3.018
3.018
Features
The DEBEG 9517 supervises and indicates
visually and acoustically the failure of
n battery chargers,
n forced ventilation of battery rooms,
n power supply units with automatic
switch-over relay contact to battery
operation and
The IMO requires in COMSAR Circular 16 The contents of the alarm messages presented on n temperature stabilisation systems used
„Guidelines on the Configuration of the Reserve the integrated LC display for power supplies in battery boxes outside of the compass
Source or Sources of Energy used to supply Radio correspond to the labelling of the automatic bridge.
Installations on GMDSS Ships“ a visual and circuit-breakers on the switchboard DEBEG 9002. The alarm panel thus serves a single
audible failure indication for all power supply As a result, the electrical loads concerned can be purpose, namely checking the functions
units which automatically switch over to battery unambiguously disconnected from the battery of power supply units and additional
operation when ship’s mains or power supply to prevent unnoticed discharging of the radio devices.
units fail. battery.
DEBEG 9517
Technical Data
MF/HF Telex
VHF Radio 1
The DEBEG 9517 incorporates n UAIS
n 2 voltage supply inputs for 24 V DC (in the case n Battery Failure, Battery Fail 1, Battery Fail 2
INM-C / EGC
of separate radio batteries for main and n Charger Port VHF
duplication equipment), n Airborne VHF
GPS n 4 input terminal pairs per battery charger for n MF/HF Radio, MF/HF Radio 1, MF/HF Radio 2
alarms from battery chargers 1 and 2, n GMDSS Alarm Unit
NAVTEX n 12 input terminal pairs for power supply n INM-C / EGC, INM-C 1 / EGC, INM-C 2
units of GMDSS equipment and n VHF Radio 1, VHF Radio 2, VHF Radio 3
VHF Radio 2 n one alarm output (change-over contact) n GPS, GPS 1, GPS 2
for the ship’s general alarm panel. n DGPS, DGPS 1, DGPS 2
GMDSS Alarm n INM-B SatCom, INM-B SatCom 1,
The internal EEPROM contains the following INM-B SatCom 2
alarm messages for radio station power supply n NAVTEX
failure. n MF/HF Telex, MF/HF Telex 1, MF/HF Telex 2
n Main PWR Supply, Dupl. PWR Supply,
n Batt.Room Vent., Batt.Room Vent.1 Each alarm message can be re-assigned easily to
Power Alarm Panel Batt.Room Vent.2 a specific terminal pair without any external
n Mains Failure, Mains Failure 1, Mains Failure 2 means, if the programmed factory standard does
DEBEG 9517
n Batt. Charger, Batt. Charger 1, Batt. Charger 2 not fit with a specific radio installation.
n Batt.Temp.Fail, Batt.Temp.Fail 1, Batt.Temp.Fail 2