Module 5
Module 5
Location
The UPS installation location should be chosen with care. The type and amount of site
preparation required will vary according to the specific location and its relative location to the
connected load. Preferably the UPS has to be installed close to the loads. If the distance
between the load and the UPS is higher, we must consider the voltage drop based on the
distance of the cable and suitable action like over sizing the cable needs to be considered.
It is important that adequate floor space has to be provided for the UPS. Check the
dimensional information on the appropriate data sheets for the floor space requirements. The
UPS equipment can be mounted with the back against a wall if rear access is not specifically
required; however, if side and rear access can be maintained, it may be helpful should service
become necessary. However, the requirement of rear clearance will be based on the
construction of UPS. If the UPS is of modular construction, then a rear clearance is
mandatory.
UPS system produces heat, which must be removed to prevent the UPS temperature from
rising to an unacceptable level. Selection of air conditioner for UPS room requires an
understanding of the amount of heat produced by the UPS. Heat is energy and is commonly
expressed in Joules, BTU, tons, or calories. common measures of heat output rate for
equipment are BTU per hour, Tons per day, and Joules per second (Joules per second is equal
to Watts)
Step 1:
Multiply the length of UPS room by its width, which will gives us the total area of the room.
Based on the below table, the basic capacity in BTU/Hr required for the UPS room can be
calculated
Step 2: Arrive at the no of person who will work in the UPS room
Generally the UPS room is unmanned apart from the time when the technician visits to
service the UPS or during the visit of maintenance engineer. It is ideal to consider 600
BTU/Hr per person to arrive at the air conditioner capacity of the UPS room.
To arrive at the capacity of the air conditioner required for UPS, we need to calculate the heat
loss of UPS in KW using the formula
It is imperative to select and specify the correct type and size of cabling in UPS installations.
Failure to do so can result in overheating, fire risk and premature failure. It is also important
to select the best method of installation alongside the most optimum routing. The same cable
sizes should be installed for input and output and the selected cable should provide
continuous full thermal current rating. A site survey will reveal the length of cable required
and what voltage drop should be catered within the project specification and what size lugs
are required.
3. highlight the types of batteries which are compatible with the UPS
There are three main types of batteries used for UPS, or uninterruptible power
supplies: Lead-Acid, Nickel-Cadmium, and Lithium Ion. There is not a single “best” type of
UPS battery. The choice of which one to use should be made on a case-by-case basis.
For UPS compatibility, the main battery types are Lead-Acid (VRLA/Flooded), Nickel-
Cadmium (NiCd), and Lithium-ion.
Here's a more detailed breakdown:
Lead-Acid Batteries:
Valve Regulated Lead Acid (VRLA): Also known as sealed lead-acid (SLA) batteries, these
are the most common type in modern UPS systems. They are sealed to prevent leakage and
have a valve to release gas pressure.
Vented Lead-Acid (VLA): Often referred to as flooded batteries, these are reliable and offer a
longer lifespan than VRLA, but require a separate battery room and present some safety
concerns.
Nickel-Cadmium (NiCd) Batteries:
These batteries are durable and can operate in a wide range of temperatures.
They can endure a high number of charge-discharge cycles.
However, their use has declined due to environmental concerns over the toxicity of cadmium.
Lithium-ion Batteries:
These batteries are a significant improvement over lead-based options.
They have a longer lifespan and a higher depth of discharge, meaning you can use the battery
for longer in each cycle.
There are many different material options for the lithium-based electrode, leading to various
types of lithium batteries.
Lithium Iron Phosphate (LiFePO4) is a popular option due to its long lifespan and high depth of
discharge.