StatohmIVManual2011-06-10
StatohmIVManual2011-06-10
INTRODUCTION
Before installation and operation of the ERC Statohm IV, DC drive, read this instruction
manual carefully. Installation should only be done by a fully qualified licensed electrician. The
ERC Statohm IV, DC drive is only a portion of a complete drive system. Refer to the instruction
manuals of the other components in the drive system for details about auxiliary equipment and
the DC motor. This user’s manual does not purport to cover all details or variations of DC drive
installation, operation or maintenance.
CAUTION
Before MEGGER or DIELECTRIC testing the DC motor.
Disconnect the DC motor from the Statohm IV control. Megger or
dielectric testing will damage the semiconductors in the control.
Table of Contents
Pg. 3 Section 1) Receiving & Storage
Pg. 3 Section 1.1) Model Number Scheme
Pg. 3 Section 2) Installation Location
Pg. 3 Section 2.1) Operating Environment
Pg. 5 Section 3) Jumper Settings
Pg. 4 Jumper Setting Diagram
Pg. 5 Section 3.1) Field Current Jumpers
Pg. 5 Section 3.2) Armature Current Jumpers
Pg. 5 Section 3.3) Motor Feedback Jumper
Pg. 5 Section 3.4) DC Tach Voltage Jumpers
Pg. 5 Section 3.5) Field Regulation Jumpers
Pg. 5 Section 3.6) Acceleration and Deceleration Time Range Jumpers
Pg. 7 Section 4) Wiring
Pg. 6 Wire Size Tables
Pg. 6 Elementary Power Connection Diagram
Pg. 7 Section 4) Power and Control Circuit Wiring Introduction
Pg. 7 Section 4.1) AC Power Connections
Pg. 7 Section 4.2) Grounding
Pg. 7 Section 4.3) Phase Sequence Test
Pg. 7 Section 4.3A) Fuse Replacement
Pg. 7 Section 4.4) Armature Connections
Pg. 8 Section 4.5) Field Connections
Pg. 8 Section 4.5A) Field Disable
Pg. 9 Section 4.6) PC, Pre-Operational Conditions (i.e. Enable Drive)
Pg. 9 Section 4.7) Speed Reference & Reverse
Pg. 10 Section 4.8) Jog
Pg. 10 Section 4.9) Start & Stop (i.e. Run & Stop)
Pg. 10 Section 4.10) Emergency Stop (E.Stop)
Pg. 10 Section 4.11) DC Tach generator Feedback
Pg. 11 Section 4.12) Meter Dimensions
Pg. 12 Section 4.13) Speed Meter Wiring and Calibration
Pg. 13 Section 4.14) Armature Ammeter Wiring and Calibration
Pg. 14 Section 4.15) Field Ammeter Wiring and Calibration
Page 1
ERC Statohm IV (Table of Contents)
Pg. 15 Section 5) Operation and Adjustment
Pg. 15 Section 5.1) Check prior to operation
Pg. 15 Section 5.2) Pre-Operation Voltage Checks
Pg. 15 Section 5.3) Test Run
Pg. 15 Section 5.4) Jog Speed & Ramp Adjustment
Pg. 16 Section 5.5) Emergency Stop (E. Stop)
Pg. 16 Section 5.6) ZD, Zero motor rotation Detection relay and signal light adjustment
Pg. 16 Section 5.7) Zero Speed Adjust (12 SCR Regenerative Drives Only)
Pg. 17 Section 5.8) Zero Speed Hysteresis Adjustment (12 SCR Regenerative Drives Only)
Pg. 17 Section 5.9) Maximum Speed Adjustment for Armature Feedback
Pg. 17 Section 10) Maximum Speed Adjustment for DC Tach Feedback
Pg. 18 Section 5.11) Field Amperage Adjustment
Pg. 18 Section 5.11A) Field Weakening Adjustment (Tach Feedback Only)
Pg. 18 Section 5.11B) Field Economy
Pg. 18 Section 5.11C) Field Disable
Pg. 18 Section 5.11E) Field Loss
Pg. 18 Section 5.11F) Field Voltage Regulation
Pg. 19 Section 5.12) Armature Current Calibration
Pg. 19 Section 5.12A) Current Limit Adjustment
Pg. 19 Section 5.12B) Forward and Reverse Current Limit Adjustment
Pg. 19 Section 5.12C) One Minute Timed Overload Shut-off Adjustment
Pg. 19 Section 5.12D) Instantaneous Overload Current Shut-off Adjustment
Pg. 20 Section 5.13) Acceleration & Declaration Time Adjustment
Pg. 20 Section 5.14) Speed Overshoot and Stability Adjustment Overview
Pg. 20 Section 5.14A) Speed Overshoot Adjustment (i.e. Speed Response)
Pg. 20 Section 5.14B) Speed Stability Adjustment (i.e. Speed Gain)
Pg. 21 Section 5.15) ASR Feedback Loop Adjustment ( i.e. Speed PID )
Pg. 21 Section 5.16) Current Gain Loop Adjustment ( i.e. Current PID )
Pg. 22 Section 5.17) Master Slave Operation
Pg. 25 Section 6) Troubleshooting
Pg. 25 Section 6.1) Phase Load Balancing
Pg. 27 Section 6.2) Motor won’t start but non of the signal lights are on.
Pg. 27 Section 6.3) Motor Speed Runaway
Pg. 28 Section 6.4) Fuses blow immediately after start and the “OC signal lights
Pg. 29 Section 6.5) Unstable Speed
Pg. 30 Section 6.6) Motor will not go to full speed
Pg. 30 Section 6.7) Excessive overshoot and undershoot
Pg. 30 Section 6.8) Overload fault “OL” signal light
Pg. 31 Section 6.9) The ES, OH, VL signal lights are on and can not be reset
Pg. 31 Section 6.10) Signal lights R and PC are on F,AP, ZD flash and relays buzz.
Pg. 31 Section 6.11) Field loss is detected.
Pg. 32 Section 6.12A) Armature current is too high at low speed and normal load.
Pg. 32 Section 6.12B) During acceleration or heavy load the field is too low.
Pg. 33 Section 6.13) PH Light is on
Pg. 33 Section 6.14) The F light is dimly lite but field loss is not detected
Pg. 33A Section 6.15) Regulator card connections
Pg. 33A Section 6.16) Utilty company transfer switch problems (PH light disable)
ATTACHMENTS
Pg. 34 “S” Model Physical Diagram
Pg. 35 “M2” Model Physical Diagram
Pg. 36 “M3” Model Physical Diagram
Pg. 37 “L1” Model Physical Diagram
Pg. 37A “L2” Model Physical Diagram
Pg. 38 IFC 1084 Card
Pg. 38 41FS Auxiliary Field Supply
Pg. 39 Synchronization Card 1058C
Pg. 40 Oscilloscopes
Pg. 42 Regulator Card Control Block Diagram #9044
Pg. 43 Regulator Card Block Diagram # 9042-1
Pg. 44 Regulator Card Block Diagram # 9042-2
Pg. 45 Regulator Card Block Diagram # 9042-3
Pg. 46 Elementary Circuit Diagrams
Pg. 47 Terminal Table (for Regulator Card)
Pg. 48 Regulator Card 1059A Physical Diagram
Pg. 49 Regulator Card Tables (for Pots, Jumpers, Signal Lights and Test Points)
Pg. 50 Common Specifications
Pg. 51 Alphabetical Index
Page 2
ERC Statohm IV Manual; Section 1&2 (Receiving & Storage and Installation Location)
y Inspect the circuit cards, damaged, loose or shorted electronic components or connections.
y If you find damage do not connect power to it. The unit must be replaced or repaired. Connecting power could
result in fire or further damage and void the warranty.
y Promptly report damage or problems you found during inspection to Electric Regulator Corp., Telephone (760)
438-7873, Fax (760) 438-0437
y Store the ERC Statohm IV control in a clean dry place, in the package it was shipped. Avoid storing the unit in
a location with high temperatures, humidity, dust or corrosive gases. Outdoor storage is not recommended.
Section 1.1) Model Number Scheme DC42NS3-4
Input Voltage: 2=208~240V, 4=440~480V, 5=575~600V
Power Rating Number
Chassi Size.
N = 6 SCR, R = 12 SCR
Model Number
42NM3-*
42RM2-*
42RM3-*
42NL1-*
42NL2-*
42NL4-*
42NL5-*
42NL7-*
42NS1-*
42NS2-*
42NS3-*
42NS4-*
42RL1-*
42RL2-*
42RS1-*
42RS2-*
42RS3-*
42RS4-*
Model Number
Max., Current 37A 70A 110A 180A 400A 550A 720A 910A 1100A 1400A 1800A
Input 208~240V, Arm 240V 7 HP 15 HP 25 HP 45 HP 100 HP 125 HP 200 HP 250 HP 300 HP --- ---
Input 440~480V, Arm 500V 14 HP 30 HP 50 HP 90 HP 200 HP 250 HP 400 HP 500 HP 600 HP 750 HP 1,000 HP
Input 575~600V, Arm 600V --- 36 HP 60 HP 108 HP 240 HP 300 HP 480 HP 600 HP 720 HP 900 HP 1,200 HP
y Corrosion Avoid locations with corrosive gases or liquids; example: ocean air.
y Hazardous Gases & Liquids Do not locate the unit were it is subject to combustible or flammable gases or
liquids.
y Ventilation Mount the unit in a lengthwise vertical position to ensure proper cooling ventilation. Provide not
less than 5 inches (125 mm) of clear space on all sides of the unit. If the unit is in a sealed enclosure, provide
adequate ventilation for air flow from top to bottom.
y Shock & Vibration Avoid mounting the unit in a location subject to shock or vibration.
Page 3
REGULATOR CARD 1059D and earlier depicted
REGULATOR CARD 1059F eliminated jumpers 2,3,6, FV, FI and added jumpers 11 and 12
P3
/10
P6
/10
P2
/10
P5
CA
/10
P1
+V -15 +15 /10
P4
/10
TL
LV
COM TG
IMX HS /10
/10 /10
9 OC
COM
USER SELECT'S OL
A-1
A-2
A-3
A-4
ARMATURE CURRENT
FU
EXTRA JUMPERS
LV
USER SELECT'S
F-1
F-2
F-3
F-4
F-5
FIELD CURRENT PH
EF
FL
FV
10
FI
8
OH
ES
FL
AP
7
P
IF FM ZERO
IFR ZD
/10 /10 /10
IG FL RL SR SG DG PI OP
/10 /10 /10 /10 /10 /10 /10 /10
TG
50H
RESET
9
5A 5
/10 8
CROS
AP
7
/10 6
FE
COM
M3 M4
1 2 4 6 10
SF
VF
+B
5
4
T-4
T-3
T-2
T-1
3
2
S-1
S-2
S-3
S-4
R5
PC
R
1
R2
TERMINALS 1 TO 40
JUMPER JUMPER
ON OFF Armature Feedback Jumper Settings
User Selects JUMPERS ON: AP, CA, FE, FI, IFR, TG, VF, 1, 2, 4, 6, 8
Regulator card 1059F does not require jumpers 2 and 6 for armature feedback
Page 4
Section 3 Jumper Setting Tables
The jumper settings must be made prior to applying power. Complete the blanks below to determine the jumper
settings for your application. Consult the jumper tables below or “Master Jumper Table” to the left.
y Armature Voltage VDC y Armature Current Limit A.
y Field Current A. y Acceleration Time Sec.
y Feedback (Arm or Tach) y Deceleration Time Sec.
y Field Regulation (constant current, field weakening, permanent magnet) (Field Economy enabled or disabled)
Jumper Tables
3.1 Field Current
“S2, S3 & S4”
“S1” Model “M2 & M3” Models M4 Model “L1 & L2” Models
Models Current Jumper Settings
Current Range Current Range Current Range Current Range
Range
F1 - On
4.3 ~ 7.1 6A ~ 10A 10A ~ 17A NA 15A ~ 25A
F2, F3, F4, F5 - Off
F2 - On
2.1 ~ 4.3 3A ~ 6A 5A ~ 10A NA 7.5A ~ 15A
F1, F3, F4, F5 - Off
F3 - On
1.4 ~ 2.1 2A ~ 3A 3.3A ~ 5A NA 5A ~ 7.5A
F1, F2, F4, F5 - Off
F4 - On
0.7 ~ 1.4 1A ~ 2A 1.7A ~ 3.3A NA 2A ~ 2.5A
F1, F2, F3, F5 - Off
F5 - On
0.6 ~ 1.2 0.8A ~ 1A 1.3A ~ 1.7A NA 1.3A ~ 2A
F1, F2, F3, F4 - Off
3.2 Armature Current (see section 5.12 for Armature Current Calibration)
“S1” Model “S2” Model “S3” & “S4 ” Model “M2” &“M3” Model “L1 & L2” Model
Jumper Settings
Current Range Current Range Current Range Current Range Current Range
A1, A2, A3, A4 -
14 ~ 23 48A ~ 81A 183A ~ 300A 366A ~ 600A 730A ~ 1,200A
On
A1, A2, A3 - On
12 ~ 20 35A ~ 58A 161A ~ 269A 322A ~ 538A 640A ~ 1,100A
A4 - Off
A1, A3 - On
8.6 ~ 14 25A ~ 42A 115A ~ 192A 230A ~ 384A 460A ~ 770A
A2, A4 - Off
A1 - On
6 ~ 10 18A ~ 30A 83A ~ 139A 166A ~ 277A 330A ~ 560A
A2, A3, A4 - Off
A2 - On
4.5 ~ 7.5 14A ~ 23A 60A ~ 100A 120A ~ 200A 240A ~ 400A
A1, A3, A4 - Off
A3 - On
3.5 ~ 5.9 11A ~ 19A 46A ~ 78A 93A ~ 150A 190A ~ 300A
A1, A2, A4 - Off
A4 - On
2.8 ~ 4.7A 7A ~ 12A 38A ~ 62.5A 75A ~ 125A 150A ~ 250A
A1, A2, A3 - Off
3.3 Motor Feedback 3.5 Field Regulation
Feedback Jumper Settings Field Operation Jumper Settings
VF, TG - On Constant Field J8 - On
Armature SF, TL - Off (default) J7 - Off
DC Tachometer Generator
SF, TG, TL - On Field Weakening J7, J8 - On
VF - Off (Tach Feedback Only)
Enable: FE - Off (default)
Field Economy Disable: FE - On
3.4 DC Tach Generator Voltage
Example: DC tach is 50VDC/1000 rpm and DC motor’s maximum FL- On
speed is 2150 rpm 2.15 x 50 = 107.5 Volts select voltage range Disabling Field Don’t connect
88v~127V., jumpers S2- On / S1, S3, S4 - Off power to F+ and F-
Standard Setting Special Setting
(R2 & R5 are (R2 & R5 are zero Jumper Settings
220k resistors) ohm jumpers) 3.6 Acceleration & Deceleration Time Range
S1, S2, S3, S4 - Time Range Jumper Setting
41V ~ 60V 27V ~ 41V
Off
S1 - On T1 - On
60V ~ 88V 41V ~ 60V S2, S3, S4 - Off 0.7 ~ 6 Sec.
T2, T3, T4 - Off
S2 - On T2 - On
88V ~ 127V 60V ~ 88V S1, S3, S4 - Off 3 ~ 20 Sec. (default)
T1, T3, T4 - Off
S3 - On T3 - On
127V ~ 172V 88V ~ 127V S1, S2, S4 - Off 7 ~ 60 Sec.
T1, T2, T4 - Off
S4 - On T3, T4 - On
172V ~ 250V 127V ~ 172V S1, S2, S3 - Off 14 ~ 120 Sec.
T1, T2 - Off
Page 5
Wire Size Tables
230 VAC 3 Phase 60 Hz Input 460 VAC 3 Phase 60 Hz Input
Full Load Minimum Wire Size Circuit Breaker Full Load Minimum Wire Size Circuit Breaker
HP HP
AC Amps for 40 ft length AC Amps at 250VAC AC Amps for 40 ft length AC Amps at 600VAC
5 17 12 AWG 25 5 8.6 14 AWG 10
7.5 25 10 AWG 30 7.5 11 14 AWG 15
10 32 8 AWG 40 10 13.5 12 AWG 20
15 49 6 AWG 70 15 21 10 AWG 30
20 63 4 AWG 90 20 27 8 AWG 35
25 79 3 AWG 100 25 34 8 AWG 40
30 93 1 AWG 125 30 40 6 AWG 50
40 124 00 AWG 175 40 54 4 AWG 70
50 156 000 AWG 200 50 67 4 AWG 90
60 184 0000 AWG 225 60 80 3 AWG 100
75 229 300 MCM 300 75 99 1 AWG 125
100 300 500 MCM 400 100 133 00 AWG 175
125 380 (2) 250 MCM 500 125 167 0000 AWG 225
150 450 (2) 350 MCM 600 150 202 250 MCM 300
200 266 (2) 000 AWG 400
250 375 (2) 250 MCM 500
240 VDC Armature 500 VDC Armature
Full Load Minimum Wire Size DC Fuse Amps Full Load Minimum Wire Size DC Fuse Amps
HP HP
DC Amps for 40 ft length (if used) DC Amps for 40 ft length (if used)
5 19 10 AWG 25 5 10 12 AWG 15
7.5 28 8 AWG 40 7.5 12 12 AWG 20
10 36 6 AWG 50 10 15 10 AWG 25
15 54 4 AWG 70 15 23 8 AWG 35
20 70 2 AWG 100 20 30 8 AWG 45
25 87 1 AWG 150 25 38 6 AWG 60
30 105 0 AWG 150 30 45 4 AWG 70
40 139 0000 AWG 200 40 60 3 AWG 100
50 173 250 MCM 250 50 75 2 AWG 150
60 205 300 MCM 300 60 90 1 AWG 150
75 254 500 MCM 400 75 110 00 AWG 200
100 337 (2) 250 MCM 600 100 148 0000 AWG 250
125 325 (2) 350 MCM 600 125 185 300 MCM 300
150 504 (2) 500 MCM 800 150 218 (2) 000 AWG 400
150 VDC Field 200 295 (2) 250 MCM 600
Wire Size for 40 ft Length 250 408 (2) 350 MCM 600
5 - 75 H.P. : 14 AWG 300 VDC Field
100 - 200 H.P. : 12 AWG Wire Size for 40 ft Length
5 - 75 H.P. : 14 AWG
100 - 200 H.P. : 14 AWG
DC Motor
A-
DC Drive
A
A+
ABC
L1F L2F L1C L2C L1S L2S L3S F+ F- L1C and L2C are alternately marked 115V.
FIELD 3A
fuse
L1 L2 L3
115V L1 L2 L3
Page 6
ERC Statohm IV Manual, Section 4 (Power & Control Circuit Wiring)
WARNING
Separate over current protection is required by the national electric code. The user is
responsible for conforming with the national electric codes and all applicable local codes
which govern such practices such as wiring protection, grounding, disconnects and other
current protection.
NOTICE
Make all power circuit connections in accordance with the drive system engineer’s wire
diagram or the elementary wire diagrams provided in this manual. The power circuit
includes terminals L1, L2, L3, L1F, L2F, L1S, L2S, L3S, A+, A-, F+, F- and 115V.
4.2 Ground in accordance with national and local electrical codes and regulations.
Page 7
ERC Statohm IV Manual, Section 4 (Power & Control Circuit Wiring)
4.4 Armature Connections
y See the motor data plate for the armature’s amp rating. Then select the wire size from the Wire Size
Table at the beginning of section 4.
y Connect the motor’s armature to the power busses marked A+ and A- .
y Current Range is selected from jumper the table below.
y For instructions bout adjusting the Current Limit, see section 5.12
“S1” Model “S2” Model “S3 & S4 ” Model “M2 & M3” Model “L1 & L2” Model
Jumper Settings
Current Range Current Range Current Range Current Range Current Range
14 ~ 23 48A ~ 81A 183A ~ 300A 366A ~ 600A 730A ~ 1,200A A1, A2, A3, A4 - On
A1, A2, A3 - On
12 ~ 20 35A ~ 58A 161A ~ 269A 322A ~ 538A 640A ~ 1,100A
A4 - Off
A1, A3 - On
8.6 ~ 14 25A ~ 42A 115A ~ 192A 230A ~ 384A 460A ~ 770A
A2, A4 - Off
A1 - On
6 ~ 10 18A ~ 30A 83A ~ 139A 166A ~ 277A 330A ~ 560A
A2, A3, A4 - Off
A2 - On
4.5 ~ 7.5 14A ~ 23A 60A ~ 100A 120A ~ 200A 240A ~ 400A
A1, A3, A4 - Off
A3 - On
3.5 ~ 5.9 11A ~ 19A 46A ~ 78A 93A ~ 150A 190A ~ 300A
A1, A2, A4 - Off
A4 - On
2.8 ~ 4.7A 7A ~ 12A 38A ~ 62.5A 75A ~ 125A 150A ~ 250A
A1, A2, A3 - Off
Page 8
ERC Statohm IV Manual, Section 4 (Power & Control Circuit Wiring)
NOTICE
Make all control circuit connections in accordance with the drive system engineer’s wire
diagram or the elementary wire diagrams provided in this manual if applicable. The
control circuit terminals 1 though 40 are located on the regulator card.
WARNING
Electrical noise pickup on the control circuit wiring can cause erratic operation.
y Never use solid wire.
y Use shielded wires or twisted wires for the control circuit. Connect shielding to common
terminal of each circuit.
y Run the control circuit wires in a separate duct or conduit. Maintain a space of 2 inches
(50 mm) or more from the general power circuit.
Page 9
ERC Statohm IV Manual, Section 4 (Power & Control Circuit Wiring)
4.8 Jog
Jog will run up to 20% of full speed. The FT pot adjusts Jog’s acceleration time equal to or faster
than ACC setting. Important note: FT also adjusts E. Stop’s deceleration time. See section 4.10
option 2. The user must decided the priority when making this setting. The control circuit should
be designed so that Jog and Start (Run) are not on simultaneously. They should only be on
alternately.
4.9 Start/Run and Stop
To start the drive close terminals 34 (Run) to 35 (Com). For normal stop with deceleration time
controlled by the Deceleration pot, open terminals 34 and 35.
Note: Don’t open PC to stop the motor, see section 4.6
4.10 Emergency Stop (E.Stop)
Emergency Stop has two options.
Option 1) Freewheeling stop is the factory default setting. The motor is allowed to coast to a
stop and the regulator card power is switched off.
Option 2) Controlled deceleration stop To enable controlled E Stop, set the EF jumper ON and
make jumper connections from terminals 21 to 35 and 23 to 36. The E. Stop deceleration time
can be set to equal to or less than the DEC pot setting. The “FT” pot adjusts the E. Stop
deceleration time. Note: FT also equally adjusts Jog’s acceleration time. (See section 4.8) Proper
adjustment of the OP pot is required for a complete stop (see section 5.5A). The OP pot sets the
point when the regulator card power is switched off. Setting the OP pot too low will cause the
ZD relay to buzz
REGULATOR CARD
and OP Pot
Page 10
ERC Statohm IV Manual, Section 4 (Power & Control Circuit Wiring)
3.86"
98mm
0.60"
15mm
M5 x 0.8
Meter Dimentions
The Statohm IV has meter outputs for Armature current, Field current and Motor Speed.
+
See page 13 17 ARMATURE AMMETER
for instructions 18 -
A INPUT: 0 TO 2V
+
See page 12 19 SPEED METER
for instructions 18 - N INPUT: 0 TO 1mA
+
See page 14 20 FIELD AMMETER
for instructions 18 - F INPUT: 0 TO 2V
Page 11
ERC Statohm IV Manual, Section 4 (Power & Control Circuit Wiring)
REGULATOR CARD
JP-7
CROS
SF VF
NA pot
S1--S4
MAX
SPEED METER
1 2 3 - - - - - - - - - - 18 19 - - - - - - - - - - - - - - - 39 40
POS + INPUT NEG
0 to 1 mA
Page 12
ERC Statohm IV Manual, Section 4 (Power & Control Circuit Wiring)
Note: The IMX pot sets the current limit circuit’s internal reference point. The AM pot sets the
output voltage scale. For example: If a motor’s rating is 50 amps, the IMX pot calibrates the
current limit circuit’s internal reference point to 50 amps. The meter has 0 to 2 volt input with
100 amp scale face plate. Next with the motor running under a 50 amp load and using an external
ammeter for reference. The AM pot is adjusted until the ammeter reads equal to the reference
meter, 50 amps. This sets the scale to 1 volt equals 50 amps. If after the ammeter is calibrated,
the IMX pot is changed to 70 amps. This changes the scale to 70 amps equals 1 volt. If the
ammeter is not recalibrated, the ammeter will read 50 amps when the armature current is actually
70 amps. The ammeter always must be recalibrated after the IMX pot is adjusted.
REGULATOR CARD
IMX
A1--A4
JP-2
JP-3
AM pot
ARMATURE
AMMETER
1 2 3 - - - - - - - - - - 17 18 - - - - - - - - - - - - - - - 39 40
NEG INPUT POS +
0 to 2V
Page 13
ERC Statohm IV Manual, Section 4 (Power & Control Circuit Wiring)
The IF pot sets the field regulation circuits’ internal reference point. The FM pot sets the scale of
the field ammeter circuits’ output voltage scale. For example: If the motor’s field is 6 amps and
the meter has a 0 to 2 volt input with a face plate scale of 0 to 10 amps. With the field energized,
the FM pot is adjusted until the field ammeter equals the reference ammeter, 6 amps. This sets
the output voltage to 1.2 volts at 6 amps. After the field ammeter is calibrated, if the IF pot or F
jumpers are changed so that the field is 4 amps. This changes the scale to 4 amps equals 1.2
volts. If the field ammeter is not recalibrated, the ammeter will read 6 amps when the field
current is actually 4 amps. The field ammeter always must be recalibrated after the IF pot is
adjusted.
REGULATOR CARD
F1----F5
FV
FI
FM Pot
IF Pot
FIELD AMMETER
1 2 3 - - - - - - - - - - -18 19 20 - - - - - - - - - - - - - 39 40
POS + INPUT NEG-
0 to 2V
Page 14
ERC Statohm IV Section 5 (Operation & Adjustment)
Page 15
ERC Statohm IV Section 5 (Operation & Adjustment)
5.6 Zero motor rotation Detection relay and signal light adjustment
The regulator card has a motor rotation detection circuit (i.e. Zero Detection, ZD). The ZD
circuit has a SPDT relay on terminals: 21 center pole, 22 normally closed, 23 normally open and
a signal light marked ZDL. The switch point of the ZD circuit is set by the OP pot. The switch
point adjustable over a range of 0 to 25% of full speed.
y While the motor is stopping adjust the OP pot to the desired switching point. The ZDL signal
light will switch on.
y Note: Adjusting the OP pot too low can cause the ZD relay to buzz when the motor is
stopped.
Page 16
ERC Statohm IV Section 5 (Operation & Adjustment)
5.8 Zero Speed Hysteresis Adjustment ( 4 Quadrant, 12 SCR, Regenerative Drives Only)
The regulator card switches the motor from forward to reverse by changing the polarity of the
speed amplifier output. The output of the speed amplifier includes ripple form the tach or arm
feedback. To minimize the effect of ripple from this feedback. A Hysteresis circuit adjusts the
input sensitivity of the to the reverse switch logic. The “HS” pot is usually set on or about
2.5 /10 scale. If the motor is frequently reversed with light load, adjust the “HS” pot clockwise.
The Hysteresis circuit is an imprecise adjustment. Set the pot and wait for the drive to stabilize
before making another adjustment. Avoid making an excessive number of adjustments.
Page 17
ERC Statohm IV Section 5 (Operation & Adjustment)
Page 18
ERC Statohm IV Section 5 (Operation & Adjustment)
5.12C) Forward and Reverse Current Limits (Reverse, 4 Quadrant, 12 SCR, Regenerative Drives Only)
Four pots are used in the adjustment of current limit: IMX, FL, RL and IA.
y The IMX pot sets the motor’s rated current.
y The FL pot sets the forward current limit.
y The RL pot sets the reverse current limit.
y The IA pot sets the one minute timed current overload shut off.
Example: The motor’s rated current is 10 amps. Regenerative drive applications set the forward current limit to the motor’s
rating of 10 amps. The reverse current limit is often set higher, in this example 13 amps for extra braking power. Short time
periods of over current for regenerative braking should not damage the motor. Make sure the FL and RL pot are set at 100% (see
Section 5.9B 4/10 scale). Run the motor in forward with load and adjust the IMX pot to 10 amps. If you want the reverse current
limit to be 13 amps for extra braking power. Run the motor in reverse and adjust the RL pot to 13 amps.
If for example you should want the forward current limit to be 6 amps. Run the motor in forward and adjust the FL pot to 6
amps. Now you have a forward current limit of 6 amps and a reverse current limit of 13 amps. Setting the IMX pot to 10 amps
calibrates the regulator card’s protection circuits. If the motor should suddenly exceed 25 amps the instantaneous shut off circ uit
will activate based on 250% of motor’s rating of 10 amps. Not at 32.5 amps (250% of RL) and not 15 amps (250% of FL).
5.12C) One Minute Timed Current Overload Shut Off Adjustment
The overload current can be set up to of current limit for a fixed period of one minute.
y When the power is on and the motor is not running. Adjust IA according to table below.
fig.
5-12 (A) (B) (C)
Stable but slow Stable and fast Fast but unstable
Page 20
ERC Statohm IV Section 5 (Operation & Adjustment)
Page 21
ERC Statohm IV Section 5 (Operation & Adjustment)
MASTER SLAVE
DC drive DC drive
3 789 13 13 14
Master Speed Gain permits the speed overshoot, stability to be controlled by the master drive.
See sections 5.14 and 5.14B for more details.
y Terminal 10 is the master speed gain output.
y Terminal 6 is the slave speed gain input.
MASTER SLAVE
DC drive DC drive
3 7 8 9 10 13 6 13 14
Page 22
ERC Statohm IV Section 5 (Operation & Adjustments)
Section 5.18) AC contactor
Not all applications required contactors, below is a elementary diagram of AC contactor circuit.
DC Motor
A-
DC Drive
A
A+
L1F L2F L1C L2C L1S L2S L3S F+ F-
ABC
FIELD 3A
fuse
L1 L2 L3
115V
AC Contactor
Connect L1S, L2S and L3S befor the contactor to prevent the LV light switching on
Close the AC contactor befor activating Run (terminal 34), not simultaneously
L1 L2 L3
Note: Electric Regulator prefers AC contactors, DC contactors can lead to a variety of problems.
Page 23
Page 24
ERC Statohm IV Manual; Section 6 (Trouble Shooting)
Page 25
ERC Statohm IV Manual; Section 6 (Trouble Shooting)
Unbalanced Balanced
Page 26
ERC Statohm Manual Section 6 (Trouble Shooting)
Section 6.2 Problem: Motor won't start but none of the red signal lights are on.
Check the following: Recommendations:
y AC input voltage: Check if the unit is receiving power.
Check if the other drive system components are working
properly.
y Control circuit relay sequence: Check if RN1, RN2, JOG and ES relays circuits are wired
properly.
When RN1, RN2, JOG and ES relays are open. Check if test
point +B is 25VDC
y Jumper JP-10 Jumper JP-10 must be off. The motor will not run when this
jumper is on.
y Measure the ramp reference signal at test Test point “4” is the acceleration and deceleration ramp signal.
point “4”. When starting the signal should ramp up to 8V or for reverse
-8V.
y Tach Generator circuit. Check if the tach generator circuit wiring is faulty.
Check if the polarity is correct.
See section 4.11 DC Tach Generator
y Tach feedback: Check voltage of test If no voltage is present at test point “1” Check wire
point “1”. The normal voltage range is connections. If wire connections are good. The regulator card
-0.02 to -8.5 V DC may need to be replaced.
y Armature feedback: Check voltage of test If no voltage is present at test point “2” Check wire
point “2”. The normal voltage range is connections. If wire connections are good. The regulator card
+0.02 to +8.5 VDC may need to be replaced.
y Armature feedback: Check the armature If this plug is not connected or reversed the motor will run
voltage plug connected to the bottom left away. The correct sequence is red wire right (H) and white
corner of the synchronization card. wire left (N). See bottom of page 39 for details.
y Measure the field current. If field current is insufficient. Check if jumpers F1-F5 are set
right and the continuity is good. See section: 3.1 Field Current
and 3.5 Field Regulation.
y Phase to the field is not correct. Line L1 and L2 must be connected respectively to L1F and
L2F. If these connections are not correct, the field voltage will
be too low, causing the motor to run fast.
y The motor’s field is not correctly See section 6.12B on page 32.
connected.
y Check jumper settings and continuity. Check if SF, TG, TL and S1-S4 are set right and the continuity
is good. See section: 3.1 Motor Feedback
Page 27
ERC Statohm Manual Section 6 (Trouble Shooting)
Section 6.4 Problem: Fuses blow immediately after start and the “OC” signal lights.
y The load on the motor is stalled. Check the load on the machine.
y SCR failure (i.e. thyristor) Disconnect L1, L2, L3 and A+, A- and measure the
resistance between them. The typical resistance
between them should be about 100k . If the
resistance is low the SCR modules may need to be
replaced. Contact the factory for assistance.
y Improper setting of current limit or Check if jumpers A1-A4 are set right and the
current protection circuits. continuity is good. See sections: 3.2 Armature
Current and 5.12 Armature Current Calibration
y Measure the resistance between The normal resistance is only a few ohms or less.
CT1R & CT1W and CT2R &
CT2W on the SYNC card.
y Rapid change of load or motor Check the machine load and motor commutator.
flash-over.
y Check for the presence of a surge If a surge is present. Connect a noise suppresser to
during the operation of the external the external contactor and relays.
contactor or relays.
Page 28
ERC Statohm Manual Section 6 (Trouble Shooting)
Section 6.5 Problem: Unstable Speed
y Measure the voltage of If there is any variation. Check the speed pot wiring.
test point “4”
y Unstable field voltage. If the regulator is set for field weakening with
armature feedback the speed will be unstable. Set
the regulator card for constant field.
See section: 3.3 Motor Feedback
y Improper installation of the tach Check the tach’s mounting, coupling and wiring.
generator. Check for noise pick up on the tach’s wiring.
y Armature feedback only: Check for instability of power supply input voltage.
If present correct the problem.
y Excessive field weakening. Field weakening applications. The field should not
go below 1/3 to 1/6 of normal full field.
Example: Full field is 300VDC . Field weakening to
100VDC or less will cause unstable motor speed. A
special regulator card PN 1059A-11 is required.
y Thyristor (SCR) has failed A thyristor has failed and must be replaced.
Page 29
ERC Statohm Manual Section 6 (Trouble Shooting)
Section 6.6 Problem: Motor will not go to full speed.
y Improper calibration of speed Check the speed with another calibrated meter for
meter comparison.
y Excessive field current. Check with calibrated ammeter and compare with
motor’s ratings.
y Check field current. Low field current reduces the power of the motor.
Page 30
ERC Statohm Manual Section 6 (Trouble Shooting)
Section 6.9 Problem: The ES, OH, VL signal lights are on and can not be reset.
Check voltage from terminal board If 25VDC is not present the 115VAC transformer may
positions 35 & 38 to +B. The voltage be damaged, check the transformer. If the
should be 25VDC = !3VDC transformer output voltages are good. The SYNC
card should be replaced.
Section 6.10 Problem: Signal lights R and PC are on, the F, AP, ZD flash and the relays
buzz.
Page 31
ERC Statohm Manual Section 6 (Trouble Shooting)
Section 6.12A) Problem: The armature current is too high at low speed and small load.
Check the following: Recommendations:
Read the field specifications on One of two problems are possible:
the motor’s name plate. Then 1) If the field input power is incorrectly connected. The
measure the field current and field power will be too low. The motor will draw too
voltage to determine if they much current during start and run too fast if the load is not
comply with the specifications. too large. Common mistakes are L3 is connected to L1F
Note: Remember to disable field or L2F or the single phase 110V ~ 120V is connected to
economy when measuring the L1F or L2F. The correct connections are shown below.
field. Field economy is disabled
by placing the FE jumper on. L1F L2F L1C L2C L1S L2S L3S F+ F-
115V
L1 L2 L3
R S T
Section 6.12B) Problem: During acceleration or heavy load the field is too low.
Check the following: Diagram
Check the motor terminal box for Elementary Motor Connection Diagram
leads S1 and S2. Some motors
have leads S1 and S2, some
motors don’t. If S1 and S2 are
STABILIZING FIELD
present and not connected. See A2 S1 S2
A-
the diagram to the right for how
to connect them. The letter “S” A
stands for Stabilizing field. If the A1
motor doesn’t have S1 and S2, A+
then the stabilizing field is
connected internally. 300 VOLT FIELD
F4 F3 F2 F1
F- F+
L1F L2F L1C L2C L1S L2S L3S F+ F-
150 VOLT FIELD
F4 F3
F- F+
F2 F1
Page 32
Section 6.13 Problem: The PH light is on
Check the following: Diagram
Several problems are possible.
1) Lines L1, L2 and L3 should be
connected respectively to terminals
L1S, L2S and L3S.
Also check the plugs on the F2 F1 F4 F3
R10
R51A
SYNCHRONIZATION CARD
SH-1058C-
R74A R73A
J3T
M5
J3T J3T
Section 6.14) The “F” light is dimly lite but field loss is not detected
Check the following:
An error was made connecting L1F L2F L1C L2C L1S L2S L3S F+ F-
power to the field. Line 3 (L3) is
connected to either L1F or L2F. 115V
Page 33
Section 6.15 Regulator Card Connections
Warning ! Diagram
Incorrect connections will
irreparably damage the regulator
card, synchronization card and
REGULATOR CARD 1058 PULSE CARD 1057
pulse card. Carefully refer to the CN3
connections.
CN3
CN24
CN1 CN8
CN1
Section 6.16 Utility Company Transfer Switch Problems (PH light disable)
Warning ! Diagram
Disabling the PH light will not
resolve incorrect input power
connections! Disabling the PH REGULATOR CARD 1058
Page 33A
Blank Page
Page 33B
A 12mm
6.4mm
1/4"
CARLSBAD, CA. USA 15/32"
Tel (760) 438-7873
Fax(760) 438-0437
[email protected]
"S" Model Ratings
19/32"
17/32"
1/2 "
420mm
447mm
470mm
S4 180 45 90 110
18
Page 34
17
16
30mm
1 3/16 "
L1 L2 L3 A+ A-
79mm 45mm 45mm 40mm 35mm
6.8mm DIA
3 1/8" 9/32" DIA 1 3/4" 1 3/4" 19/16" 1 3/8"
6.4mm
225mm
8 7/8 " 1/4"
210mm
8 1/4"
256mm
10 3/32"
176mm 176mm
7" 7mm 7"
13mm 9/32"
A 1/2"
CARLSBAD, CA. USA
Tel (760) 438-7873
70mm
2 3/4 "
129mm
5 1/16 "
"M2" Model Ratings
A-
Model Max 230VAC 460VAC 575VAC
Number Amps Max HP Max HP Max HP
M2 400 100 200 250
50mm
2"
4 13/16 "
221mm
1/2 "
19/32"
17/32"
447mm
470mm
18
240mm
A+
Page 35
16
17
150mm
5 7/8 "
L1 L2 L3
2"
50mm
8mm DIA
5/16" DIA
104mm 50mm 50mm
4 3/32 " 2" 2" 7mm
9/32"
303mm 230mm
1115/16" 9 1/16"
256mm
10 3/32"
A
Carlsbad, CA. 92009 USA
160mm
6 5/16 "
13mm
1/2"
7mm
9/32"
256mm
10 3/32"
375mm
14 25/32 "
98mm
3 27/32"
Tel (760) 438-7873
5 1/8 "
130mm
Fax(760) 438-0437
[email protected]
204mm
8 1/32"
Page 36
13/16 "
122mm
50mm
M3 550 125 250 312 2"
17/32"
1/16 "
7/16"
420mm
510mm
544mm
674mm
1/2"
A+
20
21
16
26
150mm
5 7/8 "
219mm
8 5/8 "
50mm
L1 L2 L3
2"
8mm DIA
5/16" DIA
104mm
50mm 50mm
4 3/32 " 2" 2" 7mm
9/32"
293 mm 230mm
111/2" 9 1/16"
256mm
10 3/32"
375mm 132mm
14.75" 5.19"
A
Carlsbad, CA 92009 USA
Tel. (760) 438-7873
Fax (760) 438-0437
[email protected]
9.84"
575VAC: 500HP 1.48" (37.5mm)
250mm
A
32.26"
820mm
4.12"
105mm
Page 37
25.60"
650mm
A+
2.95"
75mm
0.42" DIA
7 places
11.81"
300mm
L1 L2 L3
0.27" DIA
6 places
82.5mm 82.5mm
3.25" 3.25"
276mm
10.875" 303mm
295mm
2.00" (51mm) 11.93"
11.63"
317.5mm
12.50"
10 1/4"
260mm
Carlsbad, CA. 92009 USA
Tel (760) 438-7873
Fax (760) 438-0437 570mm 260mm
[email protected] 22 7/16 " 101/4 "
472mm
160mm
18 19/32 "
6 5/16 "
5 1/8 "
130mm
2"
50mm
100mm
Model: L-2 4"
A+ A-
70mm
Amps: 910
2 3/4"
70mm
2 3/4"
60mm
240VAC: 250HP 2 3/8 "
480VAC: 500HP
575VAC: 625HP
Page 37A
39 3/8 "
1000mm
500mm
19 11/16 "
4"
L1 L2 L3
100mm
DC
MOTOR
F+ F- F1 F4
CT1 CT1
CT4
CT4
F1K
F1K
F1G
F1G
F2K
F2K
F2G
F2G
FF2 FF1
D2 D1
F- F+
Page 38
The Synchronization Card 1058C (i.e. SYNC CARD 1059C) can be modified to work with
different model drives and input voltages by changing resistor values and jumpers.
Part Number Input Voltage Armature Voltage
1058C-01 200V ~ 240V 240V
1058C-02 380V ~ 480V 500V
F2 F1 F4 F3
R2 R1
R8 R7
T4 S4 R4
H A
WHITE RED
Page 39
Oscilloscopes
Viewing the armature voltage with a oscilloscope requires special care. The oscilloscope can
not be grounded. The oscilloscopes power can not be grounded or connected to the neutral. The
oscilloscope and step down transformer can not rest on a grounded surface, such as the floor or
metal electrical enclosure. Resting the oscilloscope and transformer on a sheet of plywood or
thick card board often provides sufficient isolation from ground. A expensive oscilloscope is not
require, a inexpensive oscilloscope is recommended.
L1 L2
Don't rest the ocilloscope Don't Ground
or transformer on grounded Step Down
surface. Transformer
Neutral can not be used to
power the oscilloscope.
Don't Ground
Oscilloscope
L3
10X Probe
DC Drive
A+
Armature
A--
L1 L2 L3
Viewing the field voltage with an oscilloscope also requires the same special care plus
additional precautions. Before starting the motor, first view the field voltage to ensure the
oscilloscope is set up correctly. Take extra precautions so that the field can not be accidentally
grounded while the motor is running. If the field were accidentally grounded while the motor is
running will result in catastrophic damage to the motor and the drive, that would requiring
replacement of the drive and rewinding the motor.
Page 40
Supplemental Field Information
Field Power
The field power is vital to DC motors. Never disconnect the field power when the
motor is running. Also if the field does not have power, don’t apply power to the armature.
Why is the field vital? The field induces resistance in the armature, without the field the
armature has virtually no resistance.
Example: A 100 HP DC motor is running at full load; the armature is 500 volts, 150
amps. The armature has an effective resistance of 3.333 ohms. If the field power is disconnected
the armature resistance will drop to about 0.08 ohms (virtually zero) and the armature current
will immediately go up to 6,250 amps. Within mille seconds both the motor and drive will
incurred serious damage that is often irreparable.
Field Voltage
The field is a ampere circuit, the field voltage will vary with temperature.
Example: The 3212AT frame, 100 HP, DC motor field current is specified to be 3.5 amps. When
the motor is cold, 20oC (68oF) the field resistance is 66.8 ohms, the voltage would be 234 volts.
When the motor warms up to 40oC (104oF) the field resistance will increase to 85.7 ohms and the
field voltage would be 300 volts.
STABILIZING FIELD
many motors don't have
leads S1 and S2.
A2 S1 S2
A-
A
A1
A+
Page 41
F/R
CONTROL
LOGIC
+15V
M3 M4 M1 M2
SR
2.2µ 47K 1µ 47K
COM SG IG
200K
-15V LINEAR
1K 2.2K
TIME
ACC SPEED CURRENT
CONTROL CONTROL
4 6 THYRISTOR
RUN
TB8 ARMATURE
SPEED THYRISTOR
DRIVER
REFERANCE
+,-8V/ TB9
JOG
+,-100% N JOG DEC 10
CURRENT CURRENT
FEEDBACK TRANSFORMER
AMPLIFIER
0.7 to 6 Sec T-1
Page 42
-/+4V / 100% IA TB13 TB19
FL DG
N SPEED METER
TB12 TB18 1mA / 100%
FORWARD AM
CURRENT LIMIT AMMETER
A 1mA / +/-150%
+4V / 100% IA TB13 TB17
RL 2 V / +/-150%
TB11
FIELD FIELD
REVERSE FUNCTION CURRENT
CURRENT LIMIT GENERATOR CONTROL THYRISTOR
-4V / 100% IA TB13 JP 7
FIELD F+
*1 THYRISTOR
DRIVER
FIELD WEAKENING FIELD
ENABLE - ON F-
DISABLE - OFF
1F
7
ARMATURE
FEEDBACK
A
CIRCUIT
Carlsbad, CA. 92009 USA
DC42 REGULATOR CONTROL BLOCK DIAGRAM DWG 9044
Regulator Block Diagram (DWG 9042-1)
Page 43
Regulator Block Diagram (DWG 9042-2)
Page 44
Regulator Block Diagram (DWG 9042-3)
Page 45
2 QUADRANT, 6 SCR
BOL
MAIN BM
ELEMENTARY MCB MCB BM DC MOTOR
BM
CONTROL L1
BOL
L1
CIRCUIT L2
L2 BM
L3
ES RESET L3
FT BM TS SHT
ES ES DC DRIVE
A+ A+
ES
L1
STOP START L2
ES L3
A
RUN RUN
L1F A- A-
RUN
F+ F1
JOG
FIELD
RUN L2F
JOG JOG
F- F2
+
L1S 1
L2S _ TG
RUN L3S 2
PC PC 30 17 ARMATURE TS
A AMMETER
JOG 31 ST
18 INPUT: 0 to 2V P1 P2
115VAC 19
ZD PC 115V N SPEED METER
1 PHASE INPUT: 0 to 1mA
18
7 8V
SPEED 20 FIELD
REFERENCE 8 REF F AMMETER
Note: All relays are showen when INPUT: 0 to 2V
9 COM 18
the power is off. Exsample: When the
power is on the ES contact will close. JOG 21
33 JOG
RUN 22 ROTATION SIGNAL
34 RUN ZD SPDT RELAY (AC 250V 0.5A)
23
35 COM
PC (Enable) 24
36 PC
25 FAULT
38 COM FT SPDT RELAY (AC 250V 0.5A)
ES 26
40 E. STOP
27
28 FIELD LOSS
FL SPDT RELAY (AC 250V 0.5A)
29
L2F
RUN RUN
F- F2
RUN +
L1S 1
JOG L2S _ TG
RUN L3S 2
JOG JOG 30 TS
17 ARMATURE
31 ST A AMMETER
18 INPUT: 0 to 2V P1 P2
115VAC 19
115V N SPEED METER
1 PHASE
RUN 18 INPUT: 0 to 1mA
PC PC 7 8V
SPEED 20 FIELD
JOG 8 REF F AMMETER
REFERENCE
9 COM 18 INPUT: 0 to 2V
ZD PC JOG 21
33 JOG
RUN 22 ROTATION SIGNAL
34 RUN ZD
23 SPDT RELAY (AC 250V 0.5A)
35 COM
Note: All relays are showen when PC (Enable) 24
36 PC
the power is off. Exsample: When the REV 25 FAULT
37 REV FT
power is on the ES contact will close. 26
SPDT RELAY (AC 250V 0.5A)
38 COM
ES
40 E. STOP 27
28 FIELD LOSS
FL SPDT RELAY (AC 250V 0.5A)
29
CA
/10
P1
+V -15 +15 /10
P4
/10
TL
LV
COM TG
IMX HS /10
/10 /10
OC
9
COM
OL
A-1
A-2
A-3
A-4
FU
EXTRA JUMPERS
LV
F-1
F-2
F-3
F-4
F-5
PH
EF
FL
FV
10
FI
8
OH
ES
FL
AP
7
P
IF FM ZERO
IFR ZD
/10 /10 /10
IG FL RL SR SG DG PI OP
/10 /10 /10 /10 /10 /10 /10 /10
TG
50H
RESET
9
5A 5
/10 8
AP
CROS 7
/10 FE
6
COM
M3 M4
1 2 4 6 10
SF
VF
+B
5
4
T-4
T-3
T-2
T-1
2
3
S-1
S-2
S-3
S-4
R5
PC
R
1
R2
CONNECTION TERMINALS 1 TO 40
42NM3-*
42RM2-*
42RM3-*
42XXNL5-*
42XXNL4-*
42XXNL7-*
42NL1-*
42NL2-*
42NS1-*
42NS2-*
42NS3-*
42NS4-*
42RL1-*
42RL2-*
42RS1-*
42RS2-*
42RS3-*
42RS4-*
Model Number
Max., Current 37A 70A 110A 180A 400A 550A 720A 910A 1,100A 1,400A 1,800A
Input 208~240V, Arm 240V 7 HP 15 HP 25 HP 45 HP 100 HP 125 HP 200 HP 250 HP 300 HP --- ---
Input 380~410V, Arm 440V 3 kW 20 kW 32 kW 58 kW 130 kW 165 kW 233 kW 375 kW --- --- ---
Input 440~480V, Arm 500V 14 HP 30 HP 50 HP 90 HP 200 HP 250 HP 400 HP 500 HP 600 HP 750 HP 1,000 HP
Input 575~600V, Arm 600V --- 36 HP 60 HP 108 HP 240 HP 300 HP 480 HP 600 HP 720 HP 900 HP 1,200 HP
Page 50
Alphabetical Index
1 Jumper (JP-1) Pg. 9 Section 4.7
10 Jumper (JP-10) Pg. 49 Jumper Table
1058C Synchronization Card Pg. 39
1059A Regulator Card Physical Diagram Pg. 48
2 Jumper (JP-2) Pg. 13, Sec 4.14 and Pg. 49
2 Quadrant, 6 SCR Elementary Diagram Pg. 54
3 Jumper (JP-3) Pg. 13, Sec 4.14 and Pg. 49
4 Jumper (JP-4) Pg. 49 Jumper Table
4 Quadrant, 12 SCR Elementary Diagram Pg. 54
5 Jumper (JP-5) Pg. 49 Jumper Table
50H Jumper Pg. 49 Jumper Table
6 Jumper (JP-6) Pg. 49 Jumper Table
7 Jumper (JP-7) Pg. 5, Sec 3.5 and Pg. 18, Sec 5.11A
8 Jumper (JP-8) Pg. 5, Sec 3.5 and Pg. 18, Sec 5.11A
9 Jumper (JP-9) Pg. 49 Jumper Table
9042-1 Regulator Card Block Diagram Pg. 43
9042-2 Regulator Card Block Diagram Pg. 44
9042-3 Regulator Card Block Diagram Pg. 45
9044 Regulator Card Control Block Diagram Pg. 42
A1~A4 Jumpers Pg. 5, Sec 3.2 and Pg. 8, Sec 4.4
AC contactor Pg 23 Section 5.18
AC Power Connections Pg. 7 Section 4.1
ACC Potentiometer Pg. 20 Section 5.13
Acceleration and Deceleration Time Range Jumpers Pg. 5 Section 3.6
AM Potentiometer Pg. 13 Section 4.14
AP Jumper Pg. 49 Jumper Table
Armature Ammeter Wiring and Calibration Pg. 13 Section 4.14
Armature and Field in series (see field disable) Pg. 18 Section 5.11C
Armature Connections Pg. 7 Section 4.4
Armature Current Calibration Pg. 19 Section 5.12
Armature Current is too high at low speed and normal load. Pg. 32 Section 6.12
Armature Current Jumpers Pg. 5 Section 3.2
Armature Current Limit Adjustment Pg. 19 Section 5.12A
Armature Feedback Jumper Settings Pg. 5
Armature Feedback Jumper Settings Pg. 4
Armature Voltage Adjustment Pg. 19 Section 5.12
ASR Feedback Loop Adjustment ( i.e. Speed PID ) Pg. 21 Section 5.15
Balancing Phase Load Pg. 25 Section 6.1
CA Jumper Pg. 18 Sections 5.11A
Check prior to operation Pg. 15 Section 5.1
CROS Potentiometer Pg. 18, Sec 5.11A & Pg. 19, Sec 5.12
Current Gain Loop Adjustment ( i.e. Current PID ) Pg. 21 Section 5.16
Current Limit Adjustment Pg. 19 Section 5.12A
DC Contactor Pg. 23 Section 5.19
DC Tach Generator Feedback Pg. 10 Section 4.11
DC Tach Voltage Jumpers Pg. 5 Section 3.4
DEC Potentiometer Pg. 20 Section 5.13
Deceleration and Acceleration Time Range Jumpers Pg. 5 Section 3.6
DG Potentiometer Pg. 49 Potentiometer Table
EF Jumper Pg. 16 Section 5.5
Elementary Circuit Diagrams Pg. 54
Elementary Diagram of DC Drive Power Connections Pg. 6
Emergency Stop (E.Stop) Pg. 10 Section 4.10
Emergency Stop (E. Stop) Pg. 16 Section 5.5
Environment, Operation Pg. 3 Section 2.1
ES light (Emergency Stop) Pg 25 and Pg. 49, Section 5.11B
Page 51
Alphabetical Index Continued
Field Ammeter Wiring and Calibration Pg. 14 Section 4.15
Field Amperage Adjustment Pg. 18 Section 5.11
Field and Armature in Series (see field disable) Pg. 18 Section 5.11C
Field Connections Pg. 8 Section 4.5
Field Current Jumpers Pg. 5 Section 3.1
Field Disable Pg. 18 Section 5.11C
Field Economy Pg. 18 Section 5.11B
Field Loss Pg. 18 Section 5.11E
Field Loss is Detected. Pg. 31 Section 6.11
Field Overview Pg. 18 Section 5.11
Field Regulation Jumpers Pg. 5 Section 3.5
Field Weakening Adjustment (Tach Feedback Only) Pg. 18 Section 5.11A
FL Jumper Pg. 18 Sections 5.11C & 5.11E
FL light Pg 25, Pg. 33 Section 6.14 and Pg. 49
FL Potentiometer Pg. 19 Section 5.12A
FM Potentiometer Pg. 14 Section 4.15
Forward and Reverse Current Limit Adjustment Pg. 19 Section 5.12B
FT Potentiometer Pg. 15, Sec 5.4 and Pg. 16, Sec 5.5
FU light Pg 25 and Pg. 49
Fuse Replacement Pg. 7 Section 4.3A
Fuses blow immediately after start and the “OC signal lights Pg. 28 Section 6.4
FV Jumper Pg. 14 Section 4.15
Grounding Pg. 7 Section 4.2
Horsepower Rating Pg. 3 Section 1.1
HS Potentiometer Pg. 17 Section 5.8
IA Potentiometer Pg. 19 Section 5.12C
IF Potentiometer Pg. 18 Sec 5.11A and Pg. 14 Sec 4.15
IFC 1084 card Pg. 38
IFR Jumper Pg. 49 Jumper Table
IG Potentiometer Pg. 21 Section 5.16
IMX Potentiometer Pg. 19 Sections 5.12, 5.12A, 5.12B
Installation Location Pg. 3 Section 2
Instantaneous Overload Current Shut-off Adjustment Pg. 19 Section 5.12D
Jog Pg. 10 Section 4.8
JOG Potentiometer Pg. 15 Section 5.4
Jog Speed & Acceleration Adjustment Pg. 15 Section 5.4
Jumper Setting Diagram Pg. 4
Jumper Settings Pg. 5 Section 3
Jumper Table Pg. 5 and Pg. 49
L1 Model Physical Diagram Pg. 37
L2 Model Physical Diagram Pg. 37A
Location, Installation Pg. 3 Section 2
LV light (i.e. LVL) Pg. 25 and Pg. 49
M2 Model Physical Diagram Pg. 35
M3 Model Physical Diagram Pg. 36
Master Slave Operation Pg. 22 Section 5.17
MAX Potentiometer Pg. 18, Sec 5.11A and Pg. 17, Sec 5.9
Maximum Speed for Armature Feedback Adjustment Pg. 17 Section 5.9
Maximum Speed for DC Tach Feedback Adjustment Pg. 17 Section 10
Meter Dimensions Pg. 11 Section 4.12
Model Number Scheme Pg. 3 Section 1.1
Motor Data and Elementary Motor Connection Diagram Pg. 41
Motor Feedback Jumpers Pg. 5 Section 3.3
Motor Rotation Detection Relay and Signal Light Adjustment (i.e. ZD) Pg. 16 Section 5.6
Motor Speed Runaway Pg. 27 Section 6.3
Motor will not go to full speed Pg. 30 Section 6.6
Page 52
Alphabetical Index Continued
Motor information Pg. 41
Motor connections Pg. 41
NA Potentiometer Pg. 12 Section 4.13
OC light Pg 25 and Pg. 49
OH light Pg 25 and Pg. 49
OL light Pg 25 and Pg. 49
One Minute Timed Overload Shut-off Adjustment Pg. 19 Section 5.12C
OP Potentiometer Pg. 16 Section 5.5
Operating Environment Pg. 3 Section 2.1
Operation and Adjustment Pg. 15 Section 5
Oscilloscope Pg. 40
Overload “OL” signal light Pg. 30 Section 6.8
Overshoot and Undershoot Pg. 30 Section 6.7
Overshoot and Undershoot Pg. 20 and Pg.30
P1 ~ P6 Potentiometer Pg. 26 Section 6.1A
PC, Pre-Operational Conditions (i.e. Enable Drive) Pg. 9 Section 4.6
Permanent Magnet Field Pg. 8 Section 4.5A
Permanent Magnet Field (see field disable) Pg. 18 Section 5.11C
PH light (Phase loss or phase sequence error) Pg 25 , Pg. 33, Pg 33A and Pg. 49
Phase Load Balancing Pg. 25 Section 6.1
Phase Sequence Test Pg. 7 Section 4.3
PI Potentiometer Pg. 21 Section 5.15
PID Current Regulation (i.e. Current Gain Loop Adjustment) Pg. 21 Section 5.16
PID Speed Regulation (See ASR Feedback Loop Adjustment) Pg. 21 Section 5.15
Potentiometer Table Pg. 49
Power and Control Circuit Wiring Introduction Pg. 7 Section 4
Pre-Operation Voltage Checks Pg. 15 Section 5.2
-R Potentiometer Pg. 49 Potentiometer Table
Receiving & Storage Pg. 3 Section 1
Regenerative 12 SCR Elementary Diagram Pg. 54
Regulator Card Block Diagram # 9042-1 Pg. 43
Regulator Card Block Diagram # 9042-2 Pg. 44
Regulator Card Block Diagram # 9042-3 Pg. 45
Regulator Card Control Block Diagram # 9044 Pg. 42
Regulator Card Physical Diagram Pg. 48
Regulator Card Tables (for Pots, Jumpers, Signal Lights and Test Points) Pg. 49
Reverse Current Limit Adjustment Pg. 19 Section 5.12B
Reversing 12 SCR Elementary Diagram Pg. 54
RL Potentiometer Pg. 19 Section 5.12A
S Model Physical Diagram Pg. 34
S1 and S2 motor leads Pg 41
S1~S4 Jumpers Pg. 5, Sec 3.4 and Pg. 10, Sec 4.11
Series Field and Armature Motors (see field disable) Pg. 18 Section 5.11C
SF Jumper Pg. 5, Sec 3.3 and Pg. 17, Sec 5.10
SG Potentiometer Pg. 20 Section 5.14A
Signal Light Table Pg. 49
Signal lights R and PC are on F,AP, ZD flash and relays buzz. Pg. 31 Section 6.10
Slave Master Operation Pg. 22 Section 5.17
Speed Meter Wiring and Calibration Pg. 12 Section 4.13
Speed Overshoot Adjustment (i.e. Speed Response) Pg. 20 Section 5.14A
Speed Overshoot and Stability Adjustment Overview Pg. 20 Section 5.14
Speed Reference & Reverse Pg. 9 Section 4.7
Speed Stability Adjustment (i.e. Speed Gain) Pg. 20 Section 5.14B
SR Potentiometer Pg. 20 Section 5.14A
Page 53
Alphabetical Index Continued
Stabilizing field winding Pg. 32 Section 6.12B and Pg 41
Start & Stop (i.e. Run & Stop) Pg. 10 Section 4.9
Synchronization Card 1058C Pg. 39
T1~T4 Jumpers Pg. 5, Sec 3.6 and Pg. 10, Sec 4.11
Tach Feedback Jumper Settings Pg. 5 Section 3.3
Terminal Table (for Regulator Card) Pg. 47
Test Point Table Pg. 49
Test Run Pg. 15 Section 5.3
TG Jumper Pg. 5 Section 3.3
TG light (i.e. TGL) Pg. 25 and Pg. 49
TG Voltage Jumpers Pg. 4 Section 3.4
The ES, OH, VL signal lights are on and can not be reset Pg. 31 Section 6.9
TL Jumper Pg. 5, Sec 3.3 and Pg. 18, Sec 5.11C
Troubleshooting Pg. 25 Section 6
Undershoot and Overshoot Pg. 30 Section 6.7
Unstable Speed Pg. 29 Section 6.5
VF Jumper Pg. 5 Section 3.3
Wire Size Tables Pg. 6
Wiring Pg. 7 Section 4
ZD, Zero motor rotation Detection relay and signal light Adjustment Pg. 16 Section 5.6
ZERO Potentiometer Pg. 16 Section 5.7
Zero Speed Hysteresis Adjustment (12 SCR Regenerative Drives Only) Pg. 17 Section 5.8
Zero Speed Adjust (12 SCR Regenerative Drives Only) Pg. 16 Section 5.7
Page 54