GS-T 10 / 20 / 25A, GS 15 / 25 / 40 / 50 / 60 / 75 / 90 / 120A
SOLID STATE RELAYS WITH LOGIC CONTROL
Main features
• Alternating current solid state relay
Main applications
• Zero crossing switching
• Plastics extrusion lines
• Copper/semiconductor coupling
and injection moulding
machines technology
• Packing and packaging • 10, 15, 20, 25, 40, 50, 60, 90, and
machines 120 Arms nominal current
• Polymerization plant for • Non-repetitive voltage: up to
synthetic fibre production 1200Vp
• Rubber moulding • Nominal Voltage: up to
machinery 530VCArms
• Driers for ceramics and
• Input control range: 5...32 Vcc
components for the
• 4000 Vrms optoinsulation
building industries
• Chemical and (input-output)
pharmaceutical industries • Green LED, drive input signal
• Industrial electric furnaces indicator
• Food processing plants • MOV (varistors)
Zero crossing relay with antiparallel General features GS-T10 (TRIAC version)
thyristor output is the most used solid Category of use: AC1 Nominal currents of the device with
state relay in industrial applications. Nominal voltage opportune heatsink in continuous
- 230Vac (max. range 24...280Vac) work: 10A
“Zero crossing” relay is energised
- 480Vac (max. range 24...530Vac) Non-repetitive overcurrent t=20 ms: 30A
when voltage meets the zero point I2t for blowout: 72A2s
and disenergised when current Nominal frequency: 50/60Hz
Non-repetitive voltage: dV/dt critical with output deactivated:
meets the zero point, depending on 500V/µs
the signal control on the input circuit. • 500Vp for model with rated voltage
For applications with merely resistive 230Vac GS-T20 (TRIAC version)
loads, “T” version is available with • for model with rated Nominal currents of the device with
TRIAC output. voltage 480Vac opportune heatsink in continuous
When the relay has to stand high Switching voltage for zero: < 20V work: 20A
currents for a long period, it is Activation time: ≤ 1/2 cycle Non-repetitive overcurrent t=20 ms: 50A
necessary to grant a proper Deactivation time: ≤ 1/2 cycle I2t for blowout: 315A2s
Potential drop at rated current: ≤ 1.4V dV/dt critical with output deactivated:
dissipation and an adequate 500V/µs
electrical connection between relay Power factor = 1
terminals and the load. Control inputs GS-T25 (TRIAC version)
Use the relè with an opportune heatsink Max. input: < 10mA@32V Nominal currents of the device with
(see section accessories). Max. reverse voltage: 36Vdc opportune heatsink in continuous
Varistors, fuses, thermostats and work: 25A
fans are available as fittings. GS-T10/T20/T25 (TRIAC version) Non-repetitive overcurrent t=20 ms: 50A
Control voltage: 5...32Vdc I2t for blowout: 315A2s
Activation voltage: > 4,2Vdc dV/dt critical with output deactivated:
Deactivation voltage: < 2Vdc 500V/µs
Accessory
LAB-1
100mm
V
Control input
A ON ON
OFF
t
V=
Voltage on load
B C
GS thermal protection
V Control input
ON
OFF
t
FUSE LOAD
Line Load
Digital output
GS 60A/480 Vac
AC1 50/60 Hz
AL
ON
6 ÷ 32 Vcc
Load
AL AL AL
ON ON ON
Digital output
Three-phase Triangle or Star connection without neutral on two phases
Phase R
Phase S
Phase T
Ground
Triangle Triangle
connection connection
Fuse Fuse
R
R R
Line Load Line Load R R
R
AL AL
Controller
ON ON
6 ÷ 32 Vcc 6 ÷ 32 Vcc
ON/OFF Control ON/OFF Control
Digital output
TABLE OF TERMINALS AND CONDUCTORS
(*) Female faston (for insertion, remove the M3 screw by making the nut re-enter the seat in the holder)
(**)The max. sections specified refer to unipolar copper wires isolated in PVC.
ACCESSORIES
A wide range of accessories is available (including fuses and fuse holders, heat sinks, ID plates and
thermostats).
To choose accessories, see the section "Solid state relays - Accessories."
ORDER CODE
GS-T / 230 GS /
Model Model
Version with
TRIAC version GS-T GS
double SCR
Rated voltage
230Vac 230
480Vac 480
•WARNINGS
Read the following warnings before installing, connecting or using the device:
• follow instructions precisely when connecting the device.
• always use cables that are suitable for the voltage and current levels indicated in the technical specifications.
• in applications with risk of damage to persons, machines or materials, you MUST install auxiliary alarm devices.
• it is advisable to be able to check alarm states during normal operation as well
• DO NOT operate the device in rooms with dangerous (inflammable or explosive) atmosphere.
• During continuous operation, the heat sink can reach up to 100°C, and stays at a high temperature even after the device is turned off due to
thermal inertia; therefore, DO NOT touch it and avoid contact with electrical wires.
• do not work on the power part without first disconnecting electrical power to the panel.
• do not remove the cover when the device is powered!
Installation:
• correctly ground the device using the specific terminal.
• power supply lines must be separated from device input and output lines; always check that the supply voltage matches the voltage indicated
on the device label.
• avoid dust, humidity, corrosive gases and heat sources.
• respect the installation distances between one device and another (to allow for dissipation of generated heat).
• to keep air in movement, we advise you to install a fan near the GTS group in the electrical panel containing the GTSs.
• respect the indicated dissipation curves
Maintenance: at regular intervals, check operation of the cooling fans and clean all air ventilation filters.
• repairs must be done out only by trained and specialized personnel. Cut power to the device before accessing internal parts.
• do not clean the box with solvents derived from hydrocarbons (trichloroethylene, gasoline, etc.). Using such solvents will compromise the
device's mechanical reliability. Use a clean cloth moistened with ethyl alcohol or water to clean external parts in plastic.
Service: GEFRAN has a service department. The warranty excludes defects caused by any use not conforming to these instructions.
GEFRAN spa reserves the right to make aesthetic or functional changes at any time and without notice.
This device conforms to European Union Directive 89/336/CEE and 73/23/CEE as amended with reference to generic standards:
CEI-EN 61000-6-2 (immunity in industrial environment) EN 61000-6-4 (emission in industrial environment) - EN 61010-1 (safety
regulations).
Main applications
• Extrusion lines and
injection presses for
plastics
• Hot channels
• Thermoforming machines
• Packing and packaging
machines
• Temperature controllers for Main features
molds • Logic signal input control
• Electric kilns for ceramics • LED display of logic control state
and goldsmith's shop • Switching at voltage zero crossing.
• Machines for the food • Overvoltage protection
industry • Faston connections
FACEPLATE DESCRIPTION
3 Load 4
5 6
A1 A2
7 + 8
LED display of control state
WORKING TYPOLOGY
V Control input
ON ON
OFF
t
V=
Load voltage
MOUNTING DIMENSIONS
24 mm
5.4
1 Line 2
58.3
3 Load 4
47.5
5 6
A1 A2
7 + 8
22 mm
5.4
weight = 70 g
Single-phase connection
Phase
Neutral
Ground
Fuse Load
1 Line 2
3 Load 4
5 6
A1 A2
7 8
+ -
Controller
For other types of connection (3-phase star with neutral, 3-phase triangle or star without neutral on two phases) refer to the
ACCESSORIES
A wide range of accessories is available, such as fuses and fuse holders, relay bases, panel attachments and DIN
guide attachments, thermostats.
To choose accessories, see the section "Solid state relays - Accessories”.
ORDER CODE
GS-L /
Model
GS-L
Nominal current
5Aac 5
10Aac 10
15Aac 15
Nominal voltage
230Vac 230
440Vac 440
•WARNINGS
GEFRAN spa reserves the right to make any kind of design or functional modification at any moment without prior notice
Main features
• Alternating current solid state relay
• Zero crossing switching
• Copper/semiconductor coupling
technology
• 10, 25, 50, and 90 Arms nominal
current
• Non-repetitive voltage: up to 1200 Vp
Main applications • Nominal Voltage: up to 530VCAms
• Packaging Machinery • Input control range:
• Thermoforming 3...32Vcc, 5...32Vcc, 90...280Vac/cc
• Plastic extrusion lines • 4000 Vrms optoinsulation
• Industrial ovens and (input-output)
furnaces • Green LED, drive input signal
• Control application with indicator
high switching speed • MOV (varistors)
RA ..25.. ..
Operating Temperature: -40°C...+100°C
Storage Temperature: -40°C...+100°C
Junction Temperature: ≤ 125°C
DIMENSIONS
**
***
***
***
***
USE
SILICON
PASTE
** = ±0,4 mm
***= ±0,5 mm **
ELECTRICAL CONNECTIONS
BLOCK DIAGRAM
RA
RA RA RA
RA
RA
SINGLE-PHASE SYSTEM
RA
RA RA RA
RA RA
!
OPERATIONAL DIAGRAM
Control
input
RA
MODEL
RA
NOMINAL VOLTAGE
230VCArms 24
400VCArms 44
480VCArms 48
NOMINAL CURRENT
25ACArms 25
50ACArms 50
90ACArms 90
CONTROL VOLTAGE
3...32VCC
D
5...32VCC
90...280VCA/CC HA
NON-REPETITIVE VOLTAGE
650Vp. (with 230VCA) 06
850Vp. (with 400VCA) 08
1200Vp. (with 480VCA) 12
Examples of the operation of the GT for different values of the input drive signal and the consequent different cycle times
(100msec and 40msec respectively).
GT thermal protection
Control
input
ON
OFF
t
t
V = Load voltage
Thermal protection
activation
FACEPLATE DESCRIPTION
Reference connection of 230V line voltage Reference connection of 480V line voltage (HB option
(HB option with 150V to 300V load) with 300V to 530V load)
The solid-state power unit, Gt, is supplied factory calibrated for 0..5V, 0..10V, 0..20mA, 4..20mA, 10Kohm potentiometer.
Minimum and maximum values are adjusted with two monorev trimmers (d,e).
Input signal type is selected with the adjustment f dip switches (S1,S2,S3).
Minimum adjustment trimmer (d) turned fully counterclockwise sets the start conducting limit at 4% of the signal; turned fully
clockwise, the minimum conducting limit is set at 18% of the input signal.
Maximum adjustment trimmer (e) turned fully clockwise sets the full conducting limit at 96% of the signal; turned fully
counterclockwise, the full conducting limit is set at 82% of the input signal.
CALIBRATION PROCEDURE OF THE INTERRUPTED LOAD ALARM
The interrupted load alarm function enables the GT to diagnose a variation of the load current (compared to a set limit),
distinguishing it from one caused by a change in grid voltage. The solid state power unit must therefore be supplied with the
voltage applied to the load terminals, i.e.: LOAD (L2): already connected internally;
LINE (h or i): connect terminal h for voltages from 150 to 300V; connect terminal i for voltages from 300 to 530V.
The alarm activates (relay closed and yellow alarm LED on) when the current, during the conduction of the device, falls below
a preset level that may be adjusted using the trimmer on the faceplate.
N.B:
the partial load break alarm function operates with power partialization exceeding 15%. For partializations below 20%, tripping
times increase due to the reduced load activation time. For correct operation of the option, the load current has to exceed 30%
of rated current for the GT.
- The logic control signal has to be connected with the correct polarities to terminals 4 and 5 of the analog input.
- Turn minimum adjustment trimmer (d) fully counterclockwise and maximum adjustment trimmer (e) fully clockwise.
- Set the 3 dip switches (f) to off.
For applications with a very short work cycle, you can drive the solid state group by means of the Master/Slave signal by
driving it with a digital signal (OFF = 0 V dc; ON = from 4 V dc to 10 V dc)
Inhibiting the GT
The GT can be used as a master to drive other solid state groups (slaves). With Master/Slave signal (3), you can drive up to 9
GTs (see connection examples for GT solid state power relays with three-phase load). You can also use a GT to drive GS solid
state power relays (maximum of 2), as shown in the connection diagrams for GT/GS solid state power relays with three-phase
load (attention: the HB option cannot be used for a three-phase application with neutral).
DIMENSIONS AND CUT-OUT TEMPLATE DIMENSIONS
GT 25 - 40 - 50 - 60 - 7560- mm
90 - 120A
60 mm
L2 i h L1
Load Line Line Line
26 mm
480 V 230 V
0..10V
g Alarm Adj
f Input selection
0..5V
e Max Adj
4..20mA d Min Adj
0..20mA c Reset Alarm
Accessory
LAB-1
GT 25A/480 Vac
100mm
47.5 mm
AC1 50/60 Hz
100 mm
AL
PWR ON
Analog Alarm
Input Master Out
24 Vac +10 Vdc
Supply Out Slave 30 Vdc/ac
8 7 6 5 4 3 2 1
CONNECTION EXAMPLES
Ground
Neutral
Phase
* *
Load
Fuse
tension. 0..5V
4..20mA
f Input selection
e Max Adj
d Min Adj
0..20mA c Reset Alarm
GT 25A/480 Vac
AC1 50/60 Hz
24Vac 1,5VA
Controller
AL
Digital output
0-20mA PWR ON
4-20mA
0-10Vdc 24 Vac +10 Vdc
Analog
Input Master
Slave
Alarm
Out
Supply Out 30 Vdc/ac
0-5Vdc 8 7 6 5 4 3 2 1
Star or delta three-phase connection without neutral, with control of two phases.
Phase R
Phase S
Phase T
Ground
Fuse
Fuse
according to the load
tension.
Star connection Three-phase connection L2
Load
i
Line
h
Line
L1
Line
L2
Load
i
Line
h
Line
L1
Line
480 V 230 V 480 V 230 V
0..10V
g Alarm Adj 0..10V
g Alarm Adj
f Input selection f Input selection
0..5V 0..5V
e Max Adj e Max Adj
4..20mA d Min Adj 4..20mA d Min Adj
0..20mA c Reset Alarm 0..20mA c Reset Alarm
24Vac 1,5VA AL AL
PWR ON PWR ON
Controller
Analog Alarm Analog Alarm
Input Master Out Input Master Out
24 Vac +10 Vdc 24 Vac +10 Vdc
Supply Out Slave 30 Vdc/ac Supply Out Slave 30 Vdc/ac
8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1
Digital output
0-20mA Potentiometer
4-20mA
0-10Vdc
0-5Vdc
Star or delta three-phase connection without neutral, with control of three phases.
Phase R
Phase S
Phase T
Ground
* * * * * *
0..10V
g Alarm Adj 0..10V
g Alarm Adj 0..10V
g Alarm Adj
f Input selection f Input selection f Input selection
0..5V 0..5V 0..5V
e Max Adj e Max Adj e Max Adj
4..20mA d Min Adj 4..20mA d Min Adj 4..20mA d Min Adj
0..20mA c Reset Alarm 0..20mA c Reset Alarm 0..20mA c Reset Alarm
8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1
Phase S
Phase T
Neutral
Ground * * * * * *
Fuse
Fuse
Fuse
load interrupted option (see
paragraph “Interrupted load
alarm)
Note: connect h or i L2
Load Line
i h
Line
L1
Line
L2
Load Line
i h
Line
L1
Line
L2
Load Line
i h
Line
L1
Line
0..10V
g Alarm Adj 0..10V g Alarm Adj 0..10V
g Alarm Adj
f Input selection f Input selection f Input selection
tension.
0..5V 0..5V 0..5V
e Max Adj e Max Adj e Max Adj
4..20mA d Min Adj 4..20mA
d Min Adj 4..20mA d Min Adj
0..20mA c Reset Alarm 0..20mA c Reset Alarm 0..20mA c Reset Alarm
24Vac 1,5VA AL AL AL
8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1
Digital output
0-20mA Potentiometer
4-20mA
0-10Vdc
0-5Vdc
Three-phase connection (triangle or star) without neutral, with control of two phases using one GT in Master configuration
and one GS in Slave configuration.
Phase R
Phase S
Phase T
Ground
* *
* Connections regarding the
load interrupted option (see
paragraph “Interrupted load
alarm)
Fuse
Fuse
Note: connect h or i
according to the load Star connection Three-phase connection
tension.
L2 i h L1
Load Line Line Load
Line Line
480 V 230 V
0..10V
g Alarm Adj
f Input selection
0..5V
e Max Adj
4..20mA d Min Adj
0..20mA c Reset Alarm
24Vac 1,5VA AL AL
ON
Controller PWR ON
0-20mA 8 7 6 5 4 3 2 1
4-20mA
0-10Vdc
0-5Vdc Potentiometer
Three-phase star connection with neutral using one GT in Master configuration and two GSs in Slave configuration.
Phase R
Phase S
Phase T
Neutral
Ground
Load
Fuse
Fuse
Fuse
L2 i h L1
Load Line Line Load Line Load
Line Line
480 V 230 V
0..10V
g Alarm Adj
f Input selection
0..5V
e Max Adj
4..20mA d Min Adj
0..20mA c Reset Alarm
24Vac 1,5VA AL AL AL
PWR ON ON ON
Controller
Analog Alarm
Input Master Out 6÷32Vcc 6÷32Vcc
24 Vac +10 Vdc
Slave ON/OFF Control ON/OFF Control
Digital output 8
Supply
7 6
Out
5 4 3
30 Vdc/ac
2 1
0-20mA
4-20mA
0-10Vdc
0-5Vdc Potentiometer
Contact Type of pre- Max section. ** Contact Type of pre- Max section. ** Contact Max section. **
Size area isolated terminal conductor area isolated terminal conductor area conductor
(WxD) tightening (WxD) tightening (WxD) tightening
screw type torque screw type torque screw type torque
25/40A 6,3x9 Eye/fork / 2.5mm2 16x18 Eye/fork 50mm2 14x16 50mm2
50/60A M3 tip 0.6Nm Max M6 3.5-6 Nm M5 1.8-2.5Nm
75-90A 6,3x9 Eye/fork / 2.5mm2 16x18 Eye/fork 50mm2 14x16 50mm2
M3 tip 0.6Nm Max M6 3.5-6 Nm M5 1.8-2.5 Nm
120A 6,3x9 Eye/fork / 2.5mm2 16x18 Eye/fork 50mm2 14x16 50mm2
M3 tip 0.6Nm Max M6 3.5-6 Nm M5 1.8-2.5 Nm
(**) The max. sections specified refer to unipolar copper wires isolated in PVC.
• Note: For the ground terminal, you have to use an eye wire terminal.
(WxD) = Width x depth
ACCESSORIES
A wide range of accessories is available (including fuses and fuse holders, supports for fastening DIN bar, ID
plates, thermostats, current transformers and isolation transformers). To choose accessories, see the section
"Solid state relays - Accessories."
ORDER CODE
GT / 480 -
Model
GT
Nominal current
25Aac 25
40Aac 40
50Aac 50
60Aac 60
75Aac 75
90Aac 90
120Aac 120
Nominal voltage
480Vac 480
Load interrupt
(HB) option
Without option 0
With load
1
interrupt option
•WARNINGS
GEFRAN spa reserves the right to make any kind of design or functional modification at any moment without prior notice
This device conforms to European Union Directive 89/336/CEE and 73/23/CEE as amended with reference to generic standards:
CEI-EN 61000-6-2 (immunity in industrial environment) EN 61000-6-4 (emission in industrial environment) - EN 61010-1 (safety
regulations).
Main applications
• Plastic extrusion lines and
injection presses
• Packing and packaging
machines
• Polymerization and
production plants for Main features
synthetic fibers • Input control from logic signal
• Rubber vulcanization plants • Switching at voltage zero crossing
• Driers for ceramics and • Versions with TRIAC and with double
construction elements SCR in antiparallel.
• Chemical and • LED power on indicator
pharmaceutical industry • MOV protections (varistor)
• Industrial electric furnaces • Fastening to DIN bar (standard);
• Food processing plants fastening to panel (optional)
24 mm 35 mm 60 mm 80 mm 127 mm
+ + + + +
30 mm
6÷32Vcc 6÷32Vcc 6÷32Vcc 6÷32Vcc 6÷32Vcc
ON/OFF Control ON/OFF Control ON/OFF Control ON/OFF Control ON/OFF Control
ON ON ON ON ON
108 mm
AL AL AL
100 mm
GTS 25A/480 Vac GTS 40A/480 Vac GTS 50A/480 Vac GTS 60A/480 Vac GTS 60A/480 Vac
AC1 50/60 Hz AC1 50/60 Hz AC1 50/60 Hz AC1 50/60 Hz AC1 50/60 Hz
Access.
LAB-1
Load Line Load Line Load Line Load Line Load Line
18 mm
14 mm
50 mm max.
Depth = 107 mm. Depth = 142 mm. Depth = 142 mm. Depth = 142 mm.
Weight = 320 g. Weight = 540 g. Weight = 900 g. Weight = 1200 g.
W V
Control input
ON ON
M5 OFF
t
V=
Voltage on load
ON
OFF
t
L(mm) W(mm)
red LED yellow LED yellow LED
ON
GTS 15-25 GTS-T 10-20 112 0 OFF
t
GTS 40 GTS-T 25 112 25
V = Voltage across load
GTS 50-60 112 44
ON
AL Controller
Load Line
Load Fuse
Phase
Neutral
Ground
Digital output
+ -
+ + +
6÷32Vcc 6÷32Vcc 6÷32Vcc
ON/OFF Control ON/OFF Control ON/OFF Control
ON ON ON
AL AL AL
Carico
Load Line Load Line Load Line
R R
Neutral
Phase R
Phase S
Phase T
Ground
+ -
+ +
6÷32Vcc 6÷32Vcc
ON/OFF Control ON/OFF Control
ON ON
AL AL
Controller
GTS 60A/480 Vac GTS 60A/480 Vac
AC1 50/60 Hz AC1 50/60 Hz
CTriangle CStar
connection connection
R
R R
R R R
Fuse Fuse
Phase R
Phase S
Phase T
Ground
DISSIPATION CURVES
GTS-T GTS 15 - 25
I (A)
40
35
30 30
25 25 25
20
15 15
10 10
0 40 80 T(C°)
30 30
20 20
10 15
0 40 80 T(C°)
N.B.: Curves for the GTS 120 refer to the device complete with standard running.
Contact Type of pre- Max section. ** Contact Type of pre- Max section. ** Contact Max section. **
Size area isolated terminal conductor area isolated terminal conductor area conductor
(WxD) tightening (WxD) tightening (WxD) tightening
screw type torque screw type torque screw type torque
10/15/ 6,4x9 Eye/fork/ 6mm2 6,4x9 Eye/fork/ 6mm2 9x12 6mm2
20A M3 Faston type conn* 0.6Nm Max M3 conn tipo Faston* 0.4-0.6 Nm M5 1.3-1.8 Nm
25A 6,4x9 Eye/fork/ 6mm2 6,4x9 Eye/fork 6mm2 9x12 6mm2
(GTS) M3 Faston type conn* 0.6Nm Max M3 0.4-0.6 Nm M5 1.3-1.8 Nm
40A 6,3x9 Eye/fork/ 2.5mm2 12x12 Eye/fork 16mm2 11,5x12 16mm2
25A(GTS-T) M3 tip 0.6Nm Max M5 1.5-2.2 Nm M5 1.5-2.2 Nm
50/60A 6,3x9 Eye/fork/ 2.5mm2 16x18 Eye/fork 50mm2 14x16 50mm2
M3 tip 0.6Nm Max M6 3.5-6 Nm M5 1.8-2.5Nm
75-90A 6,3x9 Eye/fork/ 2.5mm2 16x18 Eye/fork 50mm2 14x16 50mm2
M3 tip 0.6Nm Max M6 3.5-6 Nm M5 1.8-2.5 Nm
120A 6,3x9 Eye/fork/ 2.5mm2 16x18 Eye/fork 50mm2 14x16 50mm2
M3 tip 0.6Nm Max M6 3.5-6 Nm M5 1.8-2.5 Nm
(*) Female faston (for insertion, remove the M3 screw by making the nut re-enter the seat in the holder)
(**)The max. sections specified refer to unipolar copper wires isolated in PVC..
• Note: For the ground terminal, you have to use an eye wire terminal.
(WxD) = Width x depth
ACCESSORIES
A wide range of accessories is available (including fuses and fuse holders, heat sinks, ID plates and
thermostats).
To choose accessories, see the section "Solid state relays - Accessories."
ORDER CODE
Model Model
Version with
Version with TRIAC GTS-T GTS
double SCR
Rated current A
Rated current
15Aac 15
10Aac 10
25Aac 25
20Aac 20
40Aac 40
25Aac 25
50Aac 50
60Aac 60
Rated voltage
75Aac 75
230Vac 230
90Aac 90
120Aac 120
Rated voltage V
230Vac 230
480Vac 480
Read the following warnings before installing, connecting or using the device:
• follow instructions precisely when connecting the device.
• always use cables that are suitable for the voltage and current levels indicated in the technical specifications.
• In applications with risk of damage to persons, machines or materials, you MUST install auxiliary alarm devices.
It is advisable to verify frequently that the alarm device is functional even during the normal operation of the equipment.
• DO NOT operate the device in rooms with dangerous (inflammable or explosive) atmosphere.
• During continuous operation, the heat sink can reach up to 100°C, and stays at a high temperature even after the device is turned off due to
thermal inertia; therefore, DO NOT touch it and avoid contact with electrical wires.
• do not work on the power part without first disconnecting electrical power to the panel.
• do not remove the cover when the device is powered!
Installation:
• correctly ground the device using the specific terminal.
• power supply lines must be separated from device input and output lines; always check that the supply voltage matches the voltage indicated
on the device label.
• avoid dust, humidity, corrosive gases and heat sources.
• respect the installation distances between one device and another (to allow for dissipation of generated heat).
• to keep air in movement, we advise you to install a fan near the GTS group in the electrical panel containing the GTSs.
• respect the indicated dissipation curves
Maintenance: at regular intervals, check operation of the cooling fans and clean all air ventilation filters.
• repairs must be done out only by trained and specialized personnel. Cut power to the device before accessing internal parts.
• do not clean the box with solvents derived from hydrocarbons (trichloroethylene, gasoline, etc.). Using such solvents will compromise the
device's mechanical reliability. Use a clean cloth moistened with ethyl alcohol or water to clean external parts in plastic.
Service: GEFRAN has a service department. The warranty excludes defects caused by any use not conforming to these instructions.
GEFRAN spa reserves the right to make aesthetic or functional changes at any time and without notice.
This device conforms to European Union Directive 89/336/CEE and 73/23/CEE as amended with reference to generic standards:
CEI-EN 61000-6-2 (immunity in industrial environment) EN 61000-6-4 (emission in industrial environment) - EN 61010-1 (safety regu-
lations).
Main applications
• Extrusion lines and
injection presses for
plastics
• Hot channels
• Thermoforming machines
• Packing and packaging Main features
machines • Logic signal input control
• Temperature controllers for • Switching at voltage zero crossing.
molds • LED display of logic control state
• Electric kilns for ceramics • Overvoltage protection
and goldsmith's shop • Faston connections
• Machines for the food • Provision for DIN bar attachment,
industry panel attachment and base attachment
GTS-L 5/10/15
Ambient conditions:
Control voltage: 3...32Vdc
Activation voltage: >2.55Vdc • Working temperature:
Deactivation voltage: <1Vdc 0 to 80°C (see the dissipation
curves)
OUTPUTS • Max. relative humidity: 50% to 40°C
GTS–L 5 • Max. installation altitude:
Nominal current: 5A@40°C in continuous 2000m asl
service
Non-repetitive overcurrent t=20ms: 80A
• Pollution level: 3 • Vertical distance between a device and dissipated power.
• Storage temperature: -20..+85°C the panel walls >100mm • Installation restraints (distances to be
• Internal use • Horizontal distance between a device respected to grant dissipation with
and the panel walls: at least 20mm natural convection)
Installation notes • Vertical distance between devices: at • Line transistor max. voltage and
Models with external heatsink must be least 300mm derivative limits, for which the solid state
grounded. • Horizontal distance between devices: at relay is equipped with inside safety
Use the high-speed fuse indicated in the least 20 mm. devices (varistor).
catalog according to the connection Make sure that the wire raceways do not • pLeakage current < 4mA for GTS-Ls.
example. reduce such distances: if they do, install (max. value with rated voltage and
Applications with power solid state relays the groups cantilevered to the panel so junction temperature of 125°C).
require an automatic safety cutout to that air can flow vertically over the heat
disconnect the load power line. sink without obstructions.
For maximum reliability, install the device
correctly in the panel to have sufficient Limits of use
heat exchange between the heatsink and • Dissipation of thermic power on the
the air under conditions of normal device with restraints on the ambient
convection. temperature of the installation.
Mount it vertically (max. 10° inclination • Equipe the cabinet with an external air
from the vertical axis) change or air-condition it, to put out
FACEPLATE DESCRIPTION
3 Load 4
5 6
A1 A2
7 + 8
WORKING TYPOLOGY
V Control input
ON ON
OFF
t
V=
Load voltage
39,5 mm 22 mm 52 mm 35 mm
34 mm 46,5 mm
1 Line 2 1 Line 2
62 mm
61 mm
3 Load 4 3 Load 4
5 6 5 6
A1 A2 A1 A2
7 + 8 7 + 8
1 Line 2
47,5 mm
69 mm
3 Load 4
5 6
A1 A2
7 + 8
22 mm 35 mm
1 Line 2 1 Line 2
64 mm
62 mm
3 Load 4 3 Load 4
5 6 5 6
A1 A2 A1 A2
7 + 8 7 + 8
77 mm 35 mm
64.5 mm 27 mm
33.5 mm 20 mm
22 2
68 mm
81.5mm
DISSIPATION CURVES
GTS - L 5 / 10 / 15
I(A)
21
18
15 15
12
10
9
6 5
3
0 25 40 80 T(C°)
Single-phase connection
Phase
Neutral
Ground
* Only for 10 and 15 A models (with
external heatsink)
Fuse Load
1 Line 2
3 Load 4
5 6
A1 A2
7 8
+ -
Controller
For other types of connection (3-phase star with neutral, 3-phase triangle or star without neutral on two phases) refer to the
Contact Pre-isolated Max. section ** Contact Pre-isolated Max. section ** Contact Max. section **
Size area wire terminal conductor area wire terminal wire area conductor
(WxD) tightening (WxD) tightening (WxD) tightening
screw type torque screw type torque screw type torque
5A - Faston connector* 2.5mm2 6,4x9 Faston connector* 2.5mm2 - -
10A - Faston connector* 2.5mm2 6,4x9 Faston connector* 2.5mm2 9x12 2.5mm2
M4 1.3-1.8 Nm
15A - Faston connector* 2.5mm2 6,4x9 Faston connector* 2.5mm2 9x12 2.5mm2
M4 1.3-1.8 Nm
ACCESSORIES
A wide range of accessories is available, such as fuses and fuse holders, relay bases, panel attachments and DIN
guide attachments, thermostats.
To choose accessories, see the section "Solid state relays - Accessories”.
ORDER CODE
GTS-L /
Model
GTS-L
Nominal current
5Aac 5
10Aac 10
15Aac 15
Nominal voltage
230Vac 230
440Vac 440
•WARNINGS
GEFRAN spa reserves the right to make any kind of design or functional modification at any moment without prior notice
Examples of the operation of the GTT for different values of the input drive signal and the consequent different cycle times
(100msec and 40msec respectively)
100msec
40msec
Control
input
ON
OFF
t
t
V = Load voltage
Thermal protection
activation
FACEPLATE DESCRIPTION
Reference connection of 230V line voltage Reference connection of 480V line voltage (HB option
(HB option with 150V to 300V load) with 300V to 530V load)
The solid-state power unit, GTT, is supplied factory calibrated for 0..5V, 0..10V, 0..20mA, 4..20mA inputs, 10Kohm
potentiometer. Minimum and maximum values are adjusted with two monorev trimmers (d,e).
Input signal type is selected with the f adjustment dip switches (S1,S2,S3).
Minimum adjustment trimmer (d) turned fully counterclockwise sets the start conducting limit at 4% of the signal; turned fully
clockwise, the minimum conducting limit is set at 18% of the input signal.
Maximum adjustment trimmer (e) turned fully clockwise sets the full conducting limit at 96% of the signal; turned fully
counterclockwise, the full conducting limit is set at 82% of the input signal<
INTERRUPTED LOAD ALARM
The interrupted load alarm function enables the GTT to diagnose a variation of the load current (compared to a set limit),
distinguishing it from one caused by a change in grid voltage. e. The solid state power unit must therefore be supplied with the
voltage applied to the load terminals, i.e.: LOAD (L2): already connected internally;
LINE (h or i): connect terminal h for voltages from 150 to 300V; connect terminal i for voltages from 300 to 530V.
The alarm activates (relay closed and yellow alarm LED on) when the current, during the conduction of the device, falls below
a preset level that may be adjusted using the trimmer on the faceplate.
N.B:
the partial load break alarm function operates with power partialization exceeding 15%. For partializations below 20%, tripping
times increase due to the reduced load activation time. For correct operation of the option, the load current has to exceed 30%
of rated current for the GTT.
- The logic control signal has to be connected with the correct polarities to terminals 4 and 5 of the analog input.
- Turn minimum adjustment trimmer (d) fully counterclockwise and maximum adjustment trimmer (e) fully clockwise.
- Set the 3 dip switches (f) to off.
For applications with a very short work cycle, you can drive the solid state group by means of the Master/Slave signal by
driving it with a digital signal (OFF = 0 V dc; ON = from 4 V dc to 10 V dc)
You can inhibit operation of the GTT by means of the Master/Slave signal.
To inhibit, connect control signal - (4) with the synchronism signal for Master/Slave connection (3).
The GTT can be used as a master to drive other solid state groups (slaves). With Master/Slave signal (3), you can drive up to 9
GTTs (see connection examples for GTT solid state power relays with three-phase load). You can also use a GTT to drive GTS
solid state power relays (maximum of 2), as shown in the connection diagrams for GTT/GTS solid state power relays with
three-phase load (attention: the HB option cannot be used for a three-phase application with neutral).
DISSIPATION CURVES
GTT 25 / 40 GTT 50 / 60
GTT 75 / 90 / 120
The GTT 120 curves refer to the device complete with standard fan running.
Contact Pre-isolated Max. section ** Contact Pre-isolated Max. section ** Contact Max. section **
Size area wire terminal conductor area wire terminal wire area conductor
(WxD) tightening (WxD) tightening (WxD) tightening
screw type torque screw type torque screw type torque
25/40A 6,3x9 Eye/fork/ 2,5mm2 16x18 Eye/fork 50mm2 14x16 50mm2
50/60A M3 tip 0,6Nm Max M6 3,5-6 Nm M5 1,8-2,5Nm
75-90A 6,3x9 Eye/fork/ 2,5mm2 16x18 Eye/fork 50mm2 14x16 50mm2
M3 tip 0,6Nm Max M6 3,5-6 Nm M5 1,8-2,5 Nm
120A 6,3x9 Eye/fork/ 2,5mm2 16x18 Eye/fork 50mm2 14x16 50mm2
M3 tip 0,6Nm Max M6 3,5-6 Nm M5 1,8-2,5 Nm
(**)The maximum sections indicated refer to unipolar copper wires with PVC insulation.
• Note: you have to use an eye terminal for the ground connection.
(WxD) = width x depth
DIMENSIONS AND CUT-OUT
60 mm 80 mm 127 mm
30mm
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Alarm
Out
Master
Slave
-Analog + +10 Vdc
Out
24 Vac
Supply
Alarm
Out
Master -
Analog
+ +10 Vdc
Out
24 Vac
Supply
Alarm
Out
Master
Slave
-
Analog
+ +10 Vdc
Out
24 Vac
Supply
Slave
30 Vdc/ac Input Input 30 Vdc/ac Input
30 Vdc/ac
AL AL AL
108 mm
100 mm
50mm (max)
depth = 142mm (*) depth = 142mm (*)
weight = 900g weight = 1200g
depth = 142mm
weight GTT 90 = 1300g
weight GTT 120 = 1700g
TEMPLATE DIMENSIONS
M5
L
L (mm) W (mm)
GTT 25 - 40 - 50 - 60 112 44
GTT 75 - 90 - 120 112 113
CONNECTION EXAMPLES
Single-phase connection with optional monitoring of interrupted load (command input from analog signal or potentiometer)
Digital output
0-20mA
4-20mA
0-10Vdc
Relay output - Alarm * Potentiometer
0-5Vdc
(solid state relay)
1 2 3 4 5 6 7 8
Alarm Master - + +10 Vdc 24 Vac
Out Slave Analog Out Supply
30 Vdc/ac Input
Controller
ON PWR
Note: connect h or i
according to the load c Reset Alarm
d Min Adj
0..20mA
4..20mA
0..10V
g Alarm Adj
Line Line
Line 230 V 480 V Load
L1 h i L2
Load
Fuse
Phase * *
Neutral
Ground
Star or delta three-phase connection without neutral, with control of two phases.
Digital output
0-20mA
4-20mA
* Connections regarding the 0-10Vdc
0-5Vdc
load interrupted option Potentiometer
(see paragraph
“Interrupted load alarm)
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Alarm Master +10 Vdc 24 Vac Alarm Master +10 Vdc 24 Vac
Out Slave Analog Out Supply Out Slave Analog Out Supply
30 Vdc/ac Input 30 Vdc/ac Input
Fuse Fuse
Ground
Phase R * * * *
Phase S
Phase T
CONNECTION EXAMPLES
* * *
Digital output
0-20mA
4-20mA
0-10Vdc
Potentiometer 0-5Vdc
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Alarm Master +10 Vdc 24 Vac Alarm Master +10 Vdc 24 Vac Alarm Master +10 Vdc 24 Vac
Out Slave Analog Out Supply Out Slave Analog Out Supply Out Slave Analog Out Supply
30 Vdc/ac Input 30 Vdc/ac Input 30 Vdc/ac Input
Load
Ground
Neutral * * * * * *
Phase R
Phase S
Phase T
Star or delta three-phase connection without neutral, with control of three phases.
Digital output
0-20mA
4-20mA
* * * 0-10Vdc
0-5Vdc
Potentiometer
* Connections
regarding the 1
Alarm
Out
30 Vdc/ac
2 3
Master
Slave
4
Analog
Input
5 6
+10 Vdc
Out
7
24 Vac
Supply
8 1
Alarm
Out
30 Vdc/ac
2 3
Master
Slave
4
Analog
Input
5 6
+10 Vdc
Out
7
24 Vac
Supply
8 1
Alarm
Out
30 Vdc/ac
2 3
Master
Slave
4
Analog
Input
5 6
+10 Vdc
Out
7
24 Vac
Supply
8
load interrupted
ON PWR ON PWR ON PWR
option (see AL AL AL Controller
paragraph 24Vac 4,5VA
“Interrupted load GTT 25A/480 Vac GTT 25A/480 Vac GTT 25A/480 Vac
4..20mA
c Reset Alarm
d Min Adj
0..20mA
4..20mA
c Reset Alarm
d Min Adj
0..20mA
4..20mA
0..10V
e Max Adj
f Input selection
g Alarm Adj
0..5V
0..10V
e Max Adj
f Input selection
g Alarm Adj
0..5V
0..10V
Load
Ground
Phase R * * * * * *
Phase S
Phase T
CONNECTION EXAMPLES
Three-phase connection (triangle or star) without neutral, with control of two phases using one GTT in Master configuration
and one GTS in Slave configuration.
Digital output
0-20mA
4-20mA
* * 0-10Vdc
Potentiometer 0-5Vdc
* Connections regarding + 1 2 3 4 5 6 7 8
4..20mA
e Max Adj 0..5V
f Input selection
0..10V
g Alarm Adj
Line Line
Load Line Line 230 V 480 V Load
L1 h i L2
Three-phase connection Star connection
Fuse Fuse
Ground
Phase R * *
Phase S
Phase T
Three-phase star connection with neutral using one GTT in Master configuration and two GTSs in Slave configuration.
+ + 1 2 3 4 5 6 7 8
6÷32Vcc 6÷32Vcc Alarm Master +10 Vdc 24 Vac
Out Slave Analog Out Supply
ON/OFF Control ON/OFF Control Input
30 Vdc/ac
ON ON ON PWR Controller
AL AL AL
24Vac 1,5VA
Line Line
Line 230 V 480 V Load
Load Line Load Line
L1 h i L2
Load
Ground
Neutral
Phase R
Phase S
Phase T
ACCESSORIES
A wide range of accessories is available (including fuses and fuse holders, supports for fastening DIN bar, ID
plates, thermostats, current transformers and isolation transformers). To choose accessories, see the section
"Solid state relays - Accessories."
ORDER CODE
GTT / 480 - -
Model
GTT
Nominal current
25Aac 25
40Aac 40
50Aac 50
60Aac 60
75Aac 75
90Aac 90
120Aac (*) 120
(*) Specify fan supply: 115Vac or 230Vac
Nominal voltage
480Vac 480 Fan
(for model 120A only)
Load interrupt Fan 80x80x40
(HB) option VEN90
230V 14W
Without option 0
Fan 80x80x40
With load 115V 14W VEN91
1
interrupt option
Please contact GEFRAN personnel for information on availability of codes.
•WARNINGS
GEFRAN spa reserves the right to make any kind of design or functional modification at any moment without prior notice
This device conforms to European Union Directive 89/336/CEE and 73/23/CEE as amended with reference to generic standards:
CEI-EN 61000-6-2 (immunity in industrial environment) EN 61000-6-4 (emission in industrial environment) - EN 61010-1 (safety
regulations).
Main features
Main applications • 3-phase alternating current solid state
• Thermoforming relay
• Plastic extrusion lines • Zero crossing switching
• Industrial ovens and • 3-phase nominal current
furnaces 3x10/25/40/55A
• Heat treatments • Nominal voltage up to 600VCArms
• Control applications with • Control range: 5...32Vdc
high switching speed • Optoinsulation (input/output)
• Mold heating/cooling 4000Vrms
control units • Integrated overvoltage suppressor
• Refrigeration • Non-repetitive voltage up to 1200Vp
• Air conditioning • In Conformity with EN60947-4-3
Ue=600Vac R R
T1
T3
S
Nominal impulse withstand voltage L2 T2
S
(Uimp): 2500Vac R
L3
L2
T L3 T3 T2
R
Solid Sate Relay Dissipated Power
Calculation V
V nominal = T
V3
Three-phase relay V nominal = V
Pd=3x1,4*IRMS [W] I nominal = P +10% P
I nominal = +10%
IRMS= three-phase load current V3 • V 3•V
L1 : Phase 1 input
L2 : Phase 2 input
L3 : Phase 3 input
T1 : Phase 1 output
T2 : Phase 2 output
L1 L2 L3 Alarm T3 : Phase 3 output
B1
L1 L2 L3 A1+ A1 : Control signal (+)
B2 A2 : Control signal (-)
GZ 25/400-0-1
A1 B1 : Alarm output (+) option
AC51: 25A 400Vac 5..32
AC53a: 5A 50/60Hz T1 T2 T3 A2-
Vdc
A2
B2: Alarm output (-) option
T1 T2 T3 On
Led1: Red led signal indicator
Led2: Yellow led (alarm overtemperature
junction)
DIMENSIONS
103,5mm
92mm
L1 L2 L3 Alarm
5,2mm
B1
L1 L2 L3 A1+
47,5mm
73mm
B2
GZ 25/400-0-1
A1
AC51: 25A 400Vac 5..32
AC53a: 5A 50/60Hz T1 T2 T3 A2-
Vdc
T1 T2 T3 On A2
Depth= 43,5 mm
CONNECTION EXAMPLES
Phase R
Phase S
Phase T
Neutral
Ground
F1 F2 F3
*
I < 150mA V
<30V
>110°C
Load
L1 L2 L3 Alarm
B1
L1 L2 L3 A1+
R R R R R B2
R R GZ 25/400-0-1
A1
AC51: 25A 400Vac 5..32
R
AC53a: 5A 50/60Hz T1 T2 T3 A2-
Vdc 5-32Vdc
A2
R T1 T2 T3 On
Digital Controller
output
Heatsink (accessory)
Control input
Voltage on load t
T1
T2 t
T3
On On
Alarm output of t
overtemperature
(optional)
Heatsink temperature > 110°C (overtemperature detection)
1,5 - 2,2 Nm
(*) The max. sections specified refer to unipolar copper wires Terminal covers
isolated in PVC. If an eye terminal lug is used, the terminal covers can be
Note: For the ground terminal, you have to use an eye wire removed more easily by inserting a Phillips screwdriver (max.
terminal. width 3.5 mm) into the side slots.
(LxP) = width x depth [mm] With the point of the screwdriver, widen the side of the cover
and raise it.
The minimum acceptable nominal section based on the
nominal currents of the power solid state units is given below
for copper conductors isolated in PVC, under continuous
operating conditions and at 40°C ambient temperature
according to standards CEI 44-5, CEI 17-11, IEC 408 in
accordance with EN60204-1.
ACCESSORIES
A wide range of accessories is available heatsink, fuses and fuse holders , current transformer, thermostats.
To choose accessories, see the section “Solid state relays - Accessories”.
ORDER CODE
GZ / - -
MODEL
GZ
NOMINAL CURRENT
10Aac 10 OPTIONS
25Aac 25 0 None
40Aac 40
Alarm output
55Aac 55 1
thermal protection
NOMINAL VOLTAGE
400Vac INPUT
400
(only for models ≤ 25A) 0 5...32Vdc
480Vac
480
(only for models ≥ 25A)
600Vac
600
(only for models ≥ 40A)
GEFRAN spa reserves the right to make any kind of design or functional modification at any moment without prior notice
•WARNINGS
This device conforms to European Union Directive 89/336/CEE and 73/23/CEE as amended with reference to product:
CEI-EN 60947-4-3 (Low voltage switchgear and controlgear - Contactors and Motor-starters)
GEFRAN spa
via Sebina, 74
25050 Provaglio d’Iseo (BS)
Tel. +39 030 9888.1 - fax +39 030 9839063
cod. GZ- 11/04
Internet: http://www.gefran.com
GTZ 25 / 40 / 55
THREE-PHASE SOLID STATE RELAYS WITH LOGIC CONTROL
Main features
• 3-phase alternating current solid state
relay with integrated hestsink
• Zero crossing switching
• 3-phase nominal current
Main applications 3x25/40/55A
• Thermoforming • Nominal voltage up to 600VCArms
• Plastic extrusion lines Control range:5...32Vdc
• Industrial ovens and • Optoinsulation (input/output)
furnaces 4000Vrms
• Heat treatments • Integrated overvoltage suppressor
• Control applications with • Non-repetitive voltage up to 1200Vp
high switching speed • Component selection to operate at
• Mold heating/cooling max. declared current with ≤ 40°C
control units temperature
• Refrigeration • DIN bar mounting with fast clip-on
• Air conditioning • In Conformity with EN60947-4-3
FACEPLATE DESCRIPTION
L1 : Phase 1 input
L2 : Phase 2 input
L3 : Phase 3 input
T1 : Phase 1 output
T2 : Phase 2 output
L1 L2 L3
L1 L2 L3 A1+
Alarm
B1 T3 : Phase 3 output
GTZ 40/600-0-1
B2 A1 : Control signal (+)
VEN-90 fan:230Vac
AC51: 40A 600Vac
A1
5..32
A2 : Control signal (-)
T1 T2 T3 A2-
AC53a: 8A
T1
50/60Hz
T2 T3 On
Vdc
A2 B1 : Alarm output (+) option
B2: Alarm output (-) option
Led1: Red led signal indicator
Led2: Yellow led (alarm overtemperature
junction)
DIMENSIONS
127mm 127mm
8
8
30mm
30mm
L1 L2 L3 Alarm
B1
80mm
L1 L2 L3 A1+
L1 L2 L3 Alarm
GTZ 25/400-0-1 B2 B1
100mm
A1 L1 L2 L3 A1+
AC51: 25A 400Vac
T1 T2 T3 A2-
5..32 GTZ 40/600-0-1 B2
AC53a: 5A 50/60Hz Vdc
A2 VEN-90 fan:230Vac A1
T1 T2 T3 On AC51: 40A 600Vac T1 T2 T3 A2- 5..32
AC53a: 8A 50/60Hz Vdc
T1 T2 T3 On A2
50mm Max
TYPE OF OPERATION
Control input
Voltage on load t
T1
T2 t
T3
On On
Alarm output of t
overtemperature
(optional)
Heatsink temperature > 110°C (overtemperature detection)
DISSIPATION DIAGRAMS
I (A)
70
60 55
50
40
40
30 25
20
10
0 40 80 T (°C)
CONNECTION EXAMPLES
Three-phase Triangle or Star connection (with and without neutral)
Phase R
Phase S
Phase T
Neutral
Ground
F1 F2 F3
*
I < 150mA V
< 30V
>110°C
Load L1 L2 L3 Alarm
B1
L1 L2 L3 A1+
R R R R R B2
R R GTZ 25/400-0-1
A1
AC51: 25A 400Vac 5..32
R
AC53a: 5A 50/60Hz T1 T2 T3 A2-
Vdc 5-32Vdc
A2
R T1 T2 T3 On
Digital Controller
input
(*) The max. sections specified refer to unipolar copper wires Terminal covers
isolated in PVC. If an eye terminal lug is used, the terminal covers can be
Note: For the ground terminal, you have to use an eye wire removed more easily by inserting a Phillips screwdriver (max.
terminal. width 3.5 mm) into the side slots. With the point of the
(LxP) = width x depth [mm] screwdriver, widen the side of the cover and raise it.
The minimum acceptable nominal section based on the
nominal currents of the power solid state units is given below
for copper conductors isolated in PVC, under continuous
operating conditions and at 40°C ambient temperature
according to standards CEI 44-5, CEI 17-11, IEC 408 in
accordance with EN60204-1.
Insert the screwdriver
Nominal current Nominal section to facilitate opening
cable on mm2 of the cover
10A 2,5
25A 6
40A 10
55A 16
ACCESSORIES
A wide range of accessories is available heatsink, fuses and fuse holders , current transformer, supports to guide DIN, thermo-
stats. To choose accessories, see the section “Solid state relays - Accessories”.
ORDER CODE
GTZ / - - -
GEFRAN spa reserves the right to make any kind of design or functional modification at any moment without prior notice
•WARNINGS
This device conforms to European Union Directive 89/336/CEE and 73/23/CEE as amended with reference to product:
CEI-EN 60947-4-3 (Low voltage switchgear and controlgear - Contactors and Motor-starters)
GEFRAN spa
via Sebina, 74
25050 Provaglio d’Iseo (BS)
Tel. +39 030 9888.1 - fax +39 030 9839063
cod. GTZ- 11/04
Internet: http://www.gefran.com
W211 (25-40-75-100-150-250-400-600A)
POWER CONTROLLERS, from 1KW to 400KW
Main Features
• Conduction inhibition input
• Overcurrent protection (DE option)
• Detection of partial load failure
(RPC option)
• SCR diagnosis circuit and complete
load failure (DTC option)
Main Applications • Input control from Vdc and Vac
• Industrial heat-treatment logic signal
furnaces • Zero crossing switching of mains
• Industrial cooling plants voltage
• Painting plants • High capacity anti-parallel SCR
• Driers for ceramics, paper double thyristor
and textile products • LED status indicators
• Industrial heaters • MOV protections (varistor)
• Ovens and furnaces • DIN rail or panel mounting
• Sterilizers (depending on version)
Effective current A
Rating 75A
80 400
Rating 250A
60 300
Rating 40A
Rating 150A
40 200
Rating 25A
20 100
0°C 10°C 20°C 30°C 40°C 50°C 60°C 0°C 10°C 20°C 30°C 40°C 50°C 60°C
TYPE OF FUNCTIONING
Control signal
Load current
MOUNTING
175 mm
215 mm
66 mm
130 mm
W211 W211
W211 W211
LOAD LOAD
LOAD LOAD
Depth = 105 mm Depth = 120 mm Depth = 125 mm
Weight = 800g Weight = 1200g Weight = 1700g
Depth = 160 mm
Weight W211 100A = 2300g / W211 150A = 2700g
76 mm
Cover profile
W211 250A
LINE
170 mm
4 fixing holes 76 mm
(ø 8mm)
450 mm
2 fixing holes
(ø 6,5mm)
235 mm
330 mm
W211 W211
for panel
LOAD
LOAD
98 mm
- Ground heatsink (except for models from 400 up to 600A) Rating Fuses Fuse Rating Fuses Fuse
- IP20 protection level carrier switch
- UL94V0 self-extinguishing plastic case 25A FUS-050 PF 22x58 250A FUS-450N /
- Thermostat for models with rating ≥150A
40A FUS-063 PF 22x58 400A FUS-630N SW-FUS
75A FUS-100 PF 22x58 600A FUS-900N SW-FUS
- Thyristor high I2t
100A FUS-250 PF 27x60
- Extra fast fuses
150A FUS-250 PF 27x60
WIRING / TERMINALS
Power Terminals
- Ratings from 25A to 150A: cage terminals for stripped cable without cable terminals
- Ratings from 250A to 600A: cables with terminal cable terminals or copper bar
ORDER CODE
W211 0
400Aac 400
OPTIONS
600Aac 600
0 None
NOMINAL VOLTAGE 3 RPC
660Vac (range 20...725Vac) 5 DTC
(if the RPC option is used, the working 660
range is 350...440Vac)
660Vac (range 20...725Vac)
661
(for RPC option with range 260...350Vac)
660Vac (range 20...725Vac)
662
(for RPC option with range 180...260Vac)
660Vac (range 20...725Vac)
663
(for RPC option with range 90...180Vac) Note: RPC option not available for working range >440Vac
GEFRAN spa reserves the right to make any kind of design or functional modification at any moment without prior notice
This instrument complies with European Directives 89/336/CEE and 73/23/CEE including updates.
Main features
• Conduction inhibition input
• Overcurrent protection (DE option)
• Detection of partial load failure
(RPC option)
• SCR diagnosis circuit and complete
load failure (DTC option)
• Analogue signal Input control
Main applications in mA and potentiometer
• Industrial heat-treatment • Synchronization slave digital output
and metallurgy furnaces • Adjustable modulation cycle duration
• Industrial cooling plants • Zero crossing switching of mains
• Painting plants voltage
• Driers for ceramics, paper • High capacity anti-parallel SCR
and textile products double thyristor
• Industrial heaters • LED status indicators
• Ovens and furnaces • MOV protections (varistor)
• Sterilizers • DIN rail or panel mounting
• Furnaces for glass (depending on version)
0°C 10°C 20°C 30°C 40°C 50°C 60°C 0°C 10°C 20°C 30°C 40°C 50°C 60°C
Ambient Temperature Ambient Temperature
TYPE OF FUNCTIONING
Zero crossing with cycle time T fixed (adjustable from 0.5 to 10 sec.). The ON/OFF times ratio is a function of the analogue control signal Vi.
An example of functioning for different values of the input analogue signal Vi; bottom scale 0-10V with period T=1 sec.
% Power produced
Vi = 2,5V Vi = 5V Vi = 7,5V
25% f.s. 50% f.s. 75% f.s.
Load current
MOUNTING
Ratings from 25 up to 150A: Ratings from 250 to 600A:
- DIN rapid rail mounting - Panel mounting only
- Panel mounting kit for ratings 75-150A (option 1886001)
DIMENSIONS AND MOUNTING
W212 25A W212 40A W212 75A W212 100A (without fan)
W212 150A (with fan)
66 mm 83 mm 83 mm 83mm
175 mm
215 mm
66 mm
130 mm
W212 W212
W212 W212
LOAD LOAD
LOAD LOAD
Depth = 105 mm Depth = 120 mm Depth = 125 mm
Weight = 800g Weight = 1200g Weight = 1700g
Depth = 160 mm
Weight W212 100A = 2300g / W212 150A = 2700g
76 mm
Cover profile
W212 250A
LINE
170 mm
4 fixing holes 76 mm
(ø 8mm)
450 mm
P2 fixing holes
(ø 6,5mm)
235 mm
330 mm
W212 W212
for panel
LOAD
LOAD
98 mm
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
- Ground heatsink (except for models from 400 up to 600A) Rating Fuses Fuse Rating Fuses Fuse
- Input/output insulation voltage 3750 Vac carrier switch
- IP20 protection level 25A FUS-050 PF 22x58 250A FUS-450N /
- UL94V0 self-extinguishing plastic case
40A FUS-063 PF 22x58 400A FUS-630N SW-FUS
75A FUS-100 PF 22x58 600A FUS-900N SW-FUS
- Thermostat for models with rating ≥150A
100A FUS-250 PF 27x60
- Thyristor high I2 t
150A FUS-250 PF 27x60
- Extra fast fuses
WIRING/TERMINALS
Power Terminals
- Ratings from 25A to 150A: cage terminals for stripped cable without cable terminals
- Ratings from 250A to 600A: cables with terminal cable terminals or copper bar
ORDER CODE
W212 2
150Aac 150
OPTIONS
250Aac 250
0 None
400Aac 400
3 RPC
600Aac 600
5 DTC
NOMINAL VOLTAGE
660Vac (range 20...725Vac) INPUT
(if the RPC option is used, the working 660
range is 350…440 Vac) * 0-5 Vdc and potentiometer
GEFRAN spa reserves the right to make any kind of design or functional modification at any moment without prior notice
This instrument complies with European Directives 89/336/CEE and 73/23/CEE including updates.
Main Features
• On-board microprocessor
• Numeric/digital control by serial line or
by logic input
• Accurate measure of load voltage and
Main Applications currents (RMS)
• Tyre manufacturing plants • Completely configurable
• Wire manufacturing plants • Auto-diagnostic
• Industrial heat-treatments • Zero crossing switching of mains
• Industrial cooling plants voltage
• Painting plants • Power contacts with anti-parallel
• Driers for ceramics, paper double SCR
and textile product • R-C and MOV (varistor) protections
• Ovens and furnaces • Panel mounting, independent socket
80 140
A effective current
A effective current
120
60
100
80
40
60
20 40
20
0°C 10°C 20°C 30°C 40°C 50°C 60°C 0°C 10°C 20°C 30°C 40°C 50°C 60°C
WORKING DIAGRAM
Zero crossing with control from serial line and “T” cycle time adjustable from 3 to 300 sec. ON/OFF time values ratio is a func-
tion of 0...100% numeric control (n.c.).
Working example per different power values with T = 10sec. Time period
% Supplied power
Line
151 mm
198 mm
198 mm
151 mm
198 mm
Power terminals
Load
L1 L2
460V.a.c.
50/60 Hz
CONNECTION OF THE RS 485 LINE
Master
Computer
W401
Transmitter
+
Receiver
Load
A (RXD/TXD) Ground
Communication Communication
RS 485 RS485 Neutral
________________________ Auxiliary Power
B (RXD/TXD) Supply
115 V.a.c. 4VA 50/60 Hz
+15 V.d.c.
230 V.a.c.
NC
Logic external
command (0...30 VDC)
NC
Enabling NC
(0...30 VDC)
SAFETY AND PROTECTION
- Grounded heatsink
- IP20 protection Taglia Fusibili Sigla di
- Thyristor high I2t Ordinazione
- Extra-fast on-board fuse (optional) 45A 63A FUS-063N
100A 160A FUS-160N
- RC filter and varistor on thyristors
WIRING/TERMINALS
Power screw terminals (Ø6mm) are placed in the mounting socket of the instrument to be connected via an eyelet terminal
wire.
100A 35mm 2
35ø - Hole ø 6mm 8 - 9 Nm
ORDER CODE
W401 460 0 2 .D
MODEL OPTION
W401 000 Extra-fast Fuse
500 None
NOMINAL CURRENT
45Aac 045 AUXILIARY POWER SUPPLY
100Aac 100 2 115/230Vac, 50...60Hz
NOMINAL VOLTAGE
460Vac 460
GEFRAN spa reserves the right to make any kind of design or functional modification at any moment without prior notice
The instrument conforms to the european directives 89/336/CEE and 73/23/CEE, including updates.
Main features
• Analog/potentiometer/logic signal input
control
• Phase angle switching
Main applications • High-capacity antiparallel double
• Industrial furnaces for heat thyristor (SCR)
treatments, metallurgy • Conduction inhibitor input
• Wood-working machines • LED indicators
(edge-banding, gluing) • MOV protections (varistor)
• Welding machines • DIN bar and front panel installation
• Kilns • Softstart
20msec
200
Soft-Star
150
W312 150A I
120
100 X W312 100A
85 t
75 W312 75A
50
40 W312 40A
30
25 W312 150A
0 IRMS
0°C 10°C 20°C 30°C 40°C 50°C 60°C
Ambient temperature °C
t
Softstart time
OVERALL AND INSTALLATION DIMENSIONS
W312 25A W312 40A W312 75A W312 100A (without fan)
W312 150A (with fan)
66 mm 83 mm 83 mm 83mm
215 mm
175 mm
66 mm
W212 W212
130 mm
W212 W212
LOAD LOAD
LOAD LOAD
2 holes ø 6,5mm
for panel
assembly
98 mm
ACCESSORIES
WIRING/TERMINALS
Power terminals
The power terminals on the solid state power units let you use wires without terminals or connectors to be crimped. For 25
and 40A solid state power units, you can connect the two phases or one phase and one neutral in input. In this case, use the
internal through connection between input 1 and output 3.
Models with 230 VAC auxiliary power supply: code W312 … 020
L1
L2
Ground
Fuse
1 2
Control Card
6
5 +5Vdc
4 Power output inhibition (4...30Vdc)
Fan Control enable (4...30Vdc)
3
230Vac
2 Thermal
1 protection (**)
3 4
LOAD
Models with auxiliary power supply >230 VAC (for ex.: code W312…030, auxiliary power supply 400 Vac).
L1
L2
Ground
Fuse
1 2
Aux. power supply
(*) 400Vac (*)
9
8
(**) Common
7 (-) Analog
Control Card
6 (+) control
5 +5Vdc
4 Power output inhibition (4...30Vdc)
Fan Control enable (4...30Vdc)
230Vac
3
2 Thermal
1 protection (**)
3 4
LOAD
---- On 25A and 40A models, direct connection with terminals 1-3 is available for connecting one of the phases to
the load, as an alternative to outside connection.
(*) Auxiliary power supply for control board (indicated in code and on label): must be in phase (synchronized) with
the voltage applied to the load.
If not directly available, use an external auxiliary transformer.
IMPORTANT
On models with auxiliary power supply >230 VAC, one phase of the power supply for the control board is
already connected internally. Therefore, terminal 8 is not used and must not be connected.
(**) 150A mod. only
CONTROL OF THREE-PHASE LOADS WITH THREE WATTCORS OPERATING IN SINGLE PHASE
Example 1 - Star connection with neutral.
Line voltage 400 VAC. 3 units W312 25A (or 40A).
Analog control (linear signal). Auxiliary power supply 230 Vac (W312 - [] [] [] - 660 - [] - 020)
L1
L2
L3
Neutral
Ground
9 9 9
8 8 8
7 7 7
Control Card
Control Card
Control Card
6 6 6
5 +5Vdc 5 +5Vdc 5 +5Vdc
4 4 4
3 3 3
2 2 2
1 1 1
3 4 3 4 3 4
Unit 1 Unit 2 Unit 3
Controller
LOAD LOAD LOAD
Control
output
-- + Control enable (+)
Power output inhibition (+)
Linear input (+)
Common (-)
---- On 25A and 40A models, direct connection with terminals 1-3 is available for connecting one of the phases to the load, as
an alternative to outside connection.
(*) Auxiliary power supply 230 VAC + 10%-20%-50Hz for control board (indicated in code and on label): must be in phase
(synchronized) with the voltage applied to the load. If not directly available, use an external auxiliary transformer.
Control Card
Control Card
6 6 6
+5Vdc +5Vdc +5Vdc
5 5 5
4 4 4
3 3 3
2 2 2
1 1 1
Potentiometer
LOAD LOAD LOAD
10kOhm
+5Vdc
Power output inhibition
(*) Auxiliary power supply 400 VAC + 10%-20%-50Hz for control board (indicated in code and on label): must be in phase
(synchronized) with the voltage applied to the load.
IMPORTANT
On models with auxiliary power supply >230 VAC, one phase of the power supply for the control board is already connected
internally. Therefore, terminal 8 is not used and must not be connected.
CONTROL SIGNALS
5 +5Vdc
Enable/inhibit controls are active with voltage in the 4…30 VDC Power output
4
range, and can also be operated by means of potential-free contacts inhibition(4...30Vdc)
connected between terminals 3-5 and 4-5, respectively. 3 Control enable
(4...30Vdc)
10kOhm
-
7 7
6 6
Logic input
5 +5Vdc
5 +5Vdc
(ON = 4...30Vdc)
Power output
4 Power output
inhibition (4...30Vdc)
+ 4
inhibition (4...30Vdc)
3 Control enable
3
(4...30Vdc)
7 -
6
Digital input PWM (Pulse Width Modulation)
5 +5Vdc (carrier frequency from 500Hz to 10kHz, max 24Vdc)
Power output
4
inhibition (4...30Vdc)
3
+
OPERATING MODES
W312 units offer the following control modes selectable by dip-switches:
• analog control (dip switch GC4=OFF): the solid state power unit transfers to the load a % of power proportional to
the analog input signal (terminals 6-7).
The set power is supplied / interrupted by activating / deactivating the logic signal at terminal 3.
The type of analog signal (standard 0...10V) can be selected by the internal dip switches SW1-SW2-SW3-SW4 (see
chart)
By enabling the "Soft-start at power-on" function (dip switch GC2=ON), when the auxiliary power supply is switched
on (with logic signal present at terminal 3) the set power is reached gradually after a fixed time of about 40 sec.
By enabling the "Control variation gradient" function (dip switch GC4=ON) setpoint variations can be made more gra-
dually; for example, a set point variation from 0 to 100% is performed on the load with a ramp of about 2.2 sec.
• logic control (dip switch GC4=ON, SW1=ON, SW2=OFF, SW3=ON, SW4=OFF): the solid state power unit tran-
sfers 100% of power to the load.
The power is supplied / interrupted by activating / deactivating the logic signal at terminal 3.
For this function, terminal 6 (analog input) must not be connected.
By enabling the "Soft-start at power-on" function (dip switch GC2=ON), when the auxiliary power supply is switched
on (with logic signal present at terminal 3) the power is reached gradually after a fixed time of about 40 sec.
By enabling the "Control variation gradient" function (dip switch GC4=ON) the switching phase can be made more
gradually; for example, passage from 0 to 100% of power takes place with a ramp of about 2.2 sec.
If GC3 and GC4 are both enabled, the 2.2 sec. (approx.) ramp is also executed when the logic control is deactivated.
• PWM control (dip switch GC4=ON, GC3 = ON, SW1 = ON, SW2 = OFF, SW3 = ON, SW4 = OFF). In logic control
mode, you can send a PWM type digital signal (Pulse Width Modulation) to terminal 3.
The power controller transfers to the load a % of power proportional to the ratio between the “ON time” and the “OFF
time” within the cycle; this function lets you set a power set point by means of digital signal (for ex., from PLC or con-
troller with PWM output) with carrier frequency from 500 Hz to 10kHz, logic level Lo<0.6V, Hi>2.5V (max 24 VDC).
Example: with digital signal at 1 kHz and tON=50%, you have 50% of power output.
ORDER CODE
W312 660 2 0 0
MODEL
W312
NOMINAL CURRENT
25Aac 25 AUXILIARY SUPPLY
GEFRAN spa reserves the right to make aesthetic or functional changes at any time and without notice.
HEATSINKS
DESCRIPTION
Different models of heatsinks have been designed and tested to • Draw on the “graphs” Tmaxa, Imax points.
meet size and dimension needs. • Choose the smallest heatsink (starting from upwards), which
point [Tmaxa Imax] is in the gray working area of dissipation
How to choose a heatsink
• Set max. air temperature inside the panelboard (Tmaxa) curves
• Set max. operating current: Imax = Inom. load + 10% • Respect installation distances
INSTALLATION
In order to obtain best reliability, it is important to install a heatsink correctly inside the panel, to reach an adequate thermal exchange
between the device and the surrounding air in natural convection conditions.
MAX MAX
10° 10°
Fig. 1
> 20
> 100
> 40 > 40
AIR
FAN
Channel > 40
> 100
AIR
FAN
> 300
> 100
> 100
Channel
Channel
Channel
Channel
Channel
Channel
> 100
> 300
Channel
ARIA
FAN
Channel Channel
AIR
VFAN
> 20
DISSIPATION CURVES
Effective current controllable based on room temperature 24
Controlled effective
25
current (A)
DIS 25G
20
15
h = 100mm
65
10
5 Rth = 3,12°C/W
0
20 30 40 50 60 70 80 90 100 (*)
Room temperature (°C)
35
Controlled effective
With fans
50
current (A)
DIS 40G
40
30
h = 100mm
100
20
10 Rth = 1,90°C/W
0
20 30 40 50 60 70 80 90 100 (*)
Room temperature (°C)
Controlled effective
current (A)
50
DIS 50G
78.2
40
30
h = 100mm
20
10 Rth = 0,83°C/W
0
20 30 40 50 60 70 80 90 100 (*) 60
Room temperature (°C)
Controlled effective
80
current (A)
DIS 60G
60
98.2
40 h = 100mm
20
0
Rth = 0,66°C/W
20 30 40 50 60 70 80 90 100 (*) 82
Room temperature (°C)
Controlled effective
80
60
h = 100mm
40
20 Rth = 0,56°C/W
126.5
0 20 30 40 50 60 70 80 90 100 (*)
Room temperature (°C)
three- pahse current (A)
Controlled effective
25
DIS 908
101.5
20
15 h = 80mm
10
5
Rth = 0,7°C/W
0
20 30 40 50 60 70 80 90 100 (*) 126.6
Room temperature (°C)
three- pahse current (A)
With fans
Controlled effective
60
50
DIS 910
40
101.5
30
20
10 h = 100mm
0 20 30 40 50 60 70 80 90 100 Rth = 0,56°C/W
Room temperature (°C) 126.6
(*)
Should the stated point [Tmaxa Imax] be outside the working area, it is necessary (*) Data surveyed with 40°C ambient temperature and heatsink in vertical position
to equip the heatsink with a fan and a safety thermostat. surrounded by 15 cm free space; natural convection; contact surface with the
N.B. The operating point has not to be outside the delimited area. heating element = ~ 8cm2 [38mmx 20mm]
- DIS908/910 heatsinks are suitable for three-phase solid state relays of RZ series.
- Controlled three-phase effective current refers to the used line current of three-
phase load.
- Heatsinks used with a cooling fan should be equipped with safety thermostat, so
that the solid state relay can be switched off in case of fan failure.
HEAT SINKS
Plated heat sink DIS-P is also available. This is an aluminum plate with fins, ready for attachment to DIN support bar (DIN 5). The
DIS-P measures 100 mm high, 60 mm wide, 13 mm deep.
Heat sinks DIS-25G, DIS-40G, DIS-50G, DIS-60G, DIS-90G are also available one-meter bars (DIS - …G - 1 m).
Contact GEFRAN for thermal characteristics.
DIS-15G DIS-910
DIS-25G DIS-P
DIS-40G DIS-25G-1M
DIS-50G DIS-40G-1M
DIS-60G DIS-50G-1M
DIS-90G DIS-60G-1M
DIS-908 DIS-90G-1M
THERMOSTAT
DESCRIPTION INSTALLATION
Safety thermostat is expressly designed to prevent
overtemperature. TGRZ is installed in one of
Thanks to the miniaturized case the thermal answer is the two slots of the RZ
excellent. Furtheron, the thermostat is a very good thermal three-phase solid state
protection, as it can be mounted very near to the critical point relay case.
which has to be controlled.
When it is connected in series to control voltage, the
thermostat disenergises the relay as soon as the critical
operating temperature is reached. Relay is energised again
when temperature drops underneath the critical value (about
90°C).
For an easier wiring, the thermostat can be connected to two
free terminals (B1/B2), which are not connected internally
(GRZ model, only).
The thermostat is normally closed and opens when
temperature exceedes 90 °C (with automatic reset).
Connection in series with the input control is suggested.
The VIR-1 thermostat is supplied as a spare part for W21 x ≥
150A solid state power units.
TGR is fixed by means
of a small bracket and of
a screw (enclosed)
VARISTORS (MOV)
DESCRIPTION
MOV (metal-oxide-varistor) is an overvoltage protection device which improves the reliability of solid state relays when functioning
RV 03
RV 04
RV 05
HEATSINKS
ACCESSORIES
FANS
DESCRIPTION
An additional fan, applied to the heatsink of a solid state relay, improves its dissipation performance and allows the solid state relay
to work at higher ambient temperatures with the same current. Fan installation benefits are shown (dashed) by the dissipation
curves of the different heatsinks.
MODEL SELECTION
CODE DESCRIPTION
24 VDC fan kit for DIS-50G, DIS-60G (60x60x25 fan, 24 VDC, with 4 screws, 4 plastic fastening rivets for direct attachment to heat
VEN-60 sink. Hand guard incorporated).
230 VAC fan kit for DIS-90G, DIS-910 (80x80x40 fan, 230 VAC, 14 W, 50 Hz, with 4 M4 screws, 4 notched washers, 4 plastic
fastening rivets for direct attachment to heat sink that accepts relay type GS, GT 60 A and RZ 40 A, GTS 120 A, GTT 120 A.
VEN-90 Hand guard incorporated).
115 VAC fan kit for DIS-90G, DIS-910 (80x80x40 fan,115 VAC, 14 W, 50 Hz, with 4 M4 screws, 4 notched washers, 4 plastic
fastening rivets for direct attachment to heat sink that accepts relay type GS, GT 60 A and RZ 40 A, GTS 120 A, GTT 120 A.
VEN-91 Hand guard incorporated).
24 VDC fan kit for DIS-90G, DIS-910 (80x80x40 fan, 24 VDC, 4 W, with 4 M4 screws, 4 notched washers, 4 plastic fastening rivets
for direct attachment to heat sink that accepts relay type GS, GT 60 A and RZ 40 A, GTS 120 A, GTT 120 A. Hand guard
VEN-92 incorporated).
CODE DESCRIPTION
Support for attachment to DIN bar, for solid state power unit models: GTS-L 5/10/15GTS-T10, GTS-T20, GTS15, GTS25, DIS25G, with
DIN-2 fastening screw.
Metal support with spring for attachment to DIN bar, for solid state power unit models: W211 and W212 25/40/75/100/150 A, with
DIN-4 fastening screw.
Metal support with spring for attachment to DIN bar, for solid state power unit models: GTS-T10, GTS-T20, GTS-T25,
DIN-5 GTS15/25/40/75/90/120 A, GTT 75/90/120 A, DIS908, DIS910, DIS-9, DIS25G, DIS40G, DIS90G, with fastening screw.
Metal support with spring for attachment to DIN bar, for solid state power unit models: GTS50, GTS60, GTT25, GTT40, GTT50A,
DIN-6 GTT60A, DIS50G, DIS60G with fastening screw.
PAN-1 Bags with 2 plastic supports + 2 screws + 4 washers for attachment to panel, for GTS, GTS-T, GTT (**)
F19672 Socket for GTS-L for attachment to DIN bar
(**) Models GTS, GTT 90 A, GRZ are supplied (standard) with supports for attachment to panel
CODE DESCRIPTION
COP-GS-0 Pad-printed cover for GS-T 10A, 20A and GS 15A, 25A.
COP-GS-1 Pad-printed cover for GS-T 25A and GS40A.
COP-GS-2 Pad-printed cover for GS 50A, GS 60A, GS 75A, GS 90A, GS 120A.
COP-GTS-0 Pad-printed cover for GTS-T 10A, 20A and GTS 15A, 25A.
COP-GTS-1 Pad-printed cover for GTS-T 25A and GTS 40A.
COP-GTS-2 Pad-printed cover for GTS 50A, 60A, 75A, 90A, 120A.
COP-GT-0 Pad-printed cover for GT 25A, 40A, 50A, 60A, 75A, 90A, 120A.
COP-GTT-0 Pad-printed cover for GTT 25A, 40A, 50A, 60A, 75A, 90A, 120A.
COP-GTS-L-0 Cover for GTS-L5
COP-GTS-L-1 Cover for GTS-L10 / GTS-L15
BBR Protective cover for RA single-phase solid state relays
SOLID STATE RELAY
ACCESSORIES
DESCRIPTION
These fuses ensure the maximum safety in solid state relay applications.
Fuses with a very high cutoff power are used for this kind of applications.
MODEL SELECTION
Fuse
Nominal Dimensions Fuse holder
Relay i^2t Fuse order Notes
voltage (mm) order code
code
GS-L / GTS-L / GTS-T / GTS / GS / GTT (single-phase with antiparallel thyristor or Triac)
GS-L5 / 230
GTS-L5 45 440 5A 10x38 FUS-06-L PF-10x38 plug-in
GS-L10 / 230
GTS-L10 100 440 10A 10x38 FUS-010-L PF-10x38 plug-in
GS-L15 / 230
GTS-L15 180 440 15A 10x38 FUS-016-L PF-10x38 plug-in
GTS-T 10 72 230 10A 10x38 FUS-010 PF-10x38 plug-in
GTS-T 20 315 230 25A 10x38 FUS-025 PF-10x38 plug-in
GTS-T 25 315 230 25A 10x38 FUS-025 PF-10x38 plug-in
230
GTS / GS 15 450 480 16A 10x38 FUS-016 PF-10x38 plug-in
• Current transformer
5,5 27 5,5 2
These transformers are used for currents of 50/60 Hz. The main
9
In
electronic measurement circuit.
48
13
152050 9640
20
Order code
10
50 /0.05 A
1
8 8
38 20 330200 IN = 50Aac OUT = 50mAac
Foro di fissaggio
per viti autofilettanti: 2,9 x 9 330201 IN = 25Aac OUT = 50mAac
Type Ground terminal Screw type on heat sink side Heat sink
Contact area (WxD) *
Screw type
TERM-25 9x12 M4 DIS-25G
M5
TERM-40 11,5x12 M4 DIS-40G
M5
TERM-60 14x16 M5 DIS-50G
M5 DIS-60G
DIS-90G
THERMOCONDUCTIVE PASTE
IDENTIFICATION LABELS
ORDER CODE
CODE DESCRIPTION
SIL-1 Silicone thermoconductive paste for coupling the power module to the heat sink.
100 g tube.
LAB-1 Kit with 20 plastic identification labels for GS / GS-T / GTS / GTS-T / GTT / GT power solid state relays