MFM383A-C

The document provides operating instructions for the MFM383A and MFM383A-C models, including order code information, safety precautions, mechanical installation guidelines, and specifications. It details electrical parameters, wiring input, communication protocols, and maintenance requirements. Additionally, it outlines installation guidelines and environmental conditions for optimal usage of the equipment.

Uploaded by

Hung Cuong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
23 views

MFM383A-C

The document provides operating instructions for the MFM383A and MFM383A-C models, including order code information, safety precautions, mechanical installation guidelines, and specifications. It details electrical parameters, wiring input, communication protocols, and maintenance requirements. Additionally, it outlines installation guidelines and environmental conditions for optimal usage of the equipment.

Uploaded by

Hung Cuong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

MFM383A / MFM383A-C ORDER CODE INFORMATION SAFETY PRECAUTIONS MECHANICAL INSTALLATION

selec Operating Instructions Product Supply Certification


All safety related codifications, symbols and
instructions that appear in this operating manual or on
For installing the meter
1. Prepare the panel cutout with proper dimensions as shown
OP354-V04

LISTED
the equipment must be strictly followed to ensure the below.
100 to 240V AC, safety of the operating personnel as well as the 2. Push the meter into the panel cutout. Secure the meter in
MFM383A
-15% +12%, 50 / 60Hz (±5%)
instrument. its place by fitting the clamp on the rear side. Fit clamps on
100 to 240V AC, If the equipment is not used in a manner specified by both sides in diagonally opposite location for optimum
MFM383A-CU
-15% +12%, 50 / 60Hz (±5%) the manufacturer it might impair the protection provided fitting.
100 to 240V AC, by the equipment. 3. For proper sealing, tighten the screws evenly with required
MFM383A-C Do not use the equipment if there is any mechanical torque.
-15% +12%, 50 / 60Hz (±5%)
DC : 18 to 42V ;
damage. Terminal screw tightening torque :
MFM383A-24V /
MFM383A-C-24V AC : 18 to 28V, 50 / 60Hz Ensure that the equipment is supplied with correct 0.68 N-m to 0.79 N-m ( 6.018 In-Lb to 6.992 In-Lb )
voltage. Screw clamp tightening torque : 0.1N-m (0.885 Lb-inch)
96 x 96 Installation Category II
CAUTION : OUTLINE PANEL CUTOUT
SPECIFICATIONS 1. Read complete instructions prior to installation and Dimensions (in mm) Dimensions (in mm)
SERIAL COMMUNICATION [ Applicable for MFM383A-C ]
operation of the unit.
DISPLAY Interface standard 2. Risk of electric shock.
Liquid crystal display with backlight and protocol RS485 and MODBUS RTU
3. The equipment in its installed state must not come in

91.5
90.5
3 lines, 4 digits per line to show electrical Parameters close proximity to any heating sources, oils, steam, 99
Dedicated 7½ digit show energy Communication
1 to 255 caustic vapors or other unwanted process by products.
WIRING INPUT address
3 Ø - 4 wire, 3 Ø - 3 wire, 2 Ø - 3 wire and 99 50 91.5
Transmission WIRING GUIDELINES 5
1 Ø - 2 wire system Half duplex
mode
RATED INPUT VOLTAGE WARNING : MAINTENANCE
11 to 300V AC (L-N) ; 19 to 519V AC (L-L) ; Data types Float and Integer
1. To prevent the risk of electric shock, power supply to the 1. The equipment should be cleaned regularly to avoid
Installation Category III (600V)
Transmission equipment must be kept OFF while doing the wiring blockage of ventilating parts.
UL Approval :
distance 500m maximum arrangement. 2. Clean the equipment with a clean dry or damp cloth.
11 to 277V AC (L-N) ; 19 to 480V AC (L-L) ;
2. Wiring shall be done strictly according to the terminal Do not use any cleaning agent other than water.
Installation Category III (600V) Transmission 300, 600,1200, 2400, 4800,
FREQUENCY RANGE layout. Confirm that all connections are correct.
speed 9600,19200 (in bps) 3. Use lugged terminals.
45-65Hz TERMINAL CONNECTIONS
4. To reduce electromagnetic interference use of wires
RATED INPUT CURRENT Parity None, Odd, Even with adequate ratings and twists of the same in equal
Nominal 5A AC (Min-11mA, Max-6A) MFM383A / MFM383A-C
Stop bits 1 or 2 size shall be made with shortest connections.
BURDEN
5. Layout of connecting cables shall be away from any
0.5 VA@5A per phase
N
L
100 ms internal EMI source. Valid for
CT PRIMARY Response time communication
(max and independent of baud rate) 6. Cable used for connection to power source, must have a

+
1A / 5A to 10,000A(Programmable for any Value) PULSE O/P RS485 model only
cross section of 0.5mm2 to 2.5mm2 ( 20 to 14AWG ; 750C
Note : 1A to 10,000A if CT secondary is 1 else (minimum)).Thesewires shall have current carrying
CT primary is 5A to 10,000A ACCURACY : capacity of 6A.
CT SECONDARY 7. Copper cable should be used ( Stranded or Single core CONNECTIONS DIAGRAM
1A or 5A (programmable) Measurement Accuracy
cable ).
PT PRIMARY 8. Before attempting work on device, ensure absence of L1 L
Voltage VL-N ±0.5%
100V to 10,000V (Programmable for any value) voltages using appropriate voltage detection device. L2 O
PT SECONDARY Voltage VL-L ±0.5% L3 A
N D
100 to 500V AC (L-L)(Programmable for any value)
Current ±0.5% INSTALLATION GUIDELINES
DISPLAY UPDATE TIME S1 S2 S1 S2 S1 S2 N V1 V2 V3
I1 I2 I3
1sec. for all parameters ±0.1% CAUTION :
DISPLAY SCROLLING Frequency For L-N Voltage >20V , 1. This equipment, being built-in-type, normally becomes MFM383A-24V / MFM383A-C-24V
Automatic or Manual (Programmable) For L-L Voltage >35V a part of main control panel and in such case the
POWER CONSUMPTION
terminals do not remain accessible to the end user after
MFM383A / MFM383A-C : Less than 8VA Active Power 1%
installation and internal wiring. Valid for
MFM383A-24V / MFM383A-C-24V : Less than 4VA communication

+
Apparent power 1% 2. Conductors must not come in contact with the internal model only
ENVIRONMENTAL CONDITIONS PULSE O/P RS485
circuitry of the equipment or else it may lead to a safety
- Indoor use Reactive Power 1% hazard that may in turn endanger life or cause electrical
- Altitude of up to 2000 meters shock to the operator.
- Pollution degree II Power factor 1%
O 3. Circuit breaker or mains switch must be installed CONNECTIONS DIAGRAM
Temperature : Operating : -10 to 55 C Active energy Class 1 between power source and supply terminals to facilitate
O
Storage : -20 to 75 C power 'ON' or ‘OFF’ function. However this switch or L1 L
Humidity : Up to 85% RH, non-condensing breaker must be installed in a convenient position
L2 O

PROTECTION CLASS : II RESOLUTION : normally accessible to the operator.


L3 A
N D
MOUNTING 4. Before disconnecting the secondary of the external
Panel mounting PT Ratio x CT Ratio kWh Pulse
current transformer from the equipment, make sure that S1
I1
S2 S1
I2
S2 S1
I3
S2 N V1 V2 V3
WEIGHT <150 0.1K 0.1K the current transformer is short circuited to avoid risk of
MFM383A : 310gms ; MFM383A-C : 344gms electrical shock and injury.
MFM383A-24V : 295gms ; MFM383A-C-24V : 320gms 150 1K 1K 5. The equipment shall not be installed in environmental
OUTPUT conditions other than those mentioned in this manual.
Pulse Output : Voltage range : External 24V DC max. NOTE : 1) For Voltage, Current and Power, resolution is
6. The equipment does not have a built-in-type fuse.
Current capacity : 100mA max. automatically adjusted
Installation of external fuse of rating 275V AC / 0.5Amp
Pulse Width : 100ms ±5ms. 2) For power factor, resolution is 0.001
for electrical circuitry / battery is highly recommended.
Doc. name : OP INST MFM383A / MFM383A-C OP354-V04 (Page 1 of 4)
FRONT PANEL DESCRIPTION KEY PRESS ONLINE PAGE DESCRIPTION Config
Function
Range or Factory NETWORK SELECTION AND WIRING INPUT
page. Selection Setting
Press “P” The 8th screen : (Page 16) *7 Network selection
selec Slave Id 1 to 255 1 Wiring
MFM383A Displays active power, apparent power and in configuration mode
power factor of 2nd phase. 300, 600,1200,
V
The 9th screen : (Page 17) * 3P4W 3P4W, 2P3W, 1P2W
1
2 8 Baud Rate 2400, 4800, 9600
Displays active power, reactive power and 9600 and19200
A 3P3W 3P3W
2
3 power factor of 3rd phase. *9 Parity None, Even, Odd None
PF The 10th screen : (Page 18)
3
1
Displays active power, apparent power and *10 APPLICATION OF PULSE OUTPUT
Avg Stop Bit 1 or 2 1
power factor of 3rd phase.
PROCESS INTEGRATION
kWh
The 11th screen : (Page 19) 11 Back Light 0 to 7200 sec. 0000 24V DC
Displays total active power, reactive power maximum
and power factor of 3 phases. Max Page +
12 1 to 20 20
V VAF P The 12th screen : (Page 20) P
A/M PRG L
Displays total active power, apparent power 13 Change Sequence No / Yes No C
and power factor of 3 phases.
Note : For 3 Ø - 3 W system only the 11th 13.01 Page Sequence 1 1 to 20 1 #
ONLINE PAGE DESCRIPTION and 12th screen available.
There are 3 dedicated keys labelled as VI, VAF, P. 13.02 Page Sequence 2 1 to 20 2 +
Use these 3 keys to read meter parameters. Simply press AUTOMATIC / MANUAL MODE DESCRIPTION
13.03 Page Sequence 3 1 to 20 3
these keys to read the parameters. + +
N
L
Press ( ) key 3 sec. to toggle between Automatic and PULSE
O/P
RS485

KEY PRESS ONLINE PAGE DESCRIPTION Manual mode. 13.04 Page Sequence 4 1 to 20 4
Note : By default unit operates in automatic mode.
Press “VI” The 1st screen : (Page 1) In automatic mode online pages scroll automatically at 13.05 Page Sequence 5 1 to 20 5
MFM383A / MFM383A-C
Displays line to neutral voltage of 3 phases. the rate of 5 sec. per page.
The 2nd screen : (Page 2) In automatic mode when any key is pressed, unit 13.06 Page Sequence 6 1 to 20 6
Displays line to line voltage of 3 phases. temporarily switches to manual mode and the I1 I2 I3
The 3rd screen : (Page 3) 13.07 Page Sequence 7 1 to 20 7
appropriate page is displayed, also if any key is not S1 S2 S1 S2 S1 S2 N V1 V2 V3

Displays phase current of 3 phases. pressed for 5sec., unit resumes automatic mode.
Note : For 3 Ø 3 W system, only the 2nd and 13.08 Page Sequence 8 1 to 20 8
Pulse output from MFM383A meter can be interfaced
3rd screen available SERIAL NUMBER DESCRIPTION into a process through a PLC for on line control of
13.09 Page Sequence 9 1 to 20 9
Press The 1st screen : (Page 4) energy content in the process.
Press 4th key ( ) for 10sec. to display 8 digit serial
“VAF” Displays voltage, current of 1st phase and 13.10 Page Sequence 10 1 to 20 10 If the PLC has a self excited digital input, external DC
number on first and second row.
frequency. supply is not needed.
The 2nd screen : (Page 5) 13.11 Page Sequence 11 1 to 20 11 The kWh pulse is also used to derive average kWh
CONFIGURATION information at the PLC.
Displays voltage, current of 2nd phase and
frequency. There are 4 dedicated keys with symbols marked as 13.12 Page Sequence 12 1 to 20 12
, , , . Use these 4 keys to enter into ENERGY CONTROLLER
The 3rd screen : (Page 6)
configuration menu / change setting. 13.13 Page Sequence 13 1 to 20 13 12 / 24V DC
Displays voltage, current of 3rd phase and +
Note : The settings should be done by a professional,

COUNTER
frequency. Page Sequence 14 To
13.14 1 to 20 14

O/P
I/P
The 4th screen : (Page 7) after going through this users manual and after having Control
Displays average value of line to neutral understood the application situation. Circuit
13.15 Page Sequence 15 1 to 20 15 +
voltage, current of three phases and For the configuration setting mode : #
frequency. ! Use ( ) and ( ) keys for 3sec. to enter or exit from 13.16 Page Sequence 16 1 to 20 16
The 5th screen : (Page 8) configuration menu. +
Displays average value line to line voltage, Use ( ) and ( ) keys for increasing and decreasing 13.17 Page Sequence 17 1 to 20 17
current and Power factor of three phases. parameters value respectively. N
+ +
L
Note : For 3 Ø 3 W system, only the 1st, 2nd, ! Use ( ) key to go back to previous page. 13.18 Page Sequence 18 1 to 20 18 PULSE RS485
O/P
3rd and 5th screen available. Use ( ) key to save the setting and move on next
For 3 Ø - 4 W : Display Line to Neutral Voltage page. 13.19 Page Sequence 19 1 to 20 19
For 3 Ø - 3 W : Display Line to Line Voltage MFM383A / MFM383A-C
Config Range or Factory 13.20 Page Sequence 20 1 to 20 20
Press “P” The 1st screen : (Page 9) page. Function
Selection Setting
Displays power factor of 3 phase. 14 Factory Default No / Yes No
The 2nd screen : (Page 10) Password 0000 to 9998 10
I1 I2 I3
S1 S2 S1 S2 S1 S2 N V1 V2 V3
Displays active power of 3 phase. 15 Reset Energy No / Yes No
The 3rd screen : (Page 11) 1 Change Password No / Yes No
Displays reactive power of 3 phase. 15.1 Password 0001 to 9999 11 Pulse output from MFM383A meter can be used as
The 4th screen : (Page 12) 1.1 New Password 0000 to 9998 10 alarm generator or total energy controller by interfacing it
Displays apparent power of 3 phase. 15.2 Reset Active Energy No / Yes No with Pre-settable counter and control circuits
The 5th screen : (Page 13) 2 Network Selection 3P3W and 3P4W 3P4W (Contactors, Relay, Trip Circuit).
Displays active power, reactive power and Marked parameters are available only in MFM383A-C. The counter is loaded with the maximum energy
power factor of 1st phase. 3 CT Secondary 1A or 5A 5 For resetting energy parameters user will be prompted consumption. When count reaches setpoint it provides
The 6th screen : (Page 14) 1A, 5A to for password. If correct password is entered, the user output to control circuit to take appropriate action.
Displays active power, apparent power and 4 CT Primary 5
10,000A(10.0kA) will be able to reset all energy parameters. This
power factor of 1st phase. Note : + and - is applicable only for 24V product
5 PT Secondary 100V to 500V 350 password will be value which will be greater than the
The 7th screen : (Page 15)
Displays active power, reactive power and configuration password by 1. # All fuse types : 0.5A class CC UL type
power factor of 2nd phase. 6 PT primary 100V to 10000V 350 0.5A fast acting 600V
Doc. name : OP INST MFM383A / MFM383A-C OP354-V04 (Page 2 of 4)
MODBUS REGISTER ADDRESSES LIST
Readable parameters from MFM383A-C : [ Length (Register) : 2 ; Data Structure : Float ] MODBUS register addresses list continued

Address Hex Address Parameter Address Hex Address Parameter Readable / writable parameters from MFM383A :

30000 0x00 Voltage V1N 30030 0x1E kVA1 Address Hex Address Parameter Range Length Data
(Register) Structure
30002 0x02 Voltage V2N 30032 0x20 kVA2 Meaning
Value
30004 0x04 Voltage V3N 30034 0x22 kVA3 Parity Integer
40009 0x09 0x0000 None 1
30006 0x06 Average Voltage LN 30036 0x24 kVAr1 0x0001 Odd
30008 0x08 Voltage V12 30038 0x26 kVAr2 0x0002 Even
30010 0x0A Voltage V23 30040 0x28 kVAr3 Stop bit Integer
40010 0x0A 0x0000 1 1
30012 0x0C Voltage V31 30042 0x2A Total kW 0x0001 2
30014 0x0E Average Voltage LL 30044 0x2C Total kVA Factory Default Set to factory setting range Integer
40011 0x0B 1 1
30016 0x10 Current I1 30046 0x2E Total kVAr 40012 0x0C Reset kWh 1 Reset Total Active Energy 1 Integer
30018 0x12 Current I2 30048 0x30 PF1 Min Value Max Value
30020 0x14 Current I3 30050 0x32 PF2 40015 0x0F Auto Mode Pgs 1 20 1 Integer
30022 0x16 Average Current 30052 0x34 PF3 Page No Meaning
30024 0x18 kW1 30054 0x36 Average PF Page Address Sequence 1- First Page ; 20-Last Page Integer
40016 0x10 1- 20 1
30026 0x1A kW2 30056 0x38 Frequency Page Address Sequence 1- First Page ; 20-Last Page Integer
40017 0x11 1- 20 1
30028 0x1C kW3 30058 0x3A kWh 40018 0x12 Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer

Readable / writable parameters : 40019 0x13 Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer

Length Data 40020 0x14 Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
Address Hex Address Parameter Range
(Register) Structure
40021 0x15 Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
Min value Max value
40022 0x16 Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
40000 0x00 Password 0 9998 1 Integer
40023 0x17 Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
Value Meaning
40024 0x18 Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
40001 0x01 N/W selection 0 3P-4W 1 Integer
40025 0x19 Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
1 3P-3W 1 Integer
40026 0x1A Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
Min Value Max Value
40027 0x1B Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
40002 0x02 CT Secondary 1 5 1 Integer
40028 0x1C Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
40003 0x03 CT primary (CT Secondary = 5) 5 10000 1 Integer
40029 0x1D Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
CT primary (CT Secondary = 1) 1 10000
40030 0x1E Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
40004 0x04 PT Secondary 100 500 1 Integer
40031 0x1F Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
40005 0x05 PT primary 100 10000 2 Integer
40032 0x20 Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
40007 0x07 Slave Id 1 255 1 Integer
40033 0x21 Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
Value Meaning (bps)
40034 0x22 Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
40008 0x08 Baud rate 0x0000 300 1 Integer
40035 0x23 Page Address Sequence 1- 20 1- First Page ; 20-Last Page 1 Integer
0x0001 600
Min Value Max Value (Sec.)
0x0002 1200
40036 0x24 Backlight 0 (Always on) 7200 1 Integer
0x0003 2400

0x0004 4800

0x0005 9600

0x0006 19200

Doc. name : OP INST MFM383A / MFM383A-C OP354-V04 (Page 3 of 4)


TYPICAL WIRING DIAGRAM

3 PHASE 4-WIRE (COMMONLY USED) 3 PHASE 3-WIRE 2 PHASE - 3 WIRE 1 PHASE - 2 WIRE

3 Ø - 4 WIRE, 3 CT’S 3 Ø - 3 WIRE, 2 CT’S 2 Ø - 3 WIRE, 2 CT’S 1 Ø - 2 WIRE, 1 CT


N L N L N L N L

# + + # + +
# + + # + +

+ + + + + +
N N N
L N
L + + L L
PULSE RS485 PULSE RS485 PULSE RS485 PULSE RS485
O/P O/P O/P O/P

MFM383A / MFM383A-C MFM383A / MFM383A-C MFM383A / MFM383A-C MFM383A / MFM383A-C

I1 I2 I3 I1 I2 I3 I1 I2 I3 I1 I2 I3
S1 S2 S1 S2 S1 S2 N V1 V2 V3 S1 S2 S1 S2 S1 S2 N V1 V2 V3 S1 S2 S1 S2 S1 S2 N V1 V2 V3 S1 S2 S1 S2 S1 S2 N V1 V2 V3

# # # #

N N N
L3 L3
L2 L2 L2
L1 L1 L1 L1
LINE LOAD LINE LOAD LINE LOAD LINE LOAD

3 Ø - 4 WIRE, 3 CT’S and 3 PT’S 3 Ø - 3 WIRE, 2 CT’S and 2 PT’S 2 Ø - 3 WIRE, 2 CT’S and 2 PT’S # All fuse types : 0.5A class CC UL type
0.5A fast acting 600V
N L N L
N L
# + + # + + # + +

+ +
CONNECTION DIAGRAM FOR COMMUNICATION
N
L + +
N
L N
+ +
PULSE RS485 PULSE RS485 L
O/P PULSE RS485
O/P
O/P

Master
MFM383A / MFM383A-C MFM383A / MFM383A-C MFM383A / MFM383A-C

I1 I2 I3 I1 I2 I3 I1 I2 I3
S1 S2 S1 S2 S1 S2 N V1 V2 V3 S1 S2 S1 S2 S1 S2 N V1 V2 V3 S1 S2 S1 S2 S1 S2 N V1 V2 V3
RS485-RS232 Suggested terminating
Converter resistor
(120 ohm, ¼ watt)
# # #

V V V
1 1 1
2 2 2

A A A
2 2 2
3 3 3

PF PF PF
3 3 3
1 1 1
Avg Avg Avg

N N kWh kWh kWh

L3 L3 A/M
V VAF
PRG
P
A/M
V VAF P
PRG A/M
V VAF P
PRG

L2 L2 L2
L1 L1 L1 Contact sales for PC based monitoring
LINE LOAD LINE LOAD LINE LOAD software to communicate with the meters.

(Specifications subject to change as development is a continuous process.)

Selec Controls Pvt. Ltd., India


Factory Address :
EL-27/1, Electronic Zone, TTC Industrial Area,
MIDC, Mahape, Navi Mumbai - 400 710, INDIA.
Tel. No. : +91-22-28476443 / 1882
Fax No. : +91-22-28471733 I Toll free : 1800 227 353
Website: www.selec.com I Email: [email protected]

Doc. name : OP INST MFM383A / MFM383A-C OP354-V04 (Page 4 of 4)