1.0 INTRODUCTION
1.0 INTRODUCTION
1.1 PURPOSE
The intent of this document is to provide a standard specification that will be used for all
Appalachian State University facilities requiring cabling installation. This document provides the
minimum performance criteria for the components and sub-systems comprising a complete
cabling system that shall accommodate Appalachian State University’s requirements.
Product specifications, general design considerations, and installation guidelines are provided
in this written document. The successful contractor shall meet or exceed all requirements for
the cabling system described in this document.
The successful contractor must have a BICSI® certified RCDD review the drawings and meet with
University representatives from Facilities and the Information Technology Services (ITS) to discuss
the project and to ensure that a structured cabling system is installed that provides a
comprehensive telecommunications infrastructure.
1.2 SCOPE
This document defines the cabling system and subsystem components to include cable,
termination hardware, supporting hardware, and miscellany to install a complete
telecommunications system supporting voice and data. The intent of this document is to provide all
pertinent information to allow the contractor to bid the materials, labor, supervision, tooling, and
miscellaneous mounting hardware and consumables to install a complete system. However, it is
the responsibility of the contractor to identify any and all items required for a complete system not
identified in this specification.
The cabling system described in this specification is derived in part from the
recommendations made in industry standard documents. The documents below are
incorporated by reference.
If a conflict exists between applicable documents, then the order in the list above shall dictate the
order of precedence in resolving conflicts. This order of precedence shall be maintained unless a
lesser order document has been adopted as code by a local, state or federal entity, and is
therefore enforceable as law by a local, state or federal inspection agency.
Appalachian State University’s facilities vary in function and size. Most buildings have individual
offices for faculty and staff; in certain areas, personnel may be situated in modular office furniture
with hard wall offices around the exterior of the floor. Classrooms may have fixed seating or be
large open rooms. Generally, a ceiling distribution cabling system using cable trays and conduits
is used. These specifications apply primarily to new buildings and major renovations, but should
be followed as closely as possible for all telecommunications cabling installations.
Multi-mode fiber (50/125μm) and single mode fiber optic backbone shall be employed between the
data Main Cross-Connect (MC) and each telecommunications room (TR) for data connectivity in all
new buildings. When applicable, high pair-count Category 3 CMR riser cables are employed
between the voice MC and each TR for voice connectivity. Within the data MC and the each TR,
backbone fiber strands shall be terminated and housed in rack-mount fiber optic enclosures. Within
the voice MC and each TR, backbone copper pairs shall be terminated using 66-blocks mounted
on 4’ x 8’ x .75” virgin fire retardant plywood.
Appalachian State University’s data distribution network is based on a star topology. As a standard
configuration, each work area communications outlet contains two Category 6 jacks, all jacks are
terminated using Category 6 horizontal cables pulled and terminated on Category 6 insulation
displacement connector patch panels in the telecommunications room. Patch cords/equipment
cords are used to connect each jack to the appropriate service connector. Generally, high pair
count Category 3 CMR or CMP backbone/riser cables are employed between the Entrance
facilities or Main telecommunications room and each telecommunications room for voice
connectivity. Category 6 cables, single mode, and 50/125 μm multi-mode fiber optic cables are
used as backbone/riser cables for data.
While standards are carefully monitored to ensure that the components and practices are
technologically current, it is possible that some applications may require special consideration.
Many buildings contain special purpose facilities and equipment with unique telecommunications
requirements. Special telecommunications requirements may require deviation from these
specifications. Information Technology Services needs to be notified of these special
requirements as early in the design process as possible.
The following list contains some of the facilities that typically require special
telecommunication consideration.
Items not specifically identified in this document as a standard should obtain approval
from appropriate Information Technology Services staff prior to implementation.
The entrance facility is the location where the pathways for communications services penetrate
the building to connect to the voice and data systems within the building. The entrance facilities
are generally 4-inch rigid steel conduit that extends from the perimeter of the building to the
telecommunications main equipment room.
Appalachian State University representatives shall designate the shortest practical route for the
communications cable to connect from the building to the point of connection with the university
telephone and network cabling systems. Conduit shall be installed from the facility points of entry
to the telecommunications infrastructure as determined by Information Technology Services.
Special facilities entrance requirements may be necessary for some new buildings that will
house voice and data equipment when Appalachian State University representatives determine
that the scope and importance of the facility require it.
In the event that diverse cable facility entrances are not deemed necessary, provisions shall be
made for no less than four 4-inch conduits for access from the university cable system to the
telecommunications main equipment room. No less than two 4-inch conduits should exit the
building from different locations for the purpose of providing redundant routes. Each of these
conduits must be labeled "TELE MDF ONLY" and connect to the university
telecommunications infrastructure.
Entrance facilities must adhere to all BICSI requirements. Information Technology Services must
approve any deviations from the BICSI TDMM.
• The interbuilding backbone shall be comprised of both copper and optical fiber. Cable sizing shall
be in consultation with Information Technology Services for specific building requirements.
• Interbuilding backbone fiber and copper cables shall be sized to include no less than 50% spare for
future use. Consult with Information Technology Services for cable sizing requirements on a per
building basis.
• Interbuilding backbone cables comprised of steel or metallic parts must be grounded on both ends
of the cable as specified in section 11.0, ―Grounding and Bonding.
• Proper firestopping of all backbone pathways shall be maintained as specified in section 10.0,
―Firestop Systems.
• Interbuilding copper and backbone cables shall be installed without exceeding the minimum bend
radius and the maximum vertical rise recommended by the cable manufacturer and must not exceed
the maximum allowed pulling tension of the cable(s).
4.2.1
CABLING
● The interbuilding copper backbone cable(s) shall be 100-ohm unshielded, balanced,
● twisted-pair, Category 3 cable with round solid conductors. It shall also be armored.
● The cable shall be UL® tested and listed, and it shall meet or exceed the requirements of
Category 3 cable as specified in TIA-568-C and all applicable national and municipal fire
codes.
4.2.2 TERMINATIONS
o Interbuilding backbone copper cabling shall be terminated on 66 protected termination
blocks in the telecommunications riser rooms. Main Communication room terminations
must be done in accordance with Information Technology Services standards.
o The cable shall be continuous without splices, unless required by code or specified
differently by Information Technology Services.
o Interbuilding copper backbone cables must be properly secured to the walls to prevent
horizontal movement as specified in BICSI TDMM Chapter 4, the NEC, and all applicable
national and municipal codes.
4.3.1
CABLING
● The interbuilding optical fiber backbone cable(s) shall be single mode and multi-mode
cables consisting of 8.3/125 μm single mode and 50/125 μm multi-mode optical fiber.
There shall be no fewer than 12 strands of single mode and 12 strands of multi-mode.
● Actual cablesizing shall be determined after consultation with Information Technology
Services.
● Optical fiber cables shall meet or exceed all applicable national and local building fire
codes.
The horizontal distribution system consists of two basic elements, the horizontal pathways and
the related spaces, and the horizontal system.
Electrical contractors will generally be the installer of the telecommunications pathways, primarily
cable tray, conduit and outlet boxes. The drawings must clearly define the pathways and spaces. The
BICSI® Telecommunications Distributions Methods Manual covers all parts of the telecommunications
structured cabling system and will be used by Appalachian State University representatives to ensure
proper installation. It should also be referenced by the designer and the contractors to determine:
Telecommunications room location, dimensions, equipment layout and furnishings. Heating, cooling,
lighting, fire protection, power and grounding requirements.
The number and size of slots, sleeves, and conduits needed to provide pathways for backbone cabling and
determine fill ratios. These pathways and spaces are designed to be used for the life of the building and
should be sized accordingly. There must be at least one telecommunications room per floor in all buildings and
they must be stacked vertically in multi-floor buildings. These telecommunications rooms are designed to be
secure designated spaces for housing specialty equipment and devices and should not be used or combined
with any other services such as plumping, electrical, HVAC, housekeeping or storage. .
The telecommunications contractor will be responsible for pulling and terminating the cables
following all federal, state and local codes, accepted industry standards and the manufacturer’s
instructions. The telecommunications contractor must work closely with the electrical contractor to
ensure that the pathways are installed correctly and that they will allow for proper installation of
the cabling system. Visual inspections and upon completion of the project test results will be used
to verify proper installation practices were followed.
Each telecommunications outlet (TO) location, unless otherwise noted, shall be provided with
two Category 6 cables. Each Category 6 cable shall be terminated on an 8-position, 8-conductor
Category 6 jack to the T568B color code in the work area and in the telecommunications room.
No less than one work area communications outlet should be placed per 100 square foot
increment of useable floor space and sized to accommodate two Category 6 cables and
connectors (e.g. A 90 square foot room should have at least one, a 101-square foot. room
should have at least two). Outlets should be within 3’ of an electrical outlet and installed at the
same height, unless otherwise specified. Outlets should be placed so that the work area or
workstation cable does not exceed 5 meters (16 ft) in length. This length is figured into the
total horizontal cabling length and must not be exceeded.
OFFICE OUTLETS
No less than two multiport faceplates in each office. Each faceplate shall contain no less than two
Category 6 cables terminated on two Category 6, 8-position, 8-conductor jacks. Faceplates shall
be constructed of ABS molding compound. Faceplates shall accommodate two labels and
provide a clear polycarbonate cover for each. Faceplates shall be ivory in color unless otherwise
noted.
No less than two multiport faceplates in each academic room. Each faceplate shall contain no
less than two Category 6 cables terminated on Category 6, 8-position, 8-conductor jacks.
Faceplates shall be constructed of ABS molding compound. Faceplates shall accommodate two
labels and provide a clear polycarbonate cover for each. Faceplates shall be ivory in color
unless otherwise noted.
DORM
OUTLETS
No less than two multiport faceplates in each dorm room. Each faceplate shall contain no less than
two Category 6 cables terminated on two Category 6, 8-position, 8-conductor jacks. Faceplates
shall be constructed of ABS molding compound. Faceplates shall accommodate two labels and
provide a clear polycarbonate cover for each. Faceplates shall be ivory in color unless otherwise
noted.
WIRELESS
OUTLETS
Two Category 6 cables terminated on Category 6, 8-position, 8-conductor jacks. Faceplates
shall be constructed of ABS molding compound. Faceplates shall accommodate two labels
and provide a clear polycarbonate cover for each. Where wireless access points are located
on an accessible lay-in style ceiling surface, two Category 6 cables terminated on Category 6,
8- position, 8-conductor jacks shall be left at each location with 10’ excess neatly coiled and
supported above the ceiling.
CATEGORY 6 CABLING –
NON-PLENUM
Horizontal cabling shall be 23 AWG, 4-pair UTP, UL/NEC CMR rated, with a blue PVC jacket.
Cable jacketing shall be lead-free.
Horizontal cabling shall be 23 AWG, 4-pair UTP, UL/NEC CMP rated, with a blue plenum-rated
PVC jacket. Individual conductors shall be FEP insulated. Cable jacketing shall be lead-free.
MODULAR
JACKS
All modular jacks shall be wired to the T568B wiring pattern. Modular jacks shall be
constructed with a housing of polyphenylene oxide, 94V-0 rated. Modular jacks shall be
terminated using a 110-style pc board connector (made of 94V-0 rated polycarbonate),
color-coded for both T568A and T568B wiring. The 110-connector shall terminate 22-24 AWG
solid conductors with a maximum insulation diameter of .050 inches. The modular jack
contacts shall be plated with a minimum of 50 micro-inches of gold in the contact area over a
50 micro-inch minimum nickel underplate.
Category 6 modular (data) jacks shall be unkeyed 4-pair and shall fit in a .760” X .582”
opening. Modular jacks shall be terminated using a 110-style pc board connector, color-coded
for both T568A and T568B wiring. Each jack shall be wired to T568B.
• Cable shall be dressed and installed in accordance with manufacturer’s recommendations and
best industry practices
• Cable raceways shall not be filled greater than the NEC maximum fill for the particular raceway
type
• Cables shall be installed in continuous lengths from origin to destination (no splices) unless
specifically addressed in this document
• Where cable splices are allowed, they shall be in accessible locations and housed in an
enclosure intended and suitable for the purpose
• The cable’s minimum bend radius and maximum pulling tension shall not be exceeded
• If a J-hook or trapeze system is used to support cable bundles all horizontal cables shall be
supported at a maximum of four-foot intervals - at no point shall cable(s) rest on acoustic ceiling
grids or panels
• Horizontal distribution cables shall be bundled in groups of not greater than 40 cables (cable
bundle quantities in excess of 40 cables may cause deformation of the bottom cables within the
bundle)
• Panel terminations shall be fed by and individual bundle separated and dressed back to the
point of cable entrance into the rack or frame.
• Cable shall be installed above fire-sprinkler and systems and shall not be attached to the
system or any ancillary equipment or hardware
• The cabling system and support hardware shall be installed so that it does not obscure any
valves, fire alarm conduit, boxes, or other control devices
• Cables shall not be attached to ceiling grid or lighting support wires
• Where light support for drop cable legs is required, the Contractor shall install clips to support
the cabling
• Any cable damaged or exceeding recommended installation parameters during installation shall
be replaced by the Contractor prior to final acceptance at no cost to the Owner
• Cables shall be identified by a self-adhesive label in accordance with the System
Documentation Section of this specification
• The cable label shall be applied to the cable behind the faceplate on a section of cable that can
be accessed by removing the cover plate. Cable labels shall not be obscured from view.
• Unshielded twisted pair cable shall be installed so that there are no bends less than four times
the cables outside diameter (4 X cable O.D.) at any point in the run
• Pulling tension on 4-pair UTP cables shall not exceed 25-pounds for a single cable or cable
bundle
Each patch panel shall be separated vertically on the rack by a 2U horizontal finger
duct cable management panel.
A 12” ladder rack system shall be installed in the telecommunications room to support the
cables. The ladder should encompass the room allowing the cables to be properly dressed
and supported. Secure the top of all freestanding equipment racks using 12” ladder racks
to the wall or intersect with the ladder system encompassing the room.
All horizontal cables will be terminated on Category 6 patch panels. This allows any cable
to be used for voice, data or other purpose. Cross-connects will be done by using patch
cords in the telecommunications room to connect a jack on the horizontal cabling system
Category 6 patch panel to either network equipment or a patch panel designated for voice
or other use in the equipment racks. For voice applications, the cable will be terminated
using 66 type cross-connect block on the telecommunications back board (TBB) adjacent to
the phone demark. Voice cross-connects for dial tone will be made here using standard
cross connect wire. By using backbone cables between telecommunications rooms, voice
connections can be made throughout the building using this system. Appalachian State
University Network Services will provide and install all equipment cables and patch cords
used in the telecommunication room for data connectivity and install them along with the
network equipment. All voice or other system cross-connect cables must be provided by
that system provider. All patch cords other than voice or data must be clearly labeled and
identified by the installer.
Category 6, 100ohm, UTP as described in the horizontal distribution section for distances up to
295’. Single-mode fiber optic cable 50/125μm multi-mode fiber optic cable
The types and number of cables used for backbone systems will vary for each project and must be
documented in the project specifications and documented on the drawings. Any termination or
splice enclosures used for optical fiber will be listed in the specifications and documented on the
drawings.
• Do not exceed the cable’s minimum bend radius. Bending cable tighter than the minimum bend
Radius may result in increased optical fiber attenuation or fiber breakage.
• The minimum bend radius for indoor backbone optical fiber cable is 10 times the cables outside
diameter under no load conditions and 15 times the cables outside diameter when being pulled.
• Do not exceed the cables maximum vertical rise and tensile rating.
• Where cables are installed in an air return plenum, the cable shall be installed in conduit, or plenum
cable shall be installed in a plenum innerduct to provide protection to the cable
• Where backbone cables and distribution cables are installed in a cable tray or wireway, backbone
cables shall be installed first and bundled separately from the horizontal distribution cables use
innerduct whenever possible.
NOTE: Do not locate backbone cable pathways in elevator shafts. Do not over fill conduits, ducts or
sleeves. Refer to the BICSI® Telecommunications Distributions Methods Manual, latest edition for more
information.
In all closets the racks shall be on the opposite side of the room from the voice termination fields. Voice
termination fields shall be mounted on 4’ x 8’ x .75” virgin fire retardant plywood, unless otherwise
noted in drawings, and shall be on the opposite side of the room from the room entrance. Backbone
termination fields shall be mounted to the left of the horizontal voice fields. Conduits with 4” minimum
diameter shall be used in all closets. Conduits for data backbone shall be located adjacent to the racks
and conduits for voice shall be located adjacent to the voice termination fields. The Contractor shall
provide innerduct for all backbone fiber runs. Contractor shall provide required ladder and wall-mount
management rings to properly support and dress cables from conduits to racks and frames.
• Racks shall be securely attached to the concrete floor using 3/8” hardware
• All racks shall be grounded to the telecommunications ground bus bar in accordance
with Section 11.0 of this document
• Rack mount screws (#12-24) not used for installing fiber panels and other hardware
shall be bagged and left with the rack upon completion of the installation
• Voice termination fields shall be mounted on 4’ x 8’ x .75” virgin fire retardant plywood
that is mounted vertically at 12” A.F.F.
• One set of Quad 20A 250V NEMA 6-20 receptacles mounted horizontally within 12” of the
hardware rack for each 200 data terminations. Each quad receptacle shall consist of two
dedicated circuits.
• Two sets of Quad 20A 120V NEMA 5-20 receptacles mounted horizontally within 12” of
the hardware rack for each 200 data terminations. Each set of quad receptacles shall be
on a dedicated circuit.
• Two sets of Quad 20A 120V NEMA 5-20 receptacles at each voice termination
plywood. Each set of quad receptacles shall be on a dedicated circuit.
All cables shall be tested in accordance with this document, the ND&I Contract agreement, and
best industry practices. If any of these are in conflict, the Contractor shall be responsible to bring
any discrepancies to the attention of the project team for clarification and/or resolution.
8.1.1 COPPER
Category 6 data cable shall be performance verified using an automated test set. Test results shall be
automatically evaluated by the equipment, using the most up-to-date criteria from the TIA Standard
currently TIA-568-C, and the result shown as pass/fail. Test results shall be printed directly from the
test unit or from a download file using an application from the test equipment manufacturer. The printed
test results shall include all tests performed, the expected test result and the actual test result
achieved.
8.1.2 FIBER
All 50/125 μm multi-mode optical fiber and/or Single mode optical fiber must be manufactured by
CommScope Cable Systems or equivalent manufacture. After installation, it must be performance
verified using an automated test set. Test results shall be automatically evaluated by the equipment,
using the most up-to-date criteria from the TIA Standard currently TIA-568-C, and the results shown as
pass/fail. Test results shall be printed directly from the test unit or from a download file using an
application from the test equipment manufacturer. The printed test results shall include all tests
performed, the expected test result and the actual test result achieved.
Firestop methods should be employed that meet the requirements of all applicable codes and/or
laws.
The main entrance facility/equipment room in each building shall be equipped with a
telecommunications main grounding bus bar (TMGB). Each telecommunications closet shall be
provided with a telecommunications grounding bus bar (TGB). The TMGB shall be connected to the
building electrical entrance grounding facility. The intent of this system is to provide a grounding
system that is equal in potential to the building electrical ground system. Therefore, ground loop
current potential is minimized between telecommunications equipment and the electrical system to
which it is attached.
All racks, metallic backboards, cable sheaths, metallic strength members, splice cases, cable trays,
etc. entering or residing in the TC or ER shall be grounded to the respective TGB or TMGB using a
minimum #6 AWG stranded copper bonding conductor and compression connectors. Where
metallic panels attached to the rack to not have sufficient metal to metal contact to provide an
adequate path to ground, they shall be bonded to the rack using a minimum #14 AWG copper
conductor. The copper conductor size shall be upgraded based on the largest power conductor
feeding any rack- mount equipment. The conductor shall be continuous, attaching all isolated
components in a daisy chain fashion from top to bottom and bonded to the rack using an
appropriate compression connector.
All wires used for telecommunications grounding purposes shall be identified with green
insulation. Non-insulated wires shall be identified at each termination point with a wrap of green
tape. All cables and busbars shall be identified and labeled in accordance with the System
Documentation Section of this specification.
The TBB shall adhere to the recommendations of the TIA-607-B standard, and shall be installed in
accordance with best industry practices. Installation and termination of the main bonding conductor
to the building service entrance ground, at a minimum, shall be performed by a licensed electrical
contractor.
• Communication tray systems shall be for exclusive use by Information Technology Services and
Media Services.
• The systems shall be designed for no more than 40% fill for the expected life of the building.
• The systems must be metallic and continuous, and all separate pieces must be bonded where they
are joined.
• The systems must be grounded to the building grounding system with a minimum 6 AWG copper
conductor. Refer to Section 11.0 for specific Grounding and Bonding requirements.
• Use insulated metallic bushings for attached metallic conduits. Ground and bond the conduits to the
tray (Figure A at the end of this document).
• The wire basket-style tray shall be U shaped and constructed of round wire mesh. The basket tray
shall be installed trapeze-style or wall-mounted. It must not be center hung. Snaketray or an
Information Technology Services approved manufacturer shall be used.
• End-of-tray cable waterfalls must be used where wire drops down to prevent abrasions and cuts
from metal tray edges.
• The tray must be no closer than 6 inches from the structural ceiling, ducts, pipes, or any other
possible obstructions. A minimum separation of 5 inches from lighting, especially fluorescent
lighting, is required.
• Compliance to this standard requires that the end of rigid or flex conduit must:
o Have a bushing
o Lie within the side and end planes of the cable tray
The contractor shall develop and submit for approval a labeling system for the cable installation.
Appalachian State University will negotiate an appropriate labeling scheme with the successful
contractor. At a minimum, the labeling system shall clearly identify all components of the system:
racks, cables, panels and outlets. The labeling system shall designate the cables origin and
destination and a unique identifier for the cable within the system. Racks and patch panels shall
be labeled to identify the location within the cabling system infrastructure. All labeling information
shall be recorded on the as-built drawings and all test documents shall reflect the appropriate
labeling scheme. All label printing will be machine generated using indelible ink ribbons or
cartridges. Self- laminating labels will be used on cable jackets, appropriately sized to the OD of
the cable, and placed within view at the termination point on each end. Outlet labels will be the
manufacturer’s labels provided with the outlet assembly.
The Contractor shall provide a detailed as-built drawing to the Owner at the conclusion of the
project. The marked-up drawing set will accurately depict the as-built status of the system including
termination locations, cable routing, and all administration labeling for the cabling system. In
addition, a narrative will be provided that describes any areas of difficulty encountered during the
installation that could potentially cause problems to the telecommunications system.
Test documentation shall be provided in pdf electronic format within three weeks after the
completion of the project. Test documentation shall include scanner test results (Enhanced
Category 5 or Category 6), fiber optic attenuation test results, and OTDR traces (if any). Test data
within each section shall be presented in the sequence listed in the administration records. The
test equipment name, manufacturer, model number and last calibration date will also be provided
at the end of the document. The test document shall detail the test method used and the specific
settings of the equipment during the test.
The Contractor shall facilitate a 25-year CommScope Uniprise system performance warranty or
industry equivalent between the Manufacturer and the Owner. An extended system performance
warranty shall be provided which warrants functionality of all components used in the system for
25 years from the date of acceptance. The system performance warranty shall warrant the
installed 250 MHz horizontal copper, and both the horizontal and the backbone optical fiber
portions of the cabling system. Copper links shall be warranted to the link performance minimum
expected results defined in TIA-568-C. Fiber optic links shall be warranted to the link and segment
performance minimum expected results defined in TIA-568-C.
The Contractor shall furnish an hourly rate with the proposal submittal which shall be valid for
a period of one year from the date of acceptance.
This rate will be used when cabling support is required to affect moves, additions, and
changes (MACs) to the system. MACs shall not void the Contractor’s nor Manufacturer’s
warranty.
The contractor shall establish a point of contact with Appalachian State University who will be
responsible for reporting progress and updating Appalachian State University’s Technical
Representatives, (Facilities Project Manager, ITS Application Services, ITS Network Services)
with issues that Appalachian State University must address to facilitate the cabling system
installation. Requests for access to limited access or restricted areas shall be made no later than
the day prior to the required access.
The contractor shall maintain Appalachian State University’s facility in a neat and orderly manner
during the installation of the communications cabling system. Appalachian State University’s
facilities shall be maintained in broom clean condition at the completion of work each day. At the
completion of work in each area, the contractor will perform a final cleaning of debris prior to
moving the installation crew to the next work area.
Upon completion of the project, the Customer’s technical representative will perform a final
inspection of the installed cabling system with the Contractor’s project foreman. The final inspection
will be performed to validate that all horizontal and backbone cables were installed as defined in
the drawing package, and that the installation meets the aesthetic expectations of the Customer.
Upon receipt of the test documentation, the Customer reserves the right to perform spot testing of
a representative sample of the cabling system to validate test results provided in the test
document. Customer testing will use the same method employed by the Contractor, and minor
variations will be allowed to account for differences in test equipment and test variability. If
significant discrepancies are found, the Contractor will be notified for resolution.
During the three-week period between final inspection and delivery of the test and as-built
documentation, the Customer will activate the cabling system. The Customer will validate
operation of the cabling system during this period.