……….41
3.3 Self-learning of the lift hoistway data…………………...…………….…41
3.4 Adjusting leveling precision………….………………………..…………42
3.5 Establishing the deceleration distance…….………..……………….……43

Chapter 4 Error description..………………....…………………………………….45


Chapter 1 Introduction

1.1 Foreword
MICOLIFT M3P Control Systems for Lifts is winning more and more market share
after its launch. With beyond-measure security, friendly human-computer interface, and
competitive price, MICOLIFT M3P becomes the first-choice for lift alternation and lift
reconstruction. It is the mainstream of lift technology development, and thus has been
employed by a lot of lift factories in China.
Remark: The working voltage of Micolift M3P is 24VDC. It will damage Micolift M3P
if connecting with 220VAC.

1.2 Features
MICOLIFT M3P employs parallel communication. Main processor can handle parallel
signals within 8 floors directly. Its main board adopts five-layer board-making
techniques and surface-paste technology to maximize system’s anti-interference ability.
The top and bottom board basically are overlay without wiring. Through friendly
human-computer interface, the users do not need any programming; only need to input
several parameters according to the real instance. It has the following characteristics.
1.2.1 Hoistway parameters self-learning
1.2.2 Adopting high-speed counting technology and nicety orientation technology to
maximize leveling precision.
1.2.3 Calling lifts directly from the system. All the hall call signals and car call signals
can be operated and displayed on the system.
1.2.4 Timing automatic closing-door, opening-door and closing-door protection.
1.2.5 Choosing not to answer signals from a certain floor.
1.2.6 Choosing single-door, double-door or not opening-door in a certain floor.
1.2.7 Setting floor display for BCD code, seven-segment code or GeLei code.
1.2.8 Setting base station, and fire-control returning station.
1.2.9 Displaying the pulses-number of every floor after system self-learning, and the
location of on-line car.
1.2.10 Can run with parallel connection.
1.2.11 Fifty error history records.
1.2.12 Display running curve.
1.2.13 Supporting remote monitoring or resident section monitor.

With MICOLIFT M3P, you can solve lift problems immediately, and even keep your
lifts away from errors in advance.
1.3 Lift Control Functions
Item Function Remark
1 Inspection
2 Full collect control
3 Self-security run with slow speed
4 Automatic opening-door on arrival
5 Door security protection
6 Orderly hall call press-button operation for
opening doors at the current floor
7 Press-button operation for opening and closing
doors
8 Automatic closing-door time-delay
9 Automatic set and change direction
10 Opening doors and orienting through hall call
signal
11 Car call signal record wrong and re-press to Optional function
cancel
12 Automatic cancel command while direction Optional function
reverse
13 Automatic divide speed while single / multi-floor
run (over 1.5m/s)
14 Direct run with full load
15 Arrival gong
16 Automatic cut off car light and fan while waiting
lift
17 Automatic return to base station Activated while parallel or
group control. Optional
function while single lift
18 Humanity LED operative unit
19 Communicated with upper position computer
20 Error history
21 Hoistway floor data self-learning
22 Set the sever floor
23 Set display symbol for floor
24 Driver operate
25 Flashed lights of car call to indicate
corresponding hall call signal when running with
a driver
26 Automatic answering of car call and cancel
decelerating signal
27 Orderly answering of hall call and cancel
decelerating signal
28 Independent running
29 Floor displayer of dots matrix
30 Rolling display of run direction
31 Automatic correct for floor position signal
32 Lock lift
33 Emergency return while fire Optional for not fire lift
34 Fire man operate Optional for fire lift
35 Voice report station Optional function
36 Protection of door safe touch board
37 Over-loaded alarm and protection
38 Prevent from disturb of light load Optional function
39 Protection for run with reverse direction
40 Protection of proof slip
41 Stop car by hall call answer of the farthest reverse
direction
42 Constrained speed-changing at the terminal floor
43 Automatic re-opening-door due to closing-door
error
44 Error protection of inverter
45 Main control CPU WDT protection
46 Monitor for village (or mansion) Optional function
47 Remote monitor Optional function by
modem and telephone line
48 Parallel control run Optional function
49 Group control run Optional function
50 Service for rush time while on duty Optional while group
control
51 Waiting machine dispersedly Activated while group
control
52 Display running curve Must be equipped with
tacho encoder (optional
function)
Chapter 2 Interface
2.1 Terminal connection with dual speed
Communication I/O functions please find in followed diagram 1.
Table 1 and Table 2 describe every unit’s function of Micolift M3P. The working
voltage is 24VDC.

Table 1 Input Unit Description

INPUT UNIT

Terminal Description Remark

X00 Third floor call down NO Contactor

X01 Forth floor call down NO Contactor

X02 Fifth floor call down NO Contactor

X03 Sixth floor call down NO Contactor

X04 Seventh floor call down NO Contactor

X05 First floor car call NO Contactor

X06 Second floor car call NO Contactor

X07 Third floor car call NO Contactor

X10 Forth floor car call NO Contactor

X11 Fifth floor car call NO Contactor

X12 Sixth floor car call NO Contactor

X13 Seventh floor car call NO Contactor


Input signal for close door limit
X14 position 1 NC Contactor
Fast/Slow run, Monitor input signal
X15 for Up/Down direction NO or NC Contactor(adjustable)

X16 Monitor signal for car door lock NO Contactor

X17 Monitor signal for hall door lock NO Contactor


X20 Input signal for fast run inspection NO Contactor

X21 Monitor signal input for safe circuit NO Contactor input


Input signal for inspection slow
X22 down NO Contactor

X23 Input signal for inspection slow up NO Contactor

X24 Input signal for over load NO or NC Contactor(adjustable)


Input signal for open door limit
X25 position 1 NC Contactor

X26 Brake feed back signal NC Contactor


Input signal for close door
X27 pushbutton NO Contactor

X30 Input signal for safe touch board NO or NC Contactor(adjustable)


Input signal for open door
X31 pushbutton NO Contactor

X32 Upper leveling NO Contactor

X33 Inspection / Normal input signal Inspection status while power off
X34 Input signal for fire protection
NO or NC Contactor(adjustable)
X35 Input signal for lock lift
NO Contactor
X36 Input signal for lower limit position
NC Contactor
X37 Input signal for upper limit position
NC Contactor
X40 Down deceleration
NO Contactor
X41 Up deceleration
NO Contactor
Input signal for second forced
X42
change NC Contactor
Input signal for second upper
X43
forced change NC Contactor
Input signal for open door limit
X44
position 2 NC Contactor
Input signal for close door limit
X45
position 2 NC Contactor
X46 Input signal for driver
NO Contactor
X47 Input signal for full load
NO Contactor
X50 Down leveling
NO Contactor
X51 Seventh floor call up
NO Contactor
X52 Eighth floor call down
NO Contactor
X53 Eighth floor car call
NO Contactor
X54 First floor call up
NO Contactor
X55 Second floor call up
NO Contactor
X56 Third floor call up
NO Contactor
X57 Forth floor call up
NO Contactor
X60 Fifth floor call up
NO Contactor
X61 Sixth floor call up
NO Contactor
X62 Second floor call down

VP+ Power for input signal


Close door delay signal while used
A Close door delay
with dual speed lift
B

GND (0V)Power for Input signal


24V
(24V)Power for Input signal For external power
(Left)
GND (0V)Power for Input signal
24V
(24+)Power for Input signal For work power
(Right)
Table 2 Output Unit Description

OUTPUT UNIT

Terminal Description Remark


Used for open brake while high voltage
Output for vice brake contactor through break off this signal after 3
Y00
control seconds brake signal output, and then
remain brake open under low voltage.
Y01 Brake output Drive with main brake contactor
This point will be empty while used with
Y02 Output for run contactor control
dual speed lift
Output for lock lift contactor
Y03 Drived with lock lift contactor loop
control
Y04 Output for light relay control Light and fan in the car cabinet

Y05 2# output for close door control Door operator 2

Y06 2# output for open door control Door operator 2

Y07 1# output for close door control Door operator 1

Y10 1# output for open door control Door operator 1


Output for run up contactor of
Y11
lift
Output for run down contactor
Y12
of lift
Y13 Spare use

Y14 Output for fast run contactor

Y15 Output for slow run contactor


Output for full reactance This contactor is short connected reactance
Y16
contactor while running slow.
Output for half reactance This contactor is short connected reactance
Y17
contactor while running fast.
Y20 Light for first floor call up

Y21 Light for second floor call up


Y22 Light for third floor call up

Y23 Light for forth floor call up


Light for second floor call
Y24
down
Y25 Light for third floor call down

Y26 Light for forth floor call down

Y27 Light for fifth floor call down

Y30 Light for first floor car call

Y31 Light for second floor car call

Y32 Light for third floor car call

Y33 Light for forth floor car call

Y34 Light for fifth floor car call

Y35 Output for buzzer

Y36 Light for inspection


Output for light of run up
Y37
direction
Y40 Output for light of run down

Y41 A

Y42 B

Y43 C

Y44 D

Y45 E

Y46 F

Y47 G

Y50 ----- Negative output


Output for fire protection feed
Y51
back
Y52 Output for light of over load
Output for light of close door
Y53
delay
Y54 Light for fifth floor call up

Y55 Light for sixth floor call up

Y56 Light for seventh floor call up

Y57 Light for sixth floor call down


Light for seventh floor call
Y60
down
Y61 Light for eighth floor call down

Y62 Light for sixth floor car call

Y63 Light for seventh floor car call

Y64 Light for eighth floor car call

2.2 Terminal connection with VVVF


Communication I/O functions please find in followed diagram 2.
Table 3 and Table 4 describe every unit’s function of Micolift M3P. The working
voltage is 24VDC.

Table 3 Input Unit Description

INPUT UNIT

Terminal Description Remark

X00 Third floor call down NO contactor

X01 Forth floor call down NO contactor

X02 Fifth floor call down NO contactor

X03 Sixth floor call down NO contactor


X04 Seventh floor call down NO contactor

X05 First floor car call NO contactor

X06 Second floor car call Inspection down

X07 Third floor car call Inspection up

X10 Forth floor car call NO contactor

X11 Fifth floor car call NO contactor

X12 Sixth floor car call NO contactor

X13 Seventh floor car call NO contactor


Input signal for close door limit
X14 position 1 NC contactor

X15 Input signal for running feed back NO or NC Contactor(adjustable)

X16 Monitor signal for car door lock NO contactor

X17 Monitor signal for hall door lock NO contactor

X20 Input signal for inverter monitor NO contactor

X21 Monitor signal input for safe circuit Input for NO point

X22 Input signal for inspection slow down NO contactor

X23 Input signal for inspection slow up NO contactor

X24 Input signal for over load NO or NC Contactor(adjustable)


Input signal for open door limit
X25 position 1 NC Contactor

X26 Brake feed back signal NC Contactor


Input signal for close door
X27 pushbutton NO contactor

X30 Input signal for safe touch board NO or NC Contactor(adjustable)

X31 Input signal for open door pushbutton NO contactor

X32 Input signal for leveling inductor NO contactor


X33 Inspection / Normal input signal Inspection status while power off
X34 Input signal for fire protection
NO or NC Contactor(adjustable)
X35 Input signal for lock lift
NO contactor
X36 Input signal for lower limit position
NC Contactor
X37 Input signal for upper limit position
NC Contactor
Input signal for the first down forced
X40
change NC Contactor
Input signal for the first up forced
X41
change NC Contactor
Input signal for the second down
X42
forced change NC Contactor
Input signal for the second up forced
X43
change NC Contactor
Input signal for open door limit
X44
position 2 NC Contactor
Input signal for close door limit
X45
position 2 NC Contactor
X46 Input signal for driver
NO contactor
X47 Input signal for full load
NO contactor
Used for YASKAWA or FUJI inverter,
it is empty while used with Mico
X50 Input signal for run ready
inverter. This point will be connected
when there is current on inverter.
X51 Seventh floor call up
NO contactor
X52 Eighth floor call down
NO contactor
X53 Eighth floor car call
NO contactor
X54 First floor call up
NO contactor
X55 Second floor call up
NO contactor
X56 Third floor call up
NO contactor
X57 Forth floor call up
NO contactor
X60 Fifth floor call up
NO contactor
X61 Sixth floor call up
NO contactor
X62 Second floor call down
NO contactor
VP+ Power for input signal

A Input for A phase

B Input for B phase

(0V)Power for Input signal


GND
24V
(24V)Power for Input signal For external power
(left)
GND (0V)Power for Input signal
24V
(24+)Power for Input signal For work power
(right)

Table 4 Output Unit Description

OUTPUT UNIT

Terminal Description Remark


Used for open brake while high voltage
Output for vice brake contactor through break off this signal after 3
Y00
control seconds brake signal output, and then
remain brake open under low voltage.
For brake output signal while used with
Y01 Spare use for output
YASKAWA inverter.
Output running signal while monitor lift
Y02 Output for run contactor control
signal work normally
Output for lock lift contactor
Y03 Drived with lock lift contactor loop
control
Y04 Output for light relay control Light and fan in the car cabinet

Y05 2# output for close door control Door operator 2

Y06 2# output for open door control Door operator 2


Y07 1# output for close door control Door operator 1

Y10 1# output for open door control Door operator 1


Output for run up contactor of
Y11
lift
Output for run down contactor
Y12
of lift
Y13 Output for activated signal Used for KEB inverter
Output for multi-floor speed
Y14 Speed command
signal
Output for single floor speed
Y15 Speed command
signal
Y16 Output for run in speed signal Speed command
Output for inspection speed
Y17 Speed command
signal
Y20 Light for first floor call up

Y21 Light for second floor call up

Y22 Light for third floor call up

Y23 Light for forth floor call up


Light for second floor call
Y24
down
Y25 Light for third floor call down

Y26 Light for forth floor call down

Y27 Light for fifth floor call down

Y30 Light for first floor car call

Y31 Light for second floor car call

Y32 Light for third floor car call

Y33 Light for forth floor car call

Y34 Light for fifth floor car call

Y35 Output for buzzer


Y36 Light for inspection
Output for light of run up
Y37
direction
Y40 Output for light of run down

Y41 A

Y42 B

Y43 C

Y44 D

Y45 E

Y46 F

Y47 G

Y50 ----- Negative output


Output for fire protection feed
Y51
back
Y52 Output for light of over load

Y53 Output for arrival gong

Y54 Light for fifth floor call up

Y55 Light for sixth floor call up

Y56 Light for seventh floor call up

Y57 Light for sixth floor call down


Light for seventh floor call
Y60
down
Y61 Light for eighth floor call down

Y62 Light for sixth floor car call

Y63 Light for seventh floor car call

Y64 Light for eighth floor car call


Chapter 3 Parameter menu for M3P debugger
M3P debugger is used for monitoring and adjusting the parameters. Before adjust the
parameters, you should enter password. If it is correct, you can enter adjust interface
and the debugger will close the adjust interface if no any key pressed over 15 minutes.
You must enter password again if exit the adjust interface. It will turn back to the main
interface over 20 minutes and to the homepage over 30 minutes and screen or light
behind will be closed over 40 minutes. It has Chinese/English display function and it
can be selected through wire.

3.1 Screen and the menu


M3P parameter menu debugger is used with LCD of 128X64dot and you can select
language Chinese or English through the wire of CE_SET. S1 is used to choose whether
the light behind is lighted all long. Selected “Long”, the screen and light behind will be
lighted long while selecting “Auto”, it will turn off if no any key pressed. If any key
pressed after the screen and light behind closed, it will display again within 1.5
seconds.
First, connect the wires according to the circuit diagram and power on. You can see
followed homepage:

Press enter key, enter followed main interface:

The following are the examples of the lift conditions.


AUTO, TEST, FIRE, MANUAL, FULLY, OVER, OPEN, CLOSE, LEARN, LEVELL,
LOCK.
In the main interface, press enter key to enter select mode.
Press and . to select main menu and press Esc key to exit and back to main
interface. Press ENTER to enter sub menu.

3.2 Menu Description


MICOLIFT M3P has ten main menu options altogether. Press and key to select
among them, and press ENTER to enter submenu. The operation is same as the main
menu. Under edit mode, press and to change parameters and press enter key to
save; press esc key to quit. All parameters are set according to default value of factory
but some parameters must be reset according to real conditions.

3.2.1 Main Menu:


【10】CONFIG, 【20】TIME, 【30】STATION, 【40】CALL, 【50】IO MENU, 【60】
DOOR, 【70】ERROR HISTORY, 【80】PASSWORD, 【90】PULSE MONITOR,
【A0】INPUT SELECT, 【B0】TIME MENU 2.
Description of the submenus and adjust procedures as followed:

Remark: 【 】The number in this type symbol stands for the number of main menu.
《 》The number in this type symbol stands for the number of sub-menu.

3.2.2 【10】CONFIG Menu


Under first main menu—CONFIG:

Press enter key to enter first sub-menu (Address) of CONFIG menu.

Description for sub menu:


《11》ADDRESS: range from 0 to 15, setting address of the system in the case of
parallel-control, group-controlling or remote monitoring. While two lifts parallel
connecting, set one to 1 and the other to 2. It’d better to shut off the power again
after setting address.

Press enter key to adjust the value for address and it will display “>” on the left of the
parameter.
《12》CONNECT: Choosing the OFF-LINE mode, for spare use. (adjust the
parameters same as above)

《13》SPEED: Input the lift’s rating speed. If V<1.5m/s, the system outputs a
high-speed signal; if V>=1.6m/s, the system outputs running curve depending on
single-floor or multi-floor and it runs fast by two speeds. If V>2.0m/s, it runs fast
with three speed and it can over-floor through decelerating point.

《14》FLOOR DISPLAY: set up the floor display manner. Press ENTER to enter
the submenu.

The numerical value of the absolute floor is displayed on the top right corner, such as
“1, 2, 3……64”. The number in the middle is which needed to show. If the absolute
floor is the first floor, and “-2” floor will be displayed. To adjust the display mode,
press ENTER, then amendment mouse “>” is highlighted. Press ARROW key to adjust
the value and press ENTER to save; ESC to exit.

Letter-display is also provided; if some letters are not with the system, please contact
with us.

《17》LEARNING: Set self-learning function. It will turn to automatic run status


after lift return to lower position station and enter into door zone (i.e. position
station lower forced switch off and door zone connected). It will begin to self learn
after closing door under ON mode. The self learning will finish and lift stop
automatically while lift run to upper position station when reaching door zone.
Note: The self learning is successful while the floor value increased sequential. The
floor value can be 3 maximum if connecting direction wrong for phase A-B or
without pulse input. For dual speed lift, it needn’t self-learning just only to enter
the highest floor number.

《18》MAUNAL DOOR: Under manual status, it need to press pushbutton to close


door for long if set to ON. If set to OFF, the lift will stop by hall call signal.
《19》MANUAL DIRECTION: While landing call under manual status, it cannot
stop lift while set to “ON”. If set to “OFF”, the lift can be stopped under landing
call conditions by manual status.
《1A》CONVERTER SELECT: Select frequency inverter.
《1B》DIFERFLOOR: Difference between the floor absolute value of two lifts
while two lifts parallel connection. While the floor of two lifts is same, this value is
“0”; and while one lift has base floor and the other doesn’t, the value will be “1”.
MicoM3 micro controller is defined that address of lift without base floor (《11》
address menu) is “2” and the other is “1”.
《1C》Software version.
《1D》Pulse number for encoder. If the pulse divided, it needs to enter the pulse
number after frequency divided. If enter wrong, the running curve will be possible
display not normally.

3.2.3 TIME Menu (【20】Time)


《21》STOP: Set the delay time for main contactor off when all speed signals
deleted. If using YASKAWA inverter, it is set for brake off. If using dual speed lift,
this menu is spare for use.

Press enter key to enter in amend status and press arrow key to change the value. Then
press enter key to save and ESC to quit.
《22》START: set the time to open increasing curve. It is used for YASKAWA /
FUJI inverter. It is spare for use of dual speed lift.
《23》BRAKE: set the time to open the brake. It is used for YASKAWA / FUJI
inverter. It is spare for use of dual speed lift.
《24》DOOR OPEN: set the time to open door in advance. For VVVF lift, the time
is calculated after the lift decelerates and all speed signals break. For dual speed lift,
it is calculated after the brake opened.
《25》DOOR CLOSE: set the time to close door, showing in seconds.
《26》OPEN PROTECT: set the time of door-open protect. When door-open limit
switch cannot be shut off, this setting can stop opening to avoid the danger of
electrifying the door too long.
《27》CLOSE PROTECT: set the time of door-close protect. When door-close limit
switch or door lock error happens, this setting can stop closing and re-open the
door.
《28》RINGING: set the alarm ringing times when receiving hall call signal. This
setting is used in the MANUAL mode.
《29》GONG: set the lasting time of arrival gong.
《2A》SPEED STOP: Set the delay time to cut off all speed signals while entering
into door zone. It will cut off all speed signals when the pulse value reach to set
value after decelerating to door zone. In case of pulse calculate invalidate, this time
is set to protect so it will later than the time normally cut off. But make sure this
time doesn’t too long otherwise it cannot stop to nearest station while self secure.
《2B》FLOOR PROTECT: Floor protect time. The micro controller must get
decelerate point signal of each floor in this time; otherwise the micro controller
will display E4 error and the lift will decelerate and stop at the nearest.
《2C》TIME1: While adjusting the inspection speed, delay the time for brake
direction after the brake off. When the value is of “0”, it won’t delay.
《2D》TIME2: This is for setting time for protecting steel wire rope slip while the
car standstill. If the leveling inductor without change within this limited time, it
will display E11 of running over time error. If this error occurs, it must shut off the
power or open the inspection switch to reset.
《2E》TIME3: Spare.
《2F》RUN TIME: The running times of the lift. It just calculates the running times
while the lift run fast.

3.2.4 STATION Menu (【30】Station)


《31》BASE: set the base station and locked-floor station of the parallel connected
lift. Setting value of the base station accords to the absolute floor value.

Press enter key to enter in amend status and press arrow key to change the value. Then
press enter key to save and ESC to quit.
《32》FIRE HOUSE: set the returning floor value when the lift under the condition
of fire-protect. This value must be set according to the absolute floor value.
《33》HIGHEST: set the highest floor of the lift, according to the result of the
system automatic test.
《34》WAIT(1): set the waiting floor value when the lift under the condition of
group-control or parallel-connected.
《35》WAIT(2): set the waiting floor when the lift under the condition of
group-control or parallel-connected.
《36》REPLY STATION: set the replying floor value.

It is displayed with binary digits, “1” representing replying and “0” for no reply. From
left to right is the floor value of “1, 2……, 64”.

After pressing ENTER, one of the floor value is highlighted with the mouse in the right
top of the screen to amendment. Press arrow key to change the location of mouse and
press enter key to amend the reply status of corresponding floor (the amend symbol will
show on the left). Press ↑key to set “0” then press↓key to set “1”.

With this function, the reply station can be set without wiring.

3.2.5 CALL Menu (【40】Call)


This menu can observe or login calling lift signals of every floor and monitor and
amend the hall call signals.
《41》UP CALL: it can observe or login the calling lift signals below 64 floors and
show with the binary digits. “1” representing calling-lift signal and “0” for no signal.
Press enter key, the floor value will appear reverse video on the right top on LCD
screen.

Press ENTER again, then appears amendment symbol “>”. Press ARROW key to
amend the value located on highlighted mouse.

After registering calling lift signals, the calling-lift signal will be deleted when the lift
arrives the destination.
《42》DOWN CALL: used as UP CALL.
《43》CAR CALL: used as UP CALL.

3.2.6 IO Menu (【50】IO menu)


This menu is just for monitor and cannot be amended.
《51》INPUT 1: Display the status of system’s parallel input units.
If there is signal input, the name of terminal will be reverse video; if no, there is no
signal input.

The code accords to the code of input signal. For example, “A-B” stands pulse input
A-B, “X00” for X00 terminal, “X01” representing X01 terminal and so on.

《52》INPUT 2: Display the status of system’s parallel input units. The code accords to
the code of input signal.

《53》OUTPUT 1: Display the status of system’s parallel output units, used as


INPUT.

The code accords to the code of output signal. For example, “Y00” stands for Y00
terminal, “Y01” representing Y01 terminal, “Y11” for Y11 terminal and so on.

《54》OUTPUT 2: Display the status of system’s parallel output units. The code
accords to the code of output signal.
3.2.7 DOOR Menu (【60】Door)
《61》DOOR 1: set the floor value of opening the lift door of door machine 1#
represented by binary digits, with “1” representing open and “0” for close.

Press ENTER, then the highlighted floor value is displayed in the right top of the screen
for amendment.

Press enter key again, the amend symbol will appear and press ↑and ↓to change the
location of high lighter mouse.

《62》DOOR 2: set floor value for opening door of door machine 2#. Used as
DOOR 1.
Note: If setting one floor no reply (set in station menu), door 1 and door2 must be
set to close door.
3.2.8 ERROR HISTORY Menu (【70】Error History)
When error occurs, the code and cause of the error are displayed in the bottom of screen.
(Floor display has corresponding code too please see the detail in Chapter 4.)

MICOLIFT M3 system records maximum 50 history errors. Through this menu, user
can check which floor occurs error, the running speed of that time and the running
times of lift.

Checking error history, press enter key to enter dele mode and you can dele all error histories after
two times dele confirmation.

3.2.9 PASSWORD Menu (【80】Password)


The password is represented by five digits.

All the operations are validated by the correct password. The default password is 00000.
After inputting the password, if the power is reset or no any key be pressed within 15
minutes, the password must be re-enter to activate the operations. If enter correct
password again, it will enter to the status to amend password. The new password will
be saved after confirm the amendment.
Note: If the password is lost, all the amendment operations can not be used. The system
must be decrypted by us.

3.2.10 PULSE MONITOR Menu (【90】Pulse monitor, while used with dual
speed lift, this menu is just spare for use.)
《91》CURRENT (current pulse): display the current position of the lift-car with
pulse number. This parameter is just can be checked and not to be amended.

Remark: Under this menu, you can enter into running curve interface by pressing “enter” key.
《92》RUN IN (leveling pulse): length of door zone. 1/4 length of magnetism proof
board. Amend this value to change the length of door zone corresponding pulse
number.
《93》DEL. 1 DISTANCE: deceleration distance 1, change the value to adjust the
length of deceleration distance.
《94》DEL. 2 DISTANCE: deceleration distance 2, change the value to adjust the
length of deceleration distance.
《95》DEL. 3 DISTANCE: deceleration distance 3, change the value to adjust the
length of deceleration distance.
《96》FLOOR: display the pulse number of each floor. Press enter key to check the
pulse number.

Press ↑or ↓key to check pulse number of 1-64 floors. Press enter key to change the
pulse number.

《97》V2 DEL PERMIT (XDL): Set the distance from start to accelerate to
medium speed while selecting the single/multi-floor run curve according to the
distance. This value is multiple of length of magnetism proof board. Select the
single/multi-floors run curve depends on floor and this menu is spare.
《98》V3 DEL PERMIT (XDL): Set the distance from start to accelerate to high
speed while selecting the single/multi-floor run curve according to the distance.
This value is multiple of length of magnetism proof board. Select the
single/multi-floors run curve depends on floor and this menu is spare.
《99》RUN V2 DEL PERMIT (XDL): Set the distance for running medium speed
while selecting the single/multi-floor run curve according to the distance. This
value is multiple of length of magnetism proof board. Select the single/multi-floors
run curve depends on floor and this menu is spare.
《9A》RUN V3 DEL PERMIT (XDL): Set the distance for running high speed
while selecting the single/multi-floor run curve according to the distance. This
value is multiple of length of magnetism proof board. Select the single/multi-floors
run curve depends on floor and this menu is spare.
《9B》DOOR LENGTH: length of door zone.
With this monitor function, the data of lift self-learning can be examined. Also the
precision of leveling can be adjusted. For example, when the lift runs up or down to the
second floor, the lift-car is lower than the leveling point. This problem can be solved by
increasing the pulse number of the second floor until the lift levels precisely.

3.2.11 INPUT SELECT MENU (【A0】Input select)

《A1》TOUCH: Select NO or NC for safe touch board signal. (ON for NO, OFF
for NC.)
《A2》BRAKE: Select NO or NC for brake feed back signal. (ON for NO, OFF for
NC.)
《A3》FIRE: Select NO or NC for first signal. (ON for NO, OFF for NC.)
《A4》CONTACT: Select NO or NC for contactor feed back signal. (ON for NO,
OFF for NC.)
《A5》OVERLOAD: Select NO or NC for over load signal. (ON for NO, OFF for
NC.)
《A6》SWITCH DOOR LIMIT: Select NO or NC contactor for open/close door
limit position. Normally, this function is forbidden and the open / close door limit
position is used for NC contactor.

3.2.12 TIME MENU 2 (【B0】TIME 2) (This menu is for dual speed lift and it
is spare while used with frequency inverter.)

《B1》SOON TIME: Fast Accelerate Speed, to set the delay time of 1A switch on.
《B2》SLOW TIME: Slow accelerate speed: to set delay time of 2A switch on after
1A switch on again.
《B3》BRAKE: Set delay time for 1A switch on again after 1A break off.
《B4》CLOSE LAMP: Set the time for close light and calculated by minutes.
《B5》CLOSE DOOR DELAY: Set the delay time for close door and calculated by
minutes.

3.3 Self-learning of the hoistway data (used for frequency inverter. If for

dual speed lift, it needn’t self-learning just only input the highest floor.)
Make sure all the hoistway switches are in order, such as limit switch, forced
decelerating switch, and leveling switch.
Adjust ascending and descending forced deceleration distance.
While inspection, it runs to the lower station. I.e. the lower forced switch of terminal
station is off and the leveling switch connecting.
Lift is automatic running after return back to station.
Enter into the sub menu learning of config menu to select ON mode after
automatically close door. The lift starts running in the inspect speed automatically.
It automatically stops when arriving the top floor level. After finishing self-learning
of the hoistway data, the lift can run in high speed.
Note: to optimize the use of the lift, self-learn the hoistway data after re-adjusting
the forced deceleration distance or re-adjusting the position signal of door zone.

Some notices during self learning:


1, To sure self learning successful, the leveling sensor and forced switch must be
correct.
2, Make sure the input of pulse encoder must be correct and adopting two phase
counting. The connection for pulse input and phase must be accurate in order that pulse
will be increased while running up and decreased while running down. Otherwise,
please change the A-B phase of input. (Note: the A-B phase of encoder input cannot be
changed.)
3, Self learning is successful if the floor display changes and stops until increasing to
the highest floor. Otherwise, you should check whether the leveling inductor, forced
switch and input and phase of encoder pulse is correct.

3.4 Adjusting Leveling Precision


(1) Test method for VVVF lift
To improve leveling precision and speed up inspection process, during the course of
installing the magnetism-proof board, let the inductor in the middle of the board while
the lift-car at the leveling position. The magnetism-proof board is about 200 – 250 mm
in length.

MICOLIFT M3 system provides a function of adjusting the floor pulse number to


adjust leveling precision, needn’t entering the hoistway to adjust the magnetism-proof
board, thus speed up inspection process. The following are adjusting steps.
During installing the magnetism-proof board, let the inductor in the middle of the
board while the lift-car at the leveling position.
Adjust the inverter to move the lift to a certain floor upwards and downwards, stop
at the same position.
Comparing the real leveling position and the ideal leveling point, if the lift-car
doesn’t arrive at the ideal leveling point, then increase the pulse number of this
floor; otherwise decrease the pulse number of the floor, until the lift levels
precisely.
To adjust leveling through amend the pulse number. As the leveling will change
after self-learnng again, it is advised to reach leveling through moving leveling
inductor. Method is as followed:
Adjust the inverter to move the lift to a certain floor upwards and downwards, stop
at the same position.
Measure the differ value △Y between real position and leveling point. If the
leveling position is lower than leveling point, it should move the leveling inductor
upward of the distance for △Y. Contrarily, it should move the leveling inductor
downward of the distance for △Y.
Test method for dual speed lift:
Just move upward or downward properly for the leveling inductor according to the
leveling point and used with brake to test when necessary.

3.5 Establishing the deceleration distance


The system establishes the ascending and descending braking points according to the
value of the descending forced braking distance. This value is automatically measured
during the course of hoistway data measurement; it can also be adjusted by the user. For
lifts running more than 1.6m/s, two forced braking switch are installed for ascending
use and descending use. The system will measured low-speed forced braking distance
(the second lower forced braking distance) as every floor’s low-speed braking distance
and first lower forced braking distance as high speed braking distance while
self-learning hoistway data. For lifts of 2.0m/s, high-speed braking distance is twice of
the medium-speed braking distance. According to the above principles, the medium
speed forced braking distance must be proper and self learn hoistway data again.

The reference value of the forced deceleration distance


For lifts of 1.0m/s: 1.5m – 1.7m;
For lifts of 1.5m/s: 2.3m – 2.6m;
For lifts of 1.75m/s: second forced deceleration distance: 1.5m – 1.8m;
first forced deceleration distance: 2.5m – 3.0m;
For lifts of 2.0m/s: second forced deceleration distance: 1.5m – 1.7m;
first forced deceleration distance: 3.0m – 3.4m.
Chapter 4 Error Description
MICOLIFT M3P system records 50 errors, with the happening time and the causes.
When error happens, the error cause is displayed on the system LCD screen in English
and is displayed on the floor display with matching error code.
The followings are the error prompts and the solution.
Error 1

E1
Security Circuit Opened

When this error occurs, it will display “E” and “1” alternately for 3 times and display
current floor for few seconds and then display “E” and “1” alternately again; such
circularly.
Security Circuit Opened. Check the security circuit. The error prompt disappeared after
safe circuit work normally.
Error 2

E2
Door Lock Opened or Error

When this error occurs, it will display “E” and “2” alternately for 3 times and display
current floor for few seconds and then display “E” and “2” alternately again; such
circularly.
Door Lock Opened or Error. Check the door lock and lock circuit. The error prompt
disappeared after connecting door lock or inspection.
Error 3

E3
Can’t find the leveling point

When this error occurs, it will display “E” and “3” alternately for 3 times and display
current floor for few seconds and then display “E” and “3” alternately again; such
circularly.
Can’t Find the Leveling Point. Check the leveling inductor and the wires. The lift runs
at run in speed until receiving the door zone signal and the lift stops and opens the door.
The error prompt disappeared after solving the problem or run inspection.
Error 4

E4
Can’t find the deceleration point

When this error occurs, it will display “E” and “4” alternately for 3 times and display
current floor for few seconds and then display “E” and “4” alternately again; such
circularly.
Can’t Find the Deceleration Point. Check whether the protection time for floor in 2B
menu is right and it should increase when necessary. Check the frequency-separator.
The error prompt disappeared when decelerating to door zone. If defeated, please
replace parts.
Error 5

E5
Up Limited Switch Opened

When this error occurs, it will display “E” and “5” alternately for 3 times and display
current floor for few seconds and then display “E” and “5” alternately again; such
circularly.
Up Limited Switch Opened. Check the wires. The error prompt disappeared after
connecting up limited switch. If lift reaches up limited position, it can run downward.
Error 6

E6
Down Limited Switch Opened

When this error occurs, it will display “E” and “6” alternately for 3 times and display
current floor for few seconds and then display “E” and “6” alternately again; such
circularly.
Down Limited Switch Opened. Check the wires. The error prompt disappeared after
connecting down limited switch. If lift reaches up limited position, it can run upward.
Error 7

E7
Deceleration Switch Error

When this error occurs, it will display “E” and “7” alternately for 3 times and display
current floor for few seconds and then display “E” and “7” alternately again; such
circularly.
Deceleration Switch Error. The lift will stop suddenly if single floor forced change
without the deceleration signal from micro processor and leveling with self-survive
speed and record E7 error after the lift runs with multi-floor speed.
Error 8

E8
Contact Not Release

When this error occurs, it will display “E” and “8” alternately for 3 times and display
current floor for few seconds and then display “E” and “8” alternately again; such
circularly.
Contact Not Release. Main contact or braking-contact has not been released when
without signal output. Check the wires or replace. The error prompt disappeared after
solving the problem.
Error 9

E9
Tach Direction Error

When this error occurs, it will display “E” and “9” alternately for 3 times and display
current floor for few seconds and then display “E” and “9” alternately again; such
circularly.
The input direction of encoder is wrong. If error occurs, please change the direction
A-B phase of encoder. Note: It is forbidden to change the input value of A/B phase of
frequency inverter.
Error 10

E10
Brake Error

When this error occurs, it will display “1” and “0” alternately for 3 times and display
current floor for few seconds and then display “1” and “0” alternately again; such
circularly.
Brake error. The brake contactor closed but the mechanical brake of motor is opened or
the brake is opened but no signal. Check the brake connection.
Error 11

E11
Run Time Error

When this error occurs, it will display “1” and “1” alternately for 3 times and display
current floor for few seconds and then display “1” and “1” alternately again; such
circularly.
Normally, the lift will stop urgently if run time over the total run time set in
micro-processor. The error will be disappeared after inspection. If the signal of leveling
inductor doesn’t change, Error 11 will display.
Error 12

E12
Inverter Error

When this error occurs, it will display “1” and “2” alternately for 3 times and display
current floor for few seconds and then display “1” and “2” alternately again; such
circularly.
Inverter Error. Check the inverter. This error will be displayed when the inspection
signal of inverter off.
Error 13

E13
Door Contact not Release

When this error occurs, it will display “1” and “3” alternately for 3 times and display
current floor for few seconds and then display “1” and “3” alternately again; such
circularly.
Door contactor is not released.
Error 14

E14

When this error occurs, it will display “1” and “4” alternately for 3 times and display
current floor for few seconds and then display “1” and “4” alternately again; such
circularly.

Error 15

E15

Error 25

E25

When this error occurs, it will display “2” and “5” alternately for 3 times and display
current floor for few seconds and then display “2” and “5” alternately again; such
circularly.

REMARK:
While using with BCD code output for micro processor, the error code will display
“0” and “X” instead of “E” and “X”. (“X” stands for error code.)
All the types and performances may be changed and won’t notify specially.