Proper Corona Protection Using E-Field Modeling
Proper Corona Protection Using E-Field Modeling
Español | 中文
RHM International
USA
Related Articles
Lightning Performance of
Distribution Lines
Privacy - Terms
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 1/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 2/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
Klöckner Desma
Elastomertechnik
GmbH
Germany
PFISTERER
Germany
• The brace and line post insulators are connected using a hot line
fitting, which is unique to this design. (Note: For this case study, this
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 3/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
hotline fitting was not changed since the focus was on addition of
corona rings, for easier upgrades of existing applications).
Objective
Performance Criteria
• Limit of E-field stress on end fittings and grading rings: 2.0 kV/mm
Note: Results and conclusions for the proposed 138 kV braced post models are specific
to defined phase-to-ground clearance, as defined by the customer. The tighter the
phase spacing, the higher the E-field stresses can become.
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 4/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
Stresses on the line post insulator are different than on the brace
insulator. Since the brace, or suspension, insulator has stacked sheds,
the sheath is protected from higher electrical stresses at the line end
even without a corona ring. Moreover, the larger corona ball feature
on the brace end fitting further helps reduce amount of stress on the
sheath.
This case study will identify the E-field stresses for 3 different braced
post configurations in order to determine the ideal corona ring
applications for 138 kV braced post design.
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 5/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
Brace Insulator
The average stress on the end fitting is high, with a max stress above
the industry performance limit 2.0 kV/mm. Though this initially
appears to be a concern, the stress is on the corona ball away from
the silicone rubber; the presence of the stacked sheds minimize the
impact this stress could have on the sheath. Therefore, there is no
concern for premature aging of the sheath on this brace insulator.
• Average Stress on the End fitting = 1.95 kV/mm [Max Stress = 2.11
kV/mm]
• Average Stress on the Sheath Surface = < 0.17 kV/mm (measured
beyond shed #3)
• No exposed sheath between shed #3 and end fitting.
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 6/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
In general, the stresses are lower on the post than on the brace
insulator above. The average stress on the end fitting is not an
immediate issue. Since the stresses on the sheath are at the
threshold value, there is concern of premature ageing of the sheath
between shed #1 and the end fitting.
• Average stress on end fitting = 0.77 kV/mm [max stress = 0.94
kV/mm]
• Average stress on sheath surface (EF & shed #1) = 0.46kV/mm [max
stress = 0.49 kV/mm]
• Stress on sheath surface (sheds #1 & #2) = < 0.16 kV/mm
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 7/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 8/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
Brace Insulator
Addition of the 8” corona ring on this insulator corrects the high
stresses on the end fitting, resulting in a brace insulator that is fully
compliant with industry limits.
• Average stress on end fitting = 0.47 kV/mm [down from 1.95 kV/mm]
• Average stress on corona ring surface = 0.99 kV/mm
• Average stress on sheath surface = < 0.17 kV/mm
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 9/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 10/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 11/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
Brace Insulator
Addition of 8” corona ring on this insulator corrects the high stresses
on end fitting, resulting in a brace insulator that is fully compliant with
industry limits.
• Average stress on end fitting = 0.37 kV/mm [down from 0.47 kV/mm
in model #2]
• Average stress on sheath surface = < 0.2 kV/mm
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 12/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 13/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 14/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
Fig. 12: Braced post stress plot w/CR on both brace & line post.
EDP
Labelec
Portugal
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 15/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
Conclusions
Historically, the corrective action for this 138 kV braced post case
example may have been to just add the 8” corona ring onto the brace
insulator, which does improve performance of the braced post
assembly. However, upon reviewing E-field results in the tables
below, even with the corona ring on the brace, the line post is still
potentially vulnerable to stresses at point 4 on the sheath at the end
fitting connection point.
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 16/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
Appendix A:
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 17/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
Appendix B:
Appendix C:
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 18/19
8/24/24, 11:45 AM Proper Corona Protection Using E-Field Modeling -
Full Name
Copyright © 1993 - 2024 Zimmar Holdings
Ltd./INMR.
Your Email Address Contents are protected by international
copyrights and treaties. Reproduction in whole or
Subscribe in part, without express written permission, is
prohibited. While every effort is made to verify
the data and information contained,
INMR BUYERS GUIDE | INMR LABORATORY GUIDE INMR/Zimmar Holdings Ltd. accepts no liability,
| INMR WORLD CONGRESS direct or implied, for the accuracy of all
information presented.
https://www.inmr.com/selecting-proper-corona-protection-using-field-modeling/ 19/19