The document is a Quick Start guide for the Easergy P3 protection relays, detailing installation, operational safety, wiring, and configuration procedures. It includes specific information for various models such as P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, and P3G32. Additionally, it covers legal and compliance information, as well as warranty and complaint procedures.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views40 pages

P3X_en_QS_07_IEC_web

The document is a Quick Start guide for the Easergy P3 protection relays, detailing installation, operational safety, wiring, and configuration procedures. It includes specific information for various models such as P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, and P3G32. Additionally, it covers legal and compliance information, as well as warranty and complaint procedures.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 40

Easergy P3

P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32


Quick Start - IEC
02/2022

P3X_EN_QS_IEC+07
www.schneider-electric.com
Table of Contents P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

Table of Contents
1 About this manual.......................................................................... 8

2 General product information...........................................................9


2.1 Checking the consignment................................................................................9
2.2 Product identification.........................................................................................9
2.3 Storage............................................................................................................11
2.4 Warranty..........................................................................................................11
2.5 Complaints...................................................................................................... 11

3 Operational safety........................................................................ 12
3.1 Electrical safety...............................................................................................12
3.2 Device handling.............................................................................................. 12
3.3 Electrostatic discharge....................................................................................12

4 Wiring........................................................................................... 13
4.1 Installing connections......................................................................................13
4.2 Checking the wiring.........................................................................................13

5 Energizing.................................................................................... 14

6 Front panel................................................................................... 15
6.1 Push-buttons...................................................................................................15
6.2 LED indicators.................................................................................................16
6.3 Configuring the LED names via Easergy Pro................................................. 17
6.4 Controlling the alarm screen........................................................................... 17
6.5 Accessing operating levels............................................................................. 17
6.6 Adjusting the LCD contrast............................................................................. 18
6.7 Testing the LEDs and LCD screen..................................................................18
6.8 Releasing latches............................................................................................18
6.8.1 Releasing latches using Easergy Pro................................................... 18
6.8.2 Releasing latches using buttons and local panel display......................19
6.8.3 Releasing latches using F1 or F2 buttons............................................ 19
6.9 Controlling an object with selective control..................................................... 20
6.10 Controlling an object with direct control........................................................ 21
6.11 Menus............................................................................................................21
6.11.1 Moving in the menus .......................................................................... 23
6.11.2 Local panel messages........................................................................ 24

7 Easergy Pro setting and configuration tool.................................. 25

8 Access to device configuration.....................................................26


8.1 User accounts................................................................................................. 26
8.2 Logging on via the front panel.........................................................................26
8.3 HTTP and FTP logon details...........................................................................27

P3X_EN_QS_IEC+07 3
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 Table of Contents

8.4 Password management.................................................................................. 27


8.5 Password restoring......................................................................................... 28

9 Local port..................................................................................... 29

10 Block diagrams...........................................................................30

11 Mounting.....................................................................................34

12 Related documents.................................................................... 39

4 P3X_EN_QS_IEC+07
Legal information P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

Legal information
The Schneider Electric brand and any registered trademarks of Schneider Electric
Industries SAS referred to in this guide are the sole property of Schneider Electric
SA and its subsidiaries. They may not be used for any purpose without the
owner's permission, given in writing. This guide and its content are protected,
within the meaning of the French intellectual property code (Code de la propriété
intellectuelle français, referred to hereafter as "the Code"), under the laws of
copyright covering texts, drawings and models, as well as by trademark law. You
agree not to reproduce, other than for your own personal, noncommercial use as
defined in the Code, all or part of this guide on any medium whatsoever without
Schneider Electric's permission, given in writing. You also agree not to establish
any hypertext links to this guide or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the guide or its
content, except for a non-exclusive license to consult it on an "as is" basis, at your
own risk. All other rights are reserved.

Electrical equipment should be installed, operated, serviced and maintained only


by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.

As standards, specifications and designs change from time to time, please ask for
confirmation of the information given in this publication.

P3X_EN_QS_IEC+07 5
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 Safety information

Safety information
Important information

Read these instructions carefully and look at the equipment to become familiar
with the device before trying to install, operate, service or maintain it.

The following special messages may appear throughout this publication or on the
equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.

This is the safety alert symbol. It is used to alert you to potential


personal injury hazards. Obey all safety messages that follow
this symbol to avoid possible injury or death.

The addition of either symbol to a “Danger” or “Warning” safety


label indicates that an electrical hazard exists which will result
in personal injury if the instructions are not followed.

DANGER
DANGER indicates a hazardous situation which, if not avoided, will result
in death or serious injury.

WARNING
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.

CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could
result in minor or moderate injury.

NOTICE
NOTICE is used to address practices not related to physical injury.

Please note

Electrical equipment must only be installed, operated, serviced, and maintained


by qualified personnel. A qualified person is one who has skills and knowledge
related to the construction, installation, and operation of electrical equipment and
has received safety training to recognize and avoid the hazards involved.

No responsibility is assumed by Schneider Electric for any consequences arising


out of the use of this material.

Protective grounding

The user is responsible for compliance with all the existing international and
national electrical codes concerning protective grounding of any device.

6 P3X_EN_QS_IEC+07
EU directive and UKCA regulations compliance P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

EU directive and UKCA regulations compliance

EU directive compliance UKCA regulations compliance

Schneider Electric Limited

Telford, TF3 3BL


United Kingdom

EMC compliance EMC compliance

2014/30/EU SI 2016 No. 1091

Compliance with the European The Electromagnetic Compatibility


Commission's EMC Directive. Product Regulations:
Specific Standard was used to establish • BS EN 60255-26 2013
conformity:
• EN 60255-26 2013

Product safety Product safety

2014/35/EU SI 2016 No. 1101

Compliance with the European The Electrical Equipment (Safety)


Commission's Low Voltage Directive. Regulations:
Product Specific Safety Standard was used • BS EN 60255-27 2014
to establish conformity:
• EN 60255-27 2014

RoHS directive RoHS regulation

2011/65/EU (inclusive of Directive (EU) SI 2012 No. 3032


2015/863) Compliance
The Restriction of the Use of Certain
Compliance with the European Hazardous Substances in Electrical and
Commission's on the restriction of the use Electronic Equipment Regulations
of certain hazardous substances in • BS EN IEC 63000:2018
electrical and electronic equipment
• EN IEC 63000:2018 / IEC 63000:2016

P3X_EN_QS_IEC+07 7
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 1 About this manual

1 About this manual


This manual contains instructions for handling, mounting and wiring Easergy P3
protection relays:
• P3F30 Feeder protection
• P3L30 Line protection
• P3T32 Transformer protection
• P3M30, P3M32 Motor protection
• P3G30, P3G32 Generator protection

Carefully read through the mounting instruction of this manual before undertaking
any mounting or wiring work.

8 P3X_EN_QS_IEC+07
2 General product information P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

2 General product information


DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Wear your personal protective equipment (PPE) and comply with the safe
electrical work practices. For clothing, see applicable local standards.
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and checking
the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing device to ensure that all
power is off.
• Do not open the secondary circuit of a live current transformer.
• Always connect the polarity of the current transformer (CT) and the voltage
transformer (VT) and their secondary ground wiring according to the
connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.

Failure to follow this instruction will result in death or serious injury.

2.1 Checking the consignment


• Check that the unit packaging and the seal are intact at the receipt of the
delivery. Our products leave the factory in closed, sealed packaging. If the
transport packaging is open or the seal is broken, the confidentiality and
authenticity of the information contained in the products cannot be ensured.
• Check the device visually for possible external damage or loose parts inside
the device. If you find the device to be damaged, see 2.5 Complaints.
• Check that the device complies with the order and the Calibration and Test
Report. Check:
◦ relay type, serial number
◦ other possible order-related structural matters

If found incomplete, see 2.5 Complaints.

2.2 Product identification


Each Easergy P3 relay is delivered in a separate package containing:

• Easergy P3 protection relay with the necessary terminal connectors


• Production testing certificate
• Quick Start manual

Optional accessories are delivered in separate packages.

To identify an Easergy P3 protection relay, see the labels on the package and on
the side of the relay.

P3X_EN_QS_IEC+07 9
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 2 General product information

Serial number label

Figure 1 - Serial number label

1 Un: 100/110V Made in Finland


2 fn: 50/60Hz 12 Mfg Date: 27.7.2017
3 In: 1/5A I
5 I n: 1/5A 13 MAC: 001AD3011FF1
4 Io1n: 5/1A 6 Io2n: 1/0.2A
8 Pmax:
P: 35W 7 Io3n: 1/5A
9 Uaux: 110 240 Vac/dc
Type: 10 P3G32-CGITA-KAFNA-BAAAA
S/N: 11 EB173020002 14 VID: P3G32-001017

1. Rated voltage Un

2. Rated frequency fn

3. Rated phase current In

4. Rated earth fault current I01n

5. Rated phase current I´n *)

6. Rated earth fault current I02n

7. Rated earth fault current I03n1) *)

8. Power consumption Pmax

9. Power supply operating range UAUX

10. Order code

11. Serial number

12. Manufacturing date

13. MAC address for TCP/IP communication

14. Production identification

Unit package label

Figure 2 - P3x3x Unit package label

REL52101 A x1
Protection relay
Relais de protection
B Made in Finland
EB172730012
A REL522101
135732
Easergy - P3 C
D P3F30-CGGGG-AAENA-BA
Easergy
45292

E
3 606481 357 3 28

SCHNEIDER ELECTRIC
CS30323
F-92506 RUEIL MALMAISON CEDEX

A. Short order code D. Order code


B. Serial number E. EAN13 bar code
C. Internal product code

1) *)Available in P3M32, P3T32 and P3G32 models only

10 P3X_EN_QS_IEC+07
2 General product information P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

2.3 Storage
Store the relay in its original packaging in a closed, sheltered location with the
following ambient conditions:

• ambient temperature: -40 °C to +70 °C (or -40 °F to +158 °F)


• humidity < 90 %.

Check the ambient conditions and the packaging yearly.

2.4 Warranty
This product has a standard warranty of 2 years.

Ask your local Schneider Electric representative about our optional 10-year
warranty. Local conditions and availability apply.

2.5 Complaints
Complaints for manufacturing faults are directed in writing to the relay
manufacturer or the authorized dealer from which the product was acquired. Find
more information from our customers care center (www.schneider-electric.com/
ccc).

Complaints about transport damage must be sent to the accountable transport or


insurance company.

P3X_EN_QS_IEC+07 11
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 3 Operational safety

3 Operational safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Wear your personal protective equipment (PPE) and comply with the safe
electrical work practices. For clothing, see applicable local standards.
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and checking
the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing device to ensure that all
power is off.
• Do not open the secondary circuit of a live current transformer.
• Always connect the polarity of the current transformer (CT) and the voltage
transformer (VT) and their secondary ground wiring according to the
connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.

Failure to follow this instruction will result in death or serious injury.

3.1 Electrical safety


National electrical safety regulations must be observed when work is carried out
under live conditions. The relay manufacturer cannot be held responsible for
accidents caused by incorrect working or protection practices.

3.2 Device handling


The correct handling of the relays under all mounting and operating conditions
forms the foundation for their correct and safe use. Observe all safety notes and
warnings.

3.3 Electrostatic discharge


The devices include components that are liable to be damaged by electrostatic
discharge (ESD). Do not open the devices without permission from the
manufacturer.

12 P3X_EN_QS_IEC+07
4 Wiring P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

4 Wiring
Perform the wiring work according to national standards and possible
requirements from the customer.

4.1 Installing connections


NOTE: Use only single-strand wire or stranded wire with insulated crimp
terminals.

1. Check that the rated values of the relay comply with those of the intended
application.
◦ Check that the rated values of the voltage and current transformer
secondaries comply with those of the device. The rated values can be
found on the serial number label.
◦ Check that the load ability of the outputs is adequate.

2. Earth the relay by connecting an earthing wire using a minimum 2.5 mm2
cross-section (AWG 14) to the device's earthing terminal.

3. Wire the relay to the rest of the system according to the wiring diagrams of the
application.

4. Connect the cable shields of shielded signal cables to the device's earthing
terminal.

4.2 Checking the wiring


Check the secondary wiring by visual inspection and, when needed, by
measuring to eliminate possible incorrect wiring that may cause malfunction of the
relay or associated devices.
• Check the wiring visually:
◦ Inspect the wiring visually. Especially check the wire bunches for
adequate slack where needed over the hinges.
◦ Check the screw terminals for correct tightness.
◦ Check that no wire strands are protruding from the terminals.
• Check the wiring by measuring:
◦ Check the connections between the relay and associated devices by
using a circuit indicator lamp or buzzer.
◦ Check other possible connections by using recognized and reliable
working practices.

P3X_EN_QS_IEC+07 13
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 5 Energizing

5 Energizing

DANGER
HAZARD OF ELECTRIC SHOCK

Before connecting the devices, disconnect the supply voltage to the unit.

Failure to follow these instructions will result in death or serious injury.

The external auxiliary voltage UAUX (110–240 V ac/dc, or optionally 24–48 V dc)
of the relay is connected to the pins 1/C/1:1–2 or 1/D/1:1–2.

NOTE: When an optional 24–48 V dc power module is used, the polarity is as


follows: 1/D/2:2 positive (+), 1/D/2:1 negative (-).

NOTICE
LOSS OF PROTECTION OR RISK OF NUISANCE TRIPPING

• If the relay is no longer supplied with power or is in permanent fault state,


the protection functions are no longer active and all the Easergy P3 digital
outputs are dropped out.
• Check that the operating mode and SF relay wiring are compatible with the
installation.

Failure to follow these instructions can result in equipment damage and


unwanted shutdown of the electrical installation.

When the device is switched on, it performs the following initialization sequence
that takes approximately 5 seconds:
• Power LED ON, “Starting ..” on the screen.
• Watchdog contact starts.
The first screen displayed at the end of the sequence is the Mimic view screen.

14 P3X_EN_QS_IEC+07
6 Front panel P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

6 Front panel
Easergy P3 has a 128 x 128 LCD matrix display.

Figure 3 - Easergy P3 front panel

A B D E F

ON Service
A B
C D
E F
G H
I J
K L
M N

F1 F2

I J G C G J H

A. Power LED F. Service LED


B. CANCEL push-button G. Function push-buttons and LEDs showing their status
C. Navigation push-buttons H. Local port
D. LCD I. Object control buttons
E. INFO push-button J. User-configurable LEDs

6.1 Push-buttons

Symbol Function

HOME/CANCEL push-button for returning to the previous menu. To


return to the first menu item in the main menu, press the button for at
least 3 seconds.

INFO push-button for viewing additional information, for entering the


password view and for adjusting the LCD contrast.

Programmable function push-button.2)

Programmable function push-button.2)

ENTER push-button for activating or confirming a function.

UP navigation push-button for moving up in the menu or increasing a


numerical value.

P3X_EN_QS_IEC+07 15
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 6 Front panel

Symbol Function

DOWN navigation push-button for moving down in the menu or


decreasing a numerical value.

LEFT navigation push-button for moving backwards in a parallel menu


or selecting a digit in a numerical value.

RIGHT navigation push-button for moving forwards in a parallel menu or


selecting a digit in a numerical value.

Circuit breaker ON push-button

Circuit breaker OFF push-button

2) The default names of the function buttons are Function button 1 and 2. You can change the names
of the buttons in the Control > Names for function buttons setting view.

6.2 LED indicators


The relay has 18 LEDs on the front panel:

• two LEDs for function buttons (F1 and F2)


• two LEDs represent the unit's general status (power and service)
• 14 user-configurable LEDs (A-N)

When the relay is powered, the power LED is green. During normal use, the
service LED is not active, it activates only when an error occurs or the relay is not
operating correctly. Should this happen, contact your local representative for
further guidance. The service LED and watchdog contact are assigned to work
together. Hardwire the status output into the substation's automation system for
alarm purposes.

The user-configurable LEDs may be red or green. You can configure them via
Easergy Pro.
To customize the LED texts on the front panel for the user-configurable LEDs, the
text may be created using a template and then printed. The printed text may be
placed in the pockets beside the LEDs.

You can also customize the LED texts that are shown on the screen for active
LEDs via Easergy Pro.

Table 1 - LED indicators and their information

LED indicator LED color Meaning Measure /


Remarks

Power LED lit Green The auxiliary power Normal operation


has been switched state
on

Service LED lit Red Internal fault. The relay attempts


Operates in parallel to reboot. If the
with the self- service LED remains
supervision output lit, call for
maintenance.

16 P3X_EN_QS_IEC+07
6 Front panel P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

LED indicator LED color Meaning Measure /


Remarks

A–H LED lit Green or red Application-related Configurable in the


status indicators. Matrix setting view

F1 or F2 LED lit Green Corresponding Depending on the


function key function
pressed / activated programmed to F1 /
F2

6.3 Configuring the LED names via Easergy Pro


1. Go to General > LED names.

2. To change a LED name, click the LED Description text and type a new
name. To save the new name, press Enter.

Figure 4 - LED NAMES menu in Easergy Pro for LED configuration

6.4 Controlling the alarm screen


You can enable or disable the alarm screen either via the relay's local display or
using Easergy Pro:

• On the local display, go to Events > Alarms.


• In Easergy Pro, go to General > Local panel conf.

6.5 Accessing operating levels

1. On the front panel, press and .

2. Enter the password, and press .

P3X_EN_QS_IEC+07 17
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 6 Front panel

6.6 Adjusting the LCD contrast


Prerequisite: You have entered the correct password.

1. Press , and adjust the contrast.

◦ To increase the contrast, press .


◦ To decrease the contrast, press .

2. To return to the main menu, press .

NOTE: By nature, the LCD display changes its contrast depending on the
ambient temperature. The display may become dark or unreadable at low
temperatures. However, this condition does not affect the proper operation of
the protection or other functions.

6.7 Testing the LEDs and LCD screen


You can start the test sequence in any main menu window.

To start the LED and LCD test:

1. Press .

2. Press .

The relay tests the LCD screen and the functionality of all LEDs.

6.8 Releasing latches


You can release latches using:
• Easergy Pro
• buttons and local panel display
• F1 or F2 buttons

6.8.1 Releasing latches using Easergy Pro

1. Connect Easergy Pro to the device.

2. From the Easergy Pro toolbar, select Device > Release all latches.

18 P3X_EN_QS_IEC+07
6 Front panel P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

Figure 5 - Releasing all latches

Alternatively, go to Control > Release latches, and click the Release button.

Figure 6 - Release latches

6.8.2 Releasing latches using buttons and local panel display

Prerequisite: You have entered the correct password

1. Press .

2. Press .

3. Select Release, and press .


All latches are released.

6.8.3 Releasing latches using F1 or F2 buttons

You can use the function buttons F1 or F2 to release all latches after configuring
this function in Easergy Pro. You can make the configuration either under Control
> Release Latches or under Control > Function buttons.

• To configure F1 to release latches under Control > Release latches:

a. In Easergy Pro, go to Control > Release latches.

b. Under Release latches, select F1 from the DI to release latches drop-


down menu.

c. Set 1 s delay for Latch release signal pulse.

P3X_EN_QS_IEC+07 19
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 6 Front panel

Figure 7 - Release latches view

After this, pressing the F1 button on the relay’s front panel releases all
latches.
• To configure F1 to release latches under Control >Function buttons:

a. Under Function buttons, for F1, select PrgFncs from the Selected
control drop down menu.

b. Set 1 s delay for F1 pulse length.

c. Under Programmable functions for F1, select “On” from the Release all
latches drop-down menu.

Figure 8 - Function buttons view

After this, pressing the F1 button on the relay's front panel releases all
latches.

NOTE: The latch release signal can be activated only if the latched
output is active.

6.9 Controlling an object with selective control


Prerequisite: You have logged in with the correct password and enabled selective
control in the Objects setting view.

When selective control is enabled, the control operation needs confirmation


(select before operate).

20 P3X_EN_QS_IEC+07
6 Front panel P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

• Press to close an object.

– Press again to confirm.

– Press to cancel.
• Press to open an object.

– Press again to confirm.

– Press to cancel.

6.10 Controlling an object with direct control


Prerequisite: You have logged in with the correct password and enabled direct
control in the Objects setting view.

When direct control is enabled, the control operation is done without confirmation.
• Press to close an object.
• Press to open an object.

6.11 Menus
This section gives an overview of the menus that you can access via the device's
front panel.

The main menu

Press the right arrow to access more measurements in the main menu.

Table 2 - Main menu

Menu name Description

Active LEDs User-configurable texts for active LEDs

Measurements User-configurable measurements

Single line Single line or Single line mimic,


measurements and control view. This is a
default start view. To return to this view
from any location, press the HOME/
CANCELL button for at least 3 seconds.

Info Information about the relay: relay's name,


order code, date, time and firmware version

P Power: power factor and frequency values


calculated by the relay. Press the right
arrow to view more measurements.

P3X_EN_QS_IEC+07 21
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 6 Front panel

Menu name Description

E Energy: the amount of energy that has


passed through the protected line,
calculated by the relay from the currents
and voltages. Press the right arrow to view
more energy measurements.

I Current: phase currents and demand


values of phase currents. Press the right
arrow to view more current measurements.

U Line-to-line voltages. Press the right arrow


to view other voltage measurements.

Dema Minimum and maximum phase current and


power demand values

Umax Minimum and maximum values of voltage


and frequency

Imax Minimum and maximum current values

Pmax Minimum and maximum power values

Month Monthly maximum current and power


values

FL Short-circuit locator applied to incomer or


feeder

Evnt Event log: event codes and time stamps

DR Disturbance recorder configuration settings

Runh Running hour counter

TIMR Timers: programmable timers that you can


use to preset functions

DI Digital input statuses and settings

DO Digital output statuses and settings

Arc Arc flash detection settings

Prot Protection: settings and statuses for various


protection functions

I>, I>>, etc. Protection stage settings and statuses. The


availability of the menus are depends on
the activated protection stages.

AR Auto-reclosure settings, statuses and


registers

22 P3X_EN_QS_IEC+07
6 Front panel P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

Menu name Description

OBJ Objects: settings related to object status


data and object control (open/closed)

Lgic Logic events and counters

CONF General device setup: CT and VT scalings,


frequency adaptation, units, device info,
date, time, clock, etc.

Bus Communication port settings

Slot Slot info: card ID (CID) that is the name of


the card used by the relay firmware

Diag Diagnosis: various diagnostic information

6.11.1 Moving in the menus

Figure 9 - Moving in menus using the front panel

Main menu Submenus

Prot protection enabling

OK

ISTART setting

OK OK

• To move in the main menu, press or .


• To move in the submenus, press or .
• While in the submenu, press or to jump to the root.
• To enter a submenu, press and use or for moving down or up
in the menu.
• To edit a parameter value, press and .
• Enter the password, and press .
• To go back to the previous menu, press .
• To go back to the first menu item in the main menu, press for at least three
seconds.

NOTE: To enter the parameter edit mode, enter the password. When the
value is in edit mode, its background is dark.

P3X_EN_QS_IEC+07 23
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 6 Front panel

6.11.2 Local panel messages

Table 3 - Local panel messages


Value is not editable: The value can not be edited or password is
not given

Control disabled: Object control disabled due to wrong


operating level

Change causes autoboot: Notification that if the parameter is changed


the relay boots itself

24 P3X_EN_QS_IEC+07
7 Easergy Pro setting and configuration tool P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

7 Easergy Pro setting and configuration tool


DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC
FLASH

Only qualified personnel should operate this equipment.


Such work should be performed only after reading this
entire set of instructions and checking the technical
characteristics of the device.

Failure to follow this instruction will result in death or


serious injury.

Easergy Pro is a software tool for configuring Easergy P3 relays. It has a


graphical interface where the relay settings and parameters are grouped under
seven tabs:

• General
• Measurements
• Inputs/outputs
• Protection
• Matrix
• Logs
• Communication

The contents of the tabs depend on the relay type and the selected application
mode.

Easergy Pro stores the relay configuration in a setting file. The configuration of
one physical relay is saved in one setting file. The configurations can be printed
out and saved for later use.

For more information, see the Easergy Pro user manual.

NOTE: Download the latest version of the software from se.com/ww/en/


product-range-download/64884-easergy-p3-protection-relays.

NOTICE
HAZARD OF EQUIPMENT DAMAGE

After writing new settings or configurations to a device, perform a test to verify


that the relay operates correctly with the new settings.

Failure to follow these instructions can result in unwanted shutdown of


the electrical installation.

P3X_EN_QS_IEC+07 25
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 8 Access to device configuration

8 Access to device configuration


You can access the device configuration via:
• the Easergy Pro setting tool
• the device’s front panel

NOTE: There is a timeout mechanism for Telnet/Serial/Http connections.


When logging on via the front panel or web HMI, you are automatically logged
out after 15 minutes inactivity.

8.1 User accounts


By default, the Easergy P3 device has five user accounts.

Table 4 - User accounts

User account User name Default Use


password

User user 0 Used for reading parameter


values, measurements, and
events, for example

Operator operator 1 Used for controlling objects and


for changing the protection stages’
settings, for example

Configurator conf 2 Needed during the device


commissioning. For example, the
scaling of the voltage and current
transformers can be set only with
this user account. Also used for
logging on to the HTTP and FTP
server.

8.2 Logging on via the front panel


NOTE: To log on via the front panel, you need a password that consists of
letters, digits, or other characters in the scope of ASCII 0x21~0x7E.

1. Press and on the front panel. The Enter password view opens.

Figure 10 - Enter password view

2. Enter the password for the desired access level.

26 P3X_EN_QS_IEC+07
8 Access to device configuration P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

Select a digit value using , and if the password is longer than one digit,
move to the next digit position using .

NOTE: There are 16 digit positions in the Enter password view. Enter the
password starting from the first digit position.

For example, if the password is 2, you can enter 2***, **2*, ***2, or 0002
to log on.

3. Press to confirm the password.

Related topics
8.4 Password management

8.3 HTTP and FTP logon details


You can log on to the HTTP server and FTP using these user names and
passwords.

Table 5 - HTTP and FTP logon details

Protocol User name Password

HTTP conf 2

FTP conf 2

8.4 Password management

NOTICE
CYBERSECURITY HAZARD
To improve cybersecurity:
• Change all passwords from their default values when taking the protection
device into use.
• Change all passwords regularly.
• Ensure a minimum level of password complexity according to common
password guidelines.

Failure to follow these instructions can increase the risk of unauthorized


access.

You can change the password for the operator or configurator user accounts in
the General > Device info setting view in Easergy Pro.

The password can contain letters, digits or other characters in the scope of ASCII
0x21~0x7E. However, the new password cannot be any of the default passwords
(digits 0–4 or 9999).

Follow these guidelines to improve the password complexity and thus device
security:
• Use a password of minimum 8 characters.
• Use alphabetic (uppercase and lowercase) and numeric characters in addition
to symbols.

P3X_EN_QS_IEC+07 27
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 8 Access to device configuration

• Avoid character repetition, number or letter sequences and keyboard patterns.


• Do not use any personal information, such as birthday, name, etc.
• Do not use the same password for different user accounts.
• Do not reuse old passwords.

Also, all users must be aware of the best practices concerning passwords
including:
• not sharing personal passwords
• not displaying passwords during password entry
• not transmitting passwords in email or by other means
• not saving the passwords on PCs or other devices
• no written passwords on any supports
• regularly reminding users about the best practices concerning passwords

Related topics
8.2 Logging on via the front panel

8.5 Password restoring


If you have lost or forgotten all passwords, contact Schneider Electric to restore
the default passwords.

28 P3X_EN_QS_IEC+07
9 Local port P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

9 Local port
The relay has a USB port in the front panel.

Protocol for the USB port

The front panel USB type B port is always using the command line protocol for
Easergy Pro.
The speed of the interface is defined in the CONF/DEVICE SETUP menu via the
front panel. The default settings for the relay are 38400/8N1.

It is possible to change the front USB port's bit rate. This setting is visible only on
the relay's local display. The bit rate can be set between 1200 and 187500. This
changes the bit rate of the relay, and the Easergy Pro bit rate has to be set
separately. If the bit rate in the setting tool is incorrect, it takes a longer time to
establish the communication.

NOTE: Use the same bit rate in the relay and the Easergy Pro setting tool.

P3X_EN_QS_IEC+07 29
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 10 Block diagrams

10 Block diagrams
The status of the output contacts is shown when the relay is energized but none
of the protection, controlling or self-supervision elements are activated.

Figure 11 - Typical block diagram for P3F30, P3M30 and P3G30 relays

~ 1/C/1:20 T12
N -/~ 1/C/1:1
1/C/1:19 T12

P3M30-CGGAA-DAENA-BAAAA
L +/~ 1/C/1:2 = 1/C/1:18 T11

G
F
1/C/1:17 T11
8/E/1:1 8/1/1:1 1/C/1:16 T10
IL1 5/1A 1/C/1:15 T10
8/E/1:2 8/1/1:2
8/E/1:4 8/1/1:4 1/C/1:14 T9
IL2 5/1A 1/C/1:13 T9
8/E/1:3 8/1/1:3
8/E/1:6 8/1/1:6 1/C/1:12 T1
IL3 5/1A 1/C/1:11 T1
8/E/1:5 8/1/1:5
1/C/1:10 A1 NO
8/E/1:8 8/1/1:8 I01 5A 1/C/1:9 A1 NC
8/E/1:9 8/1/1:9 1/C/1:8 A1 COM
I01 1A
8/E/1:7 8/1/1:7 1/C/1:7 SF NC
1/C/1:6 SF NO
8/E/1:11
8/E/1:10
8/1/1:11
8/1/1:10
I02 1A
1 1/C/1:5 SF COM
I02 0.2A
8/E/1:12 8/1/1:12
8/E/2:2 8/1/1:12
U1
8/E/2:1 8/1/2:1
8/E/2:4 8/1/2:4
U2 2/G/1:13
8/E/2:3 8/1/2:3 T13
2/G/1:14
8/E/2:6 8/1/2:6
U3 2/G/1:15
8/E/2:5 8/1/2:5 T14
2/G/1:16
8/E/2:8 8/1/2:8
U4 2/G/1:17
8/E/2:7 8/1/2:7 T15
2/G/1:18
2/G/1:19
DI6 2/G/1:12 DI T16
DI6 2/G/1:11 2/G/1:20
DI5 2/G/1:10
DI5 2/G/1:9
DI4 2/G/1:8
DI4 2/G/1:7 3/G/1:13
T17
DI3 2/G/1:6 3/G/1:14
DI3 2/G/1:5 3/G/1:15
T18
DI2 2/G/1:4 3/G/1:16
DI2 2/G/1:3 3/G/1:17
DI1 2/G/1:2 T19
3/G/1:18
DI1 2/G/1:1
3/G/1:19
T20
3/G/1:20
DI12 3/G/1:12 DI
DI12 3/G/1:11
DI11 3/G/1:10
DI11 3/G/1:9
DI10 3/G/1:8
DI10 3/G/1:7
DI9 3/G/1:6 9/N/1 Eth RJ45
DI9 3/G/1:5
DI8 3/G/1:4
DI8 3/G/1:3 9/N/2 Eth RJ45
DI7 3/G/1:2
DI7 3/G/1:1

S6 - 6/D/1:8 L>
S6 + 6/D/1:7
S5 - 6/D/1:6
S5 + 6/D/1:5
S4 - 6/D/1:4
S4 + 6/D/1:3
S3 - 6/D/1:2
S3 + 6/D/1:1

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.

30 P3X_EN_QS_IEC+07
10 Block diagrams P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

Figure 12 - P3F30 and P3M30 block diagram – LPIT

~ 1/C/1:20 T12
N -/~ 1/C/1:1
1/C/1:19 T12

P3M30-CGGAA-DAMNA-BAAAA
L +/~ 1/C/1:2 = 1/C/1:18 T11

G
F
1/C/1:17 T11
LPCT 1/C/1:16 T10
IL1 RJ45 1/C/1:15 T10
IL2 RJ45 1/C/1:14 T9
IL3 RJ45 1/C/1:13 T9
LPVT 1/C/1:12 T1
HUB1 U1, U2, U3
1/C/1:11 T1
1/C/1:10 A1 NO
HUB2 U4, U5 1/C/1:9 A1 NC
1/C/1:8 A1 COM
8/M/1:1 8/M/1:1 I 1/C/1:7 SF NC
01 5A 1/C/1:6 SF NO
8/M/1:2 8/M/1:2 1/C/1:5 SF COM
I01 1A
8/M/1:3 8/M/1:3
8/M/1:4 8/M/1:4 I 1A
02
8/M/1:5 8/M/1:5
I02 0.2A
8/M/1:6 8/M/1:6

2/G/1:13
T13
2/G/1:14
2/G/1:15
T14
2/G/1:16
2/G/1:17
T15
2/G/1:18
2/G/1:19
DI6 2/G/1:12 DI T16
DI6 2/G/1:11 2/G/1:20
DI5 2/G/1:10
DI5 2/G/1:9
DI4 2/G/1:8
DI4 2/G/1:7 3/G/1:13
T17
DI3 2/G/1:6 3/G/1:14
DI3 2/G/1:5 3/G/1:15
T18
DI2 2/G/1:4 3/G/1:16
DI2 2/G/1:3 3/G/1:17
DI1 2/G/1:2 T19
3/G/1:18
DI1 2/G/1:1
3/G/1:19
T20
3/G/1:20
DI12 3/G/1:12 DI
DI12 3/G/1:11
DI11 3/G/1:10
DI11 3/G/1:9
DI10 3/G/1:8
DI10 3/G/1:7
DI9 3/G/1:6 9/N/1 Eth RJ45
DI9 3/G/1:5
DI8 3/G/1:4
DI8 3/G/1:3 9/N/2 Eth RJ45
DI7 3/G/1:2
DI7 3/G/1:1

S6 - 6/D/1:8 L>
S6 + 6/D/1:7
S5 - 6/D/1:6
S5 + 6/D/1:5
S4 - 6/D/1:4
S4 + 6/D/1:3
S3 - 6/D/1:2
S3 + 6/D/1:1

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.

P3X_EN_QS_IEC+07 31
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 10 Block diagrams

Figure 13 - Typical block diagram for P3L30 relay

~ 1/C/1:20 T12
N -/~ 1/C/1:1
1/C/1:19 T12

P3L30-CGGAA-SAENA-BA
L +/~ 1/C/1:2 = 1/C/1:18 T11
1/C/1:17 T11
1/C/1:16 T10
1/C/1:15 T10
1/C/1:14 T9
1/C/1:13 T9
1/C/1:12 T1
1/C/1:11 T1
1/C/1:10 A1 NO
1/C/1:9 A1 NC
1/C/1:8 A1 COM
8/E/1:1
IL1 5/1A 1/C/1:7 SF NC
8/E/1:2 1/C/1:6 SF NO
1/C/1:5 SF COM
8/E/1:3
IL2 5/1A
8/E/1:4
8/E/1:5
IL3 5/1A
8/E/1:6
8/E/1:7
I01 5A
8/E/1:8
I01 1A 2/G/1:13
8/E/1:9 T13
2/G/1:14
8/E/1:10 I02 1A
8/E/1:11 2/G/1:15
I02 0.2A T14
2/G/1:16
8/E/1:12
2/G/1:17
8/E/2:1 T15
U1 2/G/1:18
8/E/2:2
8/E/2:3 2/G/1:19
U2 T16
8/E/2:4 2/G/1:20
8/E/2:5
U3
8/E/2:6
8/E/2:7 3/G/1:13
U4 T17
8/E/2:8 3/G/1:14
3/G/1:15
T18
3/G/1:16
DI6 2/G/1:12 DI 3/G/1:17
DI6 2/G/1:11 T19
DI5 2/G/1:10 3/G/1:18
DI5 2/G/1:9 3/G/1:19 T20
DI4 2/G/1:8 3/G/1:20
DI4 2/G/1:7
DI3 2/G/1:6
DI3 2/G/1:5
DI2 2/G/1:4
DI2 2/G/1:3
DI1 2/G/1:2 6/S Line diff.
DI1 2/G/1:1 pilot

DI12 3/G/1:12 DI
DI12 3/G/1:11
DI11 3/G/1:10
DI11 3/G/1:9 9/N/1 Eth RJ45
DI10 3/G/1:8
DI10 3/G/1:7 9/N/2 Eth RJ45
DI9 3/G/1:6
DI9 3/G/1:5
DI8 3/G/1:4
DI8 3/G/1:3
DI7 3/G/1:2
DI7 3/G/1:1

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.

32 P3X_EN_QS_IEC+07
10 Block diagrams P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

Figure 14 - Typical block diagram for P3M32, P3T32 and P3G32 relays

N -/~ 1/C/1:1 ~ 1/C/1:20 T12


1/C/1:19 T12
L +/~ 1/C/1:2 = 1/C/1:18 T11
1/C/1:17 T11

P3T32-CGITA-AAENA-BAAAA
1/C/1:16 T10

M
G
DI1 2/G/1:1 1/C/1:15 T10
DI
DI1 2/G/1:2 1/C/1:14 T9
DI2 2/G/1:3 1/C/1:13 T9
DI2 2/G/1:4 1/C/1:12 T1
DI3 2/G/1:5
1/C/1:11 T1
DI3 2/G/1:6
1/C/1:10 A1 NO

1
DI4 2/G/1:7 1/C/1:9 A1 NC
DI4 2/G/1:8 1/C/1:8 A1 COM
DI5 2/G/1:9 1/C/1:7 SF NC
DI5 2/G/1:10 1/C/1:6 SF NO
DI6 2/G/1:11 1/C/1:5 SF COM

1
DI6 2/G/1:12

DI7 3/I/1:1 DI 2/G/1:13 T13


DI7 3/I/1:2 2/G/1:14 T13
DI8 3/I/1:3 2/G/1:15 T14
DI8 3/I/1:4
2/G/1:16 T14
DI9 3/I/1:5
3/I/1:6 2/G/1:17 T15
DI9
DI10 3/I/1:7 2/G/1:18 T15
DI10 3/I/1:8 2/G/1:19 T16
DI11 3/I/1:9 2/G/1:20 T16
DI11 3/I/1:10
DI12 3/I/1:11
DI12 3/I/1:12
DI13 3/I/1:13
DI13 3/I/1:14
DI14 3/I/1:15
DI14 3/I/1:16
DI15 3/I/1:17
DI15 3/I/1:18
DI16 3/I/1:19
DI16 3/I/1:20

IL1 (S1) 8/E/1:1 8/1/1:1


IL1 5A
IL1 (S2) 8/E/1:2 8/1/1:2
IL2 (S1) 8/E/1:3 8/1/1:3
IL2 5A
IL2 (S2) 8/E/1:4 8/1/1:4
IL3 (S1) 8/E/1:5 8/1/1:5
IL3 5A
IL3 (S2) 8/E/1:6 8/1/1:6
Io1 (S1) 8/E/1:7 8/1/1:7 I0 5A
Io1 (S2) 8/E/1:8 8/1/1:8
I0 1A
Io1 (S2) 8/E/1:9 8/1/1:9
Io2 (S1) 8/E/1:10 8/1/1:10 I0 1A
Io2 (S2) 8/E/1:11 8/1/1:11
I0 0.2A
Io2 (S2) 8/E/1:12 8/1/1:12
ULL/ULN 8/E/2:1 8/1/2:1
U1
ULL/ULN 8/E/2:2 8/1/2:2
ULL/ULN 8/E/2:3 8/1/2:3
U2
ULL/ULN 8/E/2:4 8/1/2:4
Uo/ULL/ULN 8/E/2:5 8/1/2:5
U3
Uo/ULN/ULL 8/E/2:6 8/1/2:6
Uo/ULN/ULL 8/E/2:7 8/1/2:7 U4
Uo/ULN/ULL 8/E/2:8 8/1/2:8

IꞌL1 (S1) 4/T/1:1 4/1/1:1 5A


IꞌL1 (S2) 4/T/1:2 4/1/1:2 1A
IꞌL1 (S2) 4/T/1:3 4/1/1:3
IꞌL2 (S1) 4/T/1:4 4/1/1:4 5A
IꞌL2 (S2) 4/T/1:5 4/1/1:5
1A
IꞌL2 (S2) 4/T/1:6 4/1/1:6 9/N/1 Eth1
IꞌL3 (S1) 4/T/1:7 4/1/1:7
5A 9/N/2 Eth2
IꞌL3 (S2) 4/T/1:8 4/1/1:8
IꞌL3 (S2) 1A
4/T/1:9 4/1/1:9

Io3 (S1) 4/T/1:10 4/1/1:10 5A


Io3 (S2) 4/T/1:11 4/1/1:11
1A
Io3 (S2) 4/T/1:12 4/1/1:12

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.

P3X_EN_QS_IEC+07 33
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 11 Mounting

11 Mounting
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Wear your personal protective equipment (PPE) and comply with the safe
electrical work practices. For clothing refer applicable local standards.
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and checking
the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing relay to ensure that all power
is off.
• Do not open the secondary circuit of a live current transformer.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.

Failure to follow this instruction will result in death or serious injury.

CAUTION
HAZARD OF CUTS

Trim the edges of the cut-out plates to remove any jagged edges.
Use protective gloves when moving and mounting the device.

Failure to follow these instructions can result in injury.

34 P3X_EN_QS_IEC+07
11 Mounting P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

Panel mounting

Figure 15 - Panel mounting

mm
225
1 8.86
in 2

erg y
Eas erg y
Eas

Eas erg y
152
5.98

1.0
0.0-60
4-2
.3 6

T max. 1.2 N•m T max. 0.5-0.6 N•m


3b 3c 10.6 lb-in 4.4-5.3 lb-in

2.5 N•m 3 N•m


22 lb-in 27 lb-in

3 4
3a
3a
erg yerg y
EasEas

min. 2.5mm2
Ø 5-8mm

CLICK !
Nut M5
1.5Nm, 13.3 Ib in

mm 208 253.40
in 264 9.97 24.60
8.18 0.97
10.37 223.33
183 9.17
Easergy 7.20

153
6.02
177 150
6.97 5.91 183
7.20

The conventional mounting technique has always been installing the relay on the
secondary compartment's door. A limitation of this approach could be that the
door construction is not strong enough for the relay's weight and wiring a large
amount of secondary and communication cabling could be challenging.

P3X_EN_QS_IEC+07 35
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 11 Mounting

Panel mounting with detachable display

Figure 16 - Panel mounting with detachable display

mm 247
in 9.72
180 199
7.09 7.81

Ease rgy
199
7.83 150
180 5.91
7.09

29 264
1.12 10.37

1 210
Easergy

8.27
Ø5 177
0.2 6.97

M4x20
mm Torx T-20
in 1.5Nm
100
3.94
2
18
0.71

11.5
0.45
20 34
0.79 1.34 Eas erg y

T max. 1.2Nm T max. 0.5...0.6Nm


10.6 lb.in 4.4...5.3 lb.in

3
180
7.09

Ø7
0.28

min. 2.5mm2
Ø 5-8mm

180
7.09
Nut M5
1.5 Nm, 13.3 Ib in

This mounting technique allows the door to be lighter as the relay's frame is
installed on the back of the secondary compartment. Normally, the relay is
mounted by the terminal blocks, hence the secondary wiring is short.
Communication cabling is easier, too, as the door movement does not need to be
considered. In this case, only the communication between relay base and display
have to be wired.

36 P3X_EN_QS_IEC+07
11 Mounting P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

Projection mounting

Figure 17 - Projection mounting

225
mm
1 2 8.86
in

Eas erg y

Easerg y

152
5.98

1.0
0.0-60
4-2
.36

T max. 1.2Nm T max. 0.5...0.6Nm


3b 3c 10.6 lb.in 4.4...5.3 lb.in

2.5Nm 3Nm
22 lb.in 27 lb.in

3 4

3a y y
ergerg
EasEas

Vamp 300
3a min. 2.5mm2
Ø 5-8mm ON

OK

F2

F1

I O

Nut M5
1.5Nm, 13.3 Ib in
CLICK !

mm 269
in 264 208 10.59
10.37 8.18 45
224
183 1.77
8.82
Easergy 7.20
Vamp 300

ON
152
5.98
177 150 177
6.97 5.91
OK 7.0
F1 F2
I O

If the depth dimension behind the compartment door is limited, the relay can be
equipped with a frame around the collar. This arrangement reduces the depth
inside the compartment by 45 mm.

P3X_EN_QS_IEC+07 37
P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32 11 Mounting

Example of the P3 alarm facial label insertion

A B
C D
E F

1
G H
I J
K L
M N

F1 F2

A B
C D
E F
G H
I J
K L
M N

F1 F2

A B
C D

3 E
G
I
K
M
F
H
J
L
N

F1 F2

See "P3 Advanced Series facial label instruction" document for more information.

Protective film

NOTICE
RISK OF DESTRUCTION OF THE RELAY

The protective film on the relay's display is plastic and can melt if exposed to
high temperatures intensive sunlight. Remove the protective film after mounting
the relay.
Failure to follow these instructions can result in equipment damage.

38 P3X_EN_QS_IEC+07
12 Related documents P3F30, P3L30, P3T32, P3M30, P3M32, P3G30, P3G32

12 Related documents
Table 6 - Related documents

Document Identification3)

P3 Advanced User Manual P3x/EN M/xxxx

Easergy Pro Setting and Configuration Tool P3eSetup/EN M/xxxx


User Manual

P3 Advanced Series facia label instruction P3TDS17012EN

Principles of numerical protection P3INS17019EN


techniques
3) xxxx = revision number

P3X_EN_QS_IEC+07 39
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison - France
Phone: +33 (0) 1 41 29 70 00
www.schneider-electric.com

As standards, specifications, and designs change from time to time,


please ask for confirmation of the information given in this publication.

© 2022 Schneider Electric All Rights Reserved.

P3X_EN_QS_IEC+07 — 02/2022