Table of Contents P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
Table of Contents
1 About this manual.......................................................................... 8
3 Operational safety........................................................................ 12
3.1 Electrical safety...............................................................................................12
3.2 Device handling.............................................................................................. 12
3.3 Electrostatic discharge....................................................................................12
4 Wiring........................................................................................... 13
4.1 Installing connections......................................................................................13
4.2 Checking the wiring.........................................................................................13
5 Energizing.................................................................................... 14
6 Front panel................................................................................... 15
6.1 Push-buttons...................................................................................................15
6.2 LED indicators.................................................................................................16
6.3 Configuring the LED names via Easergy Pro................................................. 17
6.4 Controlling the alarm screen........................................................................... 17
6.5 Accessing operating levels............................................................................. 17
6.6 Adjusting the LCD contrast............................................................................. 18
6.7 Testing the LEDs and LCD screen..................................................................18
6.8 Releasing latches............................................................................................18
6.8.1 Releasing latches using Easergy Pro................................................... 18
6.8.2 Releasing latches using buttons and local panel display......................19
6.8.3 Releasing latches using F1 or F2 buttons............................................ 19
6.9 Controlling an object with selective control..................................................... 20
6.10 Controlling an object with direct control........................................................ 21
6.11 Menus............................................................................................................21
6.11.1 Moving in the menus .......................................................................... 23
6.11.2 Local panel messages........................................................................ 24
P3X_EN_QS_IEC+07 3
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 Table of Contents
9 Local port..................................................................................... 29
10 Block diagrams...........................................................................30
11 Mounting.....................................................................................34
12 Related documents.................................................................... 39
4 P3X_EN_QS_IEC+07
Legal information P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
Legal information
The Schneider Electric brand and any registered trademarks of Schneider Electric
Industries SAS referred to in this guide are the sole property of Schneider Electric
SA and its subsidiaries. They may not be used for any purpose without the
owner's permission, given in writing. This guide and its content are protected,
within the meaning of the French intellectual property code (Code de la propriété
intellectuelle français, referred to hereafter as "the Code"), under the laws of
copyright covering texts, drawings and models, as well as by trademark law. You
agree not to reproduce, other than for your own personal, noncommercial use as
defined in the Code, all or part of this guide on any medium whatsoever without
Schneider Electric's permission, given in writing. You also agree not to establish
any hypertext links to this guide or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the guide or its
content, except for a non-exclusive license to consult it on an "as is" basis, at your
own risk. All other rights are reserved.
As standards, specifications and designs change from time to time, please ask for
confirmation of the information given in this publication.
P3X_EN_QS_IEC+07 5
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 Safety information
Safety information
Important information
Read these instructions carefully and look at the equipment to become familiar
with the device before trying to install, operate, service or maintain it.
The following special messages may appear throughout this publication or on the
equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result
in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could
result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please note
Protective grounding
The user is responsible for compliance with all the existing international and
national electrical codes concerning protective grounding of any device.
6 P3X_EN_QS_IEC+07
EU directive and UKCA regulations compliance P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
P3X_EN_QS_IEC+07 7
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 1 About this manual
Carefully read through the mounting instruction of this manual before undertaking
any mounting or wiring work.
8 P3X_EN_QS_IEC+07
2 General product information P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
• Wear your personal protective equipment (PPE) and comply with the safe
electrical work practices. For clothing, see applicable local standards.
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and checking
the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing device to ensure that all
power is off.
• Do not open the secondary circuit of a live current transformer.
• Always connect the polarity of the current transformer (CT) and the voltage
transformer (VT) and their secondary ground wiring according to the
connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
To identify an Easergy P3 protection relay, see the labels on the package and on
the side of the relay.
P3X_EN_QS_IEC+07 9
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 2 General product information
1. Rated voltage Un
2. Rated frequency fn
REL52101 A x1
Protection relay
Relais de protection
B Made in Finland
EB172730012
A REL522101
135732
Easergy - P3 C
D P3F30-CGGGG-AAENA-BA
Easergy
45292
E
3 606481 357 3 28
SCHNEIDER ELECTRIC
CS30323
F-92506 RUEIL MALMAISON CEDEX
10 P3X_EN_QS_IEC+07
2 General product information P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
2.3 Storage
Store the relay in its original packaging in a closed, sheltered location with the
following ambient conditions:
2.4 Warranty
This product has a standard warranty of 2 years.
Ask your local Schneider Electric representative about our optional 10-year
warranty. Local conditions and availability apply.
2.5 Complaints
Complaints for manufacturing faults are directed in writing to the relay
manufacturer or the authorized dealer from which the product was acquired. Find
more information from our customers care center (www.schneider-electric.com/
ccc).
P3X_EN_QS_IEC+07 11
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 3 Operational safety
3 Operational safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Wear your personal protective equipment (PPE) and comply with the safe
electrical work practices. For clothing, see applicable local standards.
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and checking
the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing device to ensure that all
power is off.
• Do not open the secondary circuit of a live current transformer.
• Always connect the polarity of the current transformer (CT) and the voltage
transformer (VT) and their secondary ground wiring according to the
connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
12 P3X_EN_QS_IEC+07
4 Wiring P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
4 Wiring
Perform the wiring work according to national standards and possible
requirements from the customer.
1. Check that the rated values of the relay comply with those of the intended
application.
◦ Check that the rated values of the voltage and current transformer
secondaries comply with those of the device. The rated values can be
found on the serial number label.
◦ Check that the load ability of the outputs is adequate.
2. Earth the relay by connecting an earthing wire using a minimum 2.5 mm2
cross-section (AWG 14) to the device's earthing terminal.
3. Wire the relay to the rest of the system according to the wiring diagrams of the
application.
4. Connect the cable shields of shielded signal cables to the device's earthing
terminal.
P3X_EN_QS_IEC+07 13
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 5 Energizing
5 Energizing
DANGER
HAZARD OF ELECTRIC SHOCK
Before connecting the devices, disconnect the supply voltage to the unit.
The external auxiliary voltage UAUX (110–240 V ac/dc, or optionally 24–48 V dc)
of the relay is connected to the pins 1/C/1:1–2 or 1/D/1:1–2.
NOTICE
LOSS OF PROTECTION OR RISK OF NUISANCE TRIPPING
When the device is switched on, it performs the following initialization sequence
that takes approximately 5 seconds:
• Power LED ON, “Starting ..” on the screen.
• Watchdog contact starts.
The first screen displayed at the end of the sequence is the Mimic view screen.
14 P3X_EN_QS_IEC+07
6 Front panel P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
6 Front panel
Easergy P3 has a 128 x 128 LCD matrix display.
A B D E F
ON Service
A B
C D
E F
G H
I J
K L
M N
F1 F2
I J G C G J H
6.1 Push-buttons
Symbol Function
P3X_EN_QS_IEC+07 15
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 6 Front panel
Symbol Function
2) The default names of the function buttons are Function button 1 and 2. You can change the names
of the buttons in the Control > Names for function buttons setting view.
When the relay is powered, the power LED is green. During normal use, the
service LED is not active, it activates only when an error occurs or the relay is not
operating correctly. Should this happen, contact your local representative for
further guidance. The service LED and watchdog contact are assigned to work
together. Hardwire the status output into the substation's automation system for
alarm purposes.
The user-configurable LEDs may be red or green. You can configure them via
Easergy Pro.
To customize the LED texts on the front panel for the user-configurable LEDs, the
text may be created using a template and then printed. The printed text may be
placed in the pockets beside the LEDs.
You can also customize the LED texts that are shown on the screen for active
LEDs via Easergy Pro.
16 P3X_EN_QS_IEC+07
6 Front panel P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
2. To change a LED name, click the LED Description text and type a new
name. To save the new name, press Enter.
P3X_EN_QS_IEC+07 17
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 6 Front panel
NOTE: By nature, the LCD display changes its contrast depending on the
ambient temperature. The display may become dark or unreadable at low
temperatures. However, this condition does not affect the proper operation of
the protection or other functions.
1. Press .
2. Press .
The relay tests the LCD screen and the functionality of all LEDs.
2. From the Easergy Pro toolbar, select Device > Release all latches.
18 P3X_EN_QS_IEC+07
6 Front panel P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
Alternatively, go to Control > Release latches, and click the Release button.
1. Press .
2. Press .
You can use the function buttons F1 or F2 to release all latches after configuring
this function in Easergy Pro. You can make the configuration either under Control
> Release Latches or under Control > Function buttons.
P3X_EN_QS_IEC+07 19
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 6 Front panel
After this, pressing the F1 button on the relay’s front panel releases all
latches.
• To configure F1 to release latches under Control >Function buttons:
a. Under Function buttons, for F1, select PrgFncs from the Selected
control drop down menu.
c. Under Programmable functions for F1, select “On” from the Release all
latches drop-down menu.
After this, pressing the F1 button on the relay's front panel releases all
latches.
NOTE: The latch release signal can be activated only if the latched
output is active.
20 P3X_EN_QS_IEC+07
6 Front panel P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
– Press to cancel.
• Press to open an object.
– Press to cancel.
When direct control is enabled, the control operation is done without confirmation.
• Press to close an object.
• Press to open an object.
6.11 Menus
This section gives an overview of the menus that you can access via the device's
front panel.
Press the right arrow to access more measurements in the main menu.
P3X_EN_QS_IEC+07 21
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 6 Front panel
22 P3X_EN_QS_IEC+07
6 Front panel P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
OK
ISTART setting
OK OK
NOTE: To enter the parameter edit mode, enter the password. When the
value is in edit mode, its background is dark.
P3X_EN_QS_IEC+07 23
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 6 Front panel
24 P3X_EN_QS_IEC+07
7 Easergy Pro setting and configuration tool P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
• General
• Measurements
• Inputs/outputs
• Protection
• Matrix
• Logs
• Communication
The contents of the tabs depend on the relay type and the selected application
mode.
Easergy Pro stores the relay configuration in a setting file. The configuration of
one physical relay is saved in one setting file. The configurations can be printed
out and saved for later use.
NOTICE
HAZARD OF EQUIPMENT DAMAGE
P3X_EN_QS_IEC+07 25
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 8 Access to device configuration
1. Press and on the front panel. The Enter password view opens.
26 P3X_EN_QS_IEC+07
8 Access to device configuration P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
Select a digit value using , and if the password is longer than one digit,
move to the next digit position using .
NOTE: There are 16 digit positions in the Enter password view. Enter the
password starting from the first digit position.
For example, if the password is 2, you can enter 2***, **2*, ***2, or 0002
to log on.
Related topics
8.4 Password management
HTTP conf 2
FTP conf 2
NOTICE
CYBERSECURITY HAZARD
To improve cybersecurity:
• Change all passwords from their default values when taking the protection
device into use.
• Change all passwords regularly.
• Ensure a minimum level of password complexity according to common
password guidelines.
You can change the password for the operator or configurator user accounts in
the General > Device info setting view in Easergy Pro.
The password can contain letters, digits or other characters in the scope of ASCII
0x21~0x7E. However, the new password cannot be any of the default passwords
(digits 0–4 or 9999).
Follow these guidelines to improve the password complexity and thus device
security:
• Use a password of minimum 8 characters.
• Use alphabetic (uppercase and lowercase) and numeric characters in addition
to symbols.
P3X_EN_QS_IEC+07 27
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 8 Access to device configuration
Also, all users must be aware of the best practices concerning passwords
including:
• not sharing personal passwords
• not displaying passwords during password entry
• not transmitting passwords in email or by other means
• not saving the passwords on PCs or other devices
• no written passwords on any supports
• regularly reminding users about the best practices concerning passwords
Related topics
8.2 Logging on via the front panel
28 P3X_EN_QS_IEC+07
9 Local port P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
9 Local port
The relay has a USB port in the front panel.
The front panel USB type B port is always using the command line protocol for
Easergy Pro.
The speed of the interface is defined in the CONF/DEVICE SETUP menu via the
front panel. The default settings for the relay are 38400/8N1.
It is possible to change the front USB port's bit rate. This setting is visible only on
the relay's local display. The bit rate can be set between 1200 and 187500. This
changes the bit rate of the relay, and the Easergy Pro bit rate has to be set
separately. If the bit rate in the setting tool is incorrect, it takes a longer time to
establish the communication.
NOTE: Use the same bit rate in the relay and the Easergy Pro setting tool.
P3X_EN_QS_IEC+07 29
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 10 Block diagrams
10 Block diagrams
The status of the output contacts is shown when the relay is energized but none
of the protection, controlling or self-supervision elements are activated.
Figure 11 - Typical block diagram for P3F30, P3M30 and P3G30 relays
~ 1/C/1:20 T12
N -/~ 1/C/1:1
1/C/1:19 T12
P3M30-CGGAA-DAENA-BAAAA
L +/~ 1/C/1:2 = 1/C/1:18 T11
G
F
1/C/1:17 T11
8/E/1:1 8/1/1:1 1/C/1:16 T10
IL1 5/1A 1/C/1:15 T10
8/E/1:2 8/1/1:2
8/E/1:4 8/1/1:4 1/C/1:14 T9
IL2 5/1A 1/C/1:13 T9
8/E/1:3 8/1/1:3
8/E/1:6 8/1/1:6 1/C/1:12 T1
IL3 5/1A 1/C/1:11 T1
8/E/1:5 8/1/1:5
1/C/1:10 A1 NO
8/E/1:8 8/1/1:8 I01 5A 1/C/1:9 A1 NC
8/E/1:9 8/1/1:9 1/C/1:8 A1 COM
I01 1A
8/E/1:7 8/1/1:7 1/C/1:7 SF NC
1/C/1:6 SF NO
8/E/1:11
8/E/1:10
8/1/1:11
8/1/1:10
I02 1A
1 1/C/1:5 SF COM
I02 0.2A
8/E/1:12 8/1/1:12
8/E/2:2 8/1/1:12
U1
8/E/2:1 8/1/2:1
8/E/2:4 8/1/2:4
U2 2/G/1:13
8/E/2:3 8/1/2:3 T13
2/G/1:14
8/E/2:6 8/1/2:6
U3 2/G/1:15
8/E/2:5 8/1/2:5 T14
2/G/1:16
8/E/2:8 8/1/2:8
U4 2/G/1:17
8/E/2:7 8/1/2:7 T15
2/G/1:18
2/G/1:19
DI6 2/G/1:12 DI T16
DI6 2/G/1:11 2/G/1:20
DI5 2/G/1:10
DI5 2/G/1:9
DI4 2/G/1:8
DI4 2/G/1:7 3/G/1:13
T17
DI3 2/G/1:6 3/G/1:14
DI3 2/G/1:5 3/G/1:15
T18
DI2 2/G/1:4 3/G/1:16
DI2 2/G/1:3 3/G/1:17
DI1 2/G/1:2 T19
3/G/1:18
DI1 2/G/1:1
3/G/1:19
T20
3/G/1:20
DI12 3/G/1:12 DI
DI12 3/G/1:11
DI11 3/G/1:10
DI11 3/G/1:9
DI10 3/G/1:8
DI10 3/G/1:7
DI9 3/G/1:6 9/N/1 Eth RJ45
DI9 3/G/1:5
DI8 3/G/1:4
DI8 3/G/1:3 9/N/2 Eth RJ45
DI7 3/G/1:2
DI7 3/G/1:1
S6 - 6/D/1:8 L>
S6 + 6/D/1:7
S5 - 6/D/1:6
S5 + 6/D/1:5
S4 - 6/D/1:4
S4 + 6/D/1:3
S3 - 6/D/1:2
S3 + 6/D/1:1
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
30 P3X_EN_QS_IEC+07
10 Block diagrams P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
~ 1/C/1:20 T12
N -/~ 1/C/1:1
1/C/1:19 T12
P3M30-CGGAA-DAMNA-BAAAA
L +/~ 1/C/1:2 = 1/C/1:18 T11
G
F
1/C/1:17 T11
LPCT 1/C/1:16 T10
IL1 RJ45 1/C/1:15 T10
IL2 RJ45 1/C/1:14 T9
IL3 RJ45 1/C/1:13 T9
LPVT 1/C/1:12 T1
HUB1 U1, U2, U3
1/C/1:11 T1
1/C/1:10 A1 NO
HUB2 U4, U5 1/C/1:9 A1 NC
1/C/1:8 A1 COM
8/M/1:1 8/M/1:1 I 1/C/1:7 SF NC
01 5A 1/C/1:6 SF NO
8/M/1:2 8/M/1:2 1/C/1:5 SF COM
I01 1A
8/M/1:3 8/M/1:3
8/M/1:4 8/M/1:4 I 1A
02
8/M/1:5 8/M/1:5
I02 0.2A
8/M/1:6 8/M/1:6
2/G/1:13
T13
2/G/1:14
2/G/1:15
T14
2/G/1:16
2/G/1:17
T15
2/G/1:18
2/G/1:19
DI6 2/G/1:12 DI T16
DI6 2/G/1:11 2/G/1:20
DI5 2/G/1:10
DI5 2/G/1:9
DI4 2/G/1:8
DI4 2/G/1:7 3/G/1:13
T17
DI3 2/G/1:6 3/G/1:14
DI3 2/G/1:5 3/G/1:15
T18
DI2 2/G/1:4 3/G/1:16
DI2 2/G/1:3 3/G/1:17
DI1 2/G/1:2 T19
3/G/1:18
DI1 2/G/1:1
3/G/1:19
T20
3/G/1:20
DI12 3/G/1:12 DI
DI12 3/G/1:11
DI11 3/G/1:10
DI11 3/G/1:9
DI10 3/G/1:8
DI10 3/G/1:7
DI9 3/G/1:6 9/N/1 Eth RJ45
DI9 3/G/1:5
DI8 3/G/1:4
DI8 3/G/1:3 9/N/2 Eth RJ45
DI7 3/G/1:2
DI7 3/G/1:1
S6 - 6/D/1:8 L>
S6 + 6/D/1:7
S5 - 6/D/1:6
S5 + 6/D/1:5
S4 - 6/D/1:4
S4 + 6/D/1:3
S3 - 6/D/1:2
S3 + 6/D/1:1
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
P3X_EN_QS_IEC+07 31
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 10 Block diagrams
~ 1/C/1:20 T12
N -/~ 1/C/1:1
1/C/1:19 T12
P3L30-CGGAA-SAENA-BA
L +/~ 1/C/1:2 = 1/C/1:18 T11
1/C/1:17 T11
1/C/1:16 T10
1/C/1:15 T10
1/C/1:14 T9
1/C/1:13 T9
1/C/1:12 T1
1/C/1:11 T1
1/C/1:10 A1 NO
1/C/1:9 A1 NC
1/C/1:8 A1 COM
8/E/1:1
IL1 5/1A 1/C/1:7 SF NC
8/E/1:2 1/C/1:6 SF NO
1/C/1:5 SF COM
8/E/1:3
IL2 5/1A
8/E/1:4
8/E/1:5
IL3 5/1A
8/E/1:6
8/E/1:7
I01 5A
8/E/1:8
I01 1A 2/G/1:13
8/E/1:9 T13
2/G/1:14
8/E/1:10 I02 1A
8/E/1:11 2/G/1:15
I02 0.2A T14
2/G/1:16
8/E/1:12
2/G/1:17
8/E/2:1 T15
U1 2/G/1:18
8/E/2:2
8/E/2:3 2/G/1:19
U2 T16
8/E/2:4 2/G/1:20
8/E/2:5
U3
8/E/2:6
8/E/2:7 3/G/1:13
U4 T17
8/E/2:8 3/G/1:14
3/G/1:15
T18
3/G/1:16
DI6 2/G/1:12 DI 3/G/1:17
DI6 2/G/1:11 T19
DI5 2/G/1:10 3/G/1:18
DI5 2/G/1:9 3/G/1:19 T20
DI4 2/G/1:8 3/G/1:20
DI4 2/G/1:7
DI3 2/G/1:6
DI3 2/G/1:5
DI2 2/G/1:4
DI2 2/G/1:3
DI1 2/G/1:2 6/S Line diff.
DI1 2/G/1:1 pilot
DI12 3/G/1:12 DI
DI12 3/G/1:11
DI11 3/G/1:10
DI11 3/G/1:9 9/N/1 Eth RJ45
DI10 3/G/1:8
DI10 3/G/1:7 9/N/2 Eth RJ45
DI9 3/G/1:6
DI9 3/G/1:5
DI8 3/G/1:4
DI8 3/G/1:3
DI7 3/G/1:2
DI7 3/G/1:1
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
32 P3X_EN_QS_IEC+07
10 Block diagrams P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
Figure 14 - Typical block diagram for P3M32, P3T32 and P3G32 relays
P3T32-CGITA-AAENA-BAAAA
1/C/1:16 T10
M
G
DI1 2/G/1:1 1/C/1:15 T10
DI
DI1 2/G/1:2 1/C/1:14 T9
DI2 2/G/1:3 1/C/1:13 T9
DI2 2/G/1:4 1/C/1:12 T1
DI3 2/G/1:5
1/C/1:11 T1
DI3 2/G/1:6
1/C/1:10 A1 NO
1
DI4 2/G/1:7 1/C/1:9 A1 NC
DI4 2/G/1:8 1/C/1:8 A1 COM
DI5 2/G/1:9 1/C/1:7 SF NC
DI5 2/G/1:10 1/C/1:6 SF NO
DI6 2/G/1:11 1/C/1:5 SF COM
1
DI6 2/G/1:12
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
P3X_EN_QS_IEC+07 33
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 11 Mounting
11 Mounting
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Wear your personal protective equipment (PPE) and comply with the safe
electrical work practices. For clothing refer applicable local standards.
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and checking
the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing relay to ensure that all power
is off.
• Do not open the secondary circuit of a live current transformer.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
CAUTION
HAZARD OF CUTS
Trim the edges of the cut-out plates to remove any jagged edges.
Use protective gloves when moving and mounting the device.
34 P3X_EN_QS_IEC+07
11 Mounting P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
Panel mounting
mm
225
1 8.86
in 2
erg y
Eas erg y
Eas
Eas erg y
152
5.98
1.0
0.0-60
4-2
.3 6
3 4
3a
3a
erg yerg y
EasEas
min. 2.5mm2
Ø 5-8mm
CLICK !
Nut M5
1.5Nm, 13.3 Ib in
mm 208 253.40
in 264 9.97 24.60
8.18 0.97
10.37 223.33
183 9.17
Easergy 7.20
153
6.02
177 150
6.97 5.91 183
7.20
The conventional mounting technique has always been installing the relay on the
secondary compartment's door. A limitation of this approach could be that the
door construction is not strong enough for the relay's weight and wiring a large
amount of secondary and communication cabling could be challenging.
P3X_EN_QS_IEC+07 35
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 11 Mounting
mm 247
in 9.72
180 199
7.09 7.81
Ease rgy
199
7.83 150
180 5.91
7.09
29 264
1.12 10.37
1 210
Easergy
8.27
Ø5 177
0.2 6.97
M4x20
mm Torx T-20
in 1.5Nm
100
3.94
2
18
0.71
11.5
0.45
20 34
0.79 1.34 Eas erg y
3
180
7.09
Ø7
0.28
min. 2.5mm2
Ø 5-8mm
180
7.09
Nut M5
1.5 Nm, 13.3 Ib in
This mounting technique allows the door to be lighter as the relay's frame is
installed on the back of the secondary compartment. Normally, the relay is
mounted by the terminal blocks, hence the secondary wiring is short.
Communication cabling is easier, too, as the door movement does not need to be
considered. In this case, only the communication between relay base and display
have to be wired.
36 P3X_EN_QS_IEC+07
11 Mounting P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
Projection mounting
225
mm
1 2 8.86
in
Eas erg y
Easerg y
152
5.98
1.0
0.0-60
4-2
.36
2.5Nm 3Nm
22 lb.in 27 lb.in
3 4
3a y y
ergerg
EasEas
Vamp 300
3a min. 2.5mm2
Ø 5-8mm ON
OK
F2
F1
I O
Nut M5
1.5Nm, 13.3 Ib in
CLICK !
mm 269
in 264 208 10.59
10.37 8.18 45
224
183 1.77
8.82
Easergy 7.20
Vamp 300
ON
152
5.98
177 150 177
6.97 5.91
OK 7.0
F1 F2
I O
If the depth dimension behind the compartment door is limited, the relay can be
equipped with a frame around the collar. This arrangement reduces the depth
inside the compartment by 45 mm.
P3X_EN_QS_IEC+07 37
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 11 Mounting
A B
C D
E F
1
G H
I J
K L
M N
F1 F2
A B
C D
E F
G H
I J
K L
M N
F1 F2
A B
C D
3 E
G
I
K
M
F
H
J
L
N
F1 F2
See "P3 Advanced Series facial label instruction" document for more information.
Protective film
NOTICE
RISK OF DESTRUCTION OF THE RELAY
The protective film on the relay's display is plastic and can melt if exposed to
high temperatures intensive sunlight. Remove the protective film after mounting
the relay.
Failure to follow these instructions can result in equipment damage.
38 P3X_EN_QS_IEC+07
12 Related documents P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32
12 Related documents
Table 6 - Related documents
Document Identification3)
P3X_EN_QS_IEC+07 39
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison - France
Phone: +33 (0) 1 41 29 70 00
www.schneider-electric.com