Building Permit CHECKLIST

The document is a comprehensive checklist for building permit applications in Cebu City, Philippines, detailing required documents across various sections including civil/structural, mechanical, plumbing, electrical, electronics, and architectural. It specifies necessary clearances, certifications, plans, and analyses that must be signed and sealed by licensed professionals. The checklist aims to ensure compliance with local regulations and standards for construction projects.

Uploaded by

wwogunner
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4 views

Building Permit CHECKLIST

The document is a comprehensive checklist for building permit applications in Cebu City, Philippines, detailing required documents across various sections including civil/structural, mechanical, plumbing, electrical, electronics, and architectural. It specifies necessary clearances, certifications, plans, and analyses that must be signed and sealed by licensed professionals. The checklist aims to ensure compliance with local regulations and standards for construction projects.

Uploaded by

wwogunner
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

REPUBLIC OF THE PHILIPPINES

OFFICE OF THE BUILDING OFFICIAL


CEBU CITY
Telephone Numbers: 255-7960 and 255-4045
BUILDING PERMIT APPLICATION CHECKLIST
LINE AND GRADE / GEODETIC SECTION CIVIL / STRUCTURAL DOCUMENTS
☐Inspection Report: ☐Updated PTR and PRC ID of Civil/ Structural Engineer
☐___________________________ ☐Boring test or final report on Geotechnical
☐CITOM Clearance (if applicable) for Cebu City Roads Investigation of buildings (3 storey and higher) (Soil
☐DPWH Clearance (if applicable) for National Roads bearing capacity used in the analysis must be equal or
☐MPW Form No. 77-008-B-Affidavit-For Building Lots less than recommended value)
affected by Road Widening and other Proposed ☐Structural Analysis and Design for all buildings/
Development Projects structures signed and sealed at first and last page by
☐Certified True Copy (original) of Transfer Certificate of Structural Engineer and Owner (2 - storey and higher)
Title (TCT) (footing, column, beam/ roof beam, girder, slab, truss,
☐ _____________________________ rafter, stair, independent firewall, retaining wall and
☐Certified True Copy (original) of LAND Tax riprap)
Declaration Renovation / Addition:
☐Updated Certified True Copy (original) of LAND Tax ☐Plans coincide with other plans of all sections
Clearance ☐Certification from the Civil/ Structural Engineer that
☐Original Barangay Clearance existing structure is safe to carry additional load and
☐Original SRP Clearance (If applicable) structural analysis (for additional floor)
☐Homeowners Clearance. If none, Affidavit of No ☐As-built plan of existing structure (for building
Homeowners renovations – if applicable)
☐Corporation Secretary Certificate or Corporation
Board Resolution MECHANICAL SECTION
☐DTI Certificate for Sole Proprietorship (If applicable) ☐Mechanical plans coincide with other plans of all
☐Special Power of Attorney for the Authorized sections signed and sealed
Representative (notarized)
☐Mechanical permit forms signed and sealed
☐Lot owner Consent and Authority (notarized) or
Notarized Deed of Absolute Sale or Notarized Lease ☐Updated PTR and PRC ID of PME
of Contract For Residential
☐Extra Judicial Settlement (If applicable) ☐Mechanical Plans for the following:
☐Lot Co-owners notarized Consent and Authority (Generator Set, Window Type AC, Package ACCU
☐Sketch Plan signed and sealed by Geodetic Engineer units, Water Pump, Water Heaters, any motorized
☐Technical Description Details at Sketch Plan (coincide equipment) if applicable
with TCT) For Commercial
☐ ____________________________________ ☐Mechanical plan and details for air conditioning
Encroachment (reflected at site dev and sketch plan) system
☐ ____________________________________ ☐Mechanical plan and details for the entire sprinkler
Technical Description at Site Development Plan System Including firefighting accessories and
(reflect boundaries, monuments, lot name, hydraulic calculation
lot area) ☐Mechanical plan and details for passenger elevator,
☐ ____________________________________ escalator, freight, conveyors, dumbwaiters, and car
FOR RENOVATION: lifts together with design computations
☐Occupancy Permit of the Building ☐Mechanical plan for Generator set
☐If no occupancy permit,
☐Certified True Copy (original) of Land and PLUMBING / SANITARY SECTION
Building Tax Declaration ☐Plumbing plans coincide with other plans of all
☐Certified True Copy (original) of Land and sections signed and sealed
Building Tax Declaration ☐Plumbing Permit Forms signed and sealed
☐Certified True Copy (original) of Transfer ☐Updated PTR and PRC ID of RMP/ SE
☐Certificate of Title ☐Drainage Tapping Permit from DEPW/TIC Office – for
☐ Lease of Contract (if applicable) Cebu City roads and National roads (CO 2135)
☐Plumbing Design Analysis and Computation (2 copies)
STRUCTURAL / CIVIL SECTION signed and sealed by RMP/ SE for 20 water closets
☐Structural plans drawn to scale and coincide with and more in the project)
other plans of all sections signed and sealed
☐Structural plans coincide with the structural analysis Rainwater tank blow up plans/ details (CO 1711)
(prepared by same practitioner) ☐Residential (3.00 cu.m. capacity)
☐Foundation Plan/s and Details (No overlapping ☐Commercial (7.00 cu.m. capacity)
footings and encroachments to other property) ☐Plumbing Locational and site plan
☐Floor Framing Plan/s and Details ☐Plumbing Plans, Layouts and details of minimum
☐Roof Framing/ Roof Deck Framing Plan and Details scale 1:50m (3 sets) signed and sealed by MP/SE and
☐Schedule of Column, Footings, Wall Footings and owner
Floor Slabs ☐Water supply / line plan
☐Schedule of Beams and Girders/Details ☐Drainage, waste and vent plan
☐Schedule of Trusses (Truss Details) ☐Storm water drainage plan (incorporate rainwater
For High-rise buildings and others specified in the tank)
DPWH-NBCDO MC # 2,S 2017: ☐Plumbing legend and General Notes
☐Location of Seismic Orientation Room ☐Isometric diagram of the entire plumbing system
☐Earthquake Recording Instrumentation (E.R.I.) and its (incorporate rain water tank)
corresponding location ☐Plumbing cost estimates
☐Required No. of ERI ___________ ☐Septic tank certification – distance from artesian well
☐Septic tank, catch basin, grease trap, cistern tank, ☐Methodology Specifications signed and sealed
pressure tank, overhead water tank, sump pit and of Architect and Owner
pump details (if applicable) ☐CAAP Clearance for 50 Storey’s and above (if
☐Pipe joint/ connection details applicable)
☐Sewage Treatment Plant (STP) (if applicable) ☐Arcaded Structures – Minimum Height 5 meters
Planned and designed by only registered and ☐Approved Locational Clearance (Original)
licensed Sanitary Engineer Design analysis and If Approved Variance:
computation signed and sealed by SE (3 copies) ☐Zoning Board resolution
Yard Regulations: ☐Front ☐ Rear ☐Left ☐ Right
ELECTRICAL SECTION ☐CPDO Clearance
☐Electrical plans coincide with other plans of all ☐ Number of Storey’s Approved
sections signed and sealed ☐ Change of use
☐Vicinity Map/Location Plan within a (2) Two –
☐Electrical Permit forms (3 original copies) signed and
Kilometer Radius (Streets, Landmarks)
sealed
☐Site development plan (RROW, Setbacks, Building
☐Updated PTR and PRC ID of PEE
footprint and Lot boundary points)
☐PEE details on the title block
☐Perspective
☐Plans and forms signed by owner/applicant
☐Floor Plans
☐Full name of Authorized Representative in plans
☐Elevations, at least four (4)
and forms
☐Sections, At least two (2)
☐Schedule of Loads
☐Roof plan
☐Single line Diagram
☐Ceiling plans showing lighting fixtures and diffusers
☐Riser Diagram
☐Details of ramps, parking for disabled, stairs, fire
☐General notes/ Specifications
escapes, cabinets and partitions
☐Electrical Legend
☐Schedule of doors and windows
☐Power Layout Plan
☐Schedule of finishes for floors, ceilings and walls
☐Lighting Layout Plan
☐Fence plans and details (if applicable)
☐Grounding Layout Plan
Minimum setback (free from any obstruction)
☐Lightning Arrester Details
☐Front ☐Rear ☐Left ☐ Right
☐Meter Center on the plan (must be reflected)
___________________________
☐Gutter Diagram and its main conductor computation
Abutting firewalls (1.00m from the topmost roofline
☐Sizing of Transformer and Generator
attached)
☐Dedicated source for jockey pump and fire pump
☐R1 and R2 (1/3 rear abutment) ☐Commercial
(provide/reflect)
☐Front ☐Rear ☐Left ☐ Right
☐Fault Current Calculation
___________________________
☐Voltage Drop Calculation
PWD Compliance (BP344 and City Ordinance 2396)
☐Xerox copy of PCAB license and fill out box 3 of
(for rentable and commercial spaces)
permit forms
☐PWD parking (3.70 x 5.00m)
☐Replace Ordinary outlet at near sink or inside T&B to
☐PWD ramp (1:12 ramp slope with end run of 6.00m
GFCI Outlet
and landing of 1.50m)
☐PWD toilet (2.00 x 2.00m clear width – refer to city
ELECTRONICS SECTION
ordinance 2396)
☐Electronics plans coincide with other plans of all
For hotel, motel, pension houses, apartment, and
sections
place of lodging (5 rooms & above)
☐General layout plans with legends
☐PWD unit room with PWD toilet (must be on the
☐Riser/ System diagram
ground floor if no elevator)
☐Isometry of the system, as applicable
For Interior Renovation Projects
☐Unit/ Equipment specifications, as applicable
(leasing in all commercial buildings)
☐Bill of Quantities
☐ Key Locational Plan
☐Design analysis, as applicable
☐ Interior Perspective
☐Cost estimates, as applicable
☐ Reflect “interior renovation” in project title
☐Professional Electronics Engineer (PECE)
☐ Reflect building name, floor level and unit no. of
for design and supervision (signed and sealed)
the project
☐Updated PTR and PRC ID of PECE (signature
(leasing in all commercial buildings except for malls)
specimen and seal)
☐ Parking slots required _______
☐Electronic Permit forms (3 original copies) signed and
☐ Approved Occupancy Permit (photocopy)
sealed by PECE and owner
For Renovation of Buildings
☐Provide title block for Electronics Section on the
☐As built plans (for comparison purposes)
first sheet of the submitted building plans and in the
☐Latest tax declaration (land & building)
electronics plan
☐Approved Occupancy Permit (photocopy)
Rainwater tank blow up plans/ details (except for interior
ARCHITECTURAL / ACCESSIBILITY SECTION /
renovations and projects that cost less than 500,000
LAND USE AND ZONING
Pesos)
☐Architectural plans coincide with other plans of
☐Residential (3.00 cu.m. vol. cap.)
all sections signed and sealed
☐Commercial (7.00 cu.m. vol. cap.)
☐Fire Clearance Certificate (color pink)
Green Building Compliant (refer to the Green
☐Architectural permit forms signed and sealed
building code for reference)
by Architect and Owner
☐For Corrections/ revisions made in drawing plans
☐Fence permit forms signed and sealed by Architect
☐Reflect practitioners initials to all the corrections
and Owner
Corrections / revisions made must be drawn
☐Enforcement division forms signed and sealed
according to scale, reflect to all sections and to all
by Architect and Owner
sets submitted
☐Photocopy of updated PTR and PRC ID of Architect
signed and sealed BUILDING PLANS AND DOCUMENTS ON
☐Breakdown of Bill of Materials signed and sealed E-FILE (PDF FORMAT)
by Architect and Owner ☐USB