Manual M032300 WT6000 G08600 Rev4 RAFT
Manual M032300 WT6000 G08600 Rev4 RAFT
USER MANUAL
G6 Weld Controls
Copyright 2014. All rights reserved.
Copyright 2014. All rights reserved.
TABLE OF CONTENTS
REGARDING THIS DOCUMENTATION...................................................... 8
- Revision History......................................................................................8
- Languages Available............................................................................... 8
Some of the screen shots of the software application may appear different
and are used for illustrative purpose only.
REVISION HISTORY
REVISION REL. DATE COMMENTS
4.0 10/14/14 Updated the entire manual to incorporate changes with software
version G08600-00-13
LANGUAGES AVAILABLE
-9-
M032300 V4.0/ G08600-00-13_10/2014
WTC tests all of our products to ensure that they are fully operational
when shipped from the manufacturing facility. If you are experiencing
installation or startup problems, please review the troubleshooting
information contained in this publication. If you need assistance to
get your module up and running, please contact Customer Support
(see the table below); our trained technical specialists are available to
help. When emailing please provide a photograph of the serial tag
and Hardware Status Screen on the DEP 300s if possible.
- 10 -
M032300 V4.0/ G08600-00-13_10/2014
SAFETY INSTRUCTIONS
ONLY qualified personnel are allowed to service the weld cabinet and
associated devices!
- 11 -
M032300 V4.0/ G08600-00-13_10/2014
Make certain the circuit breaker handle on the enclosure is in the OFF
position before attempting to open the door.
Cu 75o ONLY
WORKING WITH STATIC-SENSITIVE DEVICES
- 12 -
M032300 V4.0/ G08600-00-13_10/2014
ESD COSTS!
Electrostatic discharge (ESD) can ignite flammable materials and
damage electronic components. Static electricity can attract
contaminants in clean environments or cause products to stick
together. Other costs of ESD-damaged electronic devices are in their
replacement and production down time. Associated costs of repair
and rework, shipping, labor and overhead can be significant. Reducing
losses to ESD and static electricity is an ABSOLUTE NECESSITY.
PERSONNEL GROUNDING
Before touching any Electrostatic Discharge Sensitive (ESDS) devices
or circuit boards, put on and wear an Electrostatic Discharge (ESD)
wrist strap. Ground this strap through a one megohm (1 MΩ) resistor.
HANDLING OR MOVING ESDS DEVICES
Handle all circuit boards by their edges ONLY. NEVER touch the traces
or edge pad connectors.
NOTE:
Use ONLY static-shielding containers for transporting ESDS devices or
circuit boards.
WORKSTATION REQUIREMENTS
If diagnostics are required, move the circuit board to an approved ESD
workstation. A static-safe workstation must include a grounded ESD
mat, wrist strap and cord. The measured static voltage at a
workstation MUST NOT exceed 50 volts.
NOTES:
- 13 -
M032300 V4.0/ G08600-00-13_10/2014
- 14 -
M032300 V4.0/ G08600-00-13_10/2014
It is extremely important to examine the crate/packaging immediately
upon delivery to your freight dock. If there is evidence of any damage,
note it on the bill of lading before signing. If there is severe damage to
the crate/packaging, do not sign the bill of lading and refuse the
shipment.
WTC's freight terms are FOB: Shipping Point. This means once the
weld control is picked-up by the freight carrier at WTC's shipping
dock, it becomes the customers’ ownership and responsibility (the
company who issued the purchase order). Therefore, if any damage
occurs to the weld control by the freight carrier during transit, it is the
customer's responsibility to identify it upon receipt and file the
appropriate claim paperwork with the freight carrier to have it
resolved.
Typically, domestic welding control shipments are either skidded
standing upright, with multiple cabinet bolted together (back-to-
back), or skidded laying flat (for taller enclosures). If the shipment is
via ocean, welding controls are typically placed inside a special coated
bag to prevent any potential salt water induced corrosive damage to
the weld control.
- 15 of 17/Chap1_unpkg.fm -
M032300 V4.0/ G08600-00-13_10/2014
LIFTING AND
MOVING THE CRATED WELD CONTROLS ARE
WELD CONTROL NOT INTENDED TO BE STACKED.
CABINET MOVE ONLY BY EITHER
FORKLIFT OR ASSISTED LIFT.
WTC assembles most weld controls with a provision for lifting and
moving the cabinet. Never attempt to lift any size weld control
LIFTING cabinet without using the lifting brackets or eye bolts. Dropping the
BRACKETS / EYE welding control from even a short distance can cause severe damage
BOLTS and will void the warranty. NEVER put power on a welding control
that has been dropped. If the weld control has been dropped, contact
WTC as soon as possible.
- 16 of 17/Chap1_unpkg.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROBLEM SOLUTION
When contacting WTC for assistance, please have the following
information ready:
NOTE: When emailing WTC for support with a shipment issue, please
include pictures of the problem (if possible), as they can be very
helpful in quickly understanding and resolving your problem.
NOTE: WTC's firewall will not accept compressed (.zip) files as email
attachments. If you need to email a .zip file to WTC, change the file
extension to .piz prior to attaching it to the email message. This will
allow both the email and the attachment to pass through the WTC
firewall. Thank you for your understanding.
- 17 of 17/Chap1_unpkg.fm -
M032300 V4.0/ G08600-00-13_10/2014
WT6000 CABINET
SAFETY CONCERNS BEFORE YOU APPLY POWER!
- 18 of 19/Chp2_safety.fm -
M032300 V4.0/ G08600-00-13_10/2014
PRINTED CIRCUIT BOARDS MUST BE COMPLETELY POWERED DOWN
PRIOR TO PERFORMING ANY MAINTENANCE, TROUBLESHOOTING OR
REPLACEMENT.
OTHER INSTRUCTIONS:
- 19 of 19/Chp2_safety.fm -
M032300 V4.0/ G08600-00-13_10/2014
GEN6 WELD The WT6000 Weld Control converts three-phase (50/60Hz) AC line
PROCESSOR voltage into a single-phase (1000Hz- Default) AC square wave output.
The square wave output is fed to the primary of a MFDC welding
transformer, where it is rectified in the secondary to DC voltage. DC
welding has many advantages over AC welding, including a more
efficient consumption of plant power and the ability to make higher
quality welds by having more control over the welding process.
NOTE: The enclosure configuration shown below is for illustration purposes only. Your
cabinet configuration may differ depending on your specific application.
- 20 of 27/Chp3_sysov.fm -
M032300 V4.0/ G08600-00-13_10/2014
FEATURES The weld processor module, internal to the WT6000, uses free format
programming and “Flexible I/O” to create weld parameters and
programs to fit any welding application.
• Built in Ethernet/IP.
• Internal web server allows the user to view and edit timer data
from web browser, robot teach pendant or touch panel (HMI)
device. [For additional information on this feature, refer to Web
Pages Manual M032360]
INSIDE THE The WT6000 Weld Control contains the following sub-assemblies:
WELD CONTROL
• INVERTER ASSEMBLY: Converts three-phase (50/60Hz) AC line
voltage to single-phase (1000Hz) AC.
- 21 of 27/Chp3_sysov.fm -
M032300 V4.0/ G08600-00-13_10/2014
ROBOT OR HARD TOOL USAGE
- 22 of 27/Chp3_sysov.fm -
M032300 V4.0/ G08600-00-13_10/2014
A1 CONTROL
CIOM MODULE:
Local serial
interface to the CONTROL CIRCUIT BREAKER:
weld processor. TRANSFORMER: Supplies or
Has signal power Steps down line voltage interrupts line
distribution and to 120V and 24V for the voltage to the entire
controls local I/O cabinet power. weld control cabinet.
Interior View
for illustrative
purpose only.
Actual control
configuration
may vary.
ISOLATION CONTACTOR:
Located downstream of
WELD PROCESSOR
INVERTER ASSEMBLY: the inverter to interrupt
ASSEMBLY:
Converts three-phase (50/60Hz) AC line voltage/current to the
Brains of the weld control
voltage to single-phase (400Hz- 1300Hz) AC MFDC welding
and controls all Ethernet/
output depending on the setup parameters transformer.
DeviceNet communications
- 23 of 27/Chp3_sysov.fm -
M032300 V4.0/ G08600-00-13_10/2014
POWER SOURCE
- 24 of 27/Chp3_sysov.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 25 of 27/Chp3_sysov.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROCESSOR & FUNCTIONS
NUMBER OF STEPPERS 10
ENVIRONMENTAL CONDITIONS
- 26 of 27/Chp3_sysov.fm -
M032300 V4.0/ G08600-00-13_10/2014
WATER COOLING REQUIREMENTS
• Maximum temperature not to exceed 104° F. (40° C.), or fall below the dew point of
ambient air at about 70° F. (21° C.)
MAX PRESSURE DROP @ 5 LITERS/MIN FLOW Less than 70 kPa / .7 bar / 10 PSI
- 27 of 27/Chp3_sysov.fm -
M032300 V4.0/ G08600-00-13_10/2014
STANDARD CONNECTIONS
WATER PORTS
Rear View
Side View
AIR CIRCULATION VENT
- 28 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
WARNING!
STORED
ENERGY
DEVICE
- 29 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
INSTALLATION CHECKLIST
USE THE FOLLOWING CHECKLIST 3. Inspect interior of both weld control and Servo cabinet for loose
AS A GUIDE DURING THE and/or missing parts. Inspect for any shipping damage.
INSTALLATION PROCESS. IF YOU ARE
UNSURE HOW TO PROPERLY
INSTALL AND HOOKUP
4. Check and ensure the inverter cooling fan and all air circulation
THE WELD CONTROL
CABINET, CONTACT
vents on the back of the cabinet are unobstructed (if applicable).
WTC FOR ASSISTANCE.
5. Check and ensure all water drain holes are open and unblocked.
9. Connect 3-phase AC line power cables (L1, L2, L3) to top of circuit
breaker (line side) and tighten according to manufacturer specifi-
cations. Run cables through cover plate on side of enclosure.
10. Connect plant ground cable to copper grounding post inside cabi-
net. Run cable through cover plate on side of enclosure.
11. Connect power cables from output of weld control (H1, H2) to pri-
mary of welding transformer. Run cables through pilot hole on
bottom of enclosure.
- 30 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
12. Connect ground cable from copper ground bus inside cabinet to
welding transformer. Run cable through pilot hole on bottom of
enclosure.
15. Verify magnetic and thermal trip settings on circuit breaker, per
manufacturer specifications (if applicable).
16. Inspect cabinet and verify all wiring connections (high voltage,
terminals, crimp connections, etc.) are secure.
17. Close weld control cabinet door and lock with 1/4-turn fasteners.
18. Ensure cooling water circuit has no leaks and water is flowing at
specified rate (if applicable).
- 31 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
• Control Placement
• Cabinet Mounting and Fastening
• Cooling Water and Connections
Shown above: Front and top view of the MiniPak weld control cabinet
- 32 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
- 33 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
- 34 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
The MiniPak cabinet includes a vented back cover that isolates the
water cooling circuit from the internal electrical components.
The cooling water provided must comply with chemical and physical
specifications as stated in the Resistance Welder Manufacturers’
Association Bulletin 5–005.05. See Chp. 3: System Overview for
details.
NOTE: Water that is safe for drinking is generally sufficient for cooling
water, provided it is filtered to eliminate sand and rust particles. In
addition, water temperature must NOT fall more than 2° C. below the
temperature of the surrounding air - condensation may occur and
damage components.
- 35 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
- 36 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
- 37 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
ELECTRICAL INSTALLATION
- 38 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
- 39 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
- 40 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
RAFT VOLTAGE The following illustrates the hook-up of the RAFT voltage sense
SENSE WIRE wires to the RAFT connector on the weld control cabinet. Also
HOOK-UP shown is the interconnect between the RAFT connector and the
weld processor.
NOTE: The voltage sense wires are polarity sensitive. If the polarity is
reversed, the weld processor will report a zero or negative resistance
and an ADAPTQ TIP VOLT WIRE BROKEN fault will be generated at
sequence initiation.
- 41 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
WELD CONTROL Before welding can begin, the following parameters need to be
PROGRAMMING programmed into the weld processor.
AND SETUP
B Program Mode
NOTE: Refer to
Chapter 7: Faults
and Setup
Parameters for
detailed
information
regarding the
description and
programming of
setup parameters.
C Review Setups
- 42 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
Review and program the Weld Schedules as required for the welding
application.
B Program Mode
C Review Schedule
- 43 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
NOTE: Refer to
Chapter 6:
Programming
Schedules or Glossary
of Schedule Functions
for detailed
B Program Mode
information regarding
function descriptions
and the programming
of weld schedules.
C Review Stepper
- 44 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
NOTE: Refer to
Chapter 8: Linear
Current Steppers for
detailed information
regarding the
description and
programming of
linear current
steppers.
D Using the number keys edit the required functions and
press . This will turn “Apply” from gray to black. Press
to apply the changes.
- 45 of 45/Chp4_install .fm -
M032300 V4.0/ G08600-00-13_10/2014
Chapter 5: COMMUNICATIONS SETUP
PORT
COMMUNICATION TYPE DESCRIPTION
NAME
ENET IP Ethernet/IP (EIP) ENET IP is used for I/O communication between the weld pro-
cessor and other Ethernet enabled devices (e.g. a Robot or
PLC). Also used to communicate with Weld Gateway and
RAFT Gateway networking software.
SSPI WTC Proprietary I/O Communi- SSPI supports communication with optional WTC I/O peripheral
cation Protocol (Optional) devices.
COMM RS485 Serial Interface COMM is used for DEP-300s or DEP-100S data entry panel com-
munications.
DNET Device Net (Optional) DNET is used for DeviceNet I/O communications (slave only).
SEC I/V Secondary Current or Voltage Location for input wires for Secondary Current or Secondary
Monitoring Input (Optional) Voltage Monitoring.
- 46 of 55/Chp5_commsetup.fm -
M032300 V4.0/ G08600-00-13_10/2014
ETHERNET SETUP The WT6000 weld processor has two Ethernet communication ports:
PORT
COMMUNICATION TYPE DESCRIPTION
NAME
ENET IP (EIP) How to navigate through the DEP-300s to the EIP Options menu:
FACTORY
DEFAULT
SETTINGS
- 47 of 55/Chp5_commsetup.fm -
M032300 V4.0/ G08600-00-13_10/2014
C Press More
- 48 of 55/Chp5_commsetup.fm -
M032300 V4.0/ G08600-00-13_10/2014
NAME ADDRESS
IP Address 192.168.0.250
Gateway 0.0.0.0
DHCP On
- 49 of 55/Chp5_commsetup.fm -
M032300 V4.0/ G08600-00-13_10/2014
In the default settings chart on previous page, the Type is 8 and the
Size is 2 for both the inputs and outputs. Since the product of 8 and 2
is 16, the total mappable I/O is 16 for both the inputs and the
outputs.
The chart below shows all the possible combinations in which the
Type and Size can be configured and not exceed the maximum of 64
NOTE: If the Size is set to 0, the entire map is disabled and no I/O can
be mapped.
8 0 0
8 1 8
8 2 16
8 3 24
8 4 32
8 5 40
8 6 48
8 7 56
8 8 64
16 0 0
16 1 16
16 2 32
16 3 48
16 4 64
32 0 32
32 1 32
32 2 64
- 50 of 55/Chp5_commsetup.fm -
M032300 V4.0/ G08600-00-13_10/2014
ENET (STANDARD
ETHERNET) How to navigate through the DEP-300s to the Local Ethernet menu:
FACTORY DEFAULT
SETTINGS
C Press More
- 51 of 55/Chp5_commsetup.fm -
M032300 V4.0/ G08600-00-13_10/2014
D Press More
NAME ADDRESS
IP Address 89.89.200.250
Gateway 0.0.0.0
- 52 of 55/Chp5_commsetup.fm -
M032300 V4.0/ G08600-00-13_10/2014
DEVICENET SETUP The WT6000 weld processor is capable of DeviceNet I/O
communications. This requires the installation of an optional
DeviceNet peripheral board.
C Press More
- 53 of 55/Chp5_commsetup.fm -
M032300 V4.0/ G08600-00-13_10/2014
D Press More
NAME ADDRESS
NOTE: These settings
are the factory Reload Default OFF
defaults. The
customer's default Node Address 11
settings may differ
based on the welding Baud Rate 500K
application and the
requirements of the Byte Size 8by8
DeviceNet master.
Network Response Delay in mSEC. 1
- 54 of 55/Chp5_commsetup.fm -
M032300 V4.0/ G08600-00-13_10/2014
WT6000 PROCESSOR The WT6000 processor (weld processor) has four status LED's.
LED DESCRIPTION Through a combination of changing colors and flashing/solid states,
the LED's indicate the status of the EtherNet/IP Module, the
EtherNet/IP Status, Weld Sequence Status and the Weld Control
Status.
Processing
AMBER functions after
weld
FLASHING Alert
AMBER
In weld mode- not
OFF in a sequence
- 55 of 55/Chp5_commsetup.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 56 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
WELD SCHEDULE
FUNCTIONS FUNCTION
DESCRIPTION
TYPE
WELD SCHEDULE For a list of weld schedule functions and descriptions, see Chapter 13:
FUNCTION LIST Schedule Function List.
- 57 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
00 START OF SCHEDULE # 1
3 HOLD 83 MSEC
- 58 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
HOW TO READ A Weld schedules are read starting at the top and moving down, one
WELD SCHEDULE line at a time. The time it takes the weld control to complete an entire
weld schedule can be calculated by adding up all time parameters
(cycle and/or milliseconds) programmed within each function
throughout the entire schedule.
PROGRAMMING A There are several user interface options available to program a weld
WELD SCHEDULE schedule. They include the following:
In this manual, the DEP-300s data entry panel is
used in all programming instructions
- 59 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
INSERT A FUNCTION Perform the following steps on the DEP-300s to insert a function into
INTO A WELD a weld schedule:
SCHEDULE
- 60 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
D Press Sch#
F Press ENTER
- 61 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
G Press MORE
I Press INSERT
- 62 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
L Press ENTER
- 63 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
M If the
function requires parameters to be entered, proceed to
step 13. If not, proceed to step 17
- 64 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
R Press DOWNLOAD.
[Downloads the changes to the weld
processor].
- 65 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
DELETE A FUNCTION Perform the following steps on the DEP-300s to delete a function
FROM A WELD from a weld schedule:
SCHEDULE
- 66 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
D Press Sch#
F Press ENTER
- 67 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
G Press MORE
- 68 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
I Press DELETE.
[The function is immediately
deleted from the DEP-300s.]
J Press DOWNLOAD
[Downloads the changes to the
weld processor. When complete, a
“Download Complete” message will appear]
- 69 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
COPYING A WELD Perform the following steps on the DEP-300s to copy an entire weld
SCHEDULE schedule from one location and paste it into another:
- 70 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
D Press Sch#
F Press ENTER
- 71 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
G Press MORE
H Press COPY
- 72 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
I FROM SCHEDULE #
(Current Schedule will be
displayed) TO [Blank Field] enter
the paste to Schedule Number
J Press ENTER
- 73 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
SPOT ID PROGRAMMING
The SPOT ID feature allows enhanced flexibility in setting up welding sched-
ules that are associated with spot numbers. This allows the user to associate
the spot number of the weld with programming data used to create the spot
and the welding data results of the spot. A second option with this feature is
to initiate the weld control based on spot numbers instead of schedule num-
bers. There are 255 weld schedules available for spot selection 1 -255. Spot
numbers higher than 255 can be assigned freely via the Spot ID system.
These schedules are a continuation of the binary sequence select bits (1-
255). With this feature additional schedules can be added to the 255 sched-
ules already available. Individual schedules can also be customized and dupli-
cated.
Another usage is to have all the spots of the plant programmed into one
timer (as long as the number of unique welding schedules is under the 255
schedule maximum) and the Robot picks the schedule based on the spot
number. This allows the welding timers to be preprogrammed with all the
data required to operate in any welder in the plant.
If the SPOT ID is assigned, then the weld schedule associated with it will be
initiated. If the spot ID selected is not assigned, then an INVALID SEQUENCE
SELECTED fault is set.
The user will be able to select a schedule for view or edit through the use of
the spot numbers. When a schedule is chosen for edit based on a spot num-
ber, the schedule will be shown along with the other spot numbers which
are associated with that schedule.
SETUP PARAMETERS
Min: 256
SPOT No.
Max: 1073741823
- 74 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
SETUP PROCEDURES
Weld schedules with Spot ID feature can be programed via the RAFT
Gateway, DEP 300s or the WebView.
SPOT ID SETUP
ASSIGN ASSIGN A
SCHEDULE SCHEDULE TO
TO SPOT MORE THAN ONE
SPOT WITH A MAX.
OF 1000
• Modify schedule
• Duplicate Spots
- 75 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 76 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 77 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
G Enter valid spot number. This field will turn red if a number
<256 is entered. The Add Spot button will now turn yellow. Indi-
cating that schedule 4 has been assigned to spot 256.
- 78 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 79 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
B Select the function line to be deleted and click the delete button.
C The Save Changes button will turn yellow, click to apply.
- 80 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
DUPLICATING A SPOT
C An alert is annunciated.
Click Yes to confirm.
- 81 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
REMOVING A SPOT ID
C Select the Spot to delete and click Remove Spot button. This
also removes all changes made to the schedule associated with
the particular spot.
- 82 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 83 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
C Press More
- 84 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
F Press
- 85 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
F Press Execute
- 86 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
J Press More
K Press More
- 87 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
L Press More
M Press Spots
N Press Spot
- 88 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
O Press New
- 89 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
Q Press the arrow key to move the cursor to the Spot # field.
- 90 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
EDITING A SCHEDULE
- 91 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
E Press Enter
F Press Apply
- 92 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
SPOT 9 (256)
SPOT 10 (512)
SPOT 11 (1024)
SPOT 12 (2048)
SPOT 13 (4096)
SPOT 14 (8192)
SPOT 15 (16384)
SPOT 16 (32768)
SPOT 17 (65536)
SPOT 18 (131072)
SPOT 19 (262144)
SPOT 20 (524288)
SPOT 21 (1048576)
SPOT 22 (2097152)
SPOT 23 (4194304)
SPOT 24 (8388608)
SPOT 25 (16777216)
SPOT 26 (33554432)
SPOT 27 (67108864)
SPOT 28 (134217728)
SPOT 29 (268435456)
SPOT 30 (536870912)
- 93 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
00 START OF SCHEDULE #N
1 SQUEEZE 30 CYCLES
3 HOLD 5 CYCLES
- 94 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
00 START OF SCHEDULE #N
1 SQUEEZE 30 CYCLES
3 HOLD 5 CYCLES
00 START OF SCHEDULE #N
1 SQUEEZE 30 CYCLES
3 HOLD 5 CYCLES
- 95 of 95/Chp6_schd.fm -
M032300 V4.0/ G08600-00-13_10/2014
When Faults are detected, the WTC DEP-300s (Data Entry Panel) can
be used edit a Programmable Fault or Setup Parameter.
- 96 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
Press Review
Setups
- 97 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
Press ENTER
Press ENTER
- 98 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
Press APPLY
[Saves changes to the DEP-300s only]
Press DOWNLOAD
- 99 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 100 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
FAULT SEVERITY The user can set the severity of the programmable faults. The severity
option tells the weld processor how to respond when a fault
condition is detected. Conversely, the severity of non-programmable
faults are fixed and cannot be changed. See Non-Programmable
(Hidden) Faults on Page 115.
- 101 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
FAULT RESET Faults can be reset by either pressing the Reset (F5) button on the
Fault Status Menu in the DEP-300s or turning the Fault Reset input bit
HIGH. Perform the following steps to reset faults via the DEP-300s
Press Fault
- 102 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
Press Reset
Press the Options to filter what is viewed on the Fault Status Menu.
- 103 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
Press Options
Press Enter
- 104 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROGRAMMABLE FAULTS
USER DEFINED
DEFAULT
FAULT PROGRAMMABLE POSSIBLE CAUSES SOLUTIONS
VALUE
OPTIONS
Occurs at: Indicates the final step in the
STEPPER stepper program has begun
APPROACHING FAULT/ ALERT ALERT 1 the 1st weld of step 2 in the and End of Stepper is
MAX stepper program, if the tip approaching.
dress feature is enabled,
and the Remaining Tip Perform a tip dress or tip
Dresses Count has decre- change.
mented to 0.
- 105 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
USER DEFINED
DEFAULT
FAULT PROGRAMMABLE POSSIBLE CAUSES SOLUTIONS
VALUE
OPTIONS
Occurs at:
Reset the stepper (using
1 the 1st weld of step 3 in the either the external reset
END OF stepper program, if the tip input or the stepper display
STEPPER FAULT/ALERT FAULT dress feature is enabled mode). You should also dress
and the remaining Tip or replace the electrode caps.
Dresses Count has decre-
mented to 0.
NOTE: The first 40 welds
will be an ALERT. If the
stepper program is not
reset by the 41st weld, it
will change to a FAULT.
- 106 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
USER DEFINED
DEFAULT
FAULT PROGRAMMABLE POSSIBLE CAUSES SOLUTIONS
VALUE
OPTIONS
- 107 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
USER DEFINED
DEFAULT
FAULT PROGRAMMABLE POSSIBLE CAUSES SOLUTIONS
VALUE
OPTIONS
- 108 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
USER DEFINED
DEFAULT
FAULT PROGRAMMABLE POSSIBLE CAUSES SOLUTIONS
VALUE
OPTIONS
Occurs when:
1 function #70 [WAIT FOR
WELD PROCEED] is used in
the weld schedule and the
Weld Initiate input bit goes
LOW before the specified
input bit goes either OFF or
ON.
WELD FAULT/ALERT FAULT 2 function #67 [WAIT FOR WAIT FOR WELD PROCEED bit
PROCEED INPUT #n TO BE n (0 = OFF to go HIGH
1 = ON)] is used in the weld
schedule and the Weld Ini-
tiate input bit goes LOW
before the specified input
bit goes either OFF or ON.
- 109 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
USER DEFINED
DEFAULT
FAULT PROGRAMMABLE POSSIBLE CAUSES SOLUTIONS
VALUE
OPTIONS
- 110 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
USER DEFINED
DEFAULT
FAULT PROGRAMMABLE POSSIBLE CAUSES SOLUTIONS
VALUE
OPTIONS
- 111 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
USER DEFINED
DEFAULT
FAULT PROGRAMMABLE POSSIBLE CAUSES SOLUTIONS
VALUE
OPTIONS
Occurs when:
1. the Weld / No Weld bit Ensure weld gun is not open-
goes LOW while the weld ing early. Check for intermit-
control is passing current tent open connection in the
during the execution of a weld tooling (primary or sec-
WELD INTER- FAULT/ ALERT ALERT weld schedule. ondary).
RUPTION
2. the circuit breaker on
the weld cabinet is
switched OFF while the
weld control is passing
current during the exe-
cution of a weld sched-
ule. The fault will appear
after the circuit breaker
is switched back ON and
the weld processor re-
initializes.
- 112 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
USER DEFINED
DEFAULT
FAULT PROGRAMMABLE POSSIBLE CAUSES SOLUTIONS
VALUE
OPTIONS
- 113 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
USER DEFINED
DEFAULT
FAULT PROGRAMMABLE POSSIBLE CAUSES SOLUTIONS
VALUE
OPTIONS
- 114 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
USER DEFINED
DEFAULT
FAULT PROGRAMMABLE POSSIBLE CAUSES SOLUTIONS
VALUE
OPTIONS
- 115 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
DEFAULT
FAULT NAME POSSIBLE CAUSE SOLUTION
VALUE
Occurs when the Weld Initiate bit goes Ensure the schedule (sequence) number
HIGH and a schedule (sequence) num- selected via the Binary Select bits is not
ber is selected via the Binary Select bits, beyond the range of available sched-
INVALID which is beyond the range of available ules. For example, if there are 99 sched-
SEQUENCE FAULT schedules. ules available, selecting schedule 100 or
higher via the Binary Select bits will gen-
SELECTED
NOTE: This fault will only occur when the erate an INVALID SEQUENCE SELECTED
Retract Pilot input bit is mapped in the I/O. FAULT, when the Weld Initiate bit goes
HIGH.
- 116 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
DEFAULT
FAULT NAME POSSIBLE CAUSE SOLUTION
VALUE
3 when mechanical issues exist in the 4 Look for possible part fit-up and tool-
weld transformer secondary circuit ing wear issues.
(weld tooling).
5 Ensure proper air pressure is being
Typical issues include: supplied to the weld gun.
• Bad jumper cables or leaf shunts
• Bad part fit-up
• Contaminated weld caps
• Insulation from sealer, tape or
labels on part
• Gun sticking or not closing prop-
erly
• Loose or open secondary diodes
in the welding transformer
• Loose or bad primary cables.
Inspect and correct as neces-
sary.
- 117 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
DEFAULT
FAULT NAME POSSIBLE CAUSE SOLUTION
VALUE
- 118 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
DEFAULT
FAULT NAME POSSIBLE CAUSE SOLUTION
VALUE
Occurs when the System Cooling bit 1 Troubleshoot and find out why the
goes LOW prior to and during the execu- system cooling input is going LOW.
tion of the weld schedule. This bit is Could be a robot / PLC issue logic
SYSTEM FAULT normally maintained HIGH. issue or a legitimate system cooling
COOLING problem.
This bit can be used to set a weld pro-
cessor fault when a system cooling 2 Identify and correct any water flow
problem exists somewhere in the weld- issues.
ing process. For example, it could be
used to indicate a transformer over-
temp condition.
NOTE: The inverter chill plate temperature
can be viewed in the Display Mode screen
of the DEP300s.
NOTE: Prior to resetting this fault, go to the The 1st ground fault module
Hardware Status screen in the DEP-300s by (1GFM)
pressing the Display Mode (F4) key. The
The 2nd ground fault module
Hardware Status screen will provide more
specific information regarding the nature of (2GFM)
the fault. The discrete I/O module (1IO)
and
Finally to the analog I/O mod-
ule (1AIOM).
4. Also verify the modules in the com-
munication link are not defective.
- 119 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
DEFAULT
FAULT NAME POSSIBLE CAUSE SOLUTION
VALUE
- 120 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
DEFAULT
FAULT NAME POSSIBLE CAUSE SOLUTION
VALUE
Occurs when the weld processor has Reset circuit breaker on weld control
BUS detected the DC bus within the inverter cabinet. Replace inverter assembly if
CHARGING FAULT assembly did not charge correctly continually re-occurs.
(either too slow or too quickly). This
fault is monitored continuously.
- 121 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
DEFAULT
FAULT NAME POSSIBLE CAUSE SOLUTION
VALUE
Occurs when a current imbalance exists Identify and correct unidirectional cur-
OUTPUT FAULT between the two output terminals of rent path to ground between the output
GROUND the inverter assembly. of the inverter assembly and the pri-
mary of the welding transformer.
- 122 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
DEFAULT
FAULT NAME POSSIBLE CAUSE SOLUTION
VALUE
Occurs when:
INVERTER 1 a hardware failure is detected within Replace inverter assembly and weld
SYSTEM FAULT the inverter assembly or weld proces- processor module.
FAILURE sor module.
DEFAULT
SETUP DESCRIPTION PROGRAMMABLE OPTIONS
VALUE
LATCHED:
In Latched mode, a LOW to HIGH
transition on the Retract Pilot input
The Retract Mode setup parameter bit causes the state of the Retract
RETRACT MODE determines how the mapped Retract Valve output bit to latch ON or OFF. LATCHED
Valve output bit will react when the
control receives the mapped Retract UNLATCHED:
Pilot input bit: In Unlatched mode, the Retract
Valve output bit follows the state of
the Retract Pilot input bit.
AIR-NORMAL:
In Air-Normal mode, the weld tool-
ing uses an air-only cylinder that
requires a HIGH Retract Valve output
The Cylinder setup parameter bit to close the gun to the retracted
defines the type of weld gun air cyl- position. AIR-NOR-
CYL
inder being used: MAL
AIR-INVERTED:
In Air-Inverted mode, the weld tool-
ing uses an air-only cylinder that
requires a LOW Retract Valve output
bit to close the gun to the retracted
position.
- 123 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
DEFAULT
SETUP DESCRIPTION PROGRAMMABLE OPTIONS
VALUE
- 124 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
DEFAULT
SETUP DESCRIPTION PROGRAMMABLE OPTIONS
VALUE
- 125 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
DEFAULT
SETUP DESCRIPTION PROGRAMMABLE OPTIONS
VALUE
- 126 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
DEFAULT
SETUP DESCRIPTION PROGRAMMABLE OPTIONS
VALUE
PRI/PRI:
Primary Current Regulation / Pri-
mary Current Monitoring (Default
The WT6000 inverter has three firing Mode). PRI/PRI
and monitoring modes. These
modes are distinguished by PRI/SEC:
Primary Current Regulation / Sec-
FIRING / 1. The method in which the current ondary Current Monitoring.
MONITOR is regulated
MODE NOTE: Requires additional hardware for
2. The feedback monitoring method secondary current feedback monitoring.
used to determine the proper out-
put. SEC/SEC:
Secondary Current Regulation / Sec-
ondary Current Monitoring.
- 127 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
DEFAULT
SETUP DESCRIPTION PROGRAMMABLE OPTIONS
VALUE
- 128 of 128/Chp7_faults.fm -
M032300 V4.0/ G08600-00-13_10/2014
THE PURPOSE During the welding process, the face of the welding cap gradually
OF LINEAR deforms or “mushrooms.” As it does, the contact surface area with
CURRENT the work piece increases, which causes the current density at the
STEPPERS weld interface to decrease. As a result, the weld nugget gradually
becomes colder.
- 129 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
HOW LINEAR The WT6000 weld control with timer software G08600 has 10
CURRENT available linear current stepper programs. Each stepper program has
STEPPERS 5 programmable steps.
WORK
Within each of the 5 steps, the user can program the current boost
(rise) over a number of welds (run). The current boost for each step
can be expressed as either a percentage value or an absolute Amps
value. The current boost (rise) is delivered in equal, incremental
steps, over the total number of welds (run) in each step.
- 130 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
STEPPER Each stepper program has a stepper profile. In the example below,
PROFILES each step has two current values. The first value (blue) is a
percentage value and the second value (red) is an absolute Amps
value. If a Percentage of available Volt-Seconds weld function is used,
the current boost (rise) must be expressed in a percentage value. If a
Constant Current weld function is used, the current boost (rise) must
be expressed in absolute Amps.
EXAMPLE OF A WELD
STEPPER PROFILE STEP % VALUE AMPS. VALUE
FUNCTION
Stepper Group 1
Maximum Tip Dresses = 1
Aux. Counter Max. Counts = 0
- 131 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
EXAMPLE STEPPER The following is an example of a linear stepper program without tip
PROGRAM #1 dressing. This example would typically be used in either a hard-tool
(NO TIP DRESS) welding application or any other application where dressing of the
weld caps is not required.
2. Current weld function #30 (WELD nnnn MS. nnnn0 AMPS) is used
and is programmed to deliver 10000A of base current for 160 mil-
liseconds.
EXAMPLE SCHEDULE #1
00 START OF SCHEDULE # 1
03 HOLD 80 MSEC
- 132 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
Below is the stepper profile as viewed from the DEP-300s Data Entry
Panel.
STEPPER PROFILE
12000
11500
11000
10500
1
10000
9500
9000
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
452
480
Weld
- 133 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
STEPPER PROFILE
12000
11500
11000 2
10500
10000
9500
9000
Weld
48
72
96
336
360
384
408
432
452
480
120
144
168
192
216
240
264
288
312
F 30: Weld 160 Ms 1000 Amps - Base Weld Current
STEPPER PROFILE
12000
11500 3
11000
10500
10000
9500
9000
Weld
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
452
480
- 134 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
STEPPER PROFILE
12000
11500 4
11000
10500
10000
9500
9000
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
452
480
Weld
- 135 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
End of Stepper
Tip Change Required output bit HIGH
STEPPER PROFILE
12000 5
11500
11000
STEPPER APPROACHING MAX
10500
10000
9500
9000
Weld
48
72
96
336
360
384
408
432
452
480
120
144
168
192
216
240
264
288
312
- 136 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
EXAMPLE STEPPER The following is an example of a linear stepper program with tip
PROGRAM #2 dressing. This example would typically be used in a robot welding
(TIP DRESS) application.
00 Start of Schedule # 1
56 Set Pressure = 0
03 Hold 80 Msec
56 Set Pressure = 0
- 137 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
12000
11500
11000
10500
1
10000
9500
9000
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
452
480
Weld
- 138 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
12000
11500
2
11000
10500
10000
9500
9000
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
452
480
Weld
TIP DRESS REQUEST
12000
11500 3
11000
10500
10000
9500
9000
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
452
480
Weld
F 30: Weld 160 MS 1000 Amps - Base Weld Current
- 139 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
00 Start of Schedule # 61
56 Set Pressure = 0
3 STEP # 02
If the Remaining Tip Dresses Count is > 0, the stepper program
will continue towards Step 3 again.
- 140 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
TIP DRESSING
12000
11500
2
11000
10500
10000
9500
9000
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
452
480
Weld
3 STEPPER GROUP:
In example #2, Stepper #1 is assigned to Stepper Group 1. For
more information, see Stepper Groups.
- 141 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
STEPPER STATUS Perform the following steps on the DEP-300s to navigate to the
Stepper Status Screen:
B Press Status Mode
C Press Stepper Status
- 142 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
D Press Stepper#
E Enter Stepper Number.
F Press ENTER
- 143 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
PARAMETER DESCRIPTION
STEPPER Turns the stepper either ON or OFF. The default position is ON.
NOTE: This parameter is disabled in timer software version G08760
STEP COUNT The weld count within the step, the stepper program is currently in.
TOTAL WELD The total weld count since the beginning of the stepper program.
COUNT
TIP DRESSES The Remaining Tip Dresses Count is a decrementing counter, which starts at the num-
ber entered in GROUP (1-4) MAXIMUM TIP DRESSES in the setup parameters. This
counter defines the maximum number of times the weld caps may be dressed before
they must be changed. Each time the weld processor receives a tips dressed index, the
Remaining Tip Dresses Count decrements by one. When this count decrements to zero,
an END OF STEPPER FAULT is generated. This indicates the weld caps must be changed.
NOTE: A tip dress advance request occurs when:
1. Either the Tip Dress - Tip Dress Group 1 or Tip Dress Group 2 Input bits go HIGH
2. Function #93 (TIP DRESS ADVANCE: GROUP nn - STEP n) is used in the schedule.
AUX. The Auxiliary Counter is an incrementing counter, which mirrors the Total Weld Count
COUNTER counter above. Its max count is set by the value entered in the Aux Counter Max
Counts parameter in the stepper profile.
STEPPER # The stepper program number currently displayed. Pressing the Stepper # (F3) key,
allows the user to change the stepper program that is displayed.
Pressing the Advance (F2) key, advances the stepper program to the first weld of the
next step. When the stepper advances, the following changes will occur in the Stepper
Status Menu:
• The STEP COUNT will reset to zero.
ADVANCE
• The TOTAL WELD COUNT will advance to where its count would be at the first
weld of the next step.
• The Aux. Counter will not change when the stepper is advanced. If the user wants
the Aux. Counter count to match the Total Weld Count, the value will have to be
manually entered here.
RESET ALL Pressing the Reset ALL (F4) key, globally resets all stepper programs.
- 144 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
STEPPER RESET An END OF STEPPER FAULT indicates the stepper program has ended.
OPTIONS At this point, the weld caps must be replaced on the gun and the
stepper program(s) must be reset. Stepper Reset changes all counts
within the stepper program back to their beginning value. See
example below.
In weld processor software G08600, there are three ways in which the
user can reset stepper programs:
Perform the following steps from the DEP-300s Stepper Status Menu
to globally reset the stepper programs:
- 145 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
C The message “Do you want to reset all Steppers” will appear.
D Press Confirm
- 146 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
• All counts within the stepper program are changed back to their
beginning value.
NOTE: Pressing the Fault Reset button on the DEP-300s will only reset
the STEPPER APPROACHING MAX ALERT and the END OF STEPPER
FAULT. It does not reset the stepper program(s)
- 147 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
EDITING THE Perform the following steps on the DEP-300s to navigate to the
STEPPER PROFILE Review Stepper Menu:
- 148 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
D Press Stepper #
E Enter Stepper Number
F Press ENTER
- 149 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
EDITING A PARAMETER ON THE REVIEW STEPPER MENU
ON THE DEP 300s:
B
Press the or arrow keys to move the cursor
onto the parameter line to be edited.
ENTER
C Press
D Enter parameter
- 150 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
ENTER
E Press
G Press APPLY
[Saves changes to the DEP-300s only.]
I Press DOWNLOAD
- 151 of 151/Chp8_steppers.fm -
M032300 V4.0/ G08600-00-13_10/2014
In the above example, let's assume that V=5 and S=4. Then the total
shaded area would equal (V x S) or 20. Now suppose that V drops to 4.
Then S would be increased to 5 to maintain a total value of 20 in the
shaded area.
- 152 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
• Projection Welding
• Butt Welding
• Flash-Butt Welding
• Aluminum Welding
• Welding through Sealant
• Poor Metal Fit-up / Gaps
- 153 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 154 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 155 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
C Press More
E Press ENTER
- 156 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
DECREASING As the weld tooling degrades over time, its resistance (either primary
C-FACTOR or secondary) increases. As the resistance increases, the weld control
must compensate for this change, otherwise the welds will gradually
grow colder. Weld tooling degradation can be caused by the following
conditions:
INCREASING Current shunting (either primary or secondary) is essentially an
C-FACTOR unintended, alternate path of current flow occurring in the weld
tooling. Current shunting causes the overall resistance of the weld
tooling to decrease. As current is shunted across the alternate path,
less current passes through the work piece, resulting in colder welds.
Secondary current shunting paths can be caused by the following
conditions:
- 157 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
2. Insert function #92 (C-FACTOR LIMIT: HI= nnnn LOW= nnnn) near
the beginning of the weld schedule. See example schedule below:
00 START OF SCHEDULE # 1
01 SQUEEZE 30 CYCLES
03 HOLD 5 CYCLES
- 158 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
CALCULATE THE NOTE: The following instruction provides a starting point for the C-
C-FACTOR HI / LOW Factor HI / Low limits. These values will require adjustment
LIMIT VALUES: as the user becomes more familiar with the weld tooling and
what the C-Factor parameters are when weld quality issues
occur (caused by either weld tooling degradation or current
shunting).
For Example:
For example, if the reference C-Factor parameter is 200:
200 *.80 = 160. Therefore, the Low C-Factor Limit would be 160.
For Example:
If the reference C-Factor parameter is 200:
200 * 1.2 = 240. Therefore, the High C-Factor Limit would be 240.
- 159 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
SETTING THE HI AND LOW C-FACTOR LIMIT FAULTS IN THE SETUP
PARAMETERS:
- 160 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
CAR TYPE #1
CAR TYPE #2
After establishing a bin number, the processor stores the data for each weld
made in its own individual bin. The bin numbers increase by one each time a
weld is made. This will continue until another schedule containing function
#90 (SET SPC OFFSET) is executed.
Bin #99 is the last usable bin. If the weld processor reaches bin #99 and is
still collecting data, the data for each weld will be stored in bin #99 until a
new offset is assigned, therefore making the data unsuitable for analysis.
NOTE: This function does not tell the weld processor to collect weld data.
It only assigns a data storage bin number. To setup SPC data
collection parameters, see SPC Setup Parameters.
- 161 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
This function tells the weld processor to collect and sample 100% of
the weld data within the schedule. It overrides the “global” Data
Collection Sample Size and Data Collection Sample Frequency setup
parameters, described in SPC Setup Parameters below.
Function #90 (SET SPC OFFSET) should be inserted before #91 in the
weld schedule, to ensure the data is sent to the appropriate bin.
Otherwise, it will be sent to default bin #0.
The processor will continue collecting and sampling 100% of the weld
data within the schedule until the weld processor executes another
weld schedule containing function #90 (SET SPC OFFSET). At which
point, the “global” Data Collection Sample Size and Data Collection
Sample Frequency setup parameters regain their hierarchical priority.
These two parameters set a global command, which allows the weld
processor (WCU) to sample data for analysis at controlled intervals.
FOR EXAMPLE:
Let's assume function #90 (SET SPC OFFSET) is inserted in the weld
schedule and set to bin #1:
- 162 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
By setting the Data Collection Sample Size to (2) and the Data
Collection Sample Frequency to (8), the WCU will collect data for the
first two consecutive welds (in bin #1) and flag the WebView to
retrieve the data. It will then collect data for the six remaining welds
(without flagging the WebView) before repeating the process.
BIN # 1
NOTE: Weld data collection is bin dependent. Each bin has its own
independent counter and is uploaded to the Web View separately.
- 163 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
C Press More
- 164 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
D Press IO Status
In this example the I/O Status Menu shows the mapped bits relating
to the application error codes (circled in red). It should be noted this is
a simplified example and the customers application requirements
may prescribe these bits to be mapped to different I/O locations.
- 165 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
Each bit is represented by a tag. Each tag will have either a “1” or “0”
underneath it:
NOTE: For more information on mapping I/O bits, see Chapter 11:
Inputs and Outputs.
- 166 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
HOW WTC The following example is a robot welding application where the weld
ERROR CODES processor is reporting three application error codes:
ARE REPORTED
1. When a faults occurs, the EVAL output bit goes HIGH and applica-
tion error code (5) is binarily displayed on the ER1-ER16 output
bits. Since the End of Stepper is configured as a FAULT in the weld
processor, the FERR output bit will also go HIGH.
2. The HIGH EVAL output bit tells the robot to read the ER1-ER16
and FERR output bits.
3. When the robot has read these output bits, it toggles the FACK
input bit.
4. The toggling FACK input bit causes the EVAL output bit to toggle.
When this toggle occurs, the next application error code (7) is
binarily displayed on the ER1-ER16 output bits. Since the Low
Current Limit Fault is configured as a FAULT in the weld processor,
the FERR output bit will also go HIGH.
5. The toggling EVAL output bit tells the robot to read the ER1-ER16
and FERR output bits a second time.
6. When the robot has read the ER1-ER16 output bits, it toggles the
FACK input bit.
7. The toggling FACK input bit causes the EVAL output bit to toggle.
When this toggle occurs, the next application error code (19) is
binarily displayed on the ER1-ER16 output bits. Since the Low C-
Factor Limit is configured as an ALERT in the weld processor, the
AERR output bit will also go HIGH.
- 167 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
8. The toggling EVAL output bit tells the robot to read the ER1-ER16
output bits a third time.
9. When the robot has read the ER1-ER16 output bits, it toggles the
FACK input bit.
10. The toggling FACK input bit causes the EVAL output bit to toggle.
When this toggle occurs, the weld processor scrolls and re-dis-
plays application error code (5) on the ER1-ER16 output bits.
Since the End of Stepper is configured as a FAULT in the weld pro-
cessor, the FERR output bit will also go HIGH.
11. The toggling EVAL output bit tells the robot to read the ER1-ER16
and FERR output bits a fourth time.
12. When the robot reads the ER1-ER16 output bits, it recognizes
that it has previously read application error code (5) and the
reporting process ends.
- 168 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
3. INCOMPLETE WELD 3 1 1 0 0 0
5. END OF STEPPER 5 1 0 1 0 0
7. COMPENSATION ERROR 12 0 0 1 1 0
9. EXTENDED WELD 14 0 1 1 1 0
- 169 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
• CONTROL STOP
3 INCOMPLETE WELD • WELD INTERRUPTION
• SOFT OVERCURRENT
12 COMPENSATION ERROR • CURRENT REGULATION
• EXTENDED WELD
14 EXTENDED WELD • EXCESSIVE REWELD
• SECONDARY DIODE
21 WELDING TRANSFORMER • GROUND
• SYSTEM COOLING
22 OVER TEMPERATURE • TEMPERATURE
- 170 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
• IGBT SATURATION
25 INVERTER FAULT • IGBT POWER SUPPLY
• BUS VOLTAGE
• BUS CHARGING
- 171 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
00 START OF SCHEDULE # 1
01 SQUEEZE 30 CYCLES
03 HOLD 5 CYCLES
- 172 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
The following is an example tip dress schedule where the weld control
is controlling the tip dress motor. This feature requires an optional tip
dress motor control circuit installed in the weld control cabinet (see
note below). This schedule also monitors or “checks” the current
draw of the tip dress motor.
NOTE: If your weld control cabinet does not have the optional motor
control circuit installed and you are interested in using this feature,
contact your WTC sales representative for assistance.
00 START OF SCHEDULE # 1
03 HOLD 5 CYCLES
- 173 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
Function #18 (START TIP DRESS MOTOR CHECK) tells the weld
processor to turn the tip dress motor ON.
Function #17 (TIP DRESS TIME nn SEC BLANK nnnn ms) sets the total
amount of time (in seconds) the tip dress motor is ON. The blanking
time (in milliseconds) is the period of time the weld processor does
not measure the motor starting (in-rush) current.
Function #19 (STOP TIP DRESS MOTOR CHECK) tells the weld
processor to turn the tip dress motor OFF.
MODE OF OPERATION:
- 174 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
NOTES:
- 175 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
The results of the tip dress motor current check are displayed in the
Weld Data Menu. Perform the following steps on the DEP-300s to
navigate to the Weld Data Menu.
C Press More
- 176 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
In the example above the results are displayed in the Sec I column
(circled in red) in milliamps. There are three current measurements
displayed: MAX current, AVG current and MIN current.
- 177 of 177/Chp9_advtopics.fm -
M032300 V4.0/ G08600-00-13_10/2014
ISOLATION CONTACTOR
Monthly Ensure that the Contactor operates properly.
Contactor should turn OFF/ON smoothly.
Monthly
CIRCUIT BREAKER
Test shunt trip button on circuit breaker.
MOUNTING BOLTS
3 Months
Verify all mounting bolts holding cabinet in place
are tight.
- 178 of 179/Chp10_prevmain.fm -
M032300 V4.0/ G08600-00-13_10/2014
12 Months
EXTERNAL CABINET
Inspect for damage external to cabinet and that
labels are intact.
12 Months
CABINET DOOR
Inspect that door opens and closes smoothly and
that seals are not cracked or broken.
- 179 of 179/Chp10_prevmain.fm -
M032300 V4.0/ G08600-00-13_10/2014
I/O LIST The following is a complete list of the available I/O bits for the
WT6000 weld control with timer software G08600. Each I/O bit has a
tag name assigned to it. The tag name is used to identify the bit on
the DEP-300s I/O Status Menu. These bits are applicable to Ethernet
IP (EIP), Fieldbus and Discrete I/O
INPUTS
- 180 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
STEPPER RESET SR
STEPPER RESET GROUP 1 SRG1
STEPPER RESET GROUP 2 SRG2
TIP DRESS TIPD
TIP DRESS GROUP 1 TDG1
TIP DRESS GROUP 2 TDG2
STEPPER AUX WELD CNTR RESET SACR
APP ERR ACKNOWLEDGE FACK
CONTROL STOP CSTP
PRESSURE SWITCH PS1
SYSTEM COOLING COOL
PROGRAM DISPLAY SECURITY PSEC
HEAT DISPLAY SECURITY HSEC
USER INPUT 1 UI1
USER INPUT 2 UI2
USER INPUT 3 UI3
USER INPUT 4 UI4
USER INPUT 5 UI5
USER INPUT 6 UI6
RETRACT PILOT 1 RP1
RETRACT PILOT 2 RP2
SPOT 9 (256) S9
SPOT 10 (512) S10
SPOT 11 (1024) S11
SPOT 12 (2048) S12
SPOT 13 (4096) S13
SPOT 14 (8192) S14
SPOT 15 (16384) S15
SPOT 16 (32768) S16
SPOT 17 (65536) S17
SPOT 18 (131072) S18
SPOT 19 (262144) S19
SPOT 20 (524288) S20
SPOT 21 (1048576) S21
SPOT 22 (2097152) S22
SPOT 23 (4194304) S23
SPOT 24 (8388608) S24
- 181 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
OUTPUTS
- 182 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 183 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 184 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 185 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
When the NONE bit is assigned to an input, the input is disabled and not
NONE used by the weld processor.
BINARY SELECT 1 / 2 / 4 / 8 / 16 These bits are used to binarily select which of the 255 available weld sched-
/ 32 / 64 / 128 ules to run. The schedule is selected by turning the appropriate bits HIGH.
WELD INITIATE When this bit goes HIGH, the weld processor will initiate the weld schedule
selected through the Binary Select Inputs.
When this bit is HIGH, the weld control is in WELD MODE. When this bit is
WELD / NO WELD LOW, the weld control is in NO WELD MODE.
This bit is HIGH when the Fault Status illuminated pushbutton in the opera-
FAULT RESET tor's panel is pressed. When this bit goes HIGH, the weld processor will reset
all faults.
WELD PROCEED This bit is used to force the weld processor to pause the execution of a weld
schedule until the bit goes HIGH. It is used with function #70 (WAIT FOR
WELD PROCEED).
STEPPER RESET When this bit goes HIGH the weld processor will “globally” reset all 10 step-
per programs to Step 1 and Weld Count 0.
STEPPER RESET GROUP 1 When this bit goes HIGH the weld processor will reset only the stepper pro-
grams assigned to Group 1, to Step 1 and Weld Count 0.
STEPPER RESET GROUP 2 When this bit goes HIGH the weld processor will reset only the stepper pro-
grams assigned to Group 2, to Step 1 and Weld Count 0.
STEPPER AUX WELD CNTR RESET When this bit goes HIGH, the weld processor resets the Auxiliary Weld
Counter to zero and turns the Aux. Counter at Max output bit LOW.
- 186 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
APP ERR ACKNOWLEDGE The robot turns this bit HIGH to:
1 Send an acknowledgment to the weld processor that it has read the binary
fault code from the App Error output bits.
2 To send the next binary fault code to the App Error output bits.
CONTROL STOP This bit is normally maintained HIGH. When this bit goes LOW, the weld pro-
cessor will generate a CONTROL STOP FAULT.
This bit is used to force the weld processor to pause the execution of a weld
PRESSURE SWITCH schedule until the bit goes HIGH or until the wait time in function #68 has
elapsed. It is used with function #68 (WAIT nnnn CY FOR PRESSURE SWITCH
INPUT) and function #69 (WAIT FOR PRESSURE SWITCH INPUT).
This bit is normally maintained HIGH. When a System Cooling problem exists
external to the weld control unit (i.e. welding transformer, gun, etc.) this bit
will go LOW.
The weld schedule will initiate if the bit is LOW, but no current will be
passed. At the end of the schedule, the weld processor will generate a LOW
SYSTEM COOLING CURRENT FAULT and SYTEM COOLING FAULT.
If this bit goes LOW anytime during the execution of a weld schedule, the
weld processor will generate a SYSTEM COOLING FAULT. Conversely, if this
bit goes LOW before the weld function, a SYSTEM COOLING FAULT and LOW
CURRENT LIMIT FAULT will occur.
When this bit is held LOW, only data within the Stepper Status menu can be
edited.
PROGRAM DISPLAY SECURITY
When this bit is held HIGH, all data can be edited.
When this bit is held HIGH, only data in the Stepper Status and Heat Display
Menus can be edited.
HEAT DISPLAY SECURITY
When the Heat Display Security and Program Display Security bits are held
LOW simultaneously, only data in the Stepper Status, and Network Address
menus can be edited.
USER INPUT 1 / 2 / 3 / 4 / 5 / 6 Spare user definable input bit. It is used with functions #66 (WAIT nnn CY
INP #n TO BE n) and #67 (WAIT FOR INPUT #n TO BE n) in the weld schedule.
This input bit changes the state of the Close Retract 1 and Open Retract 1
output bits. A LOW to HIGH transition on the Retract Pilot input bit causes
RETRACT PILOT 1 the state of the Close Retract 1 and Open Retract 1 output bits to change.
NOTE: Both retract output bits remain off after the control is powered up
and/or after a Control Stop condition. The retract input bit must always be
toggled after these events to return the retract output bits to their expected
states.
NOTE: This bit must be mapped in the I/O to enable retraction. Operation is
fixed in LATCHED mode only.
- 187 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
RETRACT PILOT 2 This input bit changes the state of both Retract Valve 2 and Inverted Retract
Valve 2 output bits. How these output bits react to the input depends on the
parameters programmed into the Retract Mode and Cylinder Setup Parame-
ters.
The Weld Summary Record format will add the SPOT ID to the summary
information.
GUN RES CHECK This bit is used to assess the gun resistance and annunciate “WELD PROCESS
STOP” fault if resistance falls outside the acceptable range.
When this input bit goes HIGH at TURN ON WELD COMPLETE, an average
resistance of the weld is checked within the Schedule’s SOFTQ Monitor
Resistance Average settings. If the Average Resistance exceeds the fault
level limits it will turn on the Weld Process Stop output.
- 188 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
REWELD NON-RAFT This input bit allows the robot to request a reweld and make decisions on
whether to reweld with adaptive ON or OFF in the following situations:
B If the ADAPTQ MODE = 0 and there is a valid Reference and R-Measure for
a given schedule then ADAPTQ Mismatch Output bit can be turned ON.
C If there was an Internal reweld or a request for an External Re-Weld then
the ADAPTQ Mismatch output will remain high. In all other cases it will
be remain LOW.
If there are any SOFTQ settings set to check for either PI-Envelope, Monitor-
ing, or Trending the output SOFTQ Mismatch will turn OFF.
If the SOFTQ settings have been turned off by using the “RAFT” screen and
disabling the SOFTQ Monitoring the output SOFTQ Mismatch will turn ON.
If there are at least X SOFTQ exceptions or more within the Part Exceptions
buffer then turn on the WELD PROCESS STOP Output. This output will go
low with a valid Weld Initiate, or fault reset.
If the automation process desires a Re-Weld then they can monitor the state
of the No Fault / Weld Complete to assess if a RE-Weld is required and turn
on the Reweld Non-RAFT. This along with a valid schedule and Weld Initiate
will Execute the schedule and turn off the ADATPQ and SOFTQ Monitoring
features.
The schedule will use the programmed current plus stepper boost.
TIP DRESS MOTOR ON This input functions as an external request which is independent of the weld
schedule and allows the Robot or PLC to start the tip dress motor.
- 189 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
OUTPUT DESCRIPTIONS
NONE When the NONE bit is assigned to an output, the output is disabled and not
used by the weld processor.
This bit goes HIGH when function #50 (TURN ON VALVE 1) is executed in the
VALVE 1 weld schedule and goes LOW when function #51 (TURN OFF VALVE 1) is exe-
cuted.
VALVE 2 This bit goes HIGH when function #50 (TURN ON VALVE 2) is executed in the
weld schedule and goes LOW when function #51 (TURN OFF VALVE 2) is exe-
cuted.
VALVE 3 This bit goes HIGH when function #50 (TURN ON VALVE 3) is executed in the
weld schedule and goes LOW when function #51 (TURN OFF VALVE 3) is exe-
cuted.
VALVE 4 This bit goes HIGH when function #50 (TURN ON VALVE 4) is executed in the
weld schedule and goes LOW when function #51 (TURN OFF VALVE 4) is exe-
cuted.
VALVE 5 This bit goes HIGH when function #50 (TURN ON VALVE 5) is executed in the
weld schedule and goes LOW when function #51 (TURN OFF VALVE 5) is exe-
cuted.
VALVE 6 This bit goes HIGH when function #50 (TURN ON VALVE 6) is executed in the
weld schedule and goes LOW when function #51 (TURN OFF VALVE 6) is exe-
cuted.
NO FAULT This bit is normally maintained HIGH and indicates a FAULT condition does
not exist. When a FAULT occurs, this bit will go LOW.
This bit is normally maintained HIGH and indicates an ALERT condition does
NO ALERT not exist. When an ALERT occurs, this bit will go LOW.
WELD MODE ON This bit goes HIGH when the weld control is in WELD MODE.
NO WELD This bit goes HIGH when the weld control is in NO WELD MODE.
This bit goes HIGH when function #58 (TURN ON WELD IN PROGRESS) is exe-
WELD IN PROGRESS cuted in the weld schedule and goes LOW when function #59 (TURN OFF
WELD IN PROGRESS) is executed.
This bit goes HIGH when function #63 (TURN ON WELD COMPLETE) is exe-
WELD COMPLETE cuted in the weld schedule and goes LOW when function #64 (TURN OFF
WELD COMPLETE) is executed.
- 190 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
This bit goes HIGH when all the following conditions are true:
READY TO WELD 1 The weld control is in WELD MODE
2 No fault condition exists
3 The Control Stop input bit is HIGH
4 The System Cooling input bit is HIGH.
STEPPERS ARE RESET This bit goes HIGH when all 10 stepper programs are globally reset.
STEPPERS ARE RESET GROUP 1 This bit goes HIGH when the stepper programs assigned to group 1 are
reset.
STEPPERS ARE RESET GROUP 2 This bit goes HIGH when the stepper programs assigned to group 2 are
reset.
When the tip dress feature is enabled, this bit will go HIGH on the first weld
END OF STEPPER of step 3 in the stepper program, if the Remaining Tip Dresses Count has
decremented to 0. It will only go HIGH on the last weld of step 5 in the step-
per program, if the tip dress function is disabled in the Setup Parameters or
the tip dress count is greater than 0 when the tip dress feature is enabled.
This bit will go LOW when either the Stepper Reset, Stepper Reset Group 1
or Stepper Reset Group 2 input bits go HIGH.
END OF STEPPER GROUP 1 This bit will go HIGH on the last weld of step 5 in the stepper program. This
bit will go LOW when either the Stepper Reset or Stepper Reset Group 1
input bit goes HIGH.
END OF STEPPER GROUP 2 This bit will go HIGH on the last weld of step 5 in the stepper program. This
bit will go LOW when either the Stepper Reset or Stepper Reset Group 2
input bit goes HIGH.
When the tip dress feature is enabled, this bit will go HIGH on the 1st weld
STEPPER APPROACHING MAX of step 2 in the stepper program, if the Remaining Tip Dresses Count has
decremented to 0. It will only go HIGH on the 1st weld of step 5 in the step-
per profile, if the tip dress function is disabled in the Setup Parameters or
the tip dress count is greater than 0 when the tip dress feature is enabled.
This bit will go LOW when either the Stepper Reset, Stepper Reset Group 1
or Stepper Reset Group 2 input bits go HIGH.
STPR APPROACHING MAX This bit will go HIGH on the 1st weld of step 5 in the stepper profile. This bit
GROUP 1 will go LOW when either the Stepper Reset, Stepper Reset Group 1 or End of
Stepper Group 1 input bit goes HIGH.
STPR APPROACHING MAX This bit will go HIGH on the 1st weld of step 5 in the stepper profile. This bit
GROUP 2 will go LOW when either the Stepper Reset, Stepper Reset Group 2 or End of
Stepper Group 2 input bit goes HIGH.
TIP CHANGE REQUIRED This bit will go HIGH at the end of any stepper program, if the Remaining Tip
Dress Count (Tip Dresses) has decremented to zero in the Stepper Status
Menu. This bit will go LOW when the Stepper Reset input bit goes HIGH.
TIP CHANGE REQUIRED GROUP This bit will go HIGH at the end of any stepper program assigned to Group 1,
1/2 if the Remaining Tip Dress Count (Tip Dresses) has decremented to zero in
the Stepper Status Menu. This bit will go LOW when either the Stepper
Reset or Stepper Reset Group 1 / 2 input bit goes HIGH.
- 191 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
TIP DRESS REQUEST This bit will go HIGH at the first weld of Step 3 in the stepper program, if the
Remaining Tip Dresses Count is > 0. It is used as an indicator to the robot
that a tip dress is required for the weld caps. This bit will go LOW when (1)
the Tip Dress Request, Tip Dress Request Group 1 or Tip Dress Request
Group 2 input bits go HIGH or (2) the tip dress schedule is initiated.
NOTE: This bit does not latch on. It will turn off when the initiate bit is
turned off.
TIP DRESS REQUEST GROUP I / 2 This bit will go HIGH at the first weld of Step 3 in the stepper program, if the
Remaining Tip Dresses Count is > 0. It is used as an indicator to the robot
that a tip dress is required for the weld caps. This bit will go LOW when the
Tip Dress Group 1 / 2 input bit goes HIGH.
STEPPER AUX COUNTER AT MAX This output bit goes HIGH when the Auxiliary Weld Counter has reached the
value programmed in the Aux. Counter Max Counts field in the Stepper Pro-
file.
APP ERROR AVAILABLE When a fault occurs, this bit goes HIGH to advise the robot to read the
binary fault code on the App Error Bit output bits.
APP ERROR BIT 1 / 2 / 4 / 8 / 16 These bits are used by the weld processor to send binary fault codes to the
robot.
During the execution of a weld schedule, the weld processor takes the value
programmed in function #54 (TURN ON PRESSURE SELECT nnn) and turns
PRESSURE SELECT 1 / 2 / 3 / 4 the corresponding binary Pressure Select output bits HIGH. If SET PRESSURE
= 0, all four bits (1, 2, 3, 4) are LOW.
USER OUTPUT 1 / 2 / 3 / 4 / 5 / 6 This bit goes HIGH when function #52 (TURN ON OUTPUT 1 / 2 / 3/ 4 / 5/ 6)
is executed in the weld schedule and goes LOW when function #53 (TURN
OFF OUTPUT 11 / 2 / 3/ 4 / 5/ 6) is executed.
RETRACT VALVE 1 The state of this bit changes according to the status of the Retract Valve 1
input bit. How this bits reacts depends on the parameters programmed into
the Retract Mode and Cylinder Setup Parameters.
RETRACT VALVE 2 The state of this bit changes according to the status of the Retract Valve 2
input bit. How this bits reacts depends on the parameters programmed into
the Retract Mode and Cylinder Setup Parameters.
INVERTED RETRACT VALVE 1 The state of this bit changes according to the status of the Retract Pilot 1
input bit.
NOTE: This bit is functional when the Retract Pilot 1 input bit is mapped.
NOTE: Both retract output bits remain off after the control is powered up
and/or after a control stop condition. The retract input bit must always be
toggled after these events to return the retract output bits to their expected
states.
INVERTED RETRACT VALVE 2 The state of this bit changes according to the status of the Retract Valve 2
input bit. How this bits reacts depends on the parameter programmed into
the Retract Mode Setup Parameter.
- 192 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
WATER SAVER This bit goes HIGH when a weld schedule initiates. After the weld schedule
is complete, the weld processor starts an internal timer holding the bit HIGH
for an additional three minutes. When the timer has ended, the bit goes
LOW.
FORGE This bit goes HIGH when function #78 (TURN ON FORGE VALVE) is executed
in the weld schedule and goes LOW when function #79 (TURN OFF FORGE
VALVE) is executed.
GAP This bit goes HIGH when the part being welded with ADAPTQ mode enabled
detects a gap due to high resistance or an instantaneous drop in resistance.
CONTACTOR SELECT 1-6 This output works in conjunction with the MCCM (Multi Contactor Control
Module). Weld controls installed with the MCCM which is a multiplexer,
have the capability of functioning in cascade mode where one inverter
power supply allows connections to up to 3 welding transformers. The Con-
tactor Select output is used to determine which welding unit (named by
numbers 1-6) and will be active during the specified schedule and receive
feedback from the specified tip voltage sense wires in RAFT™ mode.
SOFTQ MISMATCH This out put bit goes HIGH when SOFTQ settings have been turned OFF
using RAFT™
RAFT CAPABLE This bit goes HIGH when both hardware and software to support RAFT™ is
detected.
ADAPTQ ENABLED This output bit goes HIGH when a schedule is welded in the adaptive mode.
SOFTQ ENABLED This output bit goes HIGH when a schedule is welded with SOFTQ monitor-
ing is available for the schedule.
TIP DRESS MOTOR RUNNING This output goes HIGH as a handshake acknowledgment of the TIP DRESS
MOTOR ON input.
- 193 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
I/O STATUS To navigate to the I/O Status Menu, perform the following steps on
the DEP-300s:
C Press More
- 194 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
D Press IO Status
The I/O Status Screen shows the status of every mapped I/O bit in the
WT6000. Depending on the customer's application, this can include:
• Fieldbus I/O
• Ethernet I/O
• Local I/O
- 195 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
I/O DEFAULTS
DISCRETE I/O
Weld processor software G08600 offers two default Discrete I/O (DIO)
lists. The following instructions show navigation to Default 1 on the
DEP-300s. Use the same procedure to navigate to Default 2.
C Press More
- 196 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
D Press More
- 197 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
G Press Execute
- 198 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 199 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
C Press More
- 200 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
D Press More
- 201 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 202 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
8. FAULT RESET FR
15. NONE -
16. NONE -
17. NONE -
18. NONE -
19. NONE -
20. NONE -
21. NONE -
22. NONE -
23. NONE -
24. NONE -
25. NONE -
26. NONE -
27. NONE -
- 203 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
28. NONE -
29. NONE -
30. NONE -
31. NONE -
32. NONE -
1. VALVE 1 V1
2. VALVE 2 V2
3. VALVE 3 V3
4. VALVE 4 V4
9. ALERT ALT
11. NONE -
12. NONE -
13. NONE -
14. NONE -
15. NONE -
16. NONE -
17. NONE -
18. NONE -
19. NONE -
20. NONE -
21. NONE -
22. NONE -
- 204 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
23. NONE -
24. NONE -
25. NONE -
26. NONE -
27. NONE -
28. NONE -
29. NONE -
30. NONE -
31. NONE -
32. NONE -
- 205 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
14. NONE -
17. NONE -
18. NONE -
19. NONE -
20. NONE -
21. NONE -
22. NONE -
23. NONE -
24. NONE -
25. NONE -
26. NONE -
- 206 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
27. NONE -
28. NONE -
29. NONE -
30. NONE -
31. NONE -
32. NONE -
1. FAULT FLT
2. ALERT ALT
7. VALVE 1 V1
8. VALVE 2 V2
9. VALVE 3 V3
11. NONE -
12. NONE -
13. NONE -
14. NONE -
15. NONE -
16. NONE -
17. NONE -
18. NONE -
19. NONE -
20. NONE -
21. NONE -
- 207 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
22. NONE -
23. NONE -
24. NONE -
25. NONE -
26. NONE -
27. NONE -
28. NONE -
29. NONE -
30. NONE -
31. NONE -
32. NONE -
13. NONE -
- 208 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
15. NONE -
16. NONE -
17. NONE -
18. NONE -
19. NONE -
20. NONE -
21. NONE -
22. NONE -
23. NONE -
24. NONE -
25. NONE -
26. NONE -
27. NONE -
28. NONE -
29. NONE -
30. NONE -
31. NONE -
32. NONE -
2. NO FAULT NFLT
3. ALERT ALT
8. VALVE 1 V1
- 209 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
9. VALVE 2 V2
10. VALVE 3 V3
11. NONE -
12. NONE -
13. NONE -
14. NONE -
15. NONE -
16. NONE -
20. NONE -
21. NONE -
22. NONE -
23. NONE -
24. NONE -
25. NONE -
26. NONE -
27. NONE -
28. NONE -
29. NONE -
30. NONE -
31. NONE -
32. NONE -
- 210 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
TAG
INPUT # FIELDBUS INPUT BIT NAME BYTE SIZE
NAME
2 FAULT RESET FR
11 NONE -
12 NONE -
13 STEPPER RESET SR
17 NONE -
20 NONE - 4 by 4
23 NONE -
24 NONE -
25 NONE -
26 NONE -
27 NONE -
- 211 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
28 NONE -
29 NONE -
30 NONE - 6 by 6
31 NONE -
32 NONE -
33 NONE -
34 NONE -
35 NONE - 8 by 8
36 NONE -
37 NONE -
38 NONE -
39 NONE -
40 NONE -
41 NONE -
42 NONE -
43 NONE -
44 NONE -
45 NONE -
46 NONE -
47 NONE -
48 NONE -
49 NONE -
50 NONE -
51 NONE -
52 NONE -
53 NONE -
54 NONE -
55 NONE -
56 NONE -
57 NONE -
58 NONE -
59 NONE -
60 NONE -
- 212 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
61 NONE -
62 NONE -
63 NONE -
64 NONE -
OUTPUT TAG
FIELDBUS OUTPUT BIT NAME BYTE SIZE
# NAME
2 NO FAULT NFLT
3 NO ALERT NALT
17 NONE -
20 NONE -
23 NONE -
- 213 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
26 NONE -
29 NONE -
30 NONE -
31 NONE -
32 NONE -
33 NONE -
34 NONE -
35 NONE -
36 NONE -
37 NONE -
38 NONE -
39 NONE -
40 NONE -
41 NONE -
42 NONE -
43 NONE -
44 NONE -
45 NONE -
46 NONE -
47 NONE -
48 NONE -
49 NONE -
50 NONE -
51 NONE -
52 NONE -
53 NONE -
54 NONE -
55 NONE -
56 NONE -
- 214 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
57 NONE -
58 NONE -
59 NONE -
60 NONE -
61 NONE -
62 NONE -
63 NONE -
64 NONE -
INPUT TAG
FIELDBUS INPUT BIT NAME BYTE SIZE
# NAME
2 FAULT RESET FR
4 NONE -
5 NONE -
6 NONE -
8 STEPPER RESET SR
17 SPOT 9 (256) S9
- 215 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
39 NONE -
40 NONE -
41 NONE -
42 NONE -
43 NONE - 8 by 8
44 NONE -
45 NONE -
46 NONE -
47 NONE -
48 NONE -
49 NONE -
50 NONE -
51 NONE -
52 NONE -
- 216 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
53 NONE -
54 NONE -
55 NONE -
56 NONE -
57 NONE -
58 NONE -
59 NONE -
60 NONE -
61 NONE -
62 NONE -
63 NONE -
64 NONE -
OUTPU TAG
FIELDBUS OUTPUT BIT NAME BYTE SIZE
T# NAME
2 NO FAULT NFLT
3 NO ALERT NALT
- 217 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
17 NONE -
20 NONE -
23 NONE -
26 NONE -
29 NONE -
30 NONE -
31 NONE -
32 NONE -
33 NONE -
34 NONE -
35 NONE -
36 NONE -
37 NONE -
38 NONE -
39 NONE -
40 NONE -
41 NONE -
42 NONE -
43 NONE -
44 NONE -
45 NONE -
46 NONE -
- 218 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
47 NONE -
48 NONE -
49 NONE -
50 NONE -
51 NONE -
52 NONE -
53 NONE -
54 NONE -
55 NONE -
56 NONE -
57 NONE -
58 NONE -
59 NONE -
60 NONE -
61 NONE -
62 NONE -
63 NONE -
64 NONE -
- 219 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
C Press More.
- 220 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
E Press Reload
- 221 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 222 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
C Press More.
- 223 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
For Output Mapping follow the same procedure until step 4 and
press
- 224 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
2. FAULT RESET FR
4. NONE -
5. NONE -
6. NONE -
8. STEPPER RESET SR
15. NONE -
16. NONE -
17. NONE -
18. NONE -
19. NONE -
20. NONE -
21. NONE -
22. NONE -
23. NONE -
24. NONE -
25. NONE -
26. NONE -
27. NONE -
- 225 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
28. NONE -
29. NONE -
30. NONE -
31. NONE -
32. NONE -
33. NONE -
34. NONE -
35. NONE -
36. NONE -
37. NONE -
38. NONE -
39. NONE -
40. NONE -
41. NONE -
42. NONE -
43. NONE -
44. NONE -
45. NONE -
46. NONE -
47. NONE -
48. NONE -
49. NONE -
50. NONE -
51. NONE -
52. NONE -
53. NONE -
54. NONE -
55. NONE -
56. NONE -
57. NONE -
58. NONE -
- 226 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
59. NONE -
60. NONE -
61. NONE -
62. NONE -
63. NONE -
64. NONE -
OUTPUT
EIP OUTPUT BIT NAME TAG NAME
#
1. NO ALERT NALT
4. VALVE 1 V1
5. VALVE 2 V2
6. VALVE 3 V3
7. VALVE 4 V4
8. NONE -
9. NO FAULT NFLT
15. NONE -
16. NONE -
17. NONE -
18. NONE -
- 227 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
19. NONE -
20. NONE -
21. NONE -
22. NONE -
23. NONE -
24. NONE -
25. NONE -
26. NONE -
27. NONE -
28. NONE -
29. NONE -
30. NONE -
31. NONE -
32. NONE -
33. NONE -
34. NONE -
35. NONE -
36. NONE -
37. NONE -
38. NONE -
39. NONE -
40. NONE -
41. NONE -
42. NONE -
43. NONE -
44. NONE -
45. NONE -
46. NONE -
47. NONE -
48. NONE -
49. NONE -
- 228 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
50. NONE -
51. NONE -
52. NONE -
53. NONE -
54. NONE -
55. NONE -
56. NONE -
57. NONE -
58. NONE -
59. NONE -
60. NONE -
61. NONE -
62. NONE -
63. NONE -
64. NONE -
2. FAULT RESET FR
4. NONE -
5. NONE -
6. NONE -
8. STEPPER RESET SR
- 229 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
39. NONE -
40. NONE -
41. NONE -
42. NONE -
- 230 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
43. NONE -
44. NONE -
45. NONE -
46. NONE -
47. NONE -
48. NONE -
49. NONE -
50. NONE -
51. NONE -
52. NONE -
53. NONE -
54. NONE -
55. NONE -
56. NONE -
57. NONE -
58. NONE -
59. NONE -
60. NONE -
61. NONE -
62. NONE -
63. NONE -
64. NONE -
OUTPUT
EIP OUTPUT BIT NAME TAG NAME
#
1. NO ALERT NALT
- 231 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
4. VALVE 1 V1
5. VALVE 2 V2
6. VALVE 3 V3
7. VALVE 4 V4
8. NONE -
9. NO FAULT NFLT
15. NONE -
16. NONE -
17. NONE -
18. NONE -
19. NONE -
20. NONE -
21. NONE -
22. NONE -
23. NONE -
24. NONE -
25. NONE -
26. NONE -
27. NONE -
28. NONE -
29. NONE -
30. NONE -
31. NONE -
32. NONE -
33. NONE -
34. NONE -
- 232 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
35. NONE -
36. NONE -
37. NONE -
38. NONE -
39. NONE -
40. NONE -
41. NONE -
42. NONE -
43. NONE -
44. NONE -
45. NONE -
46. NONE -
47. NONE -
48. NONE -
49. NONE -
50. NONE -
51. NONE -
52. NONE -
53. NONE -
54. NONE -
55. NONE -
56. NONE -
57. NONE -
58. NONE -
59. NONE -
60. NONE -
61. NONE -
62. NONE -
63. NONE -
64. NONE -
- 233 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
I/O MAPPING The WT6000 is designed with Flexible I/O. This means the user has
the capability of reconfiguring the I/O to meet the requirements of a
particular application. There are 16 configurable inputs and 10
configurable outputs.
C Press More
- 234 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
D Press More
E Press Fieldbus Mapping
- 235 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 236 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
J Press ENTER
- 237 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 238 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 239 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
C Press More
- 240 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
D Press More
- 241 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 242 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
I Press ENTER
- 243 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 244 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
N Press Execute
- 245 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 246 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
The steps to re-configure the EIP I/O Mapping is identical to the steps
to re-configure the FieldBus I/O Mapping. First, follow the steps
below to navigate to the EIP Options Menu on the DEP-300s. Then
follow the steps explained in the previous pages on either FieldBus
Input Mapping or FieldBus Output Mapping (whichever is applicable).
C Press More
- 247 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
Output Mapping
- 248 of 248/Chp11_inputsoutput.fm -
M032300 V4.0/ G08600-00-13_10/2014
RAFTTM HARDWARE In order to use the RAFT adaptive welding, the installation
INSTALLATION of voltage sense wires between the gun tips and the weld control
cabinet are required. Stainless steel terminals, cables and fasteners are
used at the weld gun to minimize cable failure caused by snagging and
wear due to gun and wrist movement. On a typical robot installation,
stainless steel cables are installed from the gun back to the robot arm/
wrist. At that point, the stainless steel cables are terminated to a
two-conductor copper cable (shielding is optional). The two-conductor
copper cable continues back to the weld control cabinet, where it is
terminated at the weld processor. Service connections can be made for
easier cable replacement but no more than 5 connections are
recommended. The use of the copper cable is a cost effective
alternative to running stainless steel cable all the way back to the weld
control cabinet.
- 249 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
• Place the
wires near the
water ports
located on the
welding gun
arms. This
area is ideal
since it is
unlikely to get
damaged over
time and the
resistance will
be constant.
• The secondary
voltage tip
wires are
required to be
installed
before the cap
adapter and
after the leaf
shunts. The
leaf shunts
will break over
time changing
their
resistance
which will
adversely
effect the
feedback
signal.
NOTE: This drawing is a general guide for installation. Specific installation is the responsibility of the customer
- 250 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
ADAPTQ HARDWARE
SETUP WITH VOLTAGE
SENSE WIRES
SETUP SOFTQ
- 251 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
WARNING!
If application requires
either the linear
stepper function to be
turned off (0=OFF) or
the stepper group
number to be changed,
a new R Measure
procedure must be
performed to ensure
the correct R Measure
data is stored in the
new stepper group.
- 252 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
Assign the
correct Stepper
number in the
weld schedule
Assign the
correct Group
number in the
stepper profile
REFERENCE TABLE
For portable gun welding WELD GUN # ASSIGN STEPPER # ASSIGN GROUP #
applications:
1 1 1
Gun1 = (Stepper #1 / Group #1)
Gun2 = (Stepper #2 / Group #2) 2 2 2
3 3 3
4 4 4
- 253 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
Program the
weld
function in
the weld
schedule for
210ms or 13
cycles at
10K amps.
D Install new weld caps on the gun or dress the caps depending on
the application.
E Verify that 2.7kN or 600 lbs. of force will be present at tips when
the weld schedule is initiated.
F Reset Steppers.
G Initiate the weld schedule and verify that the R Avg. (Resistance
Average) value is between 30 and 150 micro-ohms. (Ex. R Avg. 52
micro-ohms). Repeat 2-3 times and ensure the R Avg. value is
stable.
- 254 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
If the R Avg is
1000 Micro-
ohms, the
polarity of the
tip wires is
incorrect at the
weld timer.
Swap the tip
wires at the weld
timer (Pins 1&2
of the SEC I/V
connector)
The Gun Resistance Measurement has now been established and the
R Measure weld procedure is complete. R Measure is enabled for only
one weld and then turns off automatically. RAFTstores the R
Measure data in the stepper group # that was assigned.
- 255 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
REFERENCE WELD After establishing the R Measure, the next step in the RAFTGateway
procedure is setting the Reference weld.
A reference weld is the stored Constant Current (CC) weld data set
that AdaptQ™ compares the weld in process to.
- 256 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
RE
RP
MELTING PHASE FINAL NUGGET GROWTH
NUGGET GROWTH
COUPLING PHASE
- 257 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
3. Averaging a Reference.
• Averaging multiple weld graphs in the History/Graphs/
Spot tab.
4. Duplicating a Reference
• Duplicate schedule references through the Editor tab.
5. Download a Reference
• Download a .wdf reference file from a timer Status page.
- 258 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
1. TAKING A B Left click mouse on the Timer tab that reference welds will be
REFERENCE taken on.
WELD DURING
A PART RUN
C In the Status screen, left click mouse “Ref. is OFF” button which
will then change to “Ref. is ON”.
ONCE THE “REF. IS ON” BUTTON IS PRESSED AGAIN ONLY THE LAST WELDS
MADE WHILE REFERENCE WAS ON WILL BE STORED.
- 259 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
Situation A:
Ref. is ON and 10 welds are made.
The weld control will fire the schedules in order from 1 to 10.
When Ref Mode is turned OFF, these welds will be saved as
Reference welds, each with its own schedule.
Situation B:
Part 1
Schedules 1 to 5 are fired before Ref. Mode is turned ON.
Then schedules 6 to 10 are fired.
Part 2
The process is restarted with a new part where all 10
schedules are fired, in order this time. Reference mode is
turned OFF after the last weld on Part 2.
None from the Part 1. Although schedules 6-10 were executed after
the Ref mode was turned ON, the welds were overwritten by the
same schedule # welds made on part #2.
For schedules 1 to 5, only the Part 2 welds were captured and saved
as reference welds.
NOTE: Reference must be turned OFF for the reference weld data
to be stored into memory of the weld timer as a Reference
weld. Loading references to the weld timer may take several
seconds and will disable the timer momentarily.
- 260 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
VERIFY ALL WELDS MADE WHILE REFERENCE IS TURNED ON, SATISFY THE
REQUIREMENTS BELOW:
- 261 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
2. CREATING A The History/Graphs/Spot tab displays many logged welds. Open the
SINGLE REFERENCE spot data for the weld that you want to reference.
WELD FROM
PAST WELD
DATA
Double click on
the weld to view
the weld graph
Check all welds that were made satisfy the requirements below:
• Had NO expulsion.
• Had the proper R Drop for the metal being welded (15-30%
for galvanized and 30-50% for bare metals).
In case of expulsion – Decrease the weld current and
make another weld with the programmed weld schedule.
In case the R Drop is low – Increase the weld current
and make another weld with the programmed weld
schedule.
In case R Drop is high – Decrease the weld current and
make another weld with the programmed weld schedule.
- 262 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
Expulsion
icon and the
time of the
expulsion
detected
during the
weld.
- 263 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
3. AVERAGING A Select multiple welds of the same schedule with the same time and
REFERENCE current programmed from the History/Graphs/Spot screen.
WELD
- 264 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
Highlight the
selected weld
spots. Right
click and select
“Compare with
Each Other”. All
the welds
selected will
now be overlaid
in one weld
graph window. Note: “Create
Reference”
button is only
available
AFTER the
Average
Resistance
curve is
generated.
- 265 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
4. DUPLICATING
A REFERENCE
WELD
- 266 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
5. DOWNLOAD A
REFERENCE WELD
C A pop-up window will appear. Select the backup file. Then Click
“Open”.
D Uncheck all data types by clicking the Timer Data check box.
- 267 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 268 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 269 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
Preheat: 0.7mm HDG / 1.5mm HDG / 1.5mm HDG (all MILD), R Drop = 22.8
- 270 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
BEGIN RAFT
ADAPTIVE
WELDING
- 271 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 272 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
TUNING THE Follow the procedure below to tune the RATE% and WSLIDE%
ADAPTIVE WELD parameters in the main adaptive function ADAPTQ MODE=1
SCHEDULE RATE=100% WSLIDE=100%.
- 273 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 274 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
SOFTQ OVERVIEW SOFTQ is a RAFTTM feature that alerts the weld engineer/maintenance
staff when the weld process has changed. Examples of process change
include missing part, extra part, changes in water cooling, tip dress
cutter failure, tooling wear, etc.
The weld engineer selects the group of welds from which the
benchmark will be created. This group of welds should include all the
“normal” disturbances, i.e. cap wear, part placement and fit-up
variations.
- 275 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROCESS Process Integrity (P-Integrity) is a percentage value provided post
INTEGRITY (PI) weld, which represents the quality of the last weld as compared to
the Reference Weld. Process Integrity also identifies weld nuggets,
which may be undersized based on a lower percentage.
The SoftQ module allows users to set limits for acceptable Process
Integrity values, as defined in SoftQ monitoring and trending within
the RAFTTM Gateway software.
- 276 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
The SoftQ module allows users to set limits for acceptable Tooling
Integrity values, as defined in SoftQ monitoring and trending within
the RAFTTM Gateway software.
- 277 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
If reference weld nugget diameter avg. was 6.0 mm, then a weld with
NI=120 will generate a 6.0 x 1.2 = 7.2 mm avg. diameter nugget.
In the tip life cycle of a stable welding process, typical NI values are
from 80% to 120%.
- 278 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
RAFT TMMENU The RAFTTM Menu allows the user to view RAFTTM data and perform
(DEP-300S) certain RAFTTM functions. This feature is customer application specific
and may be inaccessible. For more information, see the DEP-300s
manual PN: M-035030.
C Press RAFT
- 279 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 280 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
The following describes the data tags displayed in the RAFTTM Status
Menu:
NOTE: The data displayed in this menu may vary depending upon the
customers’ application requirements. For application specific
information, consult the weld processor Firmware Manual.
h Total heat
PI Process Integrity
e Total energy
NI Nugget Integrity
TI Tooling Integrity
RA Average Resistance
RD Resistance Drop
RE End Resistance
- 281 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
WELD DATA MENU The Weld Data Menu allows the user to view various Weld and
(DEP-300S) RAFTTM data values, which occurred during the last weld.
In the above example of the DEP-300s Weld Data Menu, the data
circled in blue is Constant Current and Percent of Available Volt-
Seconds weld data. The data circled in red is RAFTTM weld data.
The following describes the data tags displayed in the DEP menu:
WELD DATA
- 282 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
RAFTTM DATA
h Total heat
PI Process Integrity
e Total energy
NI Nugget Integrity
TI Tooling Integrity
- 283 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
RAFTTM SCHEDULE The following is a list of all the RAFTTM AdaptQ and SoftQ functions
FUNCTIONS that can be programmed in the weld schedule.
This function is inserted in the weld schedule when using the AdaptQ fea-
PORTABLE GUN MODE ture to weld various metal stack-up thicknesses with one schedule. This
function should be inserted before the weld function.
This function sets the percent of resistance drop at which an ADAPTQ GAP
CONDITION FAULT is set. This is used in applications where it is necessary to
GAP RULE RD=nn eliminate false gap detection. This function overrides the default percent-
age of resistance drop set in the software.
Range: 15-99%
Default = 15
This function is used to provide higher detailed data to the RAFTTM Gateway
DETAIL MODE network gateway software.
3T MODE This function allows more or less current to be added at the beginning of
the weld, based on the part resistance versus the reference weld resistance.
No current changes will occur until the end of the blanking time.
This function is added into the schedule when the operator knows that edge
welding will occur, but still wants to accept the integrity of the nugget. An
EDGE WELD edge weld results in a number of milliseconds of heat falling under the heat
of the reference weld. Adding this function into the schedule prevents the
Nugget Integrity (NI) from changing (typically decreasing) when this occurs.
This function should be inserted before the weld function.
This function is inserted in the weld schedule when welding advanced high
HIGH STRENGTH STEEL strength steels (tensile strength > 600MPa). Because high strength steels
MODE have a small current welding window, this function modifies the algorithm
so that the current increases gradually.
- 284 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
NOTE: For information regarding the setup of the Master Offset Resistance,
see AdaptQ Welding Startup Procedure above.
MODE: This parameter turns the RAFTTM AdaptQ module either ON or OFF
for the weld schedule it is inserted into.
Range: 0-1
1=Adaptive welding mode
ADAPTQ MODE=nn
0= Constant Current Mode
RATE=nnn%
RATE: Adjusts the current control levels of the adaptive weld. The default
WSLIDE=nnn%
value is 100%.
Range: 90-120%
WSLIDE: Adjusts the Reference Resistance Drop and the Reference Total
Energy target. The default value is 100%.
Range: 95-105%
NOTE: This function must be inserted in the weld schedule prior to the
weld function and is typically the first function in the schedule.
- 285 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
IMX (Current Max): Sets the maximum secondary current limit for the adap-
tive weld (in amps).
Range:0-25,500A
IMN (Current Min): Sets the minimum secondary current limit for the adap-
tive weld (in amps).
Range: 0-25,500A
TMX (Time Max): Sets the maximum limit the AdaptQ algorithm will extend
ADAPTQ IMX=nnnn0 the weld time (in milliseconds) to achieve the Reference Weld energy and
IMN=nnnn0 TMX=nn produce a good weld.
CY Range: 0-60 CY
Range: 0-1000 MS
Programming Example:
ADAPTQ IMX=8000 IMN=7000 TMX=30 CY
WELD 15 CY. 7500 AMPS
Range: 0-2
ROBOT MODE=nn 0= Disabled
ROBOT MODE=1: Designed for very thin stack-ups 1.4 mm or below.
ROBOT MODE=2: Designed for materials with heavy coatings and higher tip
contamination. After 100 welds, the starting current of the schedule is auto-
matically increased and the adaptive current decrease is limited.
- 286 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROGRAMMABLE/
FAULT NON- POSSIBLE CAUSE SOLUTIONS
PROGRAMMABLE
Occurs when the voltage sense Verify the voltage sense wires coming
wires that run between the gun from the weld gun are properly con-
tips and the weld processor are nected to the weld processor.
ADAPTQ either broken, loose or discon-
TIP VOLT FAULT/ALERT/NONE nected.
WIRE
BROKEN DEAFAULT: FAULT Alert/ None levels are only avail-
able for Constant Current weld-
ing. For an adaptive mode weld,
the Fault level will be generated
even when this parameter is set
as Alert/ None.
- 287 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROGRAMMABLE/
FAULT NON- POSSIBLE CAUSE SOLUTIONS
PROGRAMMABLE
- 288 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROGRAMMABLE/
FAULT NON- POSSIBLE CAUSE SOLUTIONS
PROGRAMMABLE
ADAPTQ Occurs if a Reference Weld was Perform a Reference Weld for the
NO REF- Non- not performed prior to executing appropriate metal stack-up.
ERENCE Programmable an Adaptive Weld.
WELD DEFAULT: FAULT
- 289 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROGRAMMABLE/
FAULT NON- POSSIBLE CAUSE SOLUTIONS
PROGRAMMABLE
- 290 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROGRAMMABLE/
FAULT NON- POSSIBLE CAUSE SOLUTIONS
PROGRAMMABLE
- 291 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROGRAMMABLE/
FAULT NON- POSSIBLE CAUSE SOLUTIONS
PROGRAMMABLE
- 292 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROGRAMMABLE/
FAULT NON- POSSIBLE CAUSE SOLUTIONS
PROGRAMMABLE
Occurs when the SOFTQ level is 1 Verify the SOFTQ N-Integrity hard limit
setup and enabled for N-Integ- window is set correctly under normal
rity, and the average N-Integrity conditions.
exceeds the SOFTQ hard limit
SOFTQ N- FAULT/ALERT window (either high or low). 2 Verify a part disturbance doesn’t exist,
INTEG- NOTE: i.e. excessive gap, stack-up change,
RITY DEFAULT: ALERT Applies only if the SOFTQ Fault poor tip dressing, etc.
Enable check box is enabled in
the RAFTTM Gateway software.
- 293 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROGRAMMABLE/
FAULT NON- POSSIBLE CAUSE SOLUTIONS
PROGRAMMABLE
Occurs when the SOFTQ level is 1 Verify the SOFTQ current trend limit
setup and enabled for current, window is set correctly under normal
and the number of exceptions conditions.
that occurred outside the SOFTQ
trend limit window (either high 2 Verify the Sample Size parameter is
SOFTQ or low), exceeded the trend limit set correctly for each weld schedule in
CUR- FAULT/ALERT while within the trend sample the RAFTTM Gateway software.
RENT size.
TREND DEFAULT: ALERT 3 Verify the Exceptions parameter is set
NOTE 1: correctly for each weld schedule in
Applies only if the SOFTQ Trend the RAFTTM Gateway software.
Enable check box is enabled in
the RAFTTM Gateway software. 4 If the SOFTQ Current Trend Fault
occurs in conjunction with a Current
NOTE 2: Regulation or Low Current Limit Fault,
Normally, the trend window is then follow the troubleshooting pro-
set inside the fault limit win- cedure for the respective fault in the
dow. manual.
When the value of a parameter
falls outside the fault window,
both fault and trend conditions
are generated,
Example:
SOFTQ CURRENT
SOFTQ CURRENT TREND
- 294 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROGRAMMABLE/
FAULT NON- POSSIBLE CAUSE SOLUTIONS
PROGRAMMABLE
- 295 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROGRAMMABLE/
FAULT NON- POSSIBLE CAUSE SOLUTIONS
PROGRAMMABLE
- 296 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROGRAMMABLE/
FAULT NON- POSSIBLE CAUSE SOLUTIONS
PROGRAMMABLE
- 297 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROGRAMMABLE/
FAULT NON- POSSIBLE CAUSE SOLUTIONS
PROGRAMMABLE
- 298 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROGRAMMABLE/
FAULT NON- POSSIBLE CAUSE SOLUTIONS
PROGRAMMABLE
- 299 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
PROGRAMMABLE/
FAULT NON- POSSIBLE CAUSE SOLUTIONS
PROGRAMMABLE
NOTE: Applies only if the SOFTQ 4 Verify a part disturbance doesn’t exist,
Trend Enable check box is i.e. excessive gap, stack-up change,
enabled in the RAFTTM Gateway etc.
software.
- 300 of 300/Chp12_RAFT.fm -
M032300 V4.0/ G08600-00-13_10/2014
SCHEDULE The default function timing for Schedule Functions is in Cycles (CY). To
FUNCTIONS change the function timing to Milliseconds (MSEC), perform the
following steps on the DEP-300s:
Press More
- 301 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
Press ENTER
- 302 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
Press ENTER
Press Execute.
This begins the process to
download the change to the weld
processor.
- 303 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 304 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
FUNC. CATEGORY
FUNCTION NAME
#
6 “*”
9 “*”
10 “*”
11 “*”
12 “*”
15 “*”
25 “*”
26 3T MODE RAFT™
- 305 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
28 “*”
29 “*”
35 “*”
36 “*”
38 “*”
41 “*”
42 “*”
44 “*”
48 “*”
49 “*”
- 306 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
83 “*”
84 “*”
87 “*”
- 307 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
96 “*”
DELAY FUNCTIONS Delay functions cause a delay (or wait) time to occur in the weld
schedule for a specified length of time. All delay functions essentially
perform the same function, but are assigned different names to
describe their purpose in the welding process. During delay functions,
weld current does not flow and I/O status does not change.
- 308 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
CATEGORY
FUNC. # FUNCTION NAME
CATEGORY
FUNC. # FUNCTION NAME
- 309 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
MAIN WELD In the following Volt-Second Mode example, the processor will weld
FUNCTION (#20) for 20 cycles at 65% volt-seconds:
MAIN WELD In the following Constant Current Mode example, the processor will
FUNCTION (#30) weld for 20 milliseconds at 10000A current:
- 310 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
TEMPER, PRE HEAT, Temper, Pre-Heat, Post-Heat and Pre-Weld are material heating
POST HEAT AND functions and are inserted either before or after main weld functions
PRE WELD (#20 or #30). They all essentially perform the same function, but are
FUNCTIONS assigned different names to describe their purpose in the welding
process. These functions are not figured into the weld data collection
algorithm. For example:
When the weld sequence is complete, the last weld data in the Weld
Data Menu will display 10,000 Amps. As mentioned above, the pre-
heat function is not figured in the weld data collection algorithm.
When the weld sequence is complete, the last weld data in the Weld
Data Menu will display 7,500 Amps. This is because when two or
more weld functions are used in the same weld schedule, the weld
data collection algorithm calculates the average current for all the
weld functions and displays the results.
- 311 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
IMPULSE WELDING weld processor software G08300 offers two different methods of
FUNCTION pulsation (impulse) welding. The first method has NO-HEAT cool times
between the impulses and the second has LOW-HEAT cool times
between the impulses.
60 IMPULSE= nnnn HEAT CY nn COOL CY Impulse heat and cool times in cycles
Function #60 defines the length of the impulse heat time and the
length of the cool time between each impulse.
In the example below, the weld processor will weld (heat) for 10
cycles at 65% volt-seconds, then wait (cool) for 10 cycles. This heat
and cool impulse pattern will occur (4) times. As illustrated in the
timing chart, no current is flowing during the cool times.
- 312 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
60 IMPULSE= nnnn HEAT CY nn COOL CY Impulse heat and cool times in cycles
Function #60 defines the length of the impulse heat time and the
length of the cool time after each impulse. Function #30 defines the
number of impulses and the amount of current during each impulse
and the LOW current during each cool time.
In the example below, the weld processor will weld (heat) for 10
cycles and then wait (cool) for 10 cycles. This heat and cool impulse
NOTE: Although
function #60 is pattern will occur (4) times at 10,000 Amps during each impulse and
typically used in 5000 Amps during each cool time.
conjunction with
main weld functions
(#20 or #30), it can
also be used before 60 IMPULSE= 10 HEAT CY 10 COOL CY
any weld or slope 37 WELD 4 IMP HI=10000 A LO=5000A
function.
- 313 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
SLOPE FUNCTIONS Slope functions are used when either a linear increase (Up-Slope) or
decrease (Down-Slope) in welding current is required over a specified
amount of time.
SLOPE FUNCTION (VOLT-SECOND MODE)
40 SLOPE nn CY. nn%VS TO nn%VS Slope time in cycles from percent volt-second
1 (nn%VS) to percent volt-second 2 (nn%VS)
SLOPE FUNCTION (CONSTANT CURRENT MODE)
45 SLOPE nn MS. nnnn0 A TO nnnn0 A Slope time in milliseconds from current value
1 (nnnn0 A) to current value 2 (nnnn0 A)
- 314 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
In the following up-slope weld example, the weld processor will begin
welding at 35% volt-seconds and increase to 65% volt-seconds over a
40 cycle time period. Then the processor will weld at 65% volt-
seconds for 20 cycles.
NOTE: Just as the heat functions mentioned above, the slope functions are
not figured into the weld data collection algorithm. Therefore, their value is
not averaged into the last weld data viewed in the Weld Data Menu
- 315 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
I/O FUNCTIONS I/O functions are used to verify the status of, change status of, or wait
for certain I/O points to change states before continuing with the
weld schedule.
INPUT FUNCTIONS
67 WAIT FOR INPUT #n TO BE n (0 =OFF 1= ON) This function waits for the specified User Input bit
(1-6) to go either OFF (0) or ON (1). If the Weld Ini-
tiate input bit goes LOW before this occurs, a
WELD PROCEED FAULT is generated.
- 316 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
69 WAIT FOR PRESSURE SWITCH INPUT This function waits for the Pressure Switch bit to
go HIGH.
70 WAIT nnnn MS FOR WELD PROCEED INPUT This function waits for the specified amount of
time (milliseconds) for the Weld Proceed bit to go
HIGH. If the bit does not go HIGH during this time
period, a WELD PROCEED FAULT is generated.
71 WAIT FOR WELD PROCEED This function waits for the Weld Proceed bit to go
HIGH.
72 SET VALVE n TOUCH DOWN PRESSURE nnnn This function sets the specified valve bit (1-2) to
PSI the specified touch down pressure in PSI.
73 SET VALVE n TIP DRESS PRESSURE nnnn PSI This function sets the specified valve bit (1-2) to
the specified tip dress pressure in PSI.
- 317 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
74 WAIT nn MS FOR PRESSURE ACHIEVED This function waits for the number of milliseconds
specified for the cylinder pressure to be achieved.
If the pressure is not achieved during this time
period, a PRESSURE NOT ACHEIVED FAULT is gener-
ated.
79 WAIT nnnn MS FOR SYSTEM COOLING This function waits the specified amount of time
(milliseconds) for the System Cooling bit to go
HIGH. If the bit does not go HIGH during this time
period, a SYSTEM COOLING FAULT is generated.
86 TIP DRESS ADVANCE: GROUP nn - STEP n This function advances all the steppers assigned to
the specified GROUP number, to the specified STEP
number.
OUTPUT FUNCTIONS
55 TURN OFF PRESSURE SELECT n Turn OFF Pressure Select bit (1-4).
- 318 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
57 TURN OFF CONTACTOR SELECT n Turn OFF Contactor Select bit (1-6)
64 TURN OFF WELD COMPLETE Turn off the Weld Complete bit.
79 TURN OFF FORGE VALVE Turn off the Forge Valve bit.
80 FORGE DELAY nnn MSEC Inserted in the weld schedule before function
#78 (TURN ON FORGE VALVE), this function
delays turning on the Forge Valve bit for the
number of milliseconds specified
89 TURN OFF ISOLATION CONTACTOR Turn off the Isolation Contactor bit.
EXTEND FUNCTIONS Extend functions are used to extend a function under certain
conditions.
75 EXTEND UNTIL NO INITIATE This function tells the processor to monitor the
status of the Weld Initiate bit and to repeat the
previous function in the weld schedule until the
Weld Initiate bit goes LOW.
- 319 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
The following is an example of an extend function in a weld schedule:
- 320 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
SPECIAL FUNCTIONS Special functions are used to either create special conditions inside
the welding schedule, set local schedule features that over-ride global
setup parameters or to chain multiple weld schedules together.
16 MOTOR CURR LIMITS HI =nnnn Used in a tip dress schedule, this function sets the
HIGH and LOW current limits (in milliamps) for the
tip dress motor. For more information see "Tip
Dress Schedule Setup" in Ch 9 Advanced Topics.
17 TIP DRESS TIME nn SEC BLANK nnnn ms Used in a tip dress schedule, this function tells the
weld processor to start measuring the current
draw of the tip dress motor for the number of sec-
onds specified. In addition, it identifies the blank-
ing time. This is the time period at the start of the
function, during which the motor current is not
measured. For more information see "Tip Dress
Schedule Setup" in Ch 9 Advanced Topics.
18 START TIP DRESS MOTOR CHECK Used in a tip dress schedule, this function tells the
weld processor to turn the tip dress motor ON. For
more information see "Tip Dress Schedule Setup "
in Ch 9 Advanced Topics.
19 STOP TIP DRESS MOTOR CHECK Used in a tip dress schedule, this function tells the
weld processor to turn the tip dress motor OFF. For
more information see "Tip Dress Schedule Setup "
in Ch 9 Advanced Topics.
- 321 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
82 LINEAR STEPPER #nn ASSIGNED (0 = OFF) This function assign linear stepper 1-10 (0=OFF).
- 322 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 323 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
- 324 of 325/Chp13_Schd_Func.fm -
M032300 V4.0/ G08600-00-13_10/2014
00 START OF SCHEDULE # 1
54 TURN ON VALVE 1
01 SQUEEZE 15 MSEC
03 HOLD 02 MSEC
03 HOLD 10 MSEC
- 325 of 325/Chp13_Schd_Func.fm -
GLOSSARY
C-Factor
C-Factor (or Capacity Factor) is a parameter, which is used to track changes in the weld tooling.
C-Factor is calculated by determining the amount of total capacity utilized to create the target
current and dividing this value by the actual current created. The C-Factor feature can be used
as a maintenance tool to monitor weld tooling degradation and current shunting paths
(primary or secondary).
ENET
ENET is used for Standard Ethernet communications.
ENET IP
ENET IP is used for I/O communication between the weld processor and other Ethernet enabled devices
(e.g. a Robot or PLC). Also used to communicate with Weld Gateway and RAFT Gateway networking
software.
FieldBus I/O
Configuration of fieldbus input output of the weld processor. Fieldbus network system is a real-
time distributed control for industrial networks. Fieldbus works on a network structure which
typically allows daisy-chain, star, ring, branch, and tree network topologies. Fieldbus
communication scheme gives the weld processor the ability to control and allow multiple
analog and digital points to be connected at the same time.
LIO
Local (Discrete) I/O. Inputs - 2 x 24VDC Outputs - 3 x 120VAC
Schedule
A (Weld) Schedule is a list of commands or functions which are used to instruct the weld
processor to deliver a combination of heat (weld current) and time (weld time) to the weld
interface to create a weld nugget.
SSPI
WTC Proprietary I/O Communication Protocol (Optional) . SSPI supports communication with optional
WTC I/O peripheral devices.
326
SPC - Statistical Process Control
SPC data collection and binning provides the capability of compiling weld data within pre-
defined criterion established in the Setup Parameters.
Spot
Another name for a weld.
Spot ID
User assigned unique identification number that defines a specific spot created with a weld
schedule. This feature is only available with certain software.
Station ID
User defined identification number for the weld interface.
V Avg
Average secondary voltage drop of the last weld.
WebView
An interconnect between the RAFT™ Gateway and WTC legacy weld timers that use either
serial networks or are otherwise not compatible with the RAFT™ Gateway.
327
Notes:
328
Welding Technology Cor por ation
329