e Line Kx Busbar

The E-LINEKX Busbar Systems provide efficient and flexible electrical distribution solutions ranging from 400 to 6300 A, designed to replace traditional cable systems with modular components for easier installation and better performance. Key features include high short-circuit endurance, compact structure for improved heat dissipation, and customizable components for various applications. The systems comply with IEC 61439-6 standards, ensuring safety and reliability in electrical installations.

Uploaded by

ahmedalbirkhadri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
5 views

e Line Kx Busbar

The E-LINEKX Busbar Systems provide efficient and flexible electrical distribution solutions ranging from 400 to 6300 A, designed to replace traditional cable systems with modular components for easier installation and better performance. Key features include high short-circuit endurance, compact structure for improved heat dissipation, and customizable components for various applications. The systems comply with IEC 61439-6 standards, ensuring safety and reliability in electrical installations.

Uploaded by

ahmedalbirkhadri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 60

E-LINEKX Busbar Systems 400...

6300 A

www.eaeelectric.com
E-LINEKX

Please visit our website for the updated version of our catalogues.
www.eaeelectric.com
CONTENTS
E-LINE KX

Introduction.....................................................................................................................................2-3
Distribution & Horizontal Applications..............................................................................................4
Riser & Vertical Applications..............................................................................................................5
Technical Characteristics...............................................................................................................6-9
Order Code System.......................................................................................................................... 10
Straight Lengths............................................................................................................................... 11
Elbows........................................................................................................................................ 12-15
"T" Module........................................................................................................................................ 16
Reduction Modules.......................................................................................................................... 17
Expansions....................................................................................................................................... 18
Phase Transposition Module........................................................................................................... 19
End Closers....................................................................................................................................... 20
Panel Connections..................................................................................................................... 21-25
Transformer Connections ......................................................................................................... 26-30
Tap-off Boxes............................................................................................................................. 31-36
Vertical and Horizontal Busbar Applications............................................................................ 37-38
Feeder Boxes.............................................................................................................................. 39-40
Fixing Elements.......................................................................................................................... 41-49
Joint Structure.................................................................................................................................. 50
Measuring a Special Lenght............................................................................................................ 51
Inserting "Make up Section"............................................................................................................ 52
Declaration....................................................................................................................................... 53
Certificate......................................................................................................................................... 54
Product Overview............................................................................................................................. 55

Please visit our website for the updated version of our catalogues.
www.eaeelectric.com
ELINEKX
►►Introduction

Transportation and distribution of electricity especially at high ampere ratings


Wire Systems
used to be provided by paralelling a number of large sized cables. In order to
support these cables in the buildings, there were used a lot of cable trays, cable
ladders, under-floor cable channels, etc. Applications of cables, such as, fixing to
cable channels, branching, connecting, calculating distances between cables for
heat dissipation, adjusting difference lengths, etc. need special expert workers,
more time, more effort, which means more money. Even after all above
difficulties and expense, the result is not efficient enough. For example, there is
no flexibility in this solution.

In order to eliminate all above disadvantages, modern BUSBAR SYSTEMS are


developed. EAE manufactures E-LINE busbar systems from 25A up to 6.300A in
order to convert above disadvantages to advantages. High technological,
modular structured E-LINE busbar systems allow users to get safe energy how
much and where ever they need by tap off boxes, easy and efficient planning,
short installation time, better heat dissipation, automatic length adjustments,
redesign / re-using capability, better electrical characteristics, etc.
E-LINE busbar systems are designed and certified as per IEC 61439-6 standard.

E-Line KX Busbar System

Standard Prefabricated Structure


E-Line KX busbar system can be
adapted to any kind of building
structure using. Space-saving
prefabricated components.
All necessary components and
fitting elements are manufactured
items.

* Special components can be


manufactured in one week on request.

Rapid and Efficient Installation


It has been important to keep abreast
with the rapidly improving building
technologies in civil engineering, the
installation time was we have lowered
by reducing the number of bolts on the
joint points of the busbar.

Flexible Power Supply


Tap-off points at short intervals
make electrical power available
in all locations; the power supply
can be adapted to different production
processes simply by relocating the
tap-off unit.

2 www.eaeelectric.com
ELINEKX
►►Technical Features

Hybrid Insulation High Short-Circuit Endurance


The perfect design for high current busbar systems As there are no support points
is the "compact structure" where tin plated and insulated in "compact structure"
with B class polyester film and epoxy coated on conductors momentum levers are not
are tightly placed into the extruded aluminium housing. formed (Figure 1).
(Figure 1). This feature ensures high
short-circuit endurance
Epoxy Coated Extruded (Figure 5).
Aluminium Housing

Conductors (Al, Cu)


Tin plated

PE
Figure 2
Isolated Layers Figure 1

Heat Transfer
"In compact structure" there is no empty space filled with
air and heat is easily transferred to the environment by the
housing that works like a heat-shink (Figure 2).

Minimum Voltage Drop


In E-Line KX, inductive reactance is very low due to
closely placed conductors. Figure 5
The voltage drop comparison of compact and ventilated
busbar that have same cross sectional area prove
the importance of the compact structure.

One Bolt Joint Ensures Safety and Easy Installation Easy and Safe Installation:
E-Line KX Busbars are installed by tightening Due to alignment piece on the
the "one bolt joint". Belleville spring washers on joint point, block joint element
both ends of the bolt retains the original contact and busbar tray are aligned.
pressure, ensuring a more secure, reliable and This makes installation easier
maintenance - free joint. and correct on the right axes.
E-Line KX Busbar Systems are easily installed (Figure 6).
(Figures 3-4).

* The bolt is tightened to 83 Nm (60 lbft)


using the torque spanner.

Figure 3

Figure 6

50

60 Figure 4

83Nm
TORQUE SPANNER (60lbft)

www.eaeelectric.com 3
ELINEKX
►►Distribution & Horizontal Applications

While designing an electrical distribution system with E-Line KX Rated Current


a few approximate details will be necessary. The current is calculated using the following equation:

• Location, number, type and approximate ratings of loads,


P.a
• Transformer rates and short-circuit capacities, IB =
Utilization factor=a, Ö3.U.cos j
• System coordination with other distribution system (heat,
water, etc.), IB = Operation current (A)
• Determining the route of E-Line KX on layout, If necessary, P = Installed load (W)
coordination of E-Line KX Busbar with E-Line KO-II runs, a = Utilization factor
• Deciding on suitable hanger types. U = Supply voltage (V)

Utilization Factor (a) • Busbar current rating is chosen as equal to or higher then the
Utilization factor (a) depends on the type and calculated IB current.
number of loads. • After the voltage drop calculation if the chosen current rate is not
It is usually around 0.7 or lower. The utilization factor convenient, a higher rating is chosen.
of a line that supplies electricity to motors and lighting
systems is usually lower than 0.6. Short-Circuit
It is as low as 0.30 in weld shops of car factories, it can be Tested short-circuit capacities are given on technical
1 in lines where only one big load is supplied. characteristics table on pages 6-9.

Voltage Drop Busbar Installation Plan


For practical voltage drop calculation, necessary Our distributor's project & design departments will help you for
values, formula and easy calculation methods are preparing the installation plans on request.
given on the technical characteristics table on pages 6-9.

Components List
Item Components Quantity
1 KXA 20504 - STD Busbar (20 x 3m.) 60 m.

2 KXA 20504 - D Downwards Elbow 2 pcs.

3 KXA 20504 - R Right Elbow 1 pc.

4 KXA 20504 - U Upwards Elbow 1 pc.

5 KXA 20504 - L Left Elbow 1 pc.


6 pcs. KXB 2550
8 pcs. KXP 1650 6 KXA 20504 - P11 Panel Connection 1 pc.

7 KXA 20504 - S10 End Closer 1 pc.


54 m. (18 pcs. x 3 m.)
KXA 20504 8 KXA 20504 - X95 Special Straight Length 1 pc.

9 KXA 20504 - X120 Special Straight Length 1 pc.

10 KXA 20504 - X122 Special Straight Length 1 pc.

11 KXA 20504 - X200 Special Straight Length 1 pc.

12 KXA 20504 - X174 Special Straight Length 1 pc.

13 KXP 1650 Tap-off Box 8 pcs.

14 KXB 2550 Tap-off Box 6 pcs.

Company : Demir Makine


Project : II.OSB
Project No : 1128

Name : Abdullah ELDELEKLI


Prepared by

Date : 02 / 01 / 2022

Signature :

Project Sample

4 www.eaeelectric.com
ELINEKX
►►Riser & Vertical Applications

As each building's structure is different than the other for vertical applications of E-Line KX special Line end
projects has to be designed.

The details on this page briefly explain the necessary information for drawing a vertical application
a= ......
project.

L1

L1
L2
L3

L2
L3
N

N
r
rrie
e Ba
Fir
10. Floor
a= ......

h= ......
Vertical Expansion

150 150 I14


( 70 cm. )

9. Floor
a= ......
( h ) Height of store measured from ceiling to ceiling ( cm. )

h= ......
ox I13
-o ff B
B

ap 8. Floor
g-in T a= ......
Plu
t
oin
Special Length Plug-in Busbar

gP

h= ......
Tap-off Point

Plu
I12
7. Floor
a= ......

h= ......
A

I11
6. Floor
a= ......
in t
r Jo
sba

h= ......
Bu I10
5. Floor
a= ......

h= ......
I9
4. Floor
I8
a= ......
(a
)C
eili
h= ......

ng
thi
ckn I7
ess I6
(c 3. Floor
m. a= ......
)
h= ......

n I5
Project Design … 2. Floor
11 a= ......
10
The details below should be sent to our Project & Design
h= ......

9
department. 8 I4
7
1. Floor
• Location and dimensions of the floor penetration 6 a= ......
where busbar will be installed. 5

• Number, height and ceiling thickness of storeys.


h= ......

4
3
(a=..., h=...) 2
I3
• Connected load for each storey. 1 Ground Floor
a= ......
• Supply type of the vertical line (busbar or cable). Ground
Floor
Basement
h= ......

Please send the information to us by fax or e-mail with a sample


I2
drawing in Figure 1.
1.Basement
Busbar System System Cable a= ......
System
h= ......

In multipath busbars in high-rise vertical shaft applications; I1


Due to floor heights, floor thickness and product tolerances, the window or additional point
2.Basement
alignments on the upper floors may not be the same. In order for the Tap off boxes to be aligned a= ......
and the joint point not to coincide with the floor transitions, the assembly should be continued by Feeder side,
cable or busbar
h= ......

making measurements on each floor.

3.Basement
EAE is not responsible for the potential risks that may occur in cases where the products in our Figure 1
catalogue are used outside of the standard phase sequences as shown in the catalogue.
www.eaeelectric.com 5
ELINEKX
►►Technical Characteristics

Aluminium Conductor (Al)


Standards IEC 61439-6, TS EN 61439-6, IEC 61439-1, TS EN 61439-1
Rated Isolation Voltage Ui V 1000 at Cat IV
Max. Rated Operational Voltage Ue Vac 1000
Rated Impulse Withstand Voltage Uimp kV 12
Rated Frequency f Hz 50
Pollution Degree III
Protection Degree IP55 / IP65
External Mechanical Impacts (IK Code)* Bolt-on Busbar IK10+, Plug-in Busbar IK08
Rated Current In A 400 500 630 800 1000 1000 1250 1350
Busbar Code 04 05 06 08 11 10 12 14
Rated Short-time Withstand Current (1s) (Three phase) Icw kA 16 16 25 35 35 50 60 60
Rated Peak Withstand Current Ipk kA 32 32 52,5 73,5 73,5 105 132 132
Rated Short-time Withstand Current for Neutral Conductor(1s)(Single phase) Icw kA 9,6 9,6 15 21 21 30 36 36
Rated Peak Withstand Current for Neutral Conductor Ipk kA 16,32 16,32 30 44,1 44,1 63 75,6 75,6
Rated Short-time Withstand Current for PE (Housing) Conductor(1s)(Single phase) Icw kA 9,6 9,6 15 21 21 30 36 36
Rated Peak Withstand Current for PE (Housing) Conductor Ipk kA 16,32 16,32 30 44,1 44,1 63 75,6 75,6
MEAN PHASE CONDUCTOR CHARACTERISTICS AT RATED CURRENT In
Resistance at a conductor temperature of 20 °C R20 mW/m 0,197 0,163 0,121 0,088 0,077 0,061 0,044 0,040
Resistance at an ambient air temperature of 35 °C R mW/m 0,258 0,225 0,159 0,116 0,103 0,080 0,058 0,052
Reactance (Independent from Temperature) X mW/m 0,035 0,033 0,027 0,021 0,020 0,015 0,013 0,013
Positive and negative sequence impedances at an ambient air temperature of 35 °C Z mW/m 0,260 0,227 0,162 0,118 0,105 0,082 0,060 0,053
Positive and negative sequence impedances at a conductor temperature of 20 °C Z20 mW/m 0,200 0,167 0,124 0,091 0,077 0,063 0,046 0,042
DC Resistance at a conductor temperature of 20 °C for Phases R/ortph mW/m 0,197 0,161 0,124 0,087 0,075 0,060 0,043 0,039
DC Resistance at a conductor temperature of 20 °C for Neutral RN mW/m 0,198 0,164 0,126 0,090 0,075 0,061 0,044 0,039
DC Resistance at a conductor temperature of 20 °C for PE (Housing) RPE mW/m 0,038 0,033 0,028 0,024 0,024 0,023 0,023 0,026
SECTIONS
L1,L2,L3,N mm² 150 180 240 330 360 480 660 750
PE (4 ½ Conductors) mm² 75 90 120 165 180 240 330 375
PE (5 Conductors) mm² 150 180 240 330 360 480 660 750
Aluminium Housing Section (Aluminium) mm² 1449 1509 1686 1788 1829 1894 2050 2128
Conductor Dimensions mmxmm 6x25 6x30 6x40 6x55 6x60 6x80 6x110 6x125
Busbar Weight (4 Conductors) kg/m 7,0 7,4 7,9 9,2 10,1 11,3 13,9 15,2
Busbar Weight (5 Conductors) kg/m 7,4 7,9 8,6 10,2 11,1 12,8 15,9 17,5
MEAN FAULT-LOOP CHARACTERISTICS
Zero-sequence Impedance
Zero-sequence impedance at a conductor temperature of 20 °C Z(0)b20phN mW/m 0,873 0,748 0,572 0,419 0,351 0,291 0,214 0,194
Zero-sequence impedance at a conductor temperature of 20 °C (Housing) Z(0)b20phPE mW/m 0,430 0,398 0,326 0,268 0,215 0,245 0,208 0,199
Zero-sequence impedance at an ambient temperature of 35 °C Z(0)bphN mW/m 1,129 1,011 0,742 0,540 0,470 0,371 0,274 0,245
Zero-sequence impedance at an ambient temperature of 35 °C (Housing) Z(0)bphPE mW/m 0,528 0,507 0,406 0,331 0,276 0,303 0,260 0,245
RESISTANCES AND REACTANCES
Resistance at a conductor temperature of 20 °C Rb20phph mW/m 0,399 0,337 0,249 0,184 0,153 0,125 0,092 0,083
Resistance at a conductor temperature of 20 °C Rb20phN mW/m 0,408 0,347 0,255 0,192 0,161 0,131 0,096 0,087
Resistance at a conductor temperature of 20 °C (Housing) Rb20phPE mW/m 0,252 0,223 0,175 0,137 0,112 0,112 0,093 0,086
Resistance at an ambient air temperature of 35 °C Rbphph mW/m 0,523 0,464 0,328 0,241 0,211 0,164 0,120 0,107
Resistance at an ambient air temperature of 35 °C RbphN mW/m 0,534 0,477 0,336 0,252 0,220 0,171 0,126 0,113
Resistance at an ambient air temperature of 35 °C (Housing) RbphPE mW/m 0,330 0,307 0,231 0,180 0,153 0,146 0,122 0,112
Reactance (Independent from temperature) Xbphph mW/m 0,073 0,065 0,043 0,042 0,037 0,032 0,024 0,023
Reactance (Independent from temperature) XbphN mW/m 0,102 0,092 0,075 0,058 0,053 0,045 0,034 0,032
Reactance (Independent from temperature) XbphPE mW/m 0,102 0,093 0,069 0,061 0,049 0,050 0,041 0,039

6 www.eaeelectric.com
PE
L3
L2
L1
N2
N1

1600 1600 2000 2000 2500 2500 2500 3200 3200 4000 4000 5000 6000
16 17 18 20 29 27 25 32 33 40 41 51 60
PE
60 80 80 80 80 80 100 100 120 120 120 120 120 L3
L2
132 176 176 176 176 176 220 220 264 264 264 264 264 L1
36 48 48 48 48 48 60 60 72 72 72 72 72 N
75,6 100,8 100,8 100,8 100,8 100,8 132 132 158,4 158,4 158,4 158,4 158,4
36 48 48 48 48 48 60 60 72 72 72 72 72
75,6 100,8 100,8 100,8 100,8 100,8 132 132 158,4 158,4 158,4 158,4 158,4
L3
0,034 0,031 0,027 0,024 0,021 0,019 0,022 0,017 0,015 0,012 0,014 0,010 0,008 L2
0,044 0,041 0,035 0,034 0,028 0,026 0,029 0,022 0,020 0,016 0,017 0,014 0,010 L1
0,010 0,010 0,008 0,008 0,007 0,007 0,007 0,005 0,005 0,004 0,004 0,003 0,002 N
0,045 0,042 0,036 0,035 0,029 0,027 0,030 0,022 0,020 0,017 0,018 0,014 0,010
0,034 0,033 0,028 0,027 0,022 0,021 0,023 0,017 0,016 0,013 0,013 0,010 0,008
0,032 0,030 0,025 0,024 0,020 0,019 0,022 0,016 0,015 0,012 0,013 0,010 0,008 Voltage Drop Calculation
0,032 0,031 0,025 0,025 0,020 0,020 0,023 0,018 0,017 0,013 0,013 0,010 0,008 Generally Voltage drop of a busbar system
can be calculated with the following formula.
0,022 0,022 0,021 0,021 0,022 0,020 0,019 0,017 0,017 0,015 0,016 0,013 0,013

840 960 1080 1200 1380 1500 1320 1680 1920 2400 2160 3000 3600
420 480 540 600 690 750 660 840 960 1200 1080 1500 1800
DU= √3.L.I.(R .Cosj+X .Sinj) 10-3 [V]
840 960 1080 1200 1380 1500 1320 1680 1920 2400 2160 3000 3600
DU = Voltage Drop (V)
2206 2314 2410 2518 2679 2764 3912 4224 4411 4848 4640 5275 7128
L = Line Length (m)
6x140 6x160 6x180 6x200 6x230 6x250 2(6x110) 2(6x140) 2(6x160) 2(6x200) 2(6x180) 2(6x250) 3(6x200) I = Line Current or Load (A)
17,0 18,3 20,5 21,7 24,9 28,5 27,3 32,5 35,9 42,9 38,6 57,2 63,9 R = Resistance (mW/m)
X = Reactance (mW/m)
19,6 21,1 23,7 25,3 29,0 34,2 31,2 37,5 41,6 50 45,0 68,5 74,6

0,164 0,153 0,132 0,130 0,102 0,103 0,108 0,081 0,074 0,060 0,065 0,048 0,039
0,141 0,161 0,126 0,158 0,112 0,131 0,101 0,076 0,101 0,084 0,085 0,078 0,043 L
0,209 0,195 0,169 0,167 0,131 0,135 0,140 0,104 0,094 0,078 0,084 0,064 0,050 S I
0,176 0,199 0,159 0,199 0,143 0,168 0,126 0,095 0,127 0,108 0,111 0,102 0,054 S = Supply Point

0,067 0,065 0,054 0,054 0,041 0,042 0,046 0,034 0,031 0,025 0,026 0,020 0,016
0,071 0,069 0,057 0,057 0,044 0,044 0,049 0,036 0,033 0,027 0,028 0,021 0,017
All phase conductor characteristics had been
0,063 0,068 0,055 0,065 0,047 0,050 0,053 0,033 0,049 0,035 0,033 0,031 0,019 determined according to Annex BB of IEC / EN
0,088 0,086 0,071 0,072 0,055 0,057 0,059 0,044 0,040 0,033 0,035 0,027 0,021 61439-6.
Fault-loop zero-sequences impedances had
0,094 0,090 0,076 0,076 0,058 0,060 0,062 0,047 0,043 0,035 0,038 0,029 0,022 been determined according to Annex CC of IEC / EN
61439-6.
0,083 0,089 0,072 0,086 0,062 0,068 0,067 0,044 0,064 0,046 0,045 0,042 0,025
Fault-loop resistances and impedances had
0,019 0,018 0,016 0,017 0,012 0,013 0,012 0,010 0,009 0,008 0,008 0,005 0,005 been determined according to Annex DD of IEC / EN
61439-6.
0,028 0,026 0,023 0,023 0,018 0,020 0,018 0,014 0,013 0,012 0,012 0,009 0,007 * IK10 corresponds to impact energy of 20J
0,028 0,032 0,023 0,030 0,019 0,023 0,024 0,014 0,019 0,015 0,012 0,014 0,007 according to IEC 62262.

www.eaeelectric.com 7
ELINEKX
►►Technical Characteristics

Copper Conductor (Cu)


Standards IEC 61439-6, TS EN 61439-6, IEC 61439-1, TS EN 61439-1
Rated Isolation Voltage Ui V 1000 at Cat IV
Max. Rated Operational Voltage Ue Vac 1000
Rated Impulse Withstand Voltage Uimp kV 12
Rated Frequency f Hz 50
Pollution Degree III
Protection Degree IP55 / IP65
External Mechanical Impacts (IK Code)* Bolt-on Busbar IK10+, Plug-in Busbar IK08
Rated Current In A 550 650 800 1000 1250 1350
Busbar Code 05 06 08 10 12 14
Rated Short-time Withstand Current (1s) (Three phase) Icw kA 24 24 40 50 60 60
Rated Peak Withstand Current Ipk kA 50,4 50,4 84 105 132 132
Rated Short-time Withstand Current for Neutral Conductor(1s)(Single phase) Icw kA 14,4 14,4 24 30 36 36
Rated Peak Withstand Current for Neutral Conductor Ipk kA 28,8 28,8 50,4 63 75,6 75,6
Rated Short-time Withstand Current for PE (Housing) Conductor(1s)(Single phase) Icw kA 14,4 14,4 24 30 36 36
Rated Peak Withstand Current for PE (Housing) Conductor Ipk kA 28,8 28,8 50,4 63 75,6 75,6
MEAN PHASE CONDUCTOR CHARACTERISTICS AT RATED CURRENT In
Resistance at a conductor temperature of 20 °C R20 mW/m 0,123 0,100 0,074 0,055 0,044 0,038
Resistance at an ambient air temperature of 35 °C R mW/m 0,162 0,137 0,097 0,071 0,057 0,050
Reactance (Independent from Temperature) X mW/m 0,044 0,034 0,028 0,023 0,019 0,016
Positive and negative sequence impedances at an ambient air temperature of 35 °C Z mW/m 0,168 0,141 0,101 0,075 0,060 0,053
Positive and negative sequence impedances at a conductor temperature of 20 °C Z20 mW/m 0,130 0,106 0,079 0,060 0,047 0,041
Rated Power Loss at 35 °C W/m 143,5 166,8 185,5 213,6 264,8 274,5
DC Resistance at a conductor temperature of 20 °C for Phases R/ortph mW/m 0,118 0,097 0,072 0,053 0,041 0,036
DC Resistance at a conductor temperature of 20 °C for Neutral RN mW/m 0,120 0,099 0,074 0,054 0,042 0,036
DC Resistance at a conductor temperature of 20 °C for PE (Housing) RPE mW/m 0,036 0,034 0,027 0,029 0,024 0,028
SECTIONS
L1,L2,L3,N mm² 150 180 240 330 420 480
PE (4 ½ Conductors) mm² 75 90 120 165 210 240
PE (5 Conductors) mm² 150 180 240 330 420 480
Aluminium Housing Section (Aluminium) mm² 1449 1509 1686 1788 1842 1894
Conductor Dimensions mmxmm 6x25 6x30 6x40 6x55 6x70 6x80
Busbar Weight (4 Conductors) kg/m 10,7 11,9 14,4 18,3 22 24,5
Busbar Weight (5 Conductors) kg/m 12,2 13,52 16,8 21,5 26,1 29,2
MEAN FAULT-LOOP CHARACTERISTICS
Zero-sequence Impedance
Zero-sequence impedance at a conductor temperature of 20 °C Z(0)b20phN mW/m 0,585 0,489 0,393 0,295 0,250 0,198
Zero-sequence impedance at a conductor temperature of 20 °C (Housing) Z(0)b20phPE mW/m 0,365 0,338 0,268 0,281 0,229 0,209
Zero-sequence impedance at an ambient temperature of 35 °C Z(0)bphN mW/m 0,750 0,646 0,499 0,371 0,309 0,251
Zero-sequence impedance at an ambient temperature of 35 °C (Housing) Z(0)bphPE mW/m 0,442 0,419 0,324 0,345 0,286 0,259
Resistances and Reactances
Resistance at a conductor temperature of 20 °C Rb20phph mW/m 0,248 0,206 0,159 0,119 0,091 0,077
Resistance at a conductor temperature of 20 °C Rb20phN mW/m 0,256 0,214 0,167 0,126 0,097 0,083
Resistance at a conductor temperature of 20 °C (Housing) Rb20phPE mW/m 0,176 0,155 0,123 0,112 0,137 0,083
Resistance at an ambient air temperature of 35 °C Rbphph mW/m 0,328 0,283 0,209 0,154 0,118 0,103
Resistance at an ambient air temperature of 35 °C RbphN mW/m 0,339 0,294 0,219 0,163 0,126 0,110
Resistance at an ambient air temperature of 35 °C (Housing) RbphPE mW/m 0,233 0,213 0,161 0,145 0,178 0,111
Reactance (Independent from temperature) Xbphph mW/m 0,079 0,069 0,052 0,043 0,036 0,032
Reactance (Independent from temperature) XbphN mW/m 0,105 0,094 0,071 0,059 0,050 0,045
Reactance (Independent from temperature) XbphPE mW/m 0,101 0,093 0,070 0,061 0,054 0,050

8 www.eaeelectric.com
PE
L3
L2
L1
N2
N1

1600 2000 2500 2000 2500 3300 3600 4000 5000 6300
17 23 25 22 27 32 36 40 50 63
PE
80 80 100 80 100 120 120 120 120 120 L3
L2
176 176 220 176 220 264 264 264 264 264 L1
48 48 60 48 60 72 72 72 72 72 N
100,8 100,8 132 100,8 132 158,4 158,4 158,4 158,4 158,4
48 48 60 48 60 72 72 72 72 72
100,8 100,8 132 100,8 132 158,4 158,4 158,4 158,4 158,4
L3
0,032 0,024 0,016 0,028 0,021 0,014 0,012 0,011 0,008 0,005 L2
0,044 0,033 0,021 0,036 0,028 0,019 0,016 0,015 0,010 0,006 L1
0,015 0,010 0,008 0,012 0,009 0,007 0,006 0,005 0,004 0,003 N
0,047 0,034 0,022 0,038 0,030 0,020 0,017 0,016 0,011 0,007
0,035 0,026 0,018 0,030 0,023 0,016 0,014 0,012 0,009 0,006
325,1 383,3 384,4 436,8 528,8 604,4 633,7 705,6 772,5 750,1 Voltage Drop Calculation
0,031 0,022 0,014 0,025 0,021 0,013 0,012 0,010 0,007 0,005 Generally Voltage drop of a busbar system
can be calculated with the following formula.
0,031 0,023 0,014 0,026 0,021 0,015 0,012 0,009 0,008 0,005
0,028 0,039 0,031 0,019 0,022 0,018 0,023 0,021 0,021 0,011

570 750 1200 660 840 1320 1500 1680 2400 3600
DU= √3.L.I.(R .Cosj+X .Sinj) 10-3 [V]
285 375 600 330 420 660 750 840 1200 1800
DU = Voltage Drop (V)
570 750 1200 660 840 1320 1500 1680 2400 3600
L = Line Length (m)
1996 2128 2518 3340 3580 3912 4068 4224 4848 7128 I = Line Current or Load (A)
6x95 6x125 6x200 2(6x55) 2(6x70) 2(6x110) 2(6x125) 2(6x140) 2(6x200) 3(6x200) R = Resistance (mW/m)
X = Reactance (mW/m)
27,7 36,2 54,7 35,9 44 63,5 71,1 78,6 108,8 162,8
33,7 43,8 66,5 42,4 52 76,5 85,8 95,2 132,4 198,2

0,168 0,130 0,086 0,148 0,107 0,073 0,067 0,060 0,038 0,029 L
0,154 0,153 0,146 0,144 0,090 0,091 0,090 0,100 0,086 0,061 S I
0,221 0,167 0,107 0,189 0,136 0,092 0,084 0,077 0,046 0,034 S = Supply Point
0,197 0,193 0,181 0,176 0,111 0,113 0,112 0,128 0,106 0,075

0,066 0,050 0,033 0,059 0,044 0,029 0,025 0,023 0,016 0,011
0,071 0,054 0,035 0,063 0,047 0,031 0,027 0,025 0,017 0,012 All phase conductor characteristics had been
0,065 0,059 0,053 0,061 0,040 0,035 0,034 0,044 0,032 0,023 determined according to Annex BB of IEC / EN 61439-6.
Fault-loop zero-sequences impedances had been
0,091 0,067 0,043 0,077 0,058 0,038 0,033 0,030 0,020 0,013 determined according to Annex CC of IEC / EN 61439-6.
Fault-loop resistances and impedances had been
0,098 0,073 0,046 0,083 0,062 0,041 0,036 0,033 0,022 0,015
determined according to Annex DD of IEC / EN 61439-6.
0,089 0,080 0,070 0,080 0,052 0,047 0,044 0,059 0,041 0,028 * IK10 corresponds to impact energy of 20J according to
IEC 62262.
0,026 0,022 0,014 0,022 0,016 0,012 0,011 0,010 0,008 0,005
0,037 0,032 0,022 0,029 0,023 0,018 0,015 0,014 0,011 0,008
0,036 0,035 0,028 0,033 0,022 0,020 0,018 0,018 0,014 0,010

www.eaeelectric.com 9
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Order Code System PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX A 17 5 04 B TR41

COMPONENTS
Busbar Type
Standard Length STD
Special Length X
Aluminium (Al) A CONDUCTOR MATERIAL
Copper (Cu) C
Upwards Elbow U
Downwards Elbow D
KXA - Al KXC - Cu Right Elbow R
Conductor
Conductor Conductor
Left Elbow L
Rated Busbar Rated Busbar
Current Code Current Code
*400 04 *550 05 6x25 Left Horizontal Offset LH
*500 05 *650 06 6x30 Right Horizontal Offset RH
*630 06 *800 08 6x40 (*)Bolt-on tap-off box can not be used on the Upwards Vertical Offset UV
800 08 1000 10 6x55 joints of mentioned ratings of busbars. Downwards Vertical Offset DV
Plug-in points can be at one side only.
1000 11 - - 6x60 Upwards Left Combined Offset KUL
- - 1250 12 6x70 Upwards Right Combined Offset KUR
1000 10 1350 14 6x80 Downwards Left Combined Offset KDL
- - 1600 17 6x95 Downwards Right Combined Offset KDR
1250 12 - - 6x110 Busbar Left Upwards Combined Offset KLU
1350 14 2000 23 6x125 Code Right Upwards Combined Offset KRU
1600 16 - - 6x140 Left Downwards Combined Offset KLD
1600 17 - - 6x160 Right Downwards Combined Offset KRD
2000 18 - - 6x180
2000 20 2500 25 6x200 End Closer S
2500 29 - - 6x230 Reduction RD
2500 27 - - 6x250
- - 2000 22 2(6x55) Left Side Feeder "T" TYL
- - 2500 27 2(6x70) Right Side Feeder "T" TYR
2500 25 3300 32 2(6x110) Central Feeder "T" TO
- - 3600 36 2(6x125)
3200 32 4000 40 2(6x140) Horizontal Expansion YDT
3200 33 - - 2(6x160) Vertical Expansion DDT
4000 40 5000 50 2(6x200) Phase Transposition Module FDM
4000 41 - - 2(6x180)
5000 51 - - 2(6x250) Panel Connection P10
6000 60 6300 63 3(6x200) Panel Connection P11
Upwards Panel Connection PU20
PROTECTION DEGREE Upwards Panel Connection PU21
IP55 / IP65* 5 Downwards Panel Connection PD20
*Please call us for IP65 orders. Downwards Panel Connection PD21
(IP65 is not recommended for outdoor applications. Please check CR catalog.) Right Panel Connection PR30
Right Panel Connection PR31
Left Panel Connection PL30
Number of Conductor Configuration Left Panel Connection PL31
Code
Conductors L1 L2 L3 N1 N2 PE ½ CPE ½ PE
Panel Connection P40
PE CPE (Housing)

3 Conductors 03 √ √ √ √ Panel Connection P41

4 Conductors 04 √ √ √ √ √
Transformer Connection TR11
4 ½ Conductors 07 √ √ √ √ √ √ Upwards Transformer Con. TU21
4 ½ Conductors 08 √ √ √ √ √ √ Downwards Transformer Con. TD21
Transformer Connection TR31
5 Conductors 05 √ √ √ √ √ √
Transformer Connection TR41
5 Conductors 09 √ √ √ √ √ √ Right Transformer Connection TR51
6 Conductors 06 √ √ √ √ √ √ √ Left Transformer Connection TL51
Transformer Connection TR61
Transformer Connection TR71
*TYPE Utilization Type
Feeder Box B10
(B) Bolt-on Energy is supplied from the joints. Feeder Box B11
Central Feeder Box BO
Energy is supplied from the joints and the
(P) Plug-in
plug-in points. Flexible F

10 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Standard Straight Length PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX
C

Bolt-on Bolt-on Standard -S T D


Straight Length
L3 Busbar
L2
L1
N Sample Order: L3
L2
3000 2500 A, Aluminium, L1 300
0
Bolt-on, IP 55, 4 Conductors N

Electrical energy up to 1000 A can be


supplied from the joints of bolt-on type KXA 25504 - B - STD
by bolt-on tap-off boxes. O
Note:
Busbar energy should be turned off, before installing Applications:
bolt-on type tap-off boxes. • As feeder or sub-feeder line,
• Where a load has to be supplied
• from the busbar.

C
Plug-in Plug-in Standard -S T D
Straight Length
Busbar
Sample Order: L3
Bolt-on Plug-in Plug-in Bolt-on
1250 A, Copper, Plug-in, IP 55, L2
0
L1
300
L3
L2
L1 4 Conductors N
N

950 1100 950 KXC 12504 - P - STD


3000
O

Electrical energy up to 1000 A can be supplied Note: Applications:


from the joints and up to 630 A can be supplied Please, determine number and • In application of bolt-on
from the plus. side of plug-in points (single or • As vertical feeder line high rise buildings
double side). • For frequent energy supply
• If continuous energy needed, while tap-offs
Table For Outer Dimension of Busbars installed.
KXA - Al KXC - Cu
A
Conductor Conductor
Rated Busbar Rated Busbar (mm)
Current Code Current Code
*400 04 *550 05 77,5
*500 05 *650 06 82,5
*630 06 *800 08 91
800 08 1000 10 106
1000 11 - - 111
- - 1250 12 121
1000 10 1350 14 131 Special Straight C
- - 1600 17 146 Length Special Straight
1250 12 - - 161 Length in (cm)
1350 14 2000 23 176 Sample Order: L3 X
L2
1600 16 - - 191 2500 A, Copper, Bolt-on, IP 55, L1
N O
4 Conductors, 147 cm
1600 17 - - 211
2000 18 - - 233
KXC 25504 - B - X - 147
2000 20 2500 25 251
2500 29 - - 281 Note:
2500 27 - - 301 Bolt-on Minimum Length = 35cm
- - 2000 22 202 Plug-in Minimum Length = 100cm
- - 2500 27 232
2500 25 3300 32 312
- - 3600 36 342
3200 32 4000 40 372
3200 33 - - 412
4000 40 5000 50 492
4000 41 - - 454
5000 51 - - 592
6000 60 6300 63 732
Important Notice for the Tap-off box use;
*It is not possible to install tap-off box at joint side for KXA 400A, KXA500A, KXA 630A, KXC 550A, KXC 650A and KXC 800A.
KXA 400A, KXA500A, KXA 630A, KXC 550A, KXC 650A and KXC 800 busbar range may have plug-in windows at one side
only. It is highly recommended to consider these points in your project designs.
www.eaeelectric.com 11
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Elbows PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX O

Upwards Elbow -U

250
325
Sample Order:
3300 A, Copper, Bolt-on,
IP 55, 4 Conductors
L3
KXC 32504 - B - U L2
L1 C
N

0
25 5
32

5
Downwards Elbow -D 32
0
25

Sample Order:

325
3300 A, Copper, Bolt-on,

250
IP 55, 4 Conductors L3
L2
L1
N
KXC 32504 - B - D C

KXA - Al KXC - Cu
A B
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm) Left Elbow -L
Current Code Current Code O
B A
*400 04 *550 05 252 214 L3
*500 05 *650 06 257 217 Sample Order:
L2
L1
*630 06 *800 08 267 222 2000 A, Copper, Bolt-on, N
800 08 1000 10 282 229 IP 55, 4 Conductors
1000 11 - - 287 232
- - 1250 12 297 236 KXC 23504 - B - L
1000 10 1350 14 307 241 C
- - 1600 17 322 249
B A
1250 12 - - 337 256
1350 14 2000 23 352 264
1600 16 - - 367 271
1600 17 - - 387 281
2000 18 - - 408 291
2000 20 2500 25 427 301
2500 29 - - 457 316
2500 27 - - 477 326 Right Elbow -R A
A
- - 2000 22 377 276
B B
- - 2500 27 407 291
2500 25 3300 32 487 331 Sample Order:
- - 3600 36 517 346 2000 A, Aluminium, Bolt-on,
3200 32 4000 40 547 361 IP 55, 4 Conductors L3
L2
3200 33 - - 587 381 L1 O
4000 40 5000 50 667 421 KXA 20504 - B - R N C
4000 41 - - 627 401
5000 51 - - 767 471
6000 60 6300 63 907 541

Special left or right elbows between 90° and 180° can be manufactured upon request.
The dimensions given above are minumum values. Please call us for non-standard components.
12 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Elbows PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX
5
32 0
25 O
Upwards Vertical -U V
Offset H
(cm)
Sample Order:
H=25 cm, 2000 A, Aluminium
Bolt-on, IP 55, 5 Conductors

H
KXA 20505-B-UV25
Note: C
H=min:25 cm max:49 cm L3
L2
L1 0
N 25
5
32

5
32
Downwards -D V 0
25
Vertical Offset H
(cm)
O
Sample Order:
H=25 cm, 2000 A, Aluminium C
Bolt-on, IP 55, 5 Conductors
L3
L2
L1
KXA 20505-B-DV25 N

H
0
25
Note:
5
H=min:25 cm max:49 cm 32

KXA - Al KXC - Cu O
A B Hmax.
A

Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm) (mm) Left Horizontal -L H
Current Code Current Code
Offset H
*400 04 *550 05 252 214 427 (cm)
*500 05 *650 06 257 217 432 Sample Order:
*630 06 *800 08 267 222 442 H=60 cm, 3300 A, Copper
H

800 08 1000 10 282 229 457 Bolton, IP 55, 4 Conductors


1000 11 - - 287 232 462
- - 1250 12 297 236 472 KXC 32504-B-LH60 L3
L2
1000 10 1350 14 307 241 482 L1
B
A

Note: N C
- - 1600 17 322 249 497 H=min:28 cm,
1250 12 - - 337 256 512 max: *Please see table.
1350 14 2000 23 352 264 527 Used, if two horizontal elbows
can not fit.
1600 16 - - 367 271 542
1600 17 - - 387 281 562
2000 18 - - 408 291 582
2000 20 2500 25 427 301 602
2500 29 - - 457 316 632
2500 27 - - 477 326 652 Right Horizontal -R H
- - 2000 22 377 276 552 Offset H
- - 2500 27 407 291 582 (cm)
H
A

O
2500 25 3300 32 487 331 662 Sample Order:
B

- - 3600 36 517 346 692 H=60 cm, 3300 A, Copper


3200 32 4000 40 547 361 722 Bolton, IP 55, 4 Conductors
3200 33 - - 587 381 762
C
B

4000 40 5000 50 667 421 842 KXC 32504-B-RH60


A

4000 41 - - 627 401 802 Note: L3


5000 51 - - 767 471 942 H=min:28 cm, L2
L1
6000 60 6300 63 907 541 1082 max: *Please see table. N
Used, if two horizontal elbows can not fit.

Special left or right elbows between 90° and 180° can be manufactured upon request.
The dimensions given above are minumum values. Please call us for non-standard components.
www.eaeelectric.com 13
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Elbows PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX
A
B
Upwards Left -K U L
Combined Offset O

Sample Order:
3300 A, Copper
Bolt-on, IP 55, 4 Conductors

KXC 32504 - B - KUL

H
L3
L2
C
Note:
L1
H=min. 30 cm N
0
25 5
32

KXA - Al KXC - Cu
A B
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm)
Current Code Current Code A
*400 04 *550 05 252 214 B
Upwards Right -K U R
*500 05 *650 06 257 217
Combined Offset
*630 06 *800 08 267 222
800 08 1000 10 282 229 Sample Order:
1000 11 - - 287 232 3200 A, Aluminium
- - 1250 12 297 236 Bolt-on, IP 55, 4 Conductors
1000 10 1350 14 307 241 O
- - 1600 17 322 249 KXA 33504 - B - KUR

H
L3
1250 12 - - 337 256 L2 C
Note: L1
1350 14 2000 23 352 264 H=min. 30 cm N
0
1600 16 - - 367 271 25 5
32
1600 17 - - 387 281
2000 18 - - 408 291
2000 20 2500 25 427 301
2500 29 - - 457 316
2500 27 - - 477 326
- - 2000 22 377 276 325
- - 2500 27 407 291 Downwards Left -K D L
2500 25 3300 32 487 331 250
Combined Offset
- - 3600 36 517 346
3200 32 4000 40 547 361 Sample Order:
3200 33 - - 587 381 3300 A, Copper C
4000 40 5000 50 667 421 Bolt-on, IP 55, 4 Conductors
H

4000 41 - - 627 401 L3


L2
5000 51 - - 767 471 KXC 32504 - B - KDL L1 O
N
6000 60 6300 63 907 541 Note:
H=min. 30 cm
B
A

5
32
0
Downwards Right -K D R 25
Combined Offset
L3
L2
Sample Order:
H

L1
N
3200 A, Aluminium C
Bolt-on, IP 55, 4 Conductors

KXA 33504 - B - KDR

Note: B
H=min. 30 cm A O

The dimensions given above are minumum values. Please call us for non-standard components.
14 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Elbows PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX
O

Left Upwards -K L U
Combined Offset

250
325
Sample Order:
3200 A, Aluminium
Bolt-on, IP 55, 4 Conductors

KXA 33504 - B - KLU

H
Note:
H=min. 30 cm L3

B
L2

A
L1 C
N

KXA - Al KXC - Cu
A B
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm)
Current Code Current Code
*400 04 *550 05 252 214 O
Right Upwards -K R U
*500 05 *650 06 257 217
Combined Offset
*630 06 *800 08 267 222

A
800 08 1000 10 282 229 Sample Order:

B
1000 11 - - 287 232 3300 A, Copper
- - 1250 12 297 236 Bolt-on, IP 55, 4 Conductors L3
L2

250
1000 10 1350 14 307 241 L1
N
- - 1600 17 322 249 KXC 32504 - B - KRU

325
C
1250 12 - - 337 256
Note:
1350 14 2000 23 352 264

H
H=min. 30 cm
1600 16 - - 367 271
1600 17 - - 387 281
2000 18 - - 408 291
2000 20 2500 25 427 301
2500 29 - - 457 316
2500 27 - - 477 326
- - 2000 22 377 276
- - 2500 27 407 291 Left Downwards -K L D H
2500 25 3300 32 487 331 Combined Offset
- - 3600 36 517 346
3200 32 4000 40 547 361 Sample Order:
325

3200 33 - - 587 381 3200 A, Aluminium


250

4000 40 5000 50 667 421 Bolt-on, IP 55, 4 Conductors


4000 41 - - 627 401
5000 51 - - 767 471 KXA 33504 - B - KLD
6000 60 6300 63 907 541 Note:
A
B

H=min. 30 cm C
L3
L2
O L1
N
B A

Right Downwards -K R D
H

Combined Offset
L3
Sample Order: L2
L1
3300 A, Copper N
C
Bolt-on, IP 55, 4 Conductors
325

KXC 32504 - B - KRD


250

Note:
H=min. 30 cm

The dimensions given above are minumum values. Please call us for non-standard components.
www.eaeelectric.com 15
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►“ T” Elbows PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX
B C
Right Side -T Y R
Feeder "T"

Sample Order:
L3
2500 A, Copper, Bolt-on, L2
A
IP 55, 4 Conductors L1
N

KXC 25504 - B - TYR

Left Side -T Y L
Feeder "T"

A Sample Order:
2500 A, Aluminium, Bolt-on, L3
IP 55, 4 Conductors L2
L1
N
KXA 25504 - B - TYL
C B

KXA - Al KXC - Cu
A B C
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm) (mm) Central Feeder "T” -T O
Current Code Current Code
*400 04 *550 05 214 214 214
*500 05 *650 06 216 216 216 Sample Order:
*630 06 *800 08 221 221 221 3300 A, Copper, Bolton,
800 08 1000 10 229 229 229 IP 55, 4 Conductors L3
1000 11 - - 232 232 232 L2
L1
- - 1250 12 236 236 236 KXC 32504 - B - TO N
1000 10 1350 14 241 241 241
- - 1600 17 249 249 249
1250 12 - - 256 256 256
B C
1350 14 2000 23 264 264 264
1600 16 - - 271 271 271
1600 17 - - 281 281 281
2000 18 - - 291 291 291
2000 20 2500 25 301 301 301
2500 29 - - 316 316 316 A
2500 27 - - 326 326 326
- - 2000 22 276 276 276
- - 2500 27 291 291 291
2500 25 3300 32 331 331 331
- - 3600 36 346 346 346
3200 32 4000 40 361 361 361
3200 33 - - 381 381 381
4000 40 5000 50 421 421 421
4000 41 - - 401 401 401
5000 51 - - 471 471 471
6000 60 6300 63 541 541 541

The dimensions given above are minumum values. Please call us for non-standard components.
16 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Reduction Modules PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX
O
Reduction Reduction -R D
Is used to change the busbar cross section. Reduced

0
NOTE: Busbar Current

0
7
Decisions and selection of reduction module Sample Order:
and protection on lower side is under the 2000A / 1600A, Aluminium,
customer’s responsibility. Bolt-on, IP 55, 4 Conductors

5
2
2
KXA 20504 - B - RD17 L3
L2

5
7
L1

4
N C

Reducers Table
KXA - Al KXC - Cu
Conductor Conductor
Rated Reduced Busbar Current Rated Reduced Busbar Current
Current 04 05 06 08 11 10 12 14 16 17 18 20 25 29 27 32 33 40 41 51 Current 05 06 08 10 12 14 17 22 23 25 27 32 36 40 50
500 05 √ - - - - - - - - - - - - - - - - - - - 650 06 √ - - - - - - - - - - - - - -
630 06 √ √ - - - - - - - - - - - - - - - - - - 800 08 √ √ - - - - - - - - - - - - -
800 08 - √ √ - - - - - - - - - - - - - - - - - 1000 10 - √ √ - - - - - - - - - - - -
1000 11 - - √ √ - - - - - - - - - - - - - - - - 1250 12 - - √ √ - - - - - - - - - - -
1000 10 - - √ - - - - - - - - - - - - - - - - - 1350 14 - - - √ √ - - - - - - - - - -
1250 12 - - - √ √ √ - - - - - - - - - - - - - - 1600 17 - - - - √ √ - - - - - - - - -
1350 14 - - - √ √ √ - - - - - - - - - - - - - - 1 2000 22 - - - - - √ √ - - - - - - - -
1600 16 - - - - √ - √ - - - - - - - - - - - - - 2000 23 - - - - - √ √ - - - - - - - -
1 1600 17 - - - - √ - √ - - - - - - - - - - - - - 2500 25 - - - - - - - √ √ - - - - - -
2000 18 - - - - - - - √ √ - - - - - - - - - - - 2500 27 - - - - - - - √ √ - - - - - -
2000 20 - - - - - - √ √ √ - - - - - - - - - - - 3300 32 - - - - - - - - - √ √ - - - -
2500 29 - - - - - - - - √ √ √ - - - - - - - - - 3600 36 - - - - - - - - - √ √ √ - - -
2500 27 - - - - - - - - √ √ √ - - - - - - - - - 4000 40 - - - - - - - - - - - √ √ - -
2500 25 - - - - - - - - - √ √ - - - - - - - - - 5000 50 - - - - - - - - - - - - - √ √
3200 32 - - - - - - - - - - - √ √ - √ - - - - - 6300 63 - - - - - - - - - - - - - - √
3200 33 - - - - - - - - - - - √ √ - √ - - - - -
4000 40 - - - - - - - - - - - - √ √ √ √ √ - - - 2
4000 41 - - - - - - - - - - - - - - - √ √ - - -
5000 51 - - - - - - - - - - - - - - - √ √ √ √ -
6000 60 - - - - - - - - - - - - - - - - - - √ √
2

The dimensions given above are minumum values. Please call us for non-standard components.
www.eaeelectric.com 17
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Expansions PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX

Vertical Expansion Vertical -D D T


Expansion O
Used for vertical applications in multi storey
buildings. Sample Order:
One vertical expansion unit is advised 2000 A, Copper, Bolt-on,
to be used at every floor between IP 55, 4 Conductors
fixed support points.
KXC 23504 - B - DDT L3
L2

0
70
L1
N
C

Horizontal Expansion Horizontal -Y D T O


Expansion
Used at every 40m in long horizontal straight lines
and building expansion points.
Sample Order:
Not:1) Horizontal expansion joint should be utilised if 2500 A, Aluminium, Bolt-on,
busbar line is crossing to adjacent through building IP 55, 4 Conductors L3
L2
expansion joints. L1
N
KXA 25504 - B - YDT
2) This module is used on the long busbar line
00
15

(>75m.) where line is ended by end closure and is not


fixed on the support rigidly.
C
3) Horizontal expansion joint has sufficient
movement span of 54mm.

EAE requests to be consulted during design stage.


35
224

35

50 50
20 30 30 20

17mm 27mm 27mm 17mm

The dimensions given above are minumum values. Please call us for non-standard components.
18 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Phase Transposition Module PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX

Phase Transposition Module Phase Transposition - F D M O


Module
They used for transposition of phase
sequence. Sample Order:
2500 A, Aluminium, Bolt-on,
IP 55, 4 Conductors

KXA 25504 - B - FDM

00
C

15
L3 -
L2 -
L1 -
N -

When installation of the Tap-Off Boxes needed after the phase changer box , an
approvement must be taken from the customer representative in advance.

Figure 1 N L1 L2 L3

FDM Dimension Table


KXA - Al KXC - Cu
A
Conductor Conductor
Rated Busbar Rated Busbar (mm)
Current Code Current Code
*400 04 *550 05 77,5 L3 Phase Sequence Changer
*500 05 *650 06 82,5 L2
*630 06 *800 08 91 L1
800 08 1000 10 106 N
1000 11 - - 111
- - 1250 12 121 N L1 L2 L3 Figure 2
1000 10 1350 14 131
- - 1600 17 146
1250 12 - - 161
1350 14 2000 23 176
1600 16 - - 191
1600 17 - - 211
2000 18 - - 233
2000 20 2500 25 251
2500 29 - - 281
2500 27 - - 301 L3
L2
- - 2000 22 202
L1
- - 2500 27 232
N
2500 25 3300 32 312
- - 3600 36 342
Vertical Shaft Application
3200 32 4000 40 372
3200 33 - - 412 1- The neutral bar of KX busbar shall be at the bottom for
4000 40 5000 50 492 horizontal busbar lines and on the left for vertical busbar
4000 41 - - 454 lines. (Figure 1)
2- In order to maintain the neutral bar at the bottom and
5000 51 - - 592
in the vertical busbar on the left, it is required to use the
6000 60 6300 63 732 phase changing module. (Figure 2)

The dimensions given above are minumum values. Please call us for non-standard components.
www.eaeelectric.com 19
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►End Closers PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX

End Closer -S

Sample Order: L3 157


2000 A, Aluminyum, 2500 A, Copper L2
L1
Bolt-on, IP 55, 4 /4½ / 5 Conductors N
C
KX 205A / 255C - B- S 8
15

End Closer -S 1 0

Sample Order:
6300 A, Copper
Bolt-on, IP 55, 3 Conductors
L3 C
L2
KXC 63503 - B- S 10 L1

5
2
2
End Closer
Is used to close the end of busbar run.
L1, L2, L3, N + Housing 04
KXA - Al KXC - Cu
L1, L2, L3, N, ½ PE + Housing 07
Conductor Conductor
L1, L2, L3, N, PE + Housing 05
Rated Busbar Rated Busbar Dimensions End Closer -S 1 1
Current Code Current Code (mm)
Order Code
*400 04 *550 05 6x25 3066129
*500 05 *650 06 6x30 3066131 Sample Order:
*630 06 *800 08 6x40 3016698 5000 A, Copper,
800 08 1000 10 6x55 3016699 Bolt-on, IP 55, 3 Conductors
1000 11 - - 6x60 3142393
- - 1250 12 6x70 3016700 KXC 50503 - B - S 11 O
5

L3
2
2

1000 10 1350 14 6x80 3016701 L2


L1
- - 1600 17 6x95 3085740
1250 12 - - 6x110 3016702
1350 14 2000 23 6x125 3016703
1600 16 - - 6x140 3016704
1600 17 - - 6x160 3016705
2000 18 - - 6x180 3127358
2000 20 2500 25 6x200 3016706
2500 29 - - 6x230 3135702
2500 27 - - 6x250 3016710
- - 2000 22 2(6x55) 3016707
- - 2500 27 2(6x70) 3127358
2500 25 3300 32 2(6x110) 3016709
- - 3600 36 2(6x125) 3016711
3200 32 4000 40 2(6x140) 3016712
3200 33 - - 2(6x160) 3016713
4000 40 5000 50 2(6x200) 3113536
4000 41 - - 2(6x180) 3188181
5000 51 - - 2(6x250) 3127359
6000 60 6300 63 3(6x200) 3113537

The dimensions given above are minumum values. Please call us for non-standard components.
20 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Panel Connections PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX

C Panel Connection -P 1 0
Panel Feeder
225

Sample Order:
2500 A, Copper, Bolt-on, 4 Conductors
for Panel Feeder N
L1
150

L3
KXC 25504 - B - P10 L2
L2
100 100 100 L3
L1
N

O Panel Connection -P 1 1
Busbar Feeder
225

Sample Order:
2500 A, Copper, Bolt-on, 4 Conductors
for Busbar Feeder
150

N
KXC 25504 - B -P11 L1 L3
100 100 100 L2 L2
L3 L1
N

325

250 Upwards Panel -P U 2 0


Connection
Panel Feeder
C Sample Order:
275

3600 A, Copper, Bolt-on, 4 Conductors


200

for Panel Feeder


N
KXC 36504 - B - PU20
150

L1
L2
100 100 100
L3

325

250 Downwards Panel -P D 2 0


Connection
Panel Feeder
Sample Order:
275

C
4250 A, Copper, Bolt-on, 4 Conductors
200

for Panel Feeder

L3
KXC 43504 - B - PD20
150

L2
100 100 100 L1
N

For connection dimensions please refer to tables on pages 24 and 25.


Note: Please contact with us for the dimensions of our 6 conductor solutions. Do not hanger the relevant modules from the flanges.
Distance between conductors can vary in ±5 mm. The dimensions given above are minumum values. Please call us for non-standard components.
www.eaeelectric.com 21
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Panel Connections PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX
325

250 Upwards Busbar -P U 2 1


Connection
O Busbar Feeder
Sample Order:

275
3600 A, Copper, Bolt-on, 4 Conductors
200

for Busbar Feeder


N
KXC 36504 - B - PU21
150

L1
L2
100 100 100
L3

325

250 Downwards Busbar - P D 2 1


Connection
O Busbar Feeder
Sample Order:
275

4250 A, Copper, Bolt-on, 4 Conductors


200

for Busbar Feeder

KXC 43504 - B - PD21 L3


150

L2
100 100 100 L1
N

A
B Right Panel -P R 3 0
Connection
Panel Feeder
A-125

C
B-125

Sample Order:
2500 A, Copper, Bolt-on, 4 Conductors
for Panel Feeder N
150

L1
KXC 25504 - B - PR30 L2
100 100 100 L3

A
B
Left Panel -P L 3 0
Connection
A-125

B-125

C Panel Feeder
Sample Order:
2500 A, Copper, Bolt-on, 4 Conductors
for Panel Feeder
150

L3
L2
100 100 100 KXC 25504 - B - PL30 L1
The "A" and "B" dimensions for PR30 and PL30 are N
the same dimensions as left and right elbows.
Please refer to page 12 for the dimensions.
For connection dimensions please refer to tables on pages 24 and 25.
Note: Please contact with us for the dimensions of our 6 conductor solutions. Do not hanger the relevant modules from the flanges.
Distance between conductors can vary in ±5 mm. The dimensions given above are minumum values. Please call us for non-standard components.
22 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Panel Connections PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX
A
B Right Panel -P R 3 1
Connection
A-125 Busbar Feeder
Sample Order:
B-125

O 2500 A, Copper, Bolt-on, 4 Conductors


for Busbar Feeder
L3
150

L2
KXC 25504 - B - PR31 L1
100 100 100
N

A
B Left Panel -P L 3 1
Connection
Busbar Feeder
Sample Order:
A-125
B-125

2500 A, Copper, Bolt-on, 4 Conductors


O for Busbar Feeder
N
150

L1
KXC 25504 - B - PL31
L2
100 100 100
L3

Panel Connection -P 4 0
855
Panel Feeder
C Sample Order:
3300 A, Copper, Bolt-on, 4 Conductors L3
for Panel Feeder
150

L2 N

L1 L1
min. KXC 32504 - B - P40
N L2
250 165 165 165 110
L3

855
Panel Connection -P 4 1
Busbar Feeder
O
Sample Order:
3300 A, Copper, Bolt-on, 4 Conductors
150

L3
for Busbar Feeder
L2 N
min.
L1
250 165 165 165 110 KXC 32504 - B - P41 L1
N L2
The "A" and "B" dimensions for PR31 and PL31
L3
are the same dimensions as left and right elbows.
Please refer to page 12 for the dimensions.
For connection dimensions please refer to tables on pages 24 and 25.
Note: Please contact with us for the dimensions of our 6 conductor solutions. Do not hanger the relevant modules from the flanges.
Distance between conductors can vary in ±5 mm. The dimensions given above are minumum values. Please call us for non-standard components.
www.eaeelectric.com 23
ELINEKX
►►Panel Connections

Panel Connection Units

Panel Connection Units (P10,P11,PU20, PD20, PU21, PD21, PL30,PR30,PL31,PR31,P40,P41)


KXA 04 KXA 05 KXA 06 KXA 08 KXA 10
KXC 05 KXC 06 KXC 08 KXC 10 KXA 11 KXC 12 KXC 14 KXC 17 KXA 12

150±3
150±3

150±3
150±3

150±3

150±3
150±3
150±3

150±3

57
57

57
57

57

57

57
Ø14 Ø14 Ø14 Ø14 Ø14
Ø14 Ø14
Ø11 Ø11

23
23

23

23

23

23
23
23

23
12,5 15 20 27,5 30 40 15 40 20 40 27,5 40 40 15
25 30 40 55 60 70 80 95 110

KXA 14 KXA 18 KXA 20


KXC 23 KXA 16 KXA 17 KXC 27 KXC 25 KXA 29 KXA 27
150±3

150±3
150±3
150±3

150±3
150±3
150±3
57

57
57
57

Ø14 Ø14 Ø14

23
23
Ø14 Ø14 Ø14
23
23

23

23
23

40 40 22,5 40 40 30 40 40 40 20 30 40 40 40 30 40 40 40 40 20 15 40 40 40 40 40 15 25 40 40 40 40 40 25
125 140 160 180 200 230 250

KXA 32
KXC 36 KXC 40
KXA 25
KXC 22 KXC 32

150±3
150±3
150±3

Ø14
150±3

Ø14
23

Ø14
23

23
Ø14
23

35 40 40 35 25 40 40 40 40 40 40 25 20 40 40 40 40 40 40 40 20
30 40 40 40 40 40 30
150 260 290 320

KXA 40
KXA 33 KXA 41 KXC 50 KXA 51
150±3

150±3

150±3

150±3

Ø14 Ø14 Ø14 Ø14


23

23
23

23

20 40 40 40 40 40 40 40 40 20 20 40 40 40 40 40 40 40 40 40 20 20 40 40 40 40 40 40 40 40 40 40 20 30 40 40 40 40 40 40 40 40 40 40 40 40 30
360 400 440 540

KXA 60 Sample Connection


KXC 63
150±3

Ø14
X X
23

20 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 20
(Minimum X= 25 mm)
680

Note: Please contact with us for the dimensions of our 6 conductor solutions. Do not hanger the relevant modules from the flanges.
Please call us for non-standard components. Distance between conductors can vary in ±5 mm. The dimensions given above are minumum values.
24 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Panel Connections PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX

Flange Dimensions
Panel Connection Units are supplied with suitable flange as standard.

Panel Panel
Connection Connection
N Flange Flange PE
L1 PE
L2 Housing Housing
L3
PE

PE L3 L2 L1 N L3 L2 L1 N

100 100 100 100 100 100 100

Opening on the E-Line KX Panel Connection


panel board Busbar Flange
12,5
100

B
A
100

Ø7
12,5

22,5 100 100 100 22,5


470
515
* Bolt and nut sets are supplied together
Aluminium (Al) Copper (Cu) with related product as per the quantities below.

Number of * M6 Bolt/
Rated Busbar Rated Busbar Conductor A B
the holes Nut
Current Code Current Code Size (mm) (mm) along B length Set (pcs)
400 04 550 05 6x25 120 165 2 12
500 05 650 06 6x30 125 170 2 12
630 06 800 08 6x40 135 180 2 12
800 08 1000 10 6x55 150 195 2 12
1000 11 - - 6x60 155 200 2 12
- - 1250 12 6x70 165 210 2 12
1000 10 1350 14 6x80 175 220 2 12
- - 1600 17 6x95 190 235 3 14
1250 12 - - 6x110 205 250 3 14
1350 14 2000 23 6x125 220 265 3 14
1600 16 - - 6x140 235 280 3 14
1600 17 - - 6x160 255 300 3 14
2000 18 - - 6x180 275 320 3 14
2000 20 2500 25 6x200 295 340 4 16
2500 29 - - 6x230 325 370 4 16
2500 27 - - 6x250 345 390 4 16
- - 2000 22 2(6x55) 245 290 3 14
- - 2500 27 2(6x70) 275 320 3 14
2500 25 3300 32 2(6x110) 355 400 4 16
- - 3600 36 2(6x125) 385 430 4 16
3200 32 4000 40 2(6x140) 415 460 5 18
3200 33 - - 2(6x160) 455 500 5 18
4000 40 5000 50 2(6x200) 535 580 6 20
4000 41 - - 2(6x180) 495 540 5 19
5000 51 - - 2(6x250) 635 680 7 22
6000 60 6300 63 3(6x200) 775 820 8 24
Note: Please contact with us for the dimensions of our 6 conductor solutions. Do not hanger the relevant modules from the flanges.
www.eaeelectric.com 25
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Transformer Connections PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX
O
Transformer -T R 1 1
Connection

Sample Order:
2500 A, Aluminium,
Bolt-on, 4 Conductors
225

KXA 25504 - B - TR11

N
L1 L3
200

L2 L2
120 120 120
L3 L1
N

325 Upwards -T U 2 1
Transformer Connection
250

Sample Order:
O 2500 A, Copper, Bolt-on,
4 Conductors
275
200

KXC 25504 - B - TU21-120


N
L1
L2
L3
200

120 120 120

325 Downwards -T D 2 1
Transformer Connection
250

Sample Order:
2500 A, Aluminium, Bolt-on, 4
O
Conductors
275
200

KXA 25504 - B - TD21


L3
L2
L1
N
200

120 120 120

For connection dimensions please refer to tables on pages 29 and 30.


Note: Please contact with us for the dimensions of our 6 conductor solutions. Do not hanger the relevant modules from the flanges.
Distance between conductors can vary in ±5 mm. The dimensions given above are minumum values. Please call us for non-standard components.
26 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Transformer Connections PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX

For transformer and panel connection applications Transformer -T R 3 1


EAE design and planning department can prepare Connection
your projects upon request.
855
Sample Order:
For the design, the following information is required;
2500 A, Copper, Bolt-on,

200
• Plan of transformer and panel board room, 4 Conductors
heights.
• Transformer dimensions, distance between KXC 25504 - B - TR31 L3 0
bushings. L2 N 11
L1 5
O L1 16
A and B dimensions of TR51 and TL51 are same as L25
N 16
left and right elbows. L35
Please refer to page 12 for the dimensions. 16
0
25
For connection dimensions please refer to tables on
pages 29 and 30.

Flexible are used for -F Flexibles


• Transformer - busbar, L
(cm)
• Panel - busbar connections. Sample Order:
800 A, Aluminium B
*
L
X
KXA 0800 - F40

Z Y
B=.....mm
X=.....mm • This side is punched according to the
Y=.....mm needs of the custommer.
Z=.....mm
ø=.....mm

A
B Right Transformer -T R 5 1
Connection
A-125

O Sample Order:
B-125

2500 A, Copper, Bolt-on,


4 Conductors
L3
200

120 120 120 L2


KXC 25504 - B - TR51
L1
N

A
B Left Transformer -T L 5 1
Connection
O
A-125

Sample Order:
B-125

2500 A, Aluminium,
Bolt-on, 4 Conductors
N
200

120 120 120 L1


KXA 25504 - B - TL51
L2
L3

A and B dimensions of TR51 and TL51 are same as left and right elbows.
Please refer to page 12 for the dimensions.
Note: Please contact with us for the dimensions of our 6 conductor solutions. Do not hanger the relevant modules from the flanges.
Distance between conductors can vary in ±5 mm. The dimensions given above are minumum values. Please call us for non-standard components.
www.eaeelectric.com 27
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►► Transformer Connections PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX

For transformer and panel connection applications Transformer -T R 4 1


EAE design and planning department can prepare Connection
your projects upon request.
in.
Sample Order: L3 m 0
For the design, the following information is required; 11
2500 A, Copper, Bolt-on, 4 0
199
• Plan of transformer and panel board room, Conductors
heights. L2 67
0
• Transformer dimensions, distance between
bushings. KXC 25504 - B - TR41 0
L1 67
N
O 0
29
n.
mi
0
25

For connection dimensions please refer to tables on


pages 29 and 30.

O
Transformer -T R 6 1

200
Connection
0
Sample Order: 185
2500 A, Copper, Bolt-on, 4 N
Conductors L1 in.
0 m
29 0
11
KXC 36504 - B - TR61 0
L2 67

0
L3 67 175

in. 150
m0
11 200
min.
100
Transformer
TR71 Dimension Table Connection
KXA - Al KXC - Cu -T R 7 1
Conductor A B X L
Conductor Conductor (*)
Rated Busbar Rated Busbar Sample Order:
TxW (mm) (mm) (mm) (mm)
Current Code Current Code 4000 A, Copper, Bolt-on, 4
* 400 04 *550 05 6x25 263 123 85 715 Conductors
* 500 05 *650 06 6x30 265 125 90 730 N
* 630 06 *800 08 6x40 270 130 100 760
KXC 40504 - B - TR71
800 08 1000 10 6x55 278 138 115 805 L1
1000 11 - - 6x60 280 140 120 820
150
- - 1250 12 6x70 285 145 130 850
L2
1000 10 1350 14 6x80 290 150 140 880
- - 1600 17 6x95 298 158 155 925 W O
L3
1250 12 - - 6x110 305 165 170 970
1350 14 2000 23 6x125 313 173 185 1015
L3 L2 L1 N
200

1600 16 - - 6x140 320 180 200 1060 T


T T T T 150
1600 17 - - 6x160 330 190 220 1120
W W W W
2000 18 - - 6x180 340 200 240 1180
L min
2000 20 2500 25 6x200 350 210 260 1240
2500 29 - - 6x230 365 225 290 1330
2500 27 - - 6x250 375 235 310 1390 150
200
- - 2000 22 2(6x55) 278 138 115 805
- - 2500 27 2(6x70) 285 145 130 850 W A min X min X min X min B min
2500 25 3300 32 2(6x110) 305 165 170 970 W W W W
- - 3600 36 2(6x125) 313 173 185 1015 (*) Note: The conductor cross-sectional values (T x W) are the same as
3200 32 4000 40 2(6x140) 320 180 200 1060 W the transformer connection conductor dimensions.
3200 33 - - 2(6x160) 330 190 220 1120
Sample (*): Single Line Sample (*): Double Line
4000 40 5000 50 2(6x200) 350 210 260 1240 2000 A, Copper, Bolt-on, 4000 A, Copper, Bolt-on,
4000 41 - - 2(6x180) 340 200 240 1180
200

6x125 = TxW 2(6x140) = TxW


2T
5000 51 - - 2(6x250) 375 235 310 1390 T=6 W=125 2T=12 W=140
Note: Please contact with us for the dimensions of our 6 conductor solutions. Do not hanger the relevant modules from the flanges.
Distance between conductors can vary in ±5 mm. The dimensions given above are minumum values. Please call us for non-standard components.
28 www.eaeelectric.com
ELINEKX
►►Transformer Connections

Transformer Connection Units


Transformer Connection Units (TR31, TR41, TR61, TR71)
Note: No flange supplied with transformer connection units.
KXA 04 KXA 05 KXA 06 KXA 08 KXA 10
KXC 05 KXC 06 KXC 08 KXC 10 KXA 11 KXC 12 KXC 14 KXC 17 KXA 12

200±3
200±3
200±3

200±3

200±3

200±3

200±3

200±3
200±3
40 30
30

30

40 30

40 30

40 30
40 30

40 30

40 30
Ø14 Ø14 Ø14 Ø14 Ø14 Ø14 Ø14
40

40

Ø11 Ø11
30

30

30

30

30
30

30

30
30

12,5 15 20 27,5 30 40 15 40 20 40 27,5 40 40 15


25 30 40 55 60 70 80 95 110

KXA 14 KXA 20 KXA 29


KXC 23 KXA 16 KXA 17 KXA 18 KXC 25 KXA 27

200±3

40 30
Ø14
200±3
200±3

200±3
200±3
200±3

30

200±3
40 30
40 30

40 30

40 30

40 30
Ø14 Ø14 Ø14 Ø14
Ø14
40

Ø14

30
30

30
30
30

30

30

40 40 22,5 40 40 30 40 40 40 20 40 40 40 30 40 40 40 40 20 15 40 40 40 40 40 15 40 40 40 40 40 25
125 140 160 180 200 230 250

Consider the dimensions given above for TR71 Transformer Modules.

KXA 25
KXC 22 KXC 27 KXC 32 KXC 36

200±3
200±3

200±3

200±3

40 30
40 30
40 30
40 30

Ø14 Ø14 Ø14 Ø14


30

30

30
30

27,5 27,5 15 40 40 15 15 40 40 40 40 15 22,5 40 40 40 40 22,5


150 180 260 290

KXA 32 KXA 40
KXC 40 KXA 33 KXA 41 KXC 50
200±3

200±3

200±3
30

40 30

200±3

40 30

Ø14 Ø14 Ø14


40 30

Ø14
40
30

30
30

30

30 40 40 40 40 30 20 40 40 40 40 40 40 20 30 40 40 40 40 40 40 30 20 40 40 40 40 40 40 40 40 20
320 360 400 440

KXA 60
KXA 51 KXC 63
Sample Connection
200±3
200±3

200±3
40 30

40 30

Ø14 Ø14
30
30

25 40 40 40 40 40 40 40 40 40 40 25 20 40 40 40 40 40 40 40 40 40 40 40 40 20
540 680
Note: Please contact with us for the dimensions of our 6 conductor solutions. Do not hanger the relevant modules from the flanges.
Distance between conductors can vary in ±5 mm. The dimensions given above are minumum values. Please call us for non-standard components.
www.eaeelectric.com 29
ELINEKX
►► Transformer Connections

Transformer Connection Units

Transformer Connection Units (TR11, TU21, TD21, TR51, TL51)


Note: No flange supplied with transformer connection units.

KXA 04 KXA 05 KXA 06 KXA 08 KXA 10


KXC 05 KXC 06 KXC 08 KXC 10 KXA 11 KXC 12 KXC 14 KXC 17 KXA 12

200±3
200±3

200±3
200±3

200±3

200±3

200±3

200±3
200±3
40 30
30

30

30

30

30

30
30

30
Ø14

40
40
40

40
40
40

40

40
Ø14 Ø14 Ø14 Ø14 Ø14 Ø14 Ø14 Ø14
30

30

30

30

30

30
30
30

30
12,5 15 20 27,5 30 40 15 40 20 40 27,5 40 40 15
25 30 40 55 60 70 80 95 110

KXA 14 KXA 20
KXA 18
KXC 23 KXA 16 KXA 17 KXC 27 KXC 25 KXA 29

200±3
200±3

200±3
200±3

30

30
30

200±3

200±3
30

30

30
40

40
40

Ø14 Ø14
40

40

40
Ø14 Ø14 Ø14 Ø14
30

30
30
30

30

30
40 40 22,5 40 40 30 40 40 40 20 40 40 40 40 20
40 40 40 30 40 40 40 40 40 15
125 140 160 180 200 230

KXA 25 KXA 32
KXA 27 KXC 22 KXC 32 KXC 36 KXC 40

200±3
200±3

200±3
200±3
30

30
30

30
200±3

30
40

40
40

40

Ø14
40

Ø14 Ø14 Ø14 Ø14


30

30

30

30
30

40 40 40 40 40 25 40 40 35 40 40 40 40 40 30 40 40 40 40 40 40 25 40 40 40 40 40 40 40 20
250 150 260 290 320

KXA 40
KXC 50
KXA 33 KXA 41
30
200±3
200±3

200±3
30

30

40
40
40

Ø14 Ø14 Ø14


30
30

30

40 40 40 40 40 40 40 40 20 40 40 40 40 40 40 40 40 40 20 40 40 40 40 40 40 40 40 40 40 20
360 400 440
KXA 60 Sample Connection
KXA 51 KXC 63
200±3

200±3
30

30
40

40

Ø14 Ø14
30

30

40 40 40 40 40 40 40 40 40 40 40 40 30 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 20 X X
540 680

Note: Please contact with us for the dimensions of our 6 conductor solutions. Please call us for non-standard components. (Minimum X= 25 mm )
Distance between conductors can vary in ±5 mm. The dimensions given above are minumum values. Do not hanger the relevant modules from the flanges.
30 www.eaeelectric.com
ELINEKX
►►Tap-off Boxes

Easy Installation System of Tap-off Boxes


The patented hinge system is designed to allow the installation of plug-in tap-off boxes simply and easily.

Fixing System of Tap-off Boxes to Busbars


Hook system, which is used for fixing of tap-off boxes on busbars.

Locking
Point

Universal Tap-off Boxes


Tap off boxes can be equipped with any
brand of switches, circuit breakers and etc.
Please inform EAE the type and brand of
choosen MCCB, when ordering.

Please call us for non-standard components.


As of January 1, 2025, it is produced in RAL 7035. For different color options, please contact our customer representatives.
When requesting special size tap off boxes, make sure that the distance between the two plug point does not prevent the installation of the tap off boxes.
www.eaeelectric.com 31
ELINEKX
►► Technical Features

Side Opening Box Lids


A new generation of tap-off box
with side opening lids enables
easier connection to protective
devices and maintenance.

Bolt-on Tap-off Boxes


• Bolt-on tap-off boxes are designed
to be installed at the joints without
removing the joint block.
• The range of tap off boxes from
160A upto 1.000A.
• Busbar run must be de-energized
before installing bolt-on tap-off
boxes.

Effective Gasket
• Protection from dust and humidity due to effective gasket system.
• High IP Protection due to special forming.

Special
Gasket Forming

Please call us for non-standard components.


As of January 1, 2025, it is produced in RAL 7035. For different color options, please contact our customer representatives.
When requesting special size tap off boxes, make sure that the distance between the two plug point does not prevent the installation of the tap off boxes.
32 www.eaeelectric.com
ELINEKX BUSBAR TYPE
BOX TYPE
RATED CURRENT Bolt on- B
Plug in- P
►►Tap-off Boxes with PROTECTION 160 A-16
250 A-25
CONDUCTOR DEGREE 400 A-40
Fused Switches (Bolt-on-KXB) 5-1
IP55/65 -5 630 A-63

CABLE GLAND PLATES


KX

Bolt-on Tap-off Boxes

Cable Gland Plates


KX B 1 6 5 1
KX B 2 5 5 1
Cable Inner KX B 4 0 5 1
Order B
Mat. Gland Diameter KX B 6 3 5 1
Code
Type (mm)
Sample Order:

C
Sheet ---- RP0 ---- Bolt-on / 630 A / IP-55 /
5 Conductors
te
Pla
KXB 6351 l a nd )
Sheet M32 RP1 25 G es
ble id
Ca on 3 s
( N 1
L
L2 3
Sheet M40 RP2 32 L

Sheet Special RP3 63

AL 2xSpecial RP4 63

50
AL 4xM25 RP5 18

AL 4xM32 RP6 25

AL 4xM40 RP7 32

30 A 30
AL 8xM32 RP8 25

Notes:

EAE Bolt-on Tap Off Boxes are secured with an


interlocking mechanism. This protects against
attaching them to or removing them from the D
busbar in the ''ON'' position. When in the ''OFF''
position they are safe to attach to or remove from
the busbar.
• Tap off boxes shall not be used empty. Fused
switches, MCCBs or similar protection devices
must be installed into tap-off boxes before they
are installed to the busbar runs.

Bolt-on tap-off box can not be


used on the joints of mentioned
ranges of busbars.

Tap-off A B C D Fuse Standard KXA - Al KXC - Cu Gland Max. External


Boxes (mm) (mm) (mm) (mm) Size Gland Conductor Conductor Bolt-on Diameter of Cable
Tap-off Type Cros-section (mm)
KXB 16 750 380 240 265 NH00 RP2 Rated Busbar Rated Busbar Box
Current Code Current Code
M25 Ø 18
KXB 25 750 380 240 265 NH 1 RP3 M32 Ø 26
KXB 40 850 420 260 265 NH 3 RP4 400 04 550 05 x
500 05 650 06 x M40 Ø 33
KXB 63 850 420 260 265 NH 3 RP4 M50 Ø 39
630 06 800 08 x
M63 Ø 45
Special for EAE Ø 60
*Tap-off boxes can be equipped with any brand
of switches and etc.
Please call us for non-standard components.
As of January 1, 2025, it is produced in RAL 7035. For different color options, please contact our customer representatives.
When requesting special size tap off boxes, make sure that the distance between the two plug point does not prevent the installation of the tap off boxes.
www.eaeelectric.com 33
ELINEKX BUSBAR TYPE
BOX TYPE
RATED CURRENT Bolt on- B

►► Tap-off Boxes with


Plug in- P
PROTECTION 160 A-16
250 A-25
CONDUCTOR DEGREE
Fused Switches (Plug-in-KXP)
400 A-40
IP55/65 -5 630 A-63
5-1

CABLE GLAND PLATES


KX

Plug-in Tap-off Boxes

Cable Gland Plates


KX P 1 6 5 1
KX P 2 5 5 1
Cable Inner KX P 4 0 5 1
Order B
Mat. Gland Diameter KX P 6 3 5 1
Code
Type (mm)
Sample Order:

C
Sheet ---- RP0 ---- Plug-in / 630 A / IP-55
5 Conductors
te
KXP 6351 d Pla
Sheet M32 RP1 25 n
Gla es )
bl e sid
Ca on 3
( N
Sheet M40 RP2 32 L1 2
L 3
L

Sheet Special RP3 63

AL 2xSpecial RP4 63

50
AL 4xM25 RP5 18

AL 4xM32 RP6 25

AL 4xM40 RP7 32

AL 8xM32 RP8 25
30 A 30

Notes:

EAE Plug-in Tap Off Boxes are secured with an


interlocking mechanism. This protects against
attaching them to or removing them from the D
busbar in the ''ON'' position. When in the ''OFF''
position they are safe to attach to or remove from
the busbar.
• Tap off boxes shall not be used empty. Fused
switches, MCCBs or similar protection devices
must be installed into tap-off boxes before they
are installed to the busbar runs.

Tap-off A B C D Fuse Standard


Gland Max. External
Boxes (mm) (mm) (mm) (mm) Size Gland Diameter of Cable
Type Cros-section (mm)
KXP 16 520 300 210 250 NH00 RP2
KXP 25 670 380 270 310 NH 1 RP3 M25 Ø 18
KXP 40 750 420 300 285 NH 3 RP4 M32 Ø 26
KXP 63 750 420 300 285 NH 3 RP4 M40 Ø 33
M50 Ø 39
M63 Ø 45
Special for EAE Ø 60
*Tap-off boxes can be equipped with any brand
of switches and etc.

Please call us for non-standard components.


As of January 1, 2025, it is produced in RAL 7035. For different color options, please contact our customer representatives.
When requesting special size tap off boxes, make sure that the distance between the two plug point does not prevent the installation of the tap off boxes.
34 www.eaeelectric.com
ELINEKX BUSBAR TYPE
BOX TYPE
Bolt on- B
RATED CURRENT Plug in- P
►►Tap-off Boxes
160 A-16
PROTECTION 250 A-25
CONDUCTOR DEGREE 400 A-40
for MCCB's (KXB) 5-1
IP55/65 -5
630 A-63
800 A-80
1000 A-10
SWITCH TYPE M- MCCB / B- Empty
CABLE GLAND PLATES
KX

Bolt-on Tap-off Boxes

Cable Gland Plates


KX B 1 6 5 1 - B
KX B 2 5 5 1 - B
Cable Inner KX B 4 0 5 1 - B
Order
Mat. Gland Diameter KX B 6 3 5 1 - B

B
Code
Type (mm)
KX B 1 6 5 1 - M

A
KX B 2 5 5 1 - M
Sheet ---- RP0 ---- KX B 4 0 5 1 - M

C
KX B 6 3 5 1 - M

Sheet M32 RP1 25


Sample Order:
Bolt-on / 630 A / IP-55
Sheet M40 RP2 32 5 conductors, empty tap-off box
late
dP
KXB 6351 - B N 1 G lan es )
Sheet Special RP3 63 L 2
ble id
L 3
L Ca on 3 s
(

AL 2xSpecial RP4 63

50
AL 4xM25 RP5 18

AL 4xM32 RP6 25

AL 4xM40 RP7 32

30 A 30
AL 8xM32 RP8 25

D
AL 3xSpecial RP9 63

Special Cable Gland Plates


KX B 8 0 5 1 - B
Cable Inner KX B 1 0 5 1 - B
Order
Mat. Gland Diameter
Code KX B 8 0 5 1 - M
Type (mm)
KX B 1 0 5 1 - M
Sheet ---- RPK0 ----
Sample Order:
Sheet M25 RPK1 18
Bolt-on / 800 A / IP-55 /
5 conductors, empty tap-off box
Sheet M32 RPK2 25
KXB 8051 - B
Sheet M40 RPK3 32

Sheet 1xSpecial RPK4 63


Bolt-on tap-off box can not be
used on the joints of mentioned
ranges of busbars.
Tap-off A B C *D Standard
KXA - Al KXC - Cu Gland Max. External
Boxes (mm) (mm) (mm) (mm) Gland Bolt-on Diameter of Cable
Conductor Conductor Type Cros-section (mm)
KXB 16 650 300 220 130 RPK3 Tap-off
KXB 25 650 300 220 130 RPK4
Rated Busbar Rated Busbar Box M25 Ø 18
Current Code Current Code
KXB 40 800 300 220 210 RP4 400 04 550 05 x M32 Ø 26
KXB 63 800 300 220 210 RP4 500 05 650 06 x M40 Ø 33
KXB 80 1100 450 275 385 RP9 630 06 800 08 x M50 Ø 39
KXB 10 1100 450 275 385 RP9 M63 Ø 45
* D value varies as per the used switch. Special for EAE Ø 60

* Tap-off boxes can be equipped with any


brand of MCCB's.
Please call us for non-standard components.
As of January 1, 2025, it is produced in RAL 7035. For different color options, please contact our customer representatives.
When requesting special size tap off boxes, make sure that the distance between the two plug point does not prevent the installation of the tap off boxes.
www.eaeelectric.com 35
ELINEKX BUSBAR TYPE
BOX TYPE
Bolt on- B
RATED CURRENT Plug in- P
►►Tap-off Boxes
160 A-16
PROTECTION 250 A-25
CONDUCTOR DEGREE 400 A-40
for MCCB's (KXP) 5-1
IP55/65 -5
630 A-63

SWITCH TYPE M- MCCB / B- Empty


CABLE GLAND PLATES
KX

Plug-in Tap-off Boxes


Cable Gland Plates

Cable
Order Inner KX P 1 6 5 1 - B
Mat. Gland Diameter KX P 2 5 5 1 - B
Code (mm) B
Type KX P 4 0 5 1 - B
KX P 6 3 5 1 - B

A
Sheet ---- RP0 ---- KX P 1 6 5 1 - M
KX P 2 5 5 1 - M

C
KX P 4 0 5 1 - M
Sheet M32 RP1 25 KX P 6 3 5 1 - M

Sample Order:
Sheet M40 RP2 32
Plug-in / 400 A / IP-55 /
late
5 conductors, empty tap-off box dP
Sheet Special RP3 63 N 1 G lan es )
KXP 4051 - B L 2 ble id
L 3
L Ca on 3 s
(
AL 2xSpecial RP4 63

AL 4xM25 RP5 18

AL 4xM32 RP6 25

50
AL 4xM40 RP7 32

AL 8xM32 RP8 25

Special Cable Gland Plates 30 A 38

Cable Inner
Order
Mat. Gland Diameter
Code (mm)
Type
D
Sheet ---- RPK0 ----

Sheet M25 RPK1 18

Sheet M32 RPK2 25

Sheet M40 RPK3 32

Sheet 1xSpecial RPK4 63

Tap-off A B C D Standard Gland Max. External


Boxes (mm) (mm) (mm) (mm) Gland Diameter of Cable
Type Cros-section (mm)
KXP 16 520 320 250 150 RPK3 M25 Ø 18
KXP 25 520 320 250 150 RPK4 M32 Ø 26
KXP 40 700 320 250 255 RP4 M40 Ø 33
KXP 63 700 320 250 255 RP4 M50 Ø 39
M63 Ø 45
* D value varies as per the used switch.
Special for EAE Ø 60
*Tap-off boxes can be equipped with any brand
of switches and etc.
Please call us for non-standard components.
As of January 1, 2025, it is produced in RAL 7035. For different color options, please contact our customer representatives.
When requesting special size tap off boxes, make sure that the distance between the two plug point does not prevent the installation of the tap off boxes.
36 www.eaeelectric.com
ELINEKX
►►Vertical and Horizontal Busbar Applications

SLAB

WALL
100
HOLE
L3
L2
L1
N BUSBAR
100
WALL

EXTERNAL FIRE BARRIER


MATERIAL

FIGURE-5 SAMPLE WALL CROSSING WITH FIRE BARRIER


FIGURE-1 FLATWISE POSITION

SLAB

WALL
100

200 (min.)
BUSBAR-1 HOLE
L3
L2
L1
N
BUSBAR
WALL

100

BUSBAR-2 JOINT POINT


L3
L2
L1
N

100

FIGURE-6 STANDARD WALL CROSSING


FIGURE-2 FLATWISE POSITION

SLAB
min. A min.
(A/2)+50 (A/2)+50
100
BUSBAR-1

BUSBAR-2
WALL

100 100
N L1 L2 L3 N L1 L2 L3

FIGURE-3 EDGEWISE POSITION

SLAB
BEAM

100

L3
BUSBAR (FLATWISE POSITION) L2
L1
N

FIGURE-4 CROSSING UNDER A BEAM HORIZONTAL POSITION

MINIMUM DISTANCE BETWEEN BUSBAR RUNS IN


HORIZONTAL APPLICATIONS.

Please call us for non-standard tap-off boxes and detailed information. The dimensions given above are minumum values.
www.eaeelectric.com 37
ELINEKX
►► Vertical and Horizontal Busbar Applications

SLAB
N L1 L2 L3 N L1 L2 L3

BEAM

20

SLAB
BUSBAR (EDGEWISE POSITION)

N L1L2 L3

200
FIGURE-7 CROSSING UNDER A BEAM EDGEWISE POSITION

N L 1L2 L3 N L 1L2 L3

VERTICAL EXPANSION
COMPONENT
BACK WALL - CURTAIN CONCRETE

100

150 200
A
WALL

B
TAP-OFF
BOXES
FIGURE-8 MINIMUM DIMENSIONS BETWEEN 2 TAP-OFF BOXES
WALL

KXA - Al KXC - Cu
A
Conductor Conductor

PLUG-IN BUSBAR
Rated Busbar Rated Busbar (mm)
Current Code Current Code
* 400 04 *550 05 77,5
* 500 05 *650 06 82,5
* 630 06 *800 08 91
800 08 1000 10 106
1000 11 - - 111
- - 1250 12 121 NOTE : In order to accomodate the busbar
1000 10 1350 14 131 systems in the riser shaft;
- - 1600 17 146
1250 12 - - 161
1350 14 2000 23 176 MDM = Minimum Distance from the wall
1600 16 - - 191 "A" dimension = All dimensions are for
1600 17 - - 211 standard modules .
2000 18 - - 233
"C" dimension = Please see page 32-35 and special
2000 20 2500 25 251
dimension for Tap-off box “C” dimension
2500 29 - - 281
2500 27 - - 301
- - 2000 22 202 "B" dimension = Max. opening distance for Tap-off box
- - 2500 27 232 cover.
2500 25 3300 32 312 Shaft Dimension = MDM + A + C + B + 100mm
- - 3600 36 342
Shown as (Figure-8)
200

3200 32 4000 40 372


3200 33 - - 412
4000 40 5000 50 492
4000 41 - - 454
5000 51 - - 592
6000 60 6300 63 732

FIGURE-9 MINIMUM DIMENSIONS BETWEEN 2 RISERS


The dimensions given above are minumum values. All measures are given in mm.
As of January 1, 2025, it is produced in RAL 7035. For different color options, please contact our customer representatives.
38 www.eaeelectric.com
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►►Feeder Boxes PROTECTION DEGREE
CONDUCTOR CONFIGURATION
(B10,B11) UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX
Cable Gland Plates
Busbar Cable Feeder Box B10 -B 1 0
Type
Housing Type Gland Plate

Sample Order:
3200 A, Aluminium, Bolt-on
1
4 Conductors

KXA 33504 - B - B10


PE
L3
L2
L1
N
2

Feeder Box B11 -B 1 1

2
Sample Order:
3600 A, Copper, Bolt-on,
4 Conductors

3 KXC 36504 - B - B11

PE
L3
L2
L1

4
N

Ampere Ratings
KXA - Al KXC - Cu Cable
A B C D Gland Type
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm) (mm) (mm)
Current Code Current Code
* 400 04 *550 05 500 520 / 620* 355 350 1
* 500 05 *650 06 500 520 / 620* 355 350 1
225 A
* 630 06 *800 08 500 520 / 620* 355 350 1
800 08 1000 10 500 520 / 620* 355 350 1
1000 11 - - 500 520 / 620* 355 350 1
- - 1250 12 500 520 / 620* 355 350 1 B

1000 10 1350 14 500 520 / 620* 355 350 1


- - 1600 17 500 520 / 620* 355 350 1
1250 12 - - 500 520 / 620* 355 350 1 150 D 40 C 40

1350 14 2000 23 500 520 / 620* 555 350 2 4 Conductors


1600 16 - - 500 520 / 620* 555 350 2
1600 17 - - 500 520 / 620* 555 350 2 225 A
2000 18 - - 500 520 / 620* 555 350 2
2000 20 2500 25 500 520 / 620* 555 350 3
2500 29 - - 500 520 / 620* 555 350 2
B
2500 27 - - 500 520 / 620* 555 350 2
- - 2000 22 500 520 / 620* 555 350 2
- - 2500 27 500 520 / 620* 555 350 3 150 D 40 C 40
2500 25 3300 32 500 520 / 620* 555 350 3
5 Conductors
- - 3600 36 500 520 / 620* 770 550 3
3200 32 4000 40 700 520 / 620* 770 550 3
3200 33 - - 700 520 / 620* 770 550 3
4000 40 5000 50 700 520 / 620* 770 550 3
4000 41 - - 700 520 / 620* 770 550 3
5000 51 - - 700 520 / 620* 770 550 3
6000 60 6300 63 700 520 / 620* 1100 550 4
*The values are given for 08 and 09 codes clean earth models.
Please call us for special applications or for applications with MCCB's. The dimensions given above are minumum values.
As of January 1, 2025, it is produced in RAL 7035. For different color options, please contact our customer representatives.
When requesting special size tap off boxes, make sure that the distance between the two plug point does not prevent the installation of the tap off boxes.
www.eaeelectric.com 39
ELINEKX BUSBAR TYPE
CONDUCTOR MATERIAL
BUSBAR CODE
►► Feeder Boxes PROTECTION DEGREE
CONDUCTOR CONFIGURATION
(Central Feeder Boxes BO ) UTILIZATION TYPE P - Plug-in / B - Bolt-on
COMPONENT

KX
Cable Gland Plates
Busbar Cable Central Feeder Box -B O
Type
Housing Type Gland Plate

Sample Order:
2500 A, Aluminium, Bolt-on
1
4Conductor
PE

KXA 25504 - B - BO
L3
L2
L1
N

PE
L3

3 L2
L1
N

3
C

Ampere Ratings
KXA - Al KXC - Cu Cable
A B C X Gland Type
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm) (mm) (mm)
Current Code Current Code
* 400 04 *550 05 500 520 / 620* 405 175 1
* 500 05 *650 06 500 520 / 620* 405 175 1
* 630 06 *800 08 500 520 / 620* 405 175 1 B

800 08 1000 10 500 520 / 620* 405 175 1


1000 11 - - 500 520 / 620* 405 175 1
- - 1250 12 500 520 / 620* 405 175 1
225 A 225
1000 10 1350 14 500 520 / 620* 405 175 1
- - 1600 17 500 520 / 620* 405 175 1
1250 12 - - 500 520 / 620* 805 277,5 1
1350 14 2000 23 500 520 / 620* 805 277,5 2
1600 16 - - 500 520 / 620* 805 277,5 2
1600 17 - - 500 520 / 620* 805 277,5 2
2000 18 - - 500 520 / 620* 805 277,5 2
2000 20 2500 25 500 520 / 620* 805 277,5 3
2500 29 - - 500 520 / 620* 805 277,5 2
2500 27 - - 500 520 / 620* 805 277,5 2
- - 2000 22 500 520 / 620* 805 277,5 2
- - 2500 27 500 520 / 620* 805 277,5 3
2500 25 3300 32 500 520 / 620* 805 277,5 3
- - 3600 36 500 520 / 620* 805 277,5 3
3200 32 4000 40 700 520 / 620* 1005 385 3
3200 33 - - 700 520 / 620* 1005 385 3
4000 40 5000 50 700 520 / 620* 1005 385 3
4000 41 - - 700 520 / 620* 1005 385 3
5000 51 - - 700 520 / 620* 1005 385 3
6000 60 6300 63 700 520 / 620* 1005 385 4
*The values are given for 08 and 09 codes clean earth models.
Please call us for special applications or for applications with MCCB's. The dimensions given above are minumum values.
As of January 1, 2025, it is produced in RAL 7035. For different color options, please contact our customer representatives.
When requesting special size tap off boxes, make sure that the distance between the two plug point does not prevent the installation of the tap off boxes.
40 www.eaeelectric.com
ELINEKX ORDER CODE
LENGTH L (mm)

►►Fixing Elements

Supports
Description Order Code

KX Vertical Riser Fixing Unit 3048475


KX Vertical Riser Fixing Unit
3048707
(Fire Barrier)

4 4
40 40

40 40

0
24

33
250
250

(Fire Barrier)

Description Order Code

* KX Vertical Riser Fixing Unit 3305415


* KX Vertical Riser Fixing Unit
3305419
Installation Illustration (Fire Barrier)

4 4
Rear 40 40

40 40
Floor-2
0
24

0
33
250

250

Front

Floor-1
(Fire Barrier)

*KX Vertical Shaft Suspension Kit * KXA 04 * KXC 05 6x25


should be mounted individually on the * KXA 05 * KXC 06 6x30
Front and Rear sides of each floor for
the Busbar, as shown above.
* KXA 06 * KXC 08 6x40

*It is valid for the specified sections.

Fixing Elements
Description Order Code

KX Fixing Clamp for Binrak (Unistrut)


2011227
Channel

Description Order Code

KX Fixing Clamp for Steel Angle Profile 2011226

Please call us for non-standard components. The span between supports should be 1.5m
www.eaeelectric.com 41
ELINEKX ORDER CODE
LENGTH L (mm)

►► Fixing Elements

Supports Al Cu Order
L A
Conductor Conductor Code

Rated Busbar Rated Busbar (mm) (mm)


Current Code Current Code
400 04 550 05 77,5
500 05 650 06 82,5
KX - BRA HANGER 630 06 800 08 91
SET FOR EDGEWISE 800 08 1000 10 106
APPLICATION TO 1000 11 - - 111
BINRAK (UNISTRUT) - - 1250 12 121
CHANNEL
1000 10 1350 14 131
- - 1600 17 146
350 3025373
1250 12 - - 161
1350 14 2000 23 176
1600 16 - - 191
1600 17 - - 211
2000 18 - - 233
2000 20 2500 25 251
2500 29 - - 281
2500 27 - - 301

22
7,5

41
2

41

KX - BRA HANGER Al Cu Order


L A
SET FOR FLATWISE Conductor Conductor Code
APPLICATION TO
BINRAK (UNISTRUT) Rated Busbar Rated Busbar (mm) (mm)
Current Code Current Code
CHANNEL
400 04 550 05 77,5
500 05 650 06 82,5
630 06 800 08 91
800 08 1000 10 300 106 3025372
1000 11 - - 111
- - 1250 12 121
1000 10 1350 14 131
- - 1600 17 146
350 3025373
1250 12 - - 161
1350 14 2000 23 176
1600 16 - - 191
400 3025374
1600 17 - - 211
2000 18 - - 233
2000 20 2500 25 251
2500 29 - - 450 281 3025375
22
7,5
2500 27 - - 301

41
2

41

Please call us for non-standard components. The span between supports should be 1.5m
42 www.eaeelectric.com
ELINEKX ORDER CODE
LENGTH L (mm)

►►Fixing Elements

Supports KXA - Al KXC - Cu Order


L A
Conductor Conductor Code
Rated Busbar Rated Busbar (mm) (mm)
Current Code Current Code
* 400 04 *550 05 77,5
* 500 05 *650 06 82,5
* 630 06 *800 08 91
KX - UT HANGER SET 800 08 1000 10 106
FOR EDGEWISE 1000 11 - - 111
APPLICATION - - 1250 12 121
TO NPU CHANNEL 1000 10 1350 14 131
- - 1600 17 146
1250 12 - - 161
1350 14 2000 23 176
1600 16 - - 191
1600 17 - - 211
2000 18 - - 233
350 3025348
2000 20 2500 25 251
2500 29 - - 281
2500 27 - - 301
- - 2000 22 202
- - 2500 27 232
2500 25 3300 32 312
- - 3600 36 342
3200 32 4000 40 372
65 3200 33 - - 412
4000 40 5000 50 492
43 4000 41 - - 454
4
5000 51 - - 592
6000 60 6300 63 732

KX - UT HANGER SET KXA - Al KXC - Cu Order


L A
FOR FLATWISE Conductor Conductor Code
APPLICATION Rated Busbar Rated Busbar (mm) (mm)
TO NPU CHANNEL Current Code Current Code
* 400 04 *550 05 77,5
* 500 05 *650 06 82,5
* 630 06 *800 08 91
800 08 1000 10 300 106 3025347
1000 11 - - 111
- - 1250 12 121
1000 10 1350 14 131
- - 1600 17 146
350 3025348
1250 12 - - 161
1350 14 2000 23 176
1600 16 - - 191
400 3025349
1600 17 - - 211
2000 18 - - 233
2000 20 2500 25 251
2500 29 - - 450 281 3025350
2500 27 - - 301
- - 2000 22 400 202 3025349
64 - - 2500 27 450 232 3025350
2500 25 3300 32 500 312 3025351
42 - - 3600 36 342
4 550 3025352
3200 32 4000 40 372
3200 33 - - 600 412 3025353
4000 40 5000 50 492
700 3025354
4000 41 - - 454
5000 51 - - 800 592 3134130
6000 60 6300 63 900 732 3025355

Please call us for non-standard components. The span between supports should be 1.5m
www.eaeelectric.com 43
ELINEKX ORDER CODE
LENGTH L (mm)

►► Fixing Elements

Supports Al Cu Order
L A
Conductor Conductor Code

Rated Busbar Rated Busbar (mm) (mm)


Current Code Current Code
400 04 550 05 77,5
500 05 650 06 82,5
KX HANGER 630 06 800 08 91
SET FOR EDGEWISE 800 08 1000 10 106
APPLICATION 1000 11 - - 111
TO STEEL ANGLE - - 1250 12 121
PROFILE
1000 10 1350 14 131
- - 1600 17 146
350 3025344
1250 12 - - 161
1350 14 2000 23 176
1600 16 - - 191
1600 17 - - 211
2000 18 - - 233
2000 20 2500 25 251
2500 29 - - 281
2500 27 - - 301

50

5 50

KX HANGER Al Cu Order
L A
SET FOR FLATWISE Conductor Conductor Code
APPLICATION
TO STEEL ANGLE Rated Busbar Rated Busbar (mm) (mm)
Current Code Current Code
PROFILE
400 04 550 05 77,5
500 05 650 06 82,5
630 06 800 08 91
800 08 1000 10 300 106 3025343
1000 11 - - 111
- - 1250 12 121
1000 10 1350 14 131
- - 1600 17 146
350 3025344
1250 12 - - 161
1350 14 2000 23 176
1600 16 - - 191
400 3025345
1600 17 - - 211
2000 18 - - 233
2000 20 2500 25 251
2500 29 - - 450 281 3025346
50 2500 27 - - 301

5 50

Please call us for non-standard components. The span between supports should be 1.5m
44 www.eaeelectric.com
ELINEKX ORDER CODE
LENGTH L (mm)

►►Fixing Elements

R
Supports Order
Description
Code
KX IDY Support Set 2054590

KXA - Al KXC - Cu Order


L A
Conductor Conductor Code
Rated Busbar Rated Busbar
KX - IDY TWO-WAY Current Code Current Code (mm) (mm)
FOR EDGEWISE
* 400 04 *550 05 77,5
APPLICATION
TO NPI CHANNEL * 500 05 *650 06 82,5
* 630 06 *800 08 91
800 08 1000 10 106
1000 11 - - 111
- - 1250 12 121
1000 10 1350 14 131
- - 1600 17 146
1250 12 - - 161
1350 14 2000 23 176
1600 16 - - 191
1600 17 - - 211
2000 18 - - 233
300 3113547
L

2000 20 2500 25 251


2500 29 - - 281
R
2500 27 - - 301
- - 2000 22 202
- - 2500 27 232
150 2500 25 3300 32 312
- - 3600 36 342
3200 32 4000 40 372
3200 33 - - 412
A

4000 40 5000 50 492


4000 41 - - 454
KX - IDY TWO-WAY 5000 51 - - 592
FOR FLATWISE 6000 60 6300 63 732
APPLICATION
TO NPI CHANNEL KXA - Al KXC - Cu Order
L A
Conductor Conductor Code
Rated Busbar Rated Busbar (mm) (mm)
Current Code Current Code
* 400 04 *550 05 77,5
* 500 05 *650 06 82,5
* 630 06 *800 08 91
800 08 1000 10 106
1000 11 - - 111
300 3113547
- - 1250 12 121
1000 10 1350 14 131
- - 1600 17 146
1250 12 - - 161
L 1350 14 2000 23 176
1600 16 - - 191
1600 17 - - 211
R

2000 18 - - 233
2000 20 2500 25 251
400 3113548
2500 29 - - 281
A
2500 27 - - 301
- - 2000 22 202
- - 2500 27 232
150

2500 25 3300 32 312


- - 3600 36 500 342 3113549
3200 32 4000 40 372
3200 33 - - 412
4000 40 5000 50 600 492 3113550
4000 41 - - 454
5000 51 - - 700 592 3134127
Please call us for non-standard components. The span between supports should be 1.5m 6000 60 6300 63 900 732 3113553
www.eaeelectric.com 45
ELINEKX ORDER CODE
LENGTH L (mm)

►► Fixing Elements

Supports L Order
Description (mm) Code
IDY 300 300 3008242
IDY 400 400 3008290
24 IDY 500 500 3008289
IDY 600 600 3008288
L IDY IDY 700 700 3008287
IDY 800 800 3008286
IDY 900 900 3008285
IDY 1000 1000 3008284
IDY 1100 1100 3008283
IDY 1200 1200 3008282
75 IDY 1300 1300 3008236
IDY 1400 1400 3008281
IDY 1500 1500 3008280
IDY 1600 1600 3008241
IDY 1700 1700 3008240
IDY 1800 1800 3008239
IDY 1900 1900 3008238
IDY 2000 2000 3008237
IDD 300 300 3008314
IDD 400 400 3008313
5
10 19 IDD 500 500 3008312
0 IDD
IDD 600 600 3008311
IDD 700 700 3008310
10 IDD 800 800 3008309
6 IDD 900 900 3008308
105

25
25
13

11

75

0X IDD 1000 1000 3008307


Ø1
IDD 1100 1100 3008306
IDD 1200 1200 3008305
L
118 IDD 1300 1300 3008304
IDD 150 IDD 1400 1400 3008303
190 IDD 1500 1500 3008302
IDD 1600 1600 3008301
IDD 1700 1700 3008300
IDD 1800 1800 3008299
IDD 1900 1900 3008298
IDD 2000 2000 3008297
IDT Support Fitting - 3008279

IDT

IDT

IDY

Please call us for non-standard components. The span between supports should be 1.5m
46 www.eaeelectric.com
ELINEKX ORDER CODE
LENGTH L (mm)

►►Fixing Elements

Supports T L Order
Description (mm) (mm) Code
UPY 300 4 300 3004487
Steel UPY 400 4 400 3004489
Dowel UPY 500 4 500 3004491
UPY 600 4 600 3004493
UPY UPY 700 4 700 3004495
UPY 800 4 800 3004496
Threaded UPY 900 4 900 3004497
Rod UPY 1000 4 1000 3004498
UPY 1100 4 1100 3004499
UPY 1200 4 1200 3004500
UPY 1500 4 1500 3004503

T
L

UPY

65

43

Please call us for non-standard components. The span between supports should be 1.5m
www.eaeelectric.com 47
ELINEKX ORDER CODE
LENGTH L (mm)

►► Fixing Elements

Supports L Order
Description (mm) Code
UDY 300 300 3008023
UDY 400 400 3008024
Steel UDY 500 500 3008025
Dowel UDY 600 600 3008026
UDY
UDY 700 700 3008027
UDY 800 800 3008028
UDY
UDY 900 900 3008029
Threaded UDY 1000 1000 3008030
Rod UDY 1100 1100 3008031
UDY 1200 1200 3008032
UDY 1300 1300 3008033
UDY 1400 1400 3008034
UDY 1500 1500 3008035
UDY 1600 1600 3008036
UDY 1700 1700 3008037
UDY 1800 1800 3008038
UDY 1900 1900 3008039
UDY 2000 2000 3008040

UDY

Steel
Dowel
L
UDY

Threaded
Rod
65

42

UDY

Please call us for non-standard components. The span between supports should be 1.5m
48 www.eaeelectric.com
ELINEKX ORDER CODE
LENGTH L (mm)

►►Fixing Elements

Supports Order
Description L (mm)
Code
UAS-K5 Supports (1) 200 3005324
Threaded Threaded
UAS-K5 Supports (2) 250 3005323
Rod Rod
UAS-K5 Supports (3) 300 3005322
UAS-K5 UAS-K5 Supports (4) 350 3005321
UAS-K5 Supports (5) 400 3005320
UAS-K5 Supports (6) 500 3005319
UAS-K5 Supports (7) 600 3005318
UAS-K5 Supports (8) 700 3005317
UAS-K5 Supports (9) 1100 3005316
UAS-K5

50

5 50

L Order
Description (mm) Code
Connection Units BRA 12-05 Threaded Rod (M10) 500 5000037
BRA 12-10 Threaded Rod (M10) 1000 5000032
BRA 14-05 Threaded Rod (M12) 500 5000026
BRA 14-10 Threaded Rod (M12) 1000 5000034
L BRA 13 Extension Unit (M10) - 1004312
Threaded BRA 13 Extension Unit (M12) - 1004282
Rod BRA 9 Steel Dowel (M10) - 5000023
BRA 9 Steel Dowel (M12) - 5000022
M10 Steel Nut - 1000522
M12 Steel Nut - 1000964
M10 Washer - 1000504
M12 Washer - 1000505
Extension
Unit

Diameter of the
Steel Dowel hole to be drilled
M10.....Ø14
M12.....Ø16

Steel Nut

Washer

FRONT

Vertical Riser Application


Sample Order Hanging
(Special to project)

Vertical riser shaft supports that corresponds your special needs


Please call us for non-standard components. The span between supports should be 1.5m can be designed regarding to the project and shaft dimensions.
www.eaeelectric.com 49
ELINEKX
►► Joint Structure

10

8 3

4
2

1
7

12

11 6

1. Extruded Aluminium Housing


2. PE Fixing Piece
3. Insulation Layers (Epoxy+B class polyester film)
4. Joint Insulators
5. Joint Cover
6. Belleville
7. Alignment Pin (removable)
8. Conductors
9. IP55 Nut Locking Piece Figure 3 Figure 4
Joint assembly
10. Protection Plastic
11. IP55 Joint Cover Gasket
12. Alignment Pin Slot

Figure 5
Figure 1 Block Joint The joint cover is
closed by leverage.

Figure 2 Alignment Alignment Pin


Slot (removable)

Please check related installation manual for details. Figure 6


50 www.eaeelectric.com
ELINEKX
►►Measuring a Special Length

After installation of standard busbar 3m lengths, you will be in need of special lengths which are smaller than 3m The minimum length for these
special elements can be 350 mm. Please measure the lengths of these modules as shown below.

Length A is measured between housing of 2 busbars in cm. A. The special length is calculated by deducting 250mm from this measured length.

X=A-250 (mm) X=Length of Special Busbar (The busbar module will be manufactured as per X value.)

125 125

Please call us for non-standard components.


www.eaeelectric.com 51
ELINEKX
►► Inserting "Make up Section"

1 Alignment Pin
2 2a

2a
2a

1- Remove Alignment Pin on the busbar, without block 2- Insert the piece aligning conductors correctly. Fix back the
joint. Alignment pin.

3 4

3a

3a

3- Make sure busbar piece is aligned according to alignment pin. 4- Fix one of the joint cover to stabilize joint. Apply
83Nm to the main bolt.

5 6
1
First 4
Torque:
(20-30Nm) 3
2

5
Final 8
Torque:
(83Nm) 7
6

5- If there are more than one 6- Fix the remaning joint cover. Joint installation is completed.
bolt for the same phase, bolts
shall be tighten by hand
approximately 20-30Nm as per Note: If the final joint cover does not close correctly, it indicates
above sequence, then 83Nm the busbar is not completely aligned. Release the bolts and
shall be applied at final torque reapply the sequence from figure 4 to complete the joint.
with the same sequence.

Please check related installation manual for details.

52 www.eaeelectric.com
ELINEKX
►►Declaration

CE DECLARATION OF CONFORMITY
Product Group E-Line KX Busbar Energy Distribution System

Manufacturer EAE Elektrik Asansor End. Insaat San. ve Tic. A.S.


Akcaburgaz Mahallesi, 3114. Sokak,
No:10 34522 Esenyurt-Istanbul

The objects of the declaration described below is in conformity with the relevant Union harmonisation
legislation. This declaration of conformity is issued under the sole responsibility of the manufacturer.

Standard :
TS EN 61439-6
Low-voltage switchgear and controlgear assemblies - Part 6: Busbar trunking
systems

CE - Directive

2014/35/EU “The Low Voltage Directive”

2014/30/EU “Electromagnetic Compatibility (EMC) Directive”

2011/65/EU “Restriction of the use of certain hazardous substances (RoHS)”

Technical Document Preparation Official:

EAE Elektrik Asansor End. Insaat San. ve Tic. A.S.


Akcaburgaz Mahallesi, 3114. Sokak, No:10 34522 Esenyurt-Istanbul

Mustafa AKÇELİK

Date Document Authorized Signatory

20.04.2024 Elif Gamze KAYA OK


Deputy General Manager

www.eaeelectric.com 53
ELINEKX
►► Certificate

54 www.eaeelectric.com
ELINEKX
►►55

400A ... 6300A COMPACT BUSBAR


PRODUCT OVERVIEW (E-LINE KX)
1- Standards & Certification:
-Busbar system shall be designed and manufactured as per IEC 61439-6 standard, which requires below listed tests. Each busbar rating shall have a separate type test certificate from an
independent internationally accredited laboratory including below tests:
10.2- Strength of material and parts, 10.2.2- Resistance to corrosion, 10.2.3- Properties of insulating materials, 10.2.3.1- Verification of thermal stability of enclosures, 10.2.3.2- Verification
of resistance of insulating materials to abnormal heat and fire due to internal electric effects, 10.2.6- Mechanical impact, 10.2.7- Marking, 10.2.101- Ability to withstand mechanical loads ,
10.2.101.1- Test procedure for a straight busbar trunking unit, 10.2.101.2- Test procedure for a joint, 10.2.101.3- Resistance of the enclosure to crushing, 10.3- Degree of protection of assembly,
10.4- Clearances and creepage distances, 10.5-Protection against electric shock and integrity of protective circuits, 10.5.2- Effective earth continuity between the exposed conductive parts of
the assembly and the protective circuit, 10.5.3- Short-circuit withstand strength of the protective circuit, 10.9- Dielectric properties, 10.9.2- Power-frequency withstand voltage, 10.9.3- Impulse
withstand voltage, 10.10- Verification of temperature rise, 10.11- Shortcircuit withstand strength, 10.101- Resistance to flame propagation, 10.102- Fire resistance in building penetrations,
Annex BB Phase conductor characteristics, Annex CC Fault-loop zero-sequences impedances, Annex DD Fault-loop resistances and reactances.
-Busbar system shall have CE marking.
-The manufacturer of busbar system shall have ISO 9001 and ISO 14001 certification.
-Each product shall have a “Type Label” including coding system, which identifies the brand, type of the unit, number of conductors and electrical details. The same coding shall be on the related
certificate and catalogue.
2- Electrical Characteristics
-Busbar systems nominal insulation voltage shall be 1000 V.
-As per ampere rates, minimum short circuit values shall be as given below;
For Aluminium Conductors; 400-500A :1 sec/rms 16kA, Peak 32kA For Copper Conductors; 550-650A :1 sec/rms 24kA, Peak 50,4kA
630A :1 sec/rms 25kA, Peak 52,5kA 800A :1 sec/rms 40kA, Peak 84kA
800-1000A :1 sec/rms 35kA, Peak 73,5kA 1000A :1 sec/rms 50kA, Peak 105kA
1000A :1 sec/rms 50kA, Peak 105kA 1250-1350A :1 sec/rms 60kA, Peak 132kA
1250-1350-1700A :1 sec/rms 60kA, Peak 132kA 1600-2000A :1 sec/rms 80kA, Peak 176kA
1600-2000-2500A :1 sec/rms 80kA, Peak 176kA 2500A :1 sec/rms 100kA,Peak 220kA
2500-3200A :1 sec/rms 100kA,Peak 220kA 3300A and above :1 sec/rms 120kA,Peak 264kA
3200A and above :1 sec/rms 120kA,Peak 264kA
2.1- Housing
-Busbar system shall have “Sandwich-Compact” structure. Conductors shall be packed and placed into the housing without leaving air gap in order to provide low reactance.
-Housing shall be made of thermal processed, extruded aluminium, RAL7038-Electrostatic painted.
-Compact structure of the housing shall be provided by M6 screws applied at every 19cm along the entire length.
-The sandwich-compact structure shall continue at the plug-in points too. There shall not be air gap between conductors at the plug-in points.
2.2- Conductors
Aluminium or Copper conductors shall be epoxy coated and tin plated at the joints upon the wire configuration and required numbers, which are described below.
-Compact busbar system shall have aluminium conductors between 400A – 6000A.
- Compact busbar system shall have copper conductors between 550A – 6300A.
- Compact busbar system shall have the following number of conductors and wire configuration;
a) 4 Conductors: (4 full size conductors + PE (housing)).
b) 4 ½ Conductors: (4 full size conductors + PE (50% earth conductor + housing)),
c) 5 Conductors: (5 full size conductors + PE (100% earth conductor + housing)),
-Phase conductors and neutral conductor shall have the same cross-section and they shall be insulated.
-Aluminium conductors shall be of EC grade aluminium. Minimum conductivity shall be 34m/mm².W.
-Copper conductors shall be minimum 99,95% electrolytic copper. Minimum conductivity shall be 56m/mm².W.
2.3- Insulation
-Insulation system shall be suitable for 1.000V continuous operation. Conductors shall be minimum thermo-set epoxy coated. Conductor size shall be designed so that temperature rise on
the conductors shall
not exceed 130C degree at nominal current, which helps to global heating problem. With this reason, insulation class shall be “B class”.

2.4- Joint Structure


-Electrical and mechanical connection shall be made by placing conductor joints into the joint blocks of the connected conductors and followed by tightening and fastening of the joint bolts.
2.5- Protection
-Protection degree of the housing and joints shall be IP55/IP65. Call our company for your IP65 orders.
(IP65 is not recommended for outdoor applications. Please check CR catalog.)
2.6- Acessories
-Busbar system shall have all necessary accessories (elbows, offsets, panel-transformer connections, reductions, etc.) Manufacturer shall supply special dimensioned units in short time, if
the project conditions requires.
-For horizontal runs, a horizontal expansion unit shall be used at every 40m and expansion points of the building.
-For vertical applications, a vertical expansion unit shall be used at every floor. Busbar system shall be rigidly fixed by supports at every floor.
3- Tap Off Boxes
-Both, Feeder and Plug-in busbar systems shall be suitable for bolt-on type tap off box connections at the joints up to 1.000A.
-Bolt-on tap off boxes shall be installed to the joints without changing or adding any piece. Bolt-on tap off boxes shall be able to be moved between different rated busbars.
-Plug-In busbars shall have minimum 2 plug-in points on each 300cm length. Plug-in tap off box sizes shall be up to 630A. Unused plug-in points shall have covers, which can provide IP55
protection degree.
-Plug-in tap off boxes shall be suitable to install or removed from busbars without switching off the power on the busbar.
-Contacts of plug-in tap off box shall be plated by silver.
-Tap off boxes shall be manufactured of sheet steel and epoxy painted RAL7035 colour.
-Plug-in tap off boxes shall have electromechanical safety interlock system. Which means;
a-) Electromechanical interlock mechanism shall ensure that the tap off box cannot be removed mechanically from the busbar, when the switch is at “ON” position.
b-) Electromechanical interlock mechanism shall ensure that, cover of the box can be opened only, when the switch is at “OFF” position.
c-) When the cover is opened, inside protection degree shall be minimum IP2X against accessing to live conductors.
d-) While inserting the contacts of plug-in tap off box, earth contact shall make the first touch. While removing, it shall be disconnected last.
-Tap off boxes shall be suitable for any brand of MCCBs. Electromechanical interlock mechanism shall be suitable for all these MCCBs too.
4- Installation and Commisioning
-Busbar systems shall be installed as per Single-Line drawings respect to required ampere rates and manufacturer installation guide (torque values, lockers, etc.). Electrical installator shall
run an insulation test after installation according to manufacturers test procedures. The results of the test shall be reported to the manufacturer. Minimum insulation value shall be 1 Mohm.

www.eaeelectric.com 55
56
Component List
Item Component Quantity
ELINEKX
►► Project Design Form

Company :

www.eaeelectric.com
Project :
Project No :

Name :
Date :
Signature :
Prepared by

Please duplicate this page for your own use.


P R O D U CT T Y P E S

BUSBAR ENERGY DISTRIBUTION SYSTEMS

CABLE TRAYS

TROLLEY BUSBAR ENERGY DISTRIBUTION SYSTEMS

INDOOR SOLUTIONS

SUPPORT SYSTEMS

TURKEY
OMAN
SUDAN
CHILE
PERU
KENYA
LEBANON
GHANA
SUDANCHILE
YEMEN CHILEALGERIA PERU
OMAN TURKMENISTAN TURKEY
INDIA MADAGASKAR
SRI LANKA LATVIA
ETHIOPIA
TAIWAN
GHANA FRANCE
VIETNAM UKRAINE
KONGO
CAMEROON
THAILAND QATAR
ESTONIA FINLAND KUWAIT
IRELAND
BANGLADESH KUWAIT UZBEKISTAN
RWANDA ALGERIA CHINA
TANZANIA BELGIUM
MADAGASKAR
GHANA THAILAND KENYA QATAR CAMEROON DENMARK
QAT
GERMANY MOROCCO SINGAPORE PAKISTAN TANZANIA ROMANIA
BELGIUM AUSTRIA
ETHIOPIA
KENYA
PERU EQ. GUINEA TURKEY OMAN VIETNAM LATVIA MACED
CZECH REP.
PERU VIETNAMNETHERLANDS SINGAPORE
AUSTRIA INDIA LIBYA
OMAN AZERBAIJAN
TANZANIA MACEDONIA MADAGASKAR TUNISIA AZER
POLAND TURKMENISTAN
MAURITIUS GREECE KAZAKHSTAN NIGERIA LUXEMBOURG RWANDA GREECEDENMARKCROATIA SOUTH KOREA SWI
THAILAND
NMAR SPAINIRELAND SERBIA OMAN
RKEY SLOVENIA
UZBE
T FRANCE ETHIOPIA
VIETNAMCAMEROON PAKISTAN SPAIN EGYPT VIETNAM SUDANNETHERLANDS MADAGASKAR TURKEY NIGERIAITALY QATAR U.KINGDOM
KOREA
TAIWAN
BAHRAIN
IA GHANATURKMENISTAN CYPRUS BULGARIA AZERBAIJAN SWITZERLAND U. A. EMIRATES BULGARIA SOUTH AFRICA QATAR TURKEY GREECE
PAKISTAN D
VIETNAM NORWAY SERBIANORWAY SPAIN FRANCE DENMARK
E SRI LANKA
MYANMAR NIGERIAGERMANY
POLAND U. A. EMIRATES
TNAMSOUTH KOREA TURKEY ICELAND VIETNAM SWITZERLAND TURKMENISTANYEMEN SUDAN SWITZERLAND U. A. EMIRATES
HUNGARY CAMEROON YEMEN U. A. EMIRATES CHILE LUXEMBOURG LITHUANIA MACEDONIA TANZANIA MACEDON
MALTA SU
MADAGASKA
SAUDI ARABIA YEMEN BRASILBELGIUM POLAND BELGIUM U.KINGDOM TURKMENISTAN CZECH REP. AZERBAIJAN DENMARK
PAKISTAN YE
EAE Elektrik A.S.
Head Office
Akcaburgaz Mahallesi,
3114. Sokak, No: 10 34522
Esenyurt – Istanbul – TURKEY
Tel: +90 (212) 866 20 00
Fax: +90 (212) 886 24 00

EAE DL 3 Factory
Busbar
Gebze IV Istanbul Makine ve Sanayicileri
Organize Bolgesi, 6. Cadde,
No: 6 41455 Demirciler Koyu,
Dilovası – Kocaeli – TURKEY
Tel: +90 (262) 999 05 55
Fax: +90 (262) 502 05 69

Please visit our website for the updated version of our catalogues.
www.eaeelectric.com

Catalog 12- EN. / Rev 24 500 Pcs. 07.01.2025


D.S.
EAE has full right to make any revisions or changes on this catalogue without any prior notice.

You might also like