0% found this document useful (0 votes)
9 views

P3U20

The Easergy P3U20 is a universal protection relay designed for power management, featuring a power supply range of 48-230V AC/DC and multiple communication protocols including Modbus RTU and DNP3. It includes 10 digital inputs, 5 digital outputs, and various protection functions such as phase overcurrent and thermal overload protection. The device is compliant with several standards and offers a warranty of up to 10 years, emphasizing sustainability and environmental performance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
9 views

P3U20

The Easergy P3U20 is a universal protection relay designed for power management, featuring a power supply range of 48-230V AC/DC and multiple communication protocols including Modbus RTU and DNP3. It includes 10 digital inputs, 5 digital outputs, and various protection functions such as phase overcurrent and thermal overload protection. The device is compliant with several standards and offers a warranty of up to 10 years, emphasizing sustainability and environmental performance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Product datasheet

Specifications

Easergy P3U20, 4L, 1U, 10DI/


5DO, Uaux: 48-230V, DI: 24-230V,
RS-485
REL52032

Main
range of product PowerLogic P3

product or component type Protection relay

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Relay application Universal

product reference P3U20-5AAA1ABAA

Mounting case size 20TE

power supply 48...230 V AC/DC

measuring inputs : 1/5 A CT phase current 3


: 1/5 A CT residual current 1
: 100 V/110 V VT voltage 1

number of Digital Inputs (DI) 10

number of analogue inputs 0

number of Digital Outputs (DO) 1 watchdog


5

number of analogue outputs 0

type of temperature module Copper cable external module


connection Fiber optic cable external module

communication ports USB port 1 front


RS485 1 rear

communication protocols IEC 60870-5-101


IEC 60870-5-103
DNP3
Modbus RTU
DeviceNet
SPAbus

cybersecurity Port hardening


Password protection

Oct 16, 2024 1


protection functions Phase undercurrent 37
Negative sequence overcurrent 46
Broken conductor 46 I2/I1
Excessive starting time, locked rotor 48/51LR
Thermal overload protection 49
Phase overcurrent 50/51
Earth fault overcurrent 50N/51N
Breaker failure 50BF
Switch ON to fault (SOTF)
Capacitor bank unbalance 51C
Capacitor overvoltage 59C
Neutral voltage displacement 59N
Motor restart inhibition 66
Directional earth fault 67N
Transient earth fault 67NI
CT supervision 60
VT supervision 60
H2 detection 68H2
H5 detection 68H5
Recloser 79
Lockout relay 86
Cold load pick-up
Programmable stages 99
Programmable curve

Arc flash protection No

measurement functions Current 3-phase


Current zero sequence
Current positive sequence
Current negative sequence
Current ratio of negative and positive
Voltage phase to earth
Voltage phase to phase
Voltage zero sequence
Voltage positive sequence
Voltage negative sequence
Voltage ratio of negative and positive
Short circuit fault reactance
Fault location current
Earth fault reactance
Frequency
Active power
RMS active power
Reactive power
RMS reactive power
Apparent power
RMS apparent power
Active energy
Reactive energy
Cos φ
Tan φ
Power angle
Power factor
Voltage phasor diagram view
Current phasor diagram view
Current 2nd, 15th harmonics with THD
Voltage 2nd, 15th harmonics with THD
Voltage interruption
Condition monitoring CB wear

control functions Switchgear control and monitoring


Programmable switchgear interlocking
Local control on single-line diagram
Local control with I/O keys
Local/remote control
2 function keys
Mobile application with Easergy SmartApp
Web-server
Programmable logic

controllable switchgear devices 2 controlled + 4 displayed

number of setting groups 4

monitoring functions Trip circuit supervision 74


Circuit breaker monitoring
Relay self-monitoring

2 Oct 16, 2024


logs and records Event recording
Disturbance recording
Tripping context

Switchgear diagnosis type CT supervision


Trip circuit supervision ANSI code: TCS

Connections - terminals Screw removable (digital input/output)


Clamp terminal removable (current transformer)
Pin removable (voltage transformer)

Complementary
Operating threshold 24...230 V AC/DC

Software name EcoStruxure Power Device


ESetup Easergy Pro

Web server Embedded HTTP server

Display type LCD 128 x 64 pixels with single line diagram

Number of key 2 customizable

Local signalling 4 LEDs


8 LEDs programmable

Standards IEC

Height 169.5 mm

Width 170 mm

Depth 205 mm

Net weight 2.5 kg maximum

Environment
climatic withstand Exposure to dry heat Bb tests conforming to EN/IEC 60068-2-2
Exposure to cold Ad tests conforming to EN/IEC 60068-2-1
Exposure to damp heat in service Db tests conforming to EN/IEC 60068-2-30
Exposure to damp heat in service Cab tests conforming to EN/IEC 60068-2-78

Mechanical robustness Vibrations (level: class II) conforming to IEC 60255-21-1


Vibrations: Fc conforming to IEC 60068-2-6
Shocks (level: class II) conforming to IEC 60255-21-2
Shocks: Ea conforming to IEC 60068-2-27
Seismic tests method A (level: class II) conforming to IEC 60255-21-3
Bumps (level: class II) conforming to IEC 60255-21-2
Bumps: Ea conforming to IEC 60068-2-27

Electromagnetic compatibility Emission tests conforming to IEC/EN 60255-26 ed. 3


Emission tests class A conforming to CISPR 11
Emission tests class A conforming to CISPR 22
EMC immunity conforming to IEC/EN 60255-26 ed. 3
EMC immunity conforming to EN/IEC 61000-4-18
EMC immunity level 4 conforming to EN/IEC 61000-4-2
EMC immunity level 3 conforming to EN/IEC 61000-4-3
EMC immunity level 4 conforming to EN/IEC 61000-4-4
EMC immunity level 3 conforming to EN/IEC 61000-4-5
EMC immunity level 3 conforming to EN/IEC 61000-4-6
EMC immunity conforming to EN/IEC 61000-4-8
EMC immunity level 5 conforming to EN/IEC 61000-4-9
EMC immunity conforming to EN/IEC 61000-4-29
EMC immunity conforming to EN/IEC 61000-4-11
EMC immunity conforming to EN/IEC 61000-4-17

Ambient air temperature for -40…65 °C


operation
IP degree of protection IP54 conforming to IEC 60529

maximum operating altitude 2000 m

Protective treatment Conformal coating

Relative humidity 0…95 %, without condensation

Oct 16, 2024 3


Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 16 cm

Package 1 Width 21.5 cm

Package 1 Length 27.5 cm

Package 1 Weight 3.5 kg

Contractual warranty
Warranty Up to 10 years extended warranty (Standard warranty 2 years. Please check with
your local SE representative for extended warranty availability and conditions)

4 Oct 16, 2024


Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)

China Rohs Regulation China RoHS declaration

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile End of Life Information

Oct 16, 2024 5


Product datasheet REL52032

Connections and Schema

Functional View

6 Oct 16, 2024


Product datasheet REL52032

Dimensions Drawings

Base Unit Dimensions

A B

With screw connector 214 mm/8.43” 192 mm/7.6”

With ring-lug connector 226 mm/8.90” 204 mm/8.0”

Oct 16, 2024 7

You might also like