e Line Kx Busbar
e Line Kx Busbar
6300 A
www.eaeelectric.com
E-LINEKX
Please visit our website for the updated version of our catalogues.
www.eaeelectric.com
CONTENTS
E-LINE KX
Introduction.....................................................................................................................................2-3
Distribution & Horizontal Applications..............................................................................................4
Riser & Vertical Applications..............................................................................................................5
Technical Characteristics...............................................................................................................6-9
Order Code System.......................................................................................................................... 10
Straight Lengths............................................................................................................................... 11
Elbows........................................................................................................................................ 12-15
"T" Module........................................................................................................................................ 16
Reduction Modules.......................................................................................................................... 17
Expansions....................................................................................................................................... 18
Phase Transposition Module........................................................................................................... 19
End Closers....................................................................................................................................... 20
Panel Connections..................................................................................................................... 21-25
Transformer Connections ......................................................................................................... 26-30
Tap-off Boxes............................................................................................................................. 31-36
Vertical and Horizontal Busbar Applications............................................................................ 37-38
Feeder Boxes.............................................................................................................................. 39-40
Fixing Elements.......................................................................................................................... 41-49
Joint Structure.................................................................................................................................. 50
Measuring a Special Lenght............................................................................................................ 51
Inserting "Make up Section"............................................................................................................ 52
Declaration....................................................................................................................................... 53
Certificate......................................................................................................................................... 54
Product Overview............................................................................................................................. 55
Please visit our website for the updated version of our catalogues.
www.eaeelectric.com
ELINEKX
►►Introduction
2 www.eaeelectric.com
ELINEKX
►►Technical Features
PE
Figure 2
Isolated Layers Figure 1
Heat Transfer
"In compact structure" there is no empty space filled with
air and heat is easily transferred to the environment by the
housing that works like a heat-shink (Figure 2).
One Bolt Joint Ensures Safety and Easy Installation Easy and Safe Installation:
E-Line KX Busbars are installed by tightening Due to alignment piece on the
the "one bolt joint". Belleville spring washers on joint point, block joint element
both ends of the bolt retains the original contact and busbar tray are aligned.
pressure, ensuring a more secure, reliable and This makes installation easier
maintenance - free joint. and correct on the right axes.
E-Line KX Busbar Systems are easily installed (Figure 6).
(Figures 3-4).
Figure 3
Figure 6
50
60 Figure 4
83Nm
TORQUE SPANNER (60lbft)
www.eaeelectric.com 3
ELINEKX
►►Distribution & Horizontal Applications
Utilization Factor (a) • Busbar current rating is chosen as equal to or higher then the
Utilization factor (a) depends on the type and calculated IB current.
number of loads. • After the voltage drop calculation if the chosen current rate is not
It is usually around 0.7 or lower. The utilization factor convenient, a higher rating is chosen.
of a line that supplies electricity to motors and lighting
systems is usually lower than 0.6. Short-Circuit
It is as low as 0.30 in weld shops of car factories, it can be Tested short-circuit capacities are given on technical
1 in lines where only one big load is supplied. characteristics table on pages 6-9.
Components List
Item Components Quantity
1 KXA 20504 - STD Busbar (20 x 3m.) 60 m.
Date : 02 / 01 / 2022
Signature :
Project Sample
4 www.eaeelectric.com
ELINEKX
►►Riser & Vertical Applications
As each building's structure is different than the other for vertical applications of E-Line KX special Line end
projects has to be designed.
The details on this page briefly explain the necessary information for drawing a vertical application
a= ......
project.
L1
L1
L2
L3
L2
L3
N
N
r
rrie
e Ba
Fir
10. Floor
a= ......
h= ......
Vertical Expansion
9. Floor
a= ......
( h ) Height of store measured from ceiling to ceiling ( cm. )
h= ......
ox I13
-o ff B
B
ap 8. Floor
g-in T a= ......
Plu
t
oin
Special Length Plug-in Busbar
gP
h= ......
Tap-off Point
Plu
I12
7. Floor
a= ......
h= ......
A
I11
6. Floor
a= ......
in t
r Jo
sba
h= ......
Bu I10
5. Floor
a= ......
h= ......
I9
4. Floor
I8
a= ......
(a
)C
eili
h= ......
ng
thi
ckn I7
ess I6
(c 3. Floor
m. a= ......
)
h= ......
n I5
Project Design … 2. Floor
11 a= ......
10
The details below should be sent to our Project & Design
h= ......
9
department. 8 I4
7
1. Floor
• Location and dimensions of the floor penetration 6 a= ......
where busbar will be installed. 5
4
3
(a=..., h=...) 2
I3
• Connected load for each storey. 1 Ground Floor
a= ......
• Supply type of the vertical line (busbar or cable). Ground
Floor
Basement
h= ......
3.Basement
EAE is not responsible for the potential risks that may occur in cases where the products in our Figure 1
catalogue are used outside of the standard phase sequences as shown in the catalogue.
www.eaeelectric.com 5
ELINEKX
►►Technical Characteristics
6 www.eaeelectric.com
PE
L3
L2
L1
N2
N1
1600 1600 2000 2000 2500 2500 2500 3200 3200 4000 4000 5000 6000
16 17 18 20 29 27 25 32 33 40 41 51 60
PE
60 80 80 80 80 80 100 100 120 120 120 120 120 L3
L2
132 176 176 176 176 176 220 220 264 264 264 264 264 L1
36 48 48 48 48 48 60 60 72 72 72 72 72 N
75,6 100,8 100,8 100,8 100,8 100,8 132 132 158,4 158,4 158,4 158,4 158,4
36 48 48 48 48 48 60 60 72 72 72 72 72
75,6 100,8 100,8 100,8 100,8 100,8 132 132 158,4 158,4 158,4 158,4 158,4
L3
0,034 0,031 0,027 0,024 0,021 0,019 0,022 0,017 0,015 0,012 0,014 0,010 0,008 L2
0,044 0,041 0,035 0,034 0,028 0,026 0,029 0,022 0,020 0,016 0,017 0,014 0,010 L1
0,010 0,010 0,008 0,008 0,007 0,007 0,007 0,005 0,005 0,004 0,004 0,003 0,002 N
0,045 0,042 0,036 0,035 0,029 0,027 0,030 0,022 0,020 0,017 0,018 0,014 0,010
0,034 0,033 0,028 0,027 0,022 0,021 0,023 0,017 0,016 0,013 0,013 0,010 0,008
0,032 0,030 0,025 0,024 0,020 0,019 0,022 0,016 0,015 0,012 0,013 0,010 0,008 Voltage Drop Calculation
0,032 0,031 0,025 0,025 0,020 0,020 0,023 0,018 0,017 0,013 0,013 0,010 0,008 Generally Voltage drop of a busbar system
can be calculated with the following formula.
0,022 0,022 0,021 0,021 0,022 0,020 0,019 0,017 0,017 0,015 0,016 0,013 0,013
840 960 1080 1200 1380 1500 1320 1680 1920 2400 2160 3000 3600
420 480 540 600 690 750 660 840 960 1200 1080 1500 1800
DU= √3.L.I.(R .Cosj+X .Sinj) 10-3 [V]
840 960 1080 1200 1380 1500 1320 1680 1920 2400 2160 3000 3600
DU = Voltage Drop (V)
2206 2314 2410 2518 2679 2764 3912 4224 4411 4848 4640 5275 7128
L = Line Length (m)
6x140 6x160 6x180 6x200 6x230 6x250 2(6x110) 2(6x140) 2(6x160) 2(6x200) 2(6x180) 2(6x250) 3(6x200) I = Line Current or Load (A)
17,0 18,3 20,5 21,7 24,9 28,5 27,3 32,5 35,9 42,9 38,6 57,2 63,9 R = Resistance (mW/m)
X = Reactance (mW/m)
19,6 21,1 23,7 25,3 29,0 34,2 31,2 37,5 41,6 50 45,0 68,5 74,6
0,164 0,153 0,132 0,130 0,102 0,103 0,108 0,081 0,074 0,060 0,065 0,048 0,039
0,141 0,161 0,126 0,158 0,112 0,131 0,101 0,076 0,101 0,084 0,085 0,078 0,043 L
0,209 0,195 0,169 0,167 0,131 0,135 0,140 0,104 0,094 0,078 0,084 0,064 0,050 S I
0,176 0,199 0,159 0,199 0,143 0,168 0,126 0,095 0,127 0,108 0,111 0,102 0,054 S = Supply Point
0,067 0,065 0,054 0,054 0,041 0,042 0,046 0,034 0,031 0,025 0,026 0,020 0,016
0,071 0,069 0,057 0,057 0,044 0,044 0,049 0,036 0,033 0,027 0,028 0,021 0,017
All phase conductor characteristics had been
0,063 0,068 0,055 0,065 0,047 0,050 0,053 0,033 0,049 0,035 0,033 0,031 0,019 determined according to Annex BB of IEC / EN
0,088 0,086 0,071 0,072 0,055 0,057 0,059 0,044 0,040 0,033 0,035 0,027 0,021 61439-6.
Fault-loop zero-sequences impedances had
0,094 0,090 0,076 0,076 0,058 0,060 0,062 0,047 0,043 0,035 0,038 0,029 0,022 been determined according to Annex CC of IEC / EN
61439-6.
0,083 0,089 0,072 0,086 0,062 0,068 0,067 0,044 0,064 0,046 0,045 0,042 0,025
Fault-loop resistances and impedances had
0,019 0,018 0,016 0,017 0,012 0,013 0,012 0,010 0,009 0,008 0,008 0,005 0,005 been determined according to Annex DD of IEC / EN
61439-6.
0,028 0,026 0,023 0,023 0,018 0,020 0,018 0,014 0,013 0,012 0,012 0,009 0,007 * IK10 corresponds to impact energy of 20J
0,028 0,032 0,023 0,030 0,019 0,023 0,024 0,014 0,019 0,015 0,012 0,014 0,007 according to IEC 62262.
www.eaeelectric.com 7
ELINEKX
►►Technical Characteristics
8 www.eaeelectric.com
PE
L3
L2
L1
N2
N1
1600 2000 2500 2000 2500 3300 3600 4000 5000 6300
17 23 25 22 27 32 36 40 50 63
PE
80 80 100 80 100 120 120 120 120 120 L3
L2
176 176 220 176 220 264 264 264 264 264 L1
48 48 60 48 60 72 72 72 72 72 N
100,8 100,8 132 100,8 132 158,4 158,4 158,4 158,4 158,4
48 48 60 48 60 72 72 72 72 72
100,8 100,8 132 100,8 132 158,4 158,4 158,4 158,4 158,4
L3
0,032 0,024 0,016 0,028 0,021 0,014 0,012 0,011 0,008 0,005 L2
0,044 0,033 0,021 0,036 0,028 0,019 0,016 0,015 0,010 0,006 L1
0,015 0,010 0,008 0,012 0,009 0,007 0,006 0,005 0,004 0,003 N
0,047 0,034 0,022 0,038 0,030 0,020 0,017 0,016 0,011 0,007
0,035 0,026 0,018 0,030 0,023 0,016 0,014 0,012 0,009 0,006
325,1 383,3 384,4 436,8 528,8 604,4 633,7 705,6 772,5 750,1 Voltage Drop Calculation
0,031 0,022 0,014 0,025 0,021 0,013 0,012 0,010 0,007 0,005 Generally Voltage drop of a busbar system
can be calculated with the following formula.
0,031 0,023 0,014 0,026 0,021 0,015 0,012 0,009 0,008 0,005
0,028 0,039 0,031 0,019 0,022 0,018 0,023 0,021 0,021 0,011
570 750 1200 660 840 1320 1500 1680 2400 3600
DU= √3.L.I.(R .Cosj+X .Sinj) 10-3 [V]
285 375 600 330 420 660 750 840 1200 1800
DU = Voltage Drop (V)
570 750 1200 660 840 1320 1500 1680 2400 3600
L = Line Length (m)
1996 2128 2518 3340 3580 3912 4068 4224 4848 7128 I = Line Current or Load (A)
6x95 6x125 6x200 2(6x55) 2(6x70) 2(6x110) 2(6x125) 2(6x140) 2(6x200) 3(6x200) R = Resistance (mW/m)
X = Reactance (mW/m)
27,7 36,2 54,7 35,9 44 63,5 71,1 78,6 108,8 162,8
33,7 43,8 66,5 42,4 52 76,5 85,8 95,2 132,4 198,2
0,168 0,130 0,086 0,148 0,107 0,073 0,067 0,060 0,038 0,029 L
0,154 0,153 0,146 0,144 0,090 0,091 0,090 0,100 0,086 0,061 S I
0,221 0,167 0,107 0,189 0,136 0,092 0,084 0,077 0,046 0,034 S = Supply Point
0,197 0,193 0,181 0,176 0,111 0,113 0,112 0,128 0,106 0,075
0,066 0,050 0,033 0,059 0,044 0,029 0,025 0,023 0,016 0,011
0,071 0,054 0,035 0,063 0,047 0,031 0,027 0,025 0,017 0,012 All phase conductor characteristics had been
0,065 0,059 0,053 0,061 0,040 0,035 0,034 0,044 0,032 0,023 determined according to Annex BB of IEC / EN 61439-6.
Fault-loop zero-sequences impedances had been
0,091 0,067 0,043 0,077 0,058 0,038 0,033 0,030 0,020 0,013 determined according to Annex CC of IEC / EN 61439-6.
Fault-loop resistances and impedances had been
0,098 0,073 0,046 0,083 0,062 0,041 0,036 0,033 0,022 0,015
determined according to Annex DD of IEC / EN 61439-6.
0,089 0,080 0,070 0,080 0,052 0,047 0,044 0,059 0,041 0,028 * IK10 corresponds to impact energy of 20J according to
IEC 62262.
0,026 0,022 0,014 0,022 0,016 0,012 0,011 0,010 0,008 0,005
0,037 0,032 0,022 0,029 0,023 0,018 0,015 0,014 0,011 0,008
0,036 0,035 0,028 0,033 0,022 0,020 0,018 0,018 0,014 0,010
www.eaeelectric.com 9
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Order Code System PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT
KX A 17 5 04 B TR41
COMPONENTS
Busbar Type
Standard Length STD
Special Length X
Aluminium (Al) A CONDUCTOR MATERIAL
Copper (Cu) C
Upwards Elbow U
Downwards Elbow D
KXA - Al KXC - Cu Right Elbow R
Conductor
Conductor Conductor
Left Elbow L
Rated Busbar Rated Busbar
Current Code Current Code
*400 04 *550 05 6x25 Left Horizontal Offset LH
*500 05 *650 06 6x30 Right Horizontal Offset RH
*630 06 *800 08 6x40 (*)Bolt-on tap-off box can not be used on the Upwards Vertical Offset UV
800 08 1000 10 6x55 joints of mentioned ratings of busbars. Downwards Vertical Offset DV
Plug-in points can be at one side only.
1000 11 - - 6x60 Upwards Left Combined Offset KUL
- - 1250 12 6x70 Upwards Right Combined Offset KUR
1000 10 1350 14 6x80 Downwards Left Combined Offset KDL
- - 1600 17 6x95 Downwards Right Combined Offset KDR
1250 12 - - 6x110 Busbar Left Upwards Combined Offset KLU
1350 14 2000 23 6x125 Code Right Upwards Combined Offset KRU
1600 16 - - 6x140 Left Downwards Combined Offset KLD
1600 17 - - 6x160 Right Downwards Combined Offset KRD
2000 18 - - 6x180
2000 20 2500 25 6x200 End Closer S
2500 29 - - 6x230 Reduction RD
2500 27 - - 6x250
- - 2000 22 2(6x55) Left Side Feeder "T" TYL
- - 2500 27 2(6x70) Right Side Feeder "T" TYR
2500 25 3300 32 2(6x110) Central Feeder "T" TO
- - 3600 36 2(6x125)
3200 32 4000 40 2(6x140) Horizontal Expansion YDT
3200 33 - - 2(6x160) Vertical Expansion DDT
4000 40 5000 50 2(6x200) Phase Transposition Module FDM
4000 41 - - 2(6x180)
5000 51 - - 2(6x250) Panel Connection P10
6000 60 6300 63 3(6x200) Panel Connection P11
Upwards Panel Connection PU20
PROTECTION DEGREE Upwards Panel Connection PU21
IP55 / IP65* 5 Downwards Panel Connection PD20
*Please call us for IP65 orders. Downwards Panel Connection PD21
(IP65 is not recommended for outdoor applications. Please check CR catalog.) Right Panel Connection PR30
Right Panel Connection PR31
Left Panel Connection PL30
Number of Conductor Configuration Left Panel Connection PL31
Code
Conductors L1 L2 L3 N1 N2 PE ½ CPE ½ PE
Panel Connection P40
PE CPE (Housing)
4 Conductors 04 √ √ √ √ √
Transformer Connection TR11
4 ½ Conductors 07 √ √ √ √ √ √ Upwards Transformer Con. TU21
4 ½ Conductors 08 √ √ √ √ √ √ Downwards Transformer Con. TD21
Transformer Connection TR31
5 Conductors 05 √ √ √ √ √ √
Transformer Connection TR41
5 Conductors 09 √ √ √ √ √ √ Right Transformer Connection TR51
6 Conductors 06 √ √ √ √ √ √ √ Left Transformer Connection TL51
Transformer Connection TR61
Transformer Connection TR71
*TYPE Utilization Type
Feeder Box B10
(B) Bolt-on Energy is supplied from the joints. Feeder Box B11
Central Feeder Box BO
Energy is supplied from the joints and the
(P) Plug-in
plug-in points. Flexible F
10 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Standard Straight Length PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT
KX
C
C
Plug-in Plug-in Standard -S T D
Straight Length
Busbar
Sample Order: L3
Bolt-on Plug-in Plug-in Bolt-on
1250 A, Copper, Plug-in, IP 55, L2
0
L1
300
L3
L2
L1 4 Conductors N
N
KX O
Upwards Elbow -U
250
325
Sample Order:
3300 A, Copper, Bolt-on,
IP 55, 4 Conductors
L3
KXC 32504 - B - U L2
L1 C
N
0
25 5
32
5
Downwards Elbow -D 32
0
25
Sample Order:
325
3300 A, Copper, Bolt-on,
250
IP 55, 4 Conductors L3
L2
L1
N
KXC 32504 - B - D C
KXA - Al KXC - Cu
A B
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm) Left Elbow -L
Current Code Current Code O
B A
*400 04 *550 05 252 214 L3
*500 05 *650 06 257 217 Sample Order:
L2
L1
*630 06 *800 08 267 222 2000 A, Copper, Bolt-on, N
800 08 1000 10 282 229 IP 55, 4 Conductors
1000 11 - - 287 232
- - 1250 12 297 236 KXC 23504 - B - L
1000 10 1350 14 307 241 C
- - 1600 17 322 249
B A
1250 12 - - 337 256
1350 14 2000 23 352 264
1600 16 - - 367 271
1600 17 - - 387 281
2000 18 - - 408 291
2000 20 2500 25 427 301
2500 29 - - 457 316
2500 27 - - 477 326 Right Elbow -R A
A
- - 2000 22 377 276
B B
- - 2500 27 407 291
2500 25 3300 32 487 331 Sample Order:
- - 3600 36 517 346 2000 A, Aluminium, Bolt-on,
3200 32 4000 40 547 361 IP 55, 4 Conductors L3
L2
3200 33 - - 587 381 L1 O
4000 40 5000 50 667 421 KXA 20504 - B - R N C
4000 41 - - 627 401
5000 51 - - 767 471
6000 60 6300 63 907 541
Special left or right elbows between 90° and 180° can be manufactured upon request.
The dimensions given above are minumum values. Please call us for non-standard components.
12 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Elbows PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT
KX
5
32 0
25 O
Upwards Vertical -U V
Offset H
(cm)
Sample Order:
H=25 cm, 2000 A, Aluminium
Bolt-on, IP 55, 5 Conductors
H
KXA 20505-B-UV25
Note: C
H=min:25 cm max:49 cm L3
L2
L1 0
N 25
5
32
5
32
Downwards -D V 0
25
Vertical Offset H
(cm)
O
Sample Order:
H=25 cm, 2000 A, Aluminium C
Bolt-on, IP 55, 5 Conductors
L3
L2
L1
KXA 20505-B-DV25 N
H
0
25
Note:
5
H=min:25 cm max:49 cm 32
KXA - Al KXC - Cu O
A B Hmax.
A
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm) (mm) Left Horizontal -L H
Current Code Current Code
Offset H
*400 04 *550 05 252 214 427 (cm)
*500 05 *650 06 257 217 432 Sample Order:
*630 06 *800 08 267 222 442 H=60 cm, 3300 A, Copper
H
Note: N C
- - 1600 17 322 249 497 H=min:28 cm,
1250 12 - - 337 256 512 max: *Please see table.
1350 14 2000 23 352 264 527 Used, if two horizontal elbows
can not fit.
1600 16 - - 367 271 542
1600 17 - - 387 281 562
2000 18 - - 408 291 582
2000 20 2500 25 427 301 602
2500 29 - - 457 316 632
2500 27 - - 477 326 652 Right Horizontal -R H
- - 2000 22 377 276 552 Offset H
- - 2500 27 407 291 582 (cm)
H
A
O
2500 25 3300 32 487 331 662 Sample Order:
B
Special left or right elbows between 90° and 180° can be manufactured upon request.
The dimensions given above are minumum values. Please call us for non-standard components.
www.eaeelectric.com 13
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Elbows PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT
KX
A
B
Upwards Left -K U L
Combined Offset O
Sample Order:
3300 A, Copper
Bolt-on, IP 55, 4 Conductors
H
L3
L2
C
Note:
L1
H=min. 30 cm N
0
25 5
32
KXA - Al KXC - Cu
A B
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm)
Current Code Current Code A
*400 04 *550 05 252 214 B
Upwards Right -K U R
*500 05 *650 06 257 217
Combined Offset
*630 06 *800 08 267 222
800 08 1000 10 282 229 Sample Order:
1000 11 - - 287 232 3200 A, Aluminium
- - 1250 12 297 236 Bolt-on, IP 55, 4 Conductors
1000 10 1350 14 307 241 O
- - 1600 17 322 249 KXA 33504 - B - KUR
H
L3
1250 12 - - 337 256 L2 C
Note: L1
1350 14 2000 23 352 264 H=min. 30 cm N
0
1600 16 - - 367 271 25 5
32
1600 17 - - 387 281
2000 18 - - 408 291
2000 20 2500 25 427 301
2500 29 - - 457 316
2500 27 - - 477 326
- - 2000 22 377 276 325
- - 2500 27 407 291 Downwards Left -K D L
2500 25 3300 32 487 331 250
Combined Offset
- - 3600 36 517 346
3200 32 4000 40 547 361 Sample Order:
3200 33 - - 587 381 3300 A, Copper C
4000 40 5000 50 667 421 Bolt-on, IP 55, 4 Conductors
H
5
32
0
Downwards Right -K D R 25
Combined Offset
L3
L2
Sample Order:
H
L1
N
3200 A, Aluminium C
Bolt-on, IP 55, 4 Conductors
Note: B
H=min. 30 cm A O
The dimensions given above are minumum values. Please call us for non-standard components.
14 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Elbows PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT
KX
O
Left Upwards -K L U
Combined Offset
250
325
Sample Order:
3200 A, Aluminium
Bolt-on, IP 55, 4 Conductors
H
Note:
H=min. 30 cm L3
B
L2
A
L1 C
N
KXA - Al KXC - Cu
A B
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm)
Current Code Current Code
*400 04 *550 05 252 214 O
Right Upwards -K R U
*500 05 *650 06 257 217
Combined Offset
*630 06 *800 08 267 222
A
800 08 1000 10 282 229 Sample Order:
B
1000 11 - - 287 232 3300 A, Copper
- - 1250 12 297 236 Bolt-on, IP 55, 4 Conductors L3
L2
250
1000 10 1350 14 307 241 L1
N
- - 1600 17 322 249 KXC 32504 - B - KRU
325
C
1250 12 - - 337 256
Note:
1350 14 2000 23 352 264
H
H=min. 30 cm
1600 16 - - 367 271
1600 17 - - 387 281
2000 18 - - 408 291
2000 20 2500 25 427 301
2500 29 - - 457 316
2500 27 - - 477 326
- - 2000 22 377 276
- - 2500 27 407 291 Left Downwards -K L D H
2500 25 3300 32 487 331 Combined Offset
- - 3600 36 517 346
3200 32 4000 40 547 361 Sample Order:
325
H=min. 30 cm C
L3
L2
O L1
N
B A
Right Downwards -K R D
H
Combined Offset
L3
Sample Order: L2
L1
3300 A, Copper N
C
Bolt-on, IP 55, 4 Conductors
325
Note:
H=min. 30 cm
The dimensions given above are minumum values. Please call us for non-standard components.
www.eaeelectric.com 15
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►“ T” Elbows PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT
KX
B C
Right Side -T Y R
Feeder "T"
Sample Order:
L3
2500 A, Copper, Bolt-on, L2
A
IP 55, 4 Conductors L1
N
Left Side -T Y L
Feeder "T"
A Sample Order:
2500 A, Aluminium, Bolt-on, L3
IP 55, 4 Conductors L2
L1
N
KXA 25504 - B - TYL
C B
KXA - Al KXC - Cu
A B C
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm) (mm) Central Feeder "T” -T O
Current Code Current Code
*400 04 *550 05 214 214 214
*500 05 *650 06 216 216 216 Sample Order:
*630 06 *800 08 221 221 221 3300 A, Copper, Bolton,
800 08 1000 10 229 229 229 IP 55, 4 Conductors L3
1000 11 - - 232 232 232 L2
L1
- - 1250 12 236 236 236 KXC 32504 - B - TO N
1000 10 1350 14 241 241 241
- - 1600 17 249 249 249
1250 12 - - 256 256 256
B C
1350 14 2000 23 264 264 264
1600 16 - - 271 271 271
1600 17 - - 281 281 281
2000 18 - - 291 291 291
2000 20 2500 25 301 301 301
2500 29 - - 316 316 316 A
2500 27 - - 326 326 326
- - 2000 22 276 276 276
- - 2500 27 291 291 291
2500 25 3300 32 331 331 331
- - 3600 36 346 346 346
3200 32 4000 40 361 361 361
3200 33 - - 381 381 381
4000 40 5000 50 421 421 421
4000 41 - - 401 401 401
5000 51 - - 471 471 471
6000 60 6300 63 541 541 541
The dimensions given above are minumum values. Please call us for non-standard components.
16 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Reduction Modules PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT
KX
O
Reduction Reduction -R D
Is used to change the busbar cross section. Reduced
0
NOTE: Busbar Current
0
7
Decisions and selection of reduction module Sample Order:
and protection on lower side is under the 2000A / 1600A, Aluminium,
customer’s responsibility. Bolt-on, IP 55, 4 Conductors
5
2
2
KXA 20504 - B - RD17 L3
L2
5
7
L1
4
N C
Reducers Table
KXA - Al KXC - Cu
Conductor Conductor
Rated Reduced Busbar Current Rated Reduced Busbar Current
Current 04 05 06 08 11 10 12 14 16 17 18 20 25 29 27 32 33 40 41 51 Current 05 06 08 10 12 14 17 22 23 25 27 32 36 40 50
500 05 √ - - - - - - - - - - - - - - - - - - - 650 06 √ - - - - - - - - - - - - - -
630 06 √ √ - - - - - - - - - - - - - - - - - - 800 08 √ √ - - - - - - - - - - - - -
800 08 - √ √ - - - - - - - - - - - - - - - - - 1000 10 - √ √ - - - - - - - - - - - -
1000 11 - - √ √ - - - - - - - - - - - - - - - - 1250 12 - - √ √ - - - - - - - - - - -
1000 10 - - √ - - - - - - - - - - - - - - - - - 1350 14 - - - √ √ - - - - - - - - - -
1250 12 - - - √ √ √ - - - - - - - - - - - - - - 1600 17 - - - - √ √ - - - - - - - - -
1350 14 - - - √ √ √ - - - - - - - - - - - - - - 1 2000 22 - - - - - √ √ - - - - - - - -
1600 16 - - - - √ - √ - - - - - - - - - - - - - 2000 23 - - - - - √ √ - - - - - - - -
1 1600 17 - - - - √ - √ - - - - - - - - - - - - - 2500 25 - - - - - - - √ √ - - - - - -
2000 18 - - - - - - - √ √ - - - - - - - - - - - 2500 27 - - - - - - - √ √ - - - - - -
2000 20 - - - - - - √ √ √ - - - - - - - - - - - 3300 32 - - - - - - - - - √ √ - - - -
2500 29 - - - - - - - - √ √ √ - - - - - - - - - 3600 36 - - - - - - - - - √ √ √ - - -
2500 27 - - - - - - - - √ √ √ - - - - - - - - - 4000 40 - - - - - - - - - - - √ √ - -
2500 25 - - - - - - - - - √ √ - - - - - - - - - 5000 50 - - - - - - - - - - - - - √ √
3200 32 - - - - - - - - - - - √ √ - √ - - - - - 6300 63 - - - - - - - - - - - - - - √
3200 33 - - - - - - - - - - - √ √ - √ - - - - -
4000 40 - - - - - - - - - - - - √ √ √ √ √ - - - 2
4000 41 - - - - - - - - - - - - - - - √ √ - - -
5000 51 - - - - - - - - - - - - - - - √ √ √ √ -
6000 60 - - - - - - - - - - - - - - - - - - √ √
2
The dimensions given above are minumum values. Please call us for non-standard components.
www.eaeelectric.com 17
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Expansions PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT
KX
0
70
L1
N
C
35
50 50
20 30 30 20
The dimensions given above are minumum values. Please call us for non-standard components.
18 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Phase Transposition Module PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT
KX
00
C
15
L3 -
L2 -
L1 -
N -
When installation of the Tap-Off Boxes needed after the phase changer box , an
approvement must be taken from the customer representative in advance.
Figure 1 N L1 L2 L3
The dimensions given above are minumum values. Please call us for non-standard components.
www.eaeelectric.com 19
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►End Closers PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT
KX
End Closer -S
End Closer -S 1 0
Sample Order:
6300 A, Copper
Bolt-on, IP 55, 3 Conductors
L3 C
L2
KXC 63503 - B- S 10 L1
5
2
2
End Closer
Is used to close the end of busbar run.
L1, L2, L3, N + Housing 04
KXA - Al KXC - Cu
L1, L2, L3, N, ½ PE + Housing 07
Conductor Conductor
L1, L2, L3, N, PE + Housing 05
Rated Busbar Rated Busbar Dimensions End Closer -S 1 1
Current Code Current Code (mm)
Order Code
*400 04 *550 05 6x25 3066129
*500 05 *650 06 6x30 3066131 Sample Order:
*630 06 *800 08 6x40 3016698 5000 A, Copper,
800 08 1000 10 6x55 3016699 Bolt-on, IP 55, 3 Conductors
1000 11 - - 6x60 3142393
- - 1250 12 6x70 3016700 KXC 50503 - B - S 11 O
5
L3
2
2
The dimensions given above are minumum values. Please call us for non-standard components.
20 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Panel Connections PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT
KX
C Panel Connection -P 1 0
Panel Feeder
225
Sample Order:
2500 A, Copper, Bolt-on, 4 Conductors
for Panel Feeder N
L1
150
L3
KXC 25504 - B - P10 L2
L2
100 100 100 L3
L1
N
O Panel Connection -P 1 1
Busbar Feeder
225
Sample Order:
2500 A, Copper, Bolt-on, 4 Conductors
for Busbar Feeder
150
N
KXC 25504 - B -P11 L1 L3
100 100 100 L2 L2
L3 L1
N
325
L1
L2
100 100 100
L3
325
C
4250 A, Copper, Bolt-on, 4 Conductors
200
L3
KXC 43504 - B - PD20
150
L2
100 100 100 L1
N
KX
325
275
3600 A, Copper, Bolt-on, 4 Conductors
200
L1
L2
100 100 100
L3
325
L2
100 100 100 L1
N
A
B Right Panel -P R 3 0
Connection
Panel Feeder
A-125
C
B-125
Sample Order:
2500 A, Copper, Bolt-on, 4 Conductors
for Panel Feeder N
150
L1
KXC 25504 - B - PR30 L2
100 100 100 L3
A
B
Left Panel -P L 3 0
Connection
A-125
B-125
C Panel Feeder
Sample Order:
2500 A, Copper, Bolt-on, 4 Conductors
for Panel Feeder
150
L3
L2
100 100 100 KXC 25504 - B - PL30 L1
The "A" and "B" dimensions for PR30 and PL30 are N
the same dimensions as left and right elbows.
Please refer to page 12 for the dimensions.
For connection dimensions please refer to tables on pages 24 and 25.
Note: Please contact with us for the dimensions of our 6 conductor solutions. Do not hanger the relevant modules from the flanges.
Distance between conductors can vary in ±5 mm. The dimensions given above are minumum values. Please call us for non-standard components.
22 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Panel Connections PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT
KX
A
B Right Panel -P R 3 1
Connection
A-125 Busbar Feeder
Sample Order:
B-125
L2
KXC 25504 - B - PR31 L1
100 100 100
N
A
B Left Panel -P L 3 1
Connection
Busbar Feeder
Sample Order:
A-125
B-125
L1
KXC 25504 - B - PL31
L2
100 100 100
L3
Panel Connection -P 4 0
855
Panel Feeder
C Sample Order:
3300 A, Copper, Bolt-on, 4 Conductors L3
for Panel Feeder
150
L2 N
L1 L1
min. KXC 32504 - B - P40
N L2
250 165 165 165 110
L3
855
Panel Connection -P 4 1
Busbar Feeder
O
Sample Order:
3300 A, Copper, Bolt-on, 4 Conductors
150
L3
for Busbar Feeder
L2 N
min.
L1
250 165 165 165 110 KXC 32504 - B - P41 L1
N L2
The "A" and "B" dimensions for PR31 and PL31
L3
are the same dimensions as left and right elbows.
Please refer to page 12 for the dimensions.
For connection dimensions please refer to tables on pages 24 and 25.
Note: Please contact with us for the dimensions of our 6 conductor solutions. Do not hanger the relevant modules from the flanges.
Distance between conductors can vary in ±5 mm. The dimensions given above are minumum values. Please call us for non-standard components.
www.eaeelectric.com 23
ELINEKX
►►Panel Connections
150±3
150±3
150±3
150±3
150±3
150±3
150±3
150±3
150±3
57
57
57
57
57
57
57
Ø14 Ø14 Ø14 Ø14 Ø14
Ø14 Ø14
Ø11 Ø11
23
23
23
23
23
23
23
23
23
12,5 15 20 27,5 30 40 15 40 20 40 27,5 40 40 15
25 30 40 55 60 70 80 95 110
150±3
150±3
150±3
150±3
150±3
150±3
57
57
57
57
23
23
Ø14 Ø14 Ø14
23
23
23
23
23
40 40 22,5 40 40 30 40 40 40 20 30 40 40 40 30 40 40 40 40 20 15 40 40 40 40 40 15 25 40 40 40 40 40 25
125 140 160 180 200 230 250
KXA 32
KXC 36 KXC 40
KXA 25
KXC 22 KXC 32
150±3
150±3
150±3
Ø14
150±3
Ø14
23
Ø14
23
23
Ø14
23
35 40 40 35 25 40 40 40 40 40 40 25 20 40 40 40 40 40 40 40 20
30 40 40 40 40 40 30
150 260 290 320
KXA 40
KXA 33 KXA 41 KXC 50 KXA 51
150±3
150±3
150±3
150±3
23
23
23
20 40 40 40 40 40 40 40 40 20 20 40 40 40 40 40 40 40 40 40 20 20 40 40 40 40 40 40 40 40 40 40 20 30 40 40 40 40 40 40 40 40 40 40 40 40 30
360 400 440 540
Ø14
X X
23
20 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 20
(Minimum X= 25 mm)
680
Note: Please contact with us for the dimensions of our 6 conductor solutions. Do not hanger the relevant modules from the flanges.
Please call us for non-standard components. Distance between conductors can vary in ±5 mm. The dimensions given above are minumum values.
24 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Panel Connections PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT
KX
Flange Dimensions
Panel Connection Units are supplied with suitable flange as standard.
Panel Panel
Connection Connection
N Flange Flange PE
L1 PE
L2 Housing Housing
L3
PE
PE L3 L2 L1 N L3 L2 L1 N
B
A
100
Ø7
12,5
Number of * M6 Bolt/
Rated Busbar Rated Busbar Conductor A B
the holes Nut
Current Code Current Code Size (mm) (mm) along B length Set (pcs)
400 04 550 05 6x25 120 165 2 12
500 05 650 06 6x30 125 170 2 12
630 06 800 08 6x40 135 180 2 12
800 08 1000 10 6x55 150 195 2 12
1000 11 - - 6x60 155 200 2 12
- - 1250 12 6x70 165 210 2 12
1000 10 1350 14 6x80 175 220 2 12
- - 1600 17 6x95 190 235 3 14
1250 12 - - 6x110 205 250 3 14
1350 14 2000 23 6x125 220 265 3 14
1600 16 - - 6x140 235 280 3 14
1600 17 - - 6x160 255 300 3 14
2000 18 - - 6x180 275 320 3 14
2000 20 2500 25 6x200 295 340 4 16
2500 29 - - 6x230 325 370 4 16
2500 27 - - 6x250 345 390 4 16
- - 2000 22 2(6x55) 245 290 3 14
- - 2500 27 2(6x70) 275 320 3 14
2500 25 3300 32 2(6x110) 355 400 4 16
- - 3600 36 2(6x125) 385 430 4 16
3200 32 4000 40 2(6x140) 415 460 5 18
3200 33 - - 2(6x160) 455 500 5 18
4000 40 5000 50 2(6x200) 535 580 6 20
4000 41 - - 2(6x180) 495 540 5 19
5000 51 - - 2(6x250) 635 680 7 22
6000 60 6300 63 3(6x200) 775 820 8 24
Note: Please contact with us for the dimensions of our 6 conductor solutions. Do not hanger the relevant modules from the flanges.
www.eaeelectric.com 25
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Transformer Connections PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT
KX
O
Transformer -T R 1 1
Connection
Sample Order:
2500 A, Aluminium,
Bolt-on, 4 Conductors
225
N
L1 L3
200
L2 L2
120 120 120
L3 L1
N
325 Upwards -T U 2 1
Transformer Connection
250
Sample Order:
O 2500 A, Copper, Bolt-on,
4 Conductors
275
200
325 Downwards -T D 2 1
Transformer Connection
250
Sample Order:
2500 A, Aluminium, Bolt-on, 4
O
Conductors
275
200
KX
200
• Plan of transformer and panel board room, 4 Conductors
heights.
• Transformer dimensions, distance between KXC 25504 - B - TR31 L3 0
bushings. L2 N 11
L1 5
O L1 16
A and B dimensions of TR51 and TL51 are same as L25
N 16
left and right elbows. L35
Please refer to page 12 for the dimensions. 16
0
25
For connection dimensions please refer to tables on
pages 29 and 30.
Z Y
B=.....mm
X=.....mm • This side is punched according to the
Y=.....mm needs of the custommer.
Z=.....mm
ø=.....mm
A
B Right Transformer -T R 5 1
Connection
A-125
O Sample Order:
B-125
A
B Left Transformer -T L 5 1
Connection
O
A-125
Sample Order:
B-125
2500 A, Aluminium,
Bolt-on, 4 Conductors
N
200
A and B dimensions of TR51 and TL51 are same as left and right elbows.
Please refer to page 12 for the dimensions.
Note: Please contact with us for the dimensions of our 6 conductor solutions. Do not hanger the relevant modules from the flanges.
Distance between conductors can vary in ±5 mm. The dimensions given above are minumum values. Please call us for non-standard components.
www.eaeelectric.com 27
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►► Transformer Connections PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT
KX
O
Transformer -T R 6 1
200
Connection
0
Sample Order: 185
2500 A, Copper, Bolt-on, 4 N
Conductors L1 in.
0 m
29 0
11
KXC 36504 - B - TR61 0
L2 67
0
L3 67 175
in. 150
m0
11 200
min.
100
Transformer
TR71 Dimension Table Connection
KXA - Al KXC - Cu -T R 7 1
Conductor A B X L
Conductor Conductor (*)
Rated Busbar Rated Busbar Sample Order:
TxW (mm) (mm) (mm) (mm)
Current Code Current Code 4000 A, Copper, Bolt-on, 4
* 400 04 *550 05 6x25 263 123 85 715 Conductors
* 500 05 *650 06 6x30 265 125 90 730 N
* 630 06 *800 08 6x40 270 130 100 760
KXC 40504 - B - TR71
800 08 1000 10 6x55 278 138 115 805 L1
1000 11 - - 6x60 280 140 120 820
150
- - 1250 12 6x70 285 145 130 850
L2
1000 10 1350 14 6x80 290 150 140 880
- - 1600 17 6x95 298 158 155 925 W O
L3
1250 12 - - 6x110 305 165 170 970
1350 14 2000 23 6x125 313 173 185 1015
L3 L2 L1 N
200
200±3
200±3
200±3
200±3
200±3
200±3
200±3
200±3
200±3
40 30
30
30
40 30
40 30
40 30
40 30
40 30
40 30
Ø14 Ø14 Ø14 Ø14 Ø14 Ø14 Ø14
40
40
Ø11 Ø11
30
30
30
30
30
30
30
30
30
200±3
40 30
Ø14
200±3
200±3
200±3
200±3
200±3
30
200±3
40 30
40 30
40 30
40 30
40 30
Ø14 Ø14 Ø14 Ø14
Ø14
40
Ø14
30
30
30
30
30
30
30
40 40 22,5 40 40 30 40 40 40 20 40 40 40 30 40 40 40 40 20 15 40 40 40 40 40 15 40 40 40 40 40 25
125 140 160 180 200 230 250
KXA 25
KXC 22 KXC 27 KXC 32 KXC 36
200±3
200±3
200±3
200±3
40 30
40 30
40 30
40 30
30
30
30
KXA 32 KXA 40
KXC 40 KXA 33 KXA 41 KXC 50
200±3
200±3
200±3
30
40 30
200±3
40 30
Ø14
40
30
30
30
30
30 40 40 40 40 30 20 40 40 40 40 40 40 20 30 40 40 40 40 40 40 30 20 40 40 40 40 40 40 40 40 20
320 360 400 440
KXA 60
KXA 51 KXC 63
Sample Connection
200±3
200±3
200±3
40 30
40 30
Ø14 Ø14
30
30
25 40 40 40 40 40 40 40 40 40 40 25 20 40 40 40 40 40 40 40 40 40 40 40 40 20
540 680
Note: Please contact with us for the dimensions of our 6 conductor solutions. Do not hanger the relevant modules from the flanges.
Distance between conductors can vary in ±5 mm. The dimensions given above are minumum values. Please call us for non-standard components.
www.eaeelectric.com 29
ELINEKX
►► Transformer Connections
200±3
200±3
200±3
200±3
200±3
200±3
200±3
200±3
200±3
40 30
30
30
30
30
30
30
30
30
Ø14
40
40
40
40
40
40
40
40
Ø14 Ø14 Ø14 Ø14 Ø14 Ø14 Ø14 Ø14
30
30
30
30
30
30
30
30
30
12,5 15 20 27,5 30 40 15 40 20 40 27,5 40 40 15
25 30 40 55 60 70 80 95 110
KXA 14 KXA 20
KXA 18
KXC 23 KXA 16 KXA 17 KXC 27 KXC 25 KXA 29
200±3
200±3
200±3
200±3
30
30
30
200±3
200±3
30
30
30
40
40
40
Ø14 Ø14
40
40
40
Ø14 Ø14 Ø14 Ø14
30
30
30
30
30
30
40 40 22,5 40 40 30 40 40 40 20 40 40 40 40 20
40 40 40 30 40 40 40 40 40 15
125 140 160 180 200 230
KXA 25 KXA 32
KXA 27 KXC 22 KXC 32 KXC 36 KXC 40
200±3
200±3
200±3
200±3
30
30
30
30
200±3
30
40
40
40
40
Ø14
40
30
30
30
30
40 40 40 40 40 25 40 40 35 40 40 40 40 40 30 40 40 40 40 40 40 25 40 40 40 40 40 40 40 20
250 150 260 290 320
KXA 40
KXC 50
KXA 33 KXA 41
30
200±3
200±3
200±3
30
30
40
40
40
30
40 40 40 40 40 40 40 40 20 40 40 40 40 40 40 40 40 40 20 40 40 40 40 40 40 40 40 40 40 20
360 400 440
KXA 60 Sample Connection
KXA 51 KXC 63
200±3
200±3
30
30
40
40
Ø14 Ø14
30
30
40 40 40 40 40 40 40 40 40 40 40 40 30 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 20 X X
540 680
Note: Please contact with us for the dimensions of our 6 conductor solutions. Please call us for non-standard components. (Minimum X= 25 mm )
Distance between conductors can vary in ±5 mm. The dimensions given above are minumum values. Do not hanger the relevant modules from the flanges.
30 www.eaeelectric.com
ELINEKX
►►Tap-off Boxes
Locking
Point
Effective Gasket
• Protection from dust and humidity due to effective gasket system.
• High IP Protection due to special forming.
Special
Gasket Forming
C
Sheet ---- RP0 ---- Bolt-on / 630 A / IP-55 /
5 Conductors
te
Pla
KXB 6351 l a nd )
Sheet M32 RP1 25 G es
ble id
Ca on 3 s
( N 1
L
L2 3
Sheet M40 RP2 32 L
AL 2xSpecial RP4 63
50
AL 4xM25 RP5 18
AL 4xM32 RP6 25
AL 4xM40 RP7 32
30 A 30
AL 8xM32 RP8 25
Notes:
C
Sheet ---- RP0 ---- Plug-in / 630 A / IP-55
5 Conductors
te
KXP 6351 d Pla
Sheet M32 RP1 25 n
Gla es )
bl e sid
Ca on 3
( N
Sheet M40 RP2 32 L1 2
L 3
L
AL 2xSpecial RP4 63
50
AL 4xM25 RP5 18
AL 4xM32 RP6 25
AL 4xM40 RP7 32
AL 8xM32 RP8 25
30 A 30
Notes:
B
Code
Type (mm)
KX B 1 6 5 1 - M
A
KX B 2 5 5 1 - M
Sheet ---- RP0 ---- KX B 4 0 5 1 - M
C
KX B 6 3 5 1 - M
AL 2xSpecial RP4 63
50
AL 4xM25 RP5 18
AL 4xM32 RP6 25
AL 4xM40 RP7 32
30 A 30
AL 8xM32 RP8 25
D
AL 3xSpecial RP9 63
Cable
Order Inner KX P 1 6 5 1 - B
Mat. Gland Diameter KX P 2 5 5 1 - B
Code (mm) B
Type KX P 4 0 5 1 - B
KX P 6 3 5 1 - B
A
Sheet ---- RP0 ---- KX P 1 6 5 1 - M
KX P 2 5 5 1 - M
C
KX P 4 0 5 1 - M
Sheet M32 RP1 25 KX P 6 3 5 1 - M
Sample Order:
Sheet M40 RP2 32
Plug-in / 400 A / IP-55 /
late
5 conductors, empty tap-off box dP
Sheet Special RP3 63 N 1 G lan es )
KXP 4051 - B L 2 ble id
L 3
L Ca on 3 s
(
AL 2xSpecial RP4 63
AL 4xM25 RP5 18
AL 4xM32 RP6 25
50
AL 4xM40 RP7 32
AL 8xM32 RP8 25
Cable Inner
Order
Mat. Gland Diameter
Code (mm)
Type
D
Sheet ---- RPK0 ----
SLAB
WALL
100
HOLE
L3
L2
L1
N BUSBAR
100
WALL
SLAB
WALL
100
200 (min.)
BUSBAR-1 HOLE
L3
L2
L1
N
BUSBAR
WALL
100
100
SLAB
min. A min.
(A/2)+50 (A/2)+50
100
BUSBAR-1
BUSBAR-2
WALL
100 100
N L1 L2 L3 N L1 L2 L3
SLAB
BEAM
100
L3
BUSBAR (FLATWISE POSITION) L2
L1
N
Please call us for non-standard tap-off boxes and detailed information. The dimensions given above are minumum values.
www.eaeelectric.com 37
ELINEKX
►► Vertical and Horizontal Busbar Applications
SLAB
N L1 L2 L3 N L1 L2 L3
BEAM
20
SLAB
BUSBAR (EDGEWISE POSITION)
N L1L2 L3
200
FIGURE-7 CROSSING UNDER A BEAM EDGEWISE POSITION
N L 1L2 L3 N L 1L2 L3
VERTICAL EXPANSION
COMPONENT
BACK WALL - CURTAIN CONCRETE
100
150 200
A
WALL
B
TAP-OFF
BOXES
FIGURE-8 MINIMUM DIMENSIONS BETWEEN 2 TAP-OFF BOXES
WALL
KXA - Al KXC - Cu
A
Conductor Conductor
PLUG-IN BUSBAR
Rated Busbar Rated Busbar (mm)
Current Code Current Code
* 400 04 *550 05 77,5
* 500 05 *650 06 82,5
* 630 06 *800 08 91
800 08 1000 10 106
1000 11 - - 111
- - 1250 12 121 NOTE : In order to accomodate the busbar
1000 10 1350 14 131 systems in the riser shaft;
- - 1600 17 146
1250 12 - - 161
1350 14 2000 23 176 MDM = Minimum Distance from the wall
1600 16 - - 191 "A" dimension = All dimensions are for
1600 17 - - 211 standard modules .
2000 18 - - 233
"C" dimension = Please see page 32-35 and special
2000 20 2500 25 251
dimension for Tap-off box “C” dimension
2500 29 - - 281
2500 27 - - 301
- - 2000 22 202 "B" dimension = Max. opening distance for Tap-off box
- - 2500 27 232 cover.
2500 25 3300 32 312 Shaft Dimension = MDM + A + C + B + 100mm
- - 3600 36 342
Shown as (Figure-8)
200
KX
Cable Gland Plates
Busbar Cable Feeder Box B10 -B 1 0
Type
Housing Type Gland Plate
Sample Order:
3200 A, Aluminium, Bolt-on
1
4 Conductors
2
Sample Order:
3600 A, Copper, Bolt-on,
4 Conductors
PE
L3
L2
L1
4
N
Ampere Ratings
KXA - Al KXC - Cu Cable
A B C D Gland Type
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm) (mm) (mm)
Current Code Current Code
* 400 04 *550 05 500 520 / 620* 355 350 1
* 500 05 *650 06 500 520 / 620* 355 350 1
225 A
* 630 06 *800 08 500 520 / 620* 355 350 1
800 08 1000 10 500 520 / 620* 355 350 1
1000 11 - - 500 520 / 620* 355 350 1
- - 1250 12 500 520 / 620* 355 350 1 B
KX
Cable Gland Plates
Busbar Cable Central Feeder Box -B O
Type
Housing Type Gland Plate
Sample Order:
2500 A, Aluminium, Bolt-on
1
4Conductor
PE
KXA 25504 - B - BO
L3
L2
L1
N
PE
L3
3 L2
L1
N
3
C
Ampere Ratings
KXA - Al KXC - Cu Cable
A B C X Gland Type
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm) (mm) (mm)
Current Code Current Code
* 400 04 *550 05 500 520 / 620* 405 175 1
* 500 05 *650 06 500 520 / 620* 405 175 1
* 630 06 *800 08 500 520 / 620* 405 175 1 B
►►Fixing Elements
Supports
Description Order Code
4 4
40 40
40 40
0
24
33
250
250
(Fire Barrier)
4 4
Rear 40 40
40 40
Floor-2
0
24
0
33
250
250
Front
Floor-1
(Fire Barrier)
Fixing Elements
Description Order Code
Please call us for non-standard components. The span between supports should be 1.5m
www.eaeelectric.com 41
ELINEKX ORDER CODE
LENGTH L (mm)
►► Fixing Elements
Supports Al Cu Order
L A
Conductor Conductor Code
22
7,5
41
2
41
41
2
41
Please call us for non-standard components. The span between supports should be 1.5m
42 www.eaeelectric.com
ELINEKX ORDER CODE
LENGTH L (mm)
►►Fixing Elements
Please call us for non-standard components. The span between supports should be 1.5m
www.eaeelectric.com 43
ELINEKX ORDER CODE
LENGTH L (mm)
►► Fixing Elements
Supports Al Cu Order
L A
Conductor Conductor Code
50
5 50
KX HANGER Al Cu Order
L A
SET FOR FLATWISE Conductor Conductor Code
APPLICATION
TO STEEL ANGLE Rated Busbar Rated Busbar (mm) (mm)
Current Code Current Code
PROFILE
400 04 550 05 77,5
500 05 650 06 82,5
630 06 800 08 91
800 08 1000 10 300 106 3025343
1000 11 - - 111
- - 1250 12 121
1000 10 1350 14 131
- - 1600 17 146
350 3025344
1250 12 - - 161
1350 14 2000 23 176
1600 16 - - 191
400 3025345
1600 17 - - 211
2000 18 - - 233
2000 20 2500 25 251
2500 29 - - 450 281 3025346
50 2500 27 - - 301
5 50
Please call us for non-standard components. The span between supports should be 1.5m
44 www.eaeelectric.com
ELINEKX ORDER CODE
LENGTH L (mm)
►►Fixing Elements
R
Supports Order
Description
Code
KX IDY Support Set 2054590
2000 18 - - 233
2000 20 2500 25 251
400 3113548
2500 29 - - 281
A
2500 27 - - 301
- - 2000 22 202
- - 2500 27 232
150
►► Fixing Elements
Supports L Order
Description (mm) Code
IDY 300 300 3008242
IDY 400 400 3008290
24 IDY 500 500 3008289
IDY 600 600 3008288
L IDY IDY 700 700 3008287
IDY 800 800 3008286
IDY 900 900 3008285
IDY 1000 1000 3008284
IDY 1100 1100 3008283
IDY 1200 1200 3008282
75 IDY 1300 1300 3008236
IDY 1400 1400 3008281
IDY 1500 1500 3008280
IDY 1600 1600 3008241
IDY 1700 1700 3008240
IDY 1800 1800 3008239
IDY 1900 1900 3008238
IDY 2000 2000 3008237
IDD 300 300 3008314
IDD 400 400 3008313
5
10 19 IDD 500 500 3008312
0 IDD
IDD 600 600 3008311
IDD 700 700 3008310
10 IDD 800 800 3008309
6 IDD 900 900 3008308
105
25
25
13
11
75
IDT
IDT
IDY
Please call us for non-standard components. The span between supports should be 1.5m
46 www.eaeelectric.com
ELINEKX ORDER CODE
LENGTH L (mm)
►►Fixing Elements
Supports T L Order
Description (mm) (mm) Code
UPY 300 4 300 3004487
Steel UPY 400 4 400 3004489
Dowel UPY 500 4 500 3004491
UPY 600 4 600 3004493
UPY UPY 700 4 700 3004495
UPY 800 4 800 3004496
Threaded UPY 900 4 900 3004497
Rod UPY 1000 4 1000 3004498
UPY 1100 4 1100 3004499
UPY 1200 4 1200 3004500
UPY 1500 4 1500 3004503
T
L
UPY
65
43
Please call us for non-standard components. The span between supports should be 1.5m
www.eaeelectric.com 47
ELINEKX ORDER CODE
LENGTH L (mm)
►► Fixing Elements
Supports L Order
Description (mm) Code
UDY 300 300 3008023
UDY 400 400 3008024
Steel UDY 500 500 3008025
Dowel UDY 600 600 3008026
UDY
UDY 700 700 3008027
UDY 800 800 3008028
UDY
UDY 900 900 3008029
Threaded UDY 1000 1000 3008030
Rod UDY 1100 1100 3008031
UDY 1200 1200 3008032
UDY 1300 1300 3008033
UDY 1400 1400 3008034
UDY 1500 1500 3008035
UDY 1600 1600 3008036
UDY 1700 1700 3008037
UDY 1800 1800 3008038
UDY 1900 1900 3008039
UDY 2000 2000 3008040
UDY
Steel
Dowel
L
UDY
Threaded
Rod
65
42
UDY
Please call us for non-standard components. The span between supports should be 1.5m
48 www.eaeelectric.com
ELINEKX ORDER CODE
LENGTH L (mm)
►►Fixing Elements
Supports Order
Description L (mm)
Code
UAS-K5 Supports (1) 200 3005324
Threaded Threaded
UAS-K5 Supports (2) 250 3005323
Rod Rod
UAS-K5 Supports (3) 300 3005322
UAS-K5 UAS-K5 Supports (4) 350 3005321
UAS-K5 Supports (5) 400 3005320
UAS-K5 Supports (6) 500 3005319
UAS-K5 Supports (7) 600 3005318
UAS-K5 Supports (8) 700 3005317
UAS-K5 Supports (9) 1100 3005316
UAS-K5
50
5 50
L Order
Description (mm) Code
Connection Units BRA 12-05 Threaded Rod (M10) 500 5000037
BRA 12-10 Threaded Rod (M10) 1000 5000032
BRA 14-05 Threaded Rod (M12) 500 5000026
BRA 14-10 Threaded Rod (M12) 1000 5000034
L BRA 13 Extension Unit (M10) - 1004312
Threaded BRA 13 Extension Unit (M12) - 1004282
Rod BRA 9 Steel Dowel (M10) - 5000023
BRA 9 Steel Dowel (M12) - 5000022
M10 Steel Nut - 1000522
M12 Steel Nut - 1000964
M10 Washer - 1000504
M12 Washer - 1000505
Extension
Unit
Diameter of the
Steel Dowel hole to be drilled
M10.....Ø14
M12.....Ø16
Steel Nut
Washer
FRONT
10
8 3
4
2
1
7
12
11 6
Figure 5
Figure 1 Block Joint The joint cover is
closed by leverage.
After installation of standard busbar 3m lengths, you will be in need of special lengths which are smaller than 3m The minimum length for these
special elements can be 350 mm. Please measure the lengths of these modules as shown below.
Length A is measured between housing of 2 busbars in cm. A. The special length is calculated by deducting 250mm from this measured length.
X=A-250 (mm) X=Length of Special Busbar (The busbar module will be manufactured as per X value.)
125 125
1 Alignment Pin
2 2a
2a
2a
1- Remove Alignment Pin on the busbar, without block 2- Insert the piece aligning conductors correctly. Fix back the
joint. Alignment pin.
3 4
3a
3a
3- Make sure busbar piece is aligned according to alignment pin. 4- Fix one of the joint cover to stabilize joint. Apply
83Nm to the main bolt.
5 6
1
First 4
Torque:
(20-30Nm) 3
2
5
Final 8
Torque:
(83Nm) 7
6
5- If there are more than one 6- Fix the remaning joint cover. Joint installation is completed.
bolt for the same phase, bolts
shall be tighten by hand
approximately 20-30Nm as per Note: If the final joint cover does not close correctly, it indicates
above sequence, then 83Nm the busbar is not completely aligned. Release the bolts and
shall be applied at final torque reapply the sequence from figure 4 to complete the joint.
with the same sequence.
52 www.eaeelectric.com
ELINEKX
►►Declaration
CE DECLARATION OF CONFORMITY
Product Group E-Line KX Busbar Energy Distribution System
The objects of the declaration described below is in conformity with the relevant Union harmonisation
legislation. This declaration of conformity is issued under the sole responsibility of the manufacturer.
Standard :
TS EN 61439-6
Low-voltage switchgear and controlgear assemblies - Part 6: Busbar trunking
systems
CE - Directive
Mustafa AKÇELİK
www.eaeelectric.com 53
ELINEKX
►► Certificate
54 www.eaeelectric.com
ELINEKX
►►55
www.eaeelectric.com 55
56
Component List
Item Component Quantity
ELINEKX
►► Project Design Form
Company :
www.eaeelectric.com
Project :
Project No :
Name :
Date :
Signature :
Prepared by
CABLE TRAYS
INDOOR SOLUTIONS
SUPPORT SYSTEMS
TURKEY
OMAN
SUDAN
CHILE
PERU
KENYA
LEBANON
GHANA
SUDANCHILE
YEMEN CHILEALGERIA PERU
OMAN TURKMENISTAN TURKEY
INDIA MADAGASKAR
SRI LANKA LATVIA
ETHIOPIA
TAIWAN
GHANA FRANCE
VIETNAM UKRAINE
KONGO
CAMEROON
THAILAND QATAR
ESTONIA FINLAND KUWAIT
IRELAND
BANGLADESH KUWAIT UZBEKISTAN
RWANDA ALGERIA CHINA
TANZANIA BELGIUM
MADAGASKAR
GHANA THAILAND KENYA QATAR CAMEROON DENMARK
QAT
GERMANY MOROCCO SINGAPORE PAKISTAN TANZANIA ROMANIA
BELGIUM AUSTRIA
ETHIOPIA
KENYA
PERU EQ. GUINEA TURKEY OMAN VIETNAM LATVIA MACED
CZECH REP.
PERU VIETNAMNETHERLANDS SINGAPORE
AUSTRIA INDIA LIBYA
OMAN AZERBAIJAN
TANZANIA MACEDONIA MADAGASKAR TUNISIA AZER
POLAND TURKMENISTAN
MAURITIUS GREECE KAZAKHSTAN NIGERIA LUXEMBOURG RWANDA GREECEDENMARKCROATIA SOUTH KOREA SWI
THAILAND
NMAR SPAINIRELAND SERBIA OMAN
RKEY SLOVENIA
UZBE
T FRANCE ETHIOPIA
VIETNAMCAMEROON PAKISTAN SPAIN EGYPT VIETNAM SUDANNETHERLANDS MADAGASKAR TURKEY NIGERIAITALY QATAR U.KINGDOM
KOREA
TAIWAN
BAHRAIN
IA GHANATURKMENISTAN CYPRUS BULGARIA AZERBAIJAN SWITZERLAND U. A. EMIRATES BULGARIA SOUTH AFRICA QATAR TURKEY GREECE
PAKISTAN D
VIETNAM NORWAY SERBIANORWAY SPAIN FRANCE DENMARK
E SRI LANKA
MYANMAR NIGERIAGERMANY
POLAND U. A. EMIRATES
TNAMSOUTH KOREA TURKEY ICELAND VIETNAM SWITZERLAND TURKMENISTANYEMEN SUDAN SWITZERLAND U. A. EMIRATES
HUNGARY CAMEROON YEMEN U. A. EMIRATES CHILE LUXEMBOURG LITHUANIA MACEDONIA TANZANIA MACEDON
MALTA SU
MADAGASKA
SAUDI ARABIA YEMEN BRASILBELGIUM POLAND BELGIUM U.KINGDOM TURKMENISTAN CZECH REP. AZERBAIJAN DENMARK
PAKISTAN YE
EAE Elektrik A.S.
Head Office
Akcaburgaz Mahallesi,
3114. Sokak, No: 10 34522
Esenyurt – Istanbul – TURKEY
Tel: +90 (212) 866 20 00
Fax: +90 (212) 886 24 00
EAE DL 3 Factory
Busbar
Gebze IV Istanbul Makine ve Sanayicileri
Organize Bolgesi, 6. Cadde,
No: 6 41455 Demirciler Koyu,
Dilovası – Kocaeli – TURKEY
Tel: +90 (262) 999 05 55
Fax: +90 (262) 502 05 69