Practical 1_Hardware
Practical 1_Hardware
School of Engineering
Howard College Campus
Power Systems 2 (ENEL 4WA H1)
Practical – 1: Calculation of asymmetrical fault currents
Objectives:
The objective of this practical is to calculate asymmetrical fault currents in a power system consisting
of a three-phase alternator and three-phase transformer.
Method:
Neglecting all resistances present in the system, the sequence reactances of the alternator and
transformer are to be measured using following methods:
A A
Rotor R V Shorting
Suppy Rectifier A
Y Switches
A
B
Generator
A
Rotor R V
Suppy Rectifier
Y
A
B
Generator
Follow the same procedure as for determination of positive sequence impedance measurement, but in
this case, only white and blue phases are short-circuited and run the machine up to rated speed. Again,
increase the excitation until full-load current flows in the stator phases. Negative sequence of the
alternator is:
𝑉𝑉
𝑋𝑋𝑔𝑔2 =
3𝐼𝐼
(2)
√
V= line voltage; I= average current of the stator phases.
Zero sequence impedance of alternator:
For measurement of zero sequence of the alternator use the circuit configuration 3.
A
R
Rotor V
220 V
Shorted
AC
Y B Variac
Generator
Circuit 3: Alternator zero sequence impedance measurement
With the rotor shorted and stator connected in open-delta as shown in circuit 3, run the machine up to
rated speed and inject a single-phase current in the open-delta. Take the current and voltage readings.
The zero sequence impedance of the alternator is given by:
𝑉𝑉
𝑋𝑋𝑔𝑔0 = (3)
3𝐼𝐼
For measurement of zero sequence of the alternator use the circuit configuration 4. Apply a three-
phase short-circuit to the secondary side of the transformer, run the machine up to rated speed, and
increase excitation until full-load current flows in the stator phases. Transformer reactances are given
by:
𝑉𝑉
𝑋𝑋𝑡𝑡1 = 𝑋𝑋𝑡𝑡2 = 𝑋𝑋𝑡𝑡0 =
3𝐼𝐼
(4)
√
A A
Rotor R L-L Fault
V
Suppy A example
Rectifier
Y
A
B N
Generator
Transformer