20221012chandy222187-20221012142552 2

The document details the engineering specifications for a residential truss system for SC Building Systems, including job number 222187 and location in Brandon, MB. It outlines design criteria, loading specifications, and includes truss drawings and bearing locations. Additional notes emphasize the need for professional engineering review and proper handling during installation to prevent damage.

Uploaded by

landenmcd
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views4 pages

20221012chandy222187-20221012142552 2

The document details the engineering specifications for a residential truss system for SC Building Systems, including job number 222187 and location in Brandon, MB. It outlines design criteria, loading specifications, and includes truss drawings and bearing locations. Additional notes emphasize the need for professional engineering review and proper handling during installation to prevent damage.

Uploaded by

landenmcd
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Alpine Systems Corporation

120 Travail Road


Markham, ON L3S 3J1
Phone: (905)417-2766

10/12/2022

Site Information: Page 1:


Customer: SC Building Systems Job Number: 222187
Job Description: -AH -Alair Homes Brandon
Address: Brandon, MB

Job Engineering Criteria:


Building Code: NBCC 2010 Ground Snow Load (psf): 43.85 JRef #: 1XJQ92590001
Design Criteria: RESIDENTIAL Rain Load (psf): 4.18 Floor Load (psf): N/A Wind Pressure (psf): N/A
TPIC Standard: TPIC 2011 IntelliVIEW Version: 22.01.01B
CSA Standard: CSA O86-09

This package contains general notes pages, 2 truss drawing(s) and 1 detail(s).

Item Drawing Number Truss Item Drawing Number Truss


1 285.22.1425.26270 A01 2 285.22.1425.29613 A02
3 A100

#%INDEX?$
SEQN: 28417 GABL Ply: 1 Job Number: 222187 Cust: R 9259 JRef: 1XJQ92590001 T1 Bearing Locations
FROM: BR Qty: 1 -AH -Alair Homes Brandon DrwNo: 285.22.1425.26270 Loc Ht / W / Min Req / Ctrl
Truss Label: A01 / MB 10/12/2022
AJ 8'1"2 / 30'11"8/ - /-
Bearing AJ is a rigid surface.

2' Bearing Reactions (lbs)


(TYP)
9"12
Loc / S /L /D /F / Hz /U
A 12
2 AJ / 1752 / 0 / 1238 / 134 /0 /

Members not listed have forces less than 375#


3X6
I
8'4"6

3'2"7
AJ S
AB
3X6

30'11"8

30'11"8
30'11"8

Conforms To: Loading Criteria (psf) Wind Criteria Defl/CSI Criteria


Bldg Code: NBCC 2010 TCLL: 28.30 q: NA PP Deflection in loc L/defl L/D
Design Criteria: Residential TCDL: 10.00 Ref Ht: NA VERT(LL): 0.002 I 999 360
TPIC Std: TPIC 2011 BCLL: 0.00 Calc'd Int. Press: NA VERT(TL): 0.004 I 999 360
CSA Std: CSA O86-09 BCDL: 10.00 Exposure: NA HORZ(LL): 0.016 A - -
Ground Snow Load: 43.85 Des Ld: 48.30 BLDG Cat: NA HORZ(TL): 0.033 A - 1.00
Rain Load: 4.18 Lumber Duration: 1.00 Ceiling Attached: NA Creep Factor: 1.0
Cb: 0.55 Plate Duration: 1.00 TCDL: NA Overhang: Non-removable
Cs: 1.00 Spacing: 24.0 " BCDL: NA Max TC CSI: 0.06
Cw: 1.00 Load Sharing: Yes Duration of Load: NA Max BC CSI: 0.06
If: 1.00 PT/IT/RT: 4sx/10%/ 5 deg Max Web CSI: 0.22
Slippery Roof: N/A Plate Type: VIEW Ver: 22.01.01B.0530.21
Wind Exposed: N/A Wave-Canada
Lumber Additional Notes
Top Chord: 2x4 SPF #1/#2; Interaction equation as per Clause 5.5.10 of CSA-O86-O9.
Bot Chord: 2x4 SPF #1/#2; L/E vertical may not be exposed to horiz. wind pressure.
Webs: 2x4 SPF #1/#2;
Properly fasten sheathing to one face of this gable as per the
Plating Notes National Building Code of Canada, latest edition.
See A-100, Specification Note 7.E for standard plate positioning.
Plates designed for fabrication using seasoned lumber.
All plates are 1.5X4 except as noted.
Handling stresses not considered for the plates. Special care in
handling of this truss is required by truss manufacturer and
Installation Contractor to prevent plate damage.

Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 120 0.00 30.96
Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.

Loading
Loading spec'd by auth. having jurisdiction @ time of design.

10/12/2022

THIS DRAWING MUST BE REVIEWED BY A REGISTERED PROFESSIONAL ENGINEER BEFORE USE. SC Building Systems
SEE A100 FOR GENERAL NOTES, IMPORTANT SPECIFICATIONS AND WARNINGS. CCMC #12182-L, 12802-L, 13124-L 170, 2nd St. NE
Carman,
** MB
THIS DWG PREPARED FROM COMPUTER IMPUT (LOADS AND DIMENSIONS) SUBMITTED BY TRUSS MFR
(___)___-____ 120 Travail Road Markham, ON L3S 2J1
SEQN: 28432 MONO Ply: 1 Job Number: 222187 Cust: R 9259 JRef: 1XJQ92590001 T3 Bearing Locations
FROM: BR Qty: 7 -AH -Alair Homes Brandon DrwNo: 285.22.1425.29613 Loc Ht / W / Min Req / Ctrl
Truss Label: A02 / MB 10/12/2022
P 8'1"2 / 3"8 / 3"4 / Truss
J 8'1"2 / 5"8 / 4" / Truss
6'2"5 12'4"8 13'9"7 18'6"14 23'7"13 24'9"3 30'11"8
Bearings P & J are a rigid surface.
6'2"5 6'2"3 1'4"15 4'9"8 5'0"14 1'1"6 6'2"5
Bearing Reactions (lbs)
4X5[0] Loc / S /L /D /F / Hz /U
A 12
2
1.5X4
B
P / 872 /0 / 618 / 2081 / 0 /
3X4 J / 985 /0 / 657 / 2300 / 0 /
C 3X6
D
3X4
E 3X6 Members not listed have forces less than 375#
1.5X4
F G
Maximum Top Chord Forces Per Ply (lbs)
8'7"15

(a)
4X6[13] Chords Tens.Comp. Chords Tens. Comp.
(a) H
I
(a) A-B 0 - 1569 E-F 0 - 2591
B-C 0 - 1557 F-G 0 - 2612

3'6"
C-D 0 - 2783 G-H 0 - 2610
D-E 0 - 2869

P O N M L K J
3X4[1] 5X8[2] 3X6 3X4 3X8 4X10[11] 3X4[14] Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp. Chords Tens. Comp.
30'11"8 O-N 2493 0 M-L 2973 0
N-M 2493 0 L-K 2973 0
6'1"13 1'10"3 7'5"12 1'5"12 7'9"15 6'2"1 1'10"8
6'1"13 8' 15'5"12 16'11"8 24'9"7 30'11"8
Maximum Web Forces Per Ply (lbs)
Conforms To: Loading Criteria (psf) Wind Criteria Defl/CSI Criteria Webs Tens.Comp. Webs Tens. Comp.
Bldg Code: NBCC 2010 TCLL: 28.30 q: NA PP Deflection in loc L/defl L/D
Design Criteria: Residential TCDL: 10.00 Ref Ht: NA VERT(LL): 0.132 D 999 360 A-P 0 - 2027 M-E 0 - 388
TPIC Std: TPIC 2011 BCLL: 0.00 Calc'd Int. Press: NA VERT(TL): 0.277 D 999 360 A-O 2490 0 E-K 0 - 595
CSA Std: CSA O86-09 BCDL: 10.00 Exposure: NA HORZ(LL): 0.051 A - -
O-B 0 - 768 K-G 0 - 712
Ground Snow Load: 43.85 Des Ld: 48.30 BLDG Cat: NA HORZ(TL): 0.106 A - 1.00
Ceiling Attached: NA Creep Factor: 1.0 O-C 0 - 1437 K-H 2843 0
Rain Load: 4.18 Lumber Duration: 1.00
Cb: 0.55 Plate Duration: 1.00 TCDL: NA Overhang: Non-removable C-M 642 0 H-J 0 - 2244
Cs: 1.00 Spacing: 24.0 " BCDL: NA Max TC CSI: 0.53
Cw: 1.00 Load Sharing: Yes Duration of Load: NA Max BC CSI: 0.75
If: 1.00 PT/IT/RT: 4sx/10%/ 5 deg Max Web CSI: 0.69
Slippery Roof: N/A Plate Type: VIEW Ver: 22.01.01B.0530.21
Wind Exposed: N/A Wave-Canada
Lumber Purlins
Top Chord: 2x4 SPF #1/#2; In lieu of structural panels or rigid ceiling use purlins
Bot Chord: 2x4 SPF #1/#2; to laterally brace chords as follows:
Webs: 2x4 SPF #1/#2; Chord Spacing(in oc) Start(ft) End(ft)
BC 120 0.00 30.96
Bracing Apply purlins to any chords above or below fillers
(a)1x4 SPF #3 or better continuous lateral bracing to be eq. at 24" OC unless shown otherwise above.
spaced. Attach w/(2) 2.5" nails. Bracing material supplied &
attached @ both ends to a suitable support by Erection Loading
Contractor. Loading spec'd by auth. having jurisdiction @ time of design.

Plating Notes Additional Notes


See A-100, Specification Note 7.E for standard plate positioning. Interaction equation as per Clause 5.5.13.5 of CSA-O86-O9 for
Plates designed for fabrication using seasoned lumber. truss design.
Handling stresses not considered for the plates. Special care in L/E vertical may not be exposed to horiz. wind pressure.
handling of this truss is required by truss manufacturer and
Installation Contractor to prevent plate damage.

Plate Shift Table


JT Plate Lateral Chord JT Plate Lateral Chord
No Size Shift Bite No Size Shift Bite
[ 0] 4X5 3.75 R 1.50 [ 1] 3X4 S 2.25
[ 2] 5X8 2.75 L 1.50 [11] 4X10 3.50 R 1.50
[13] 4X6 2.50 R 1.50 [14] 3X4 S 2.50
10/12/2022

THIS DRAWING MUST BE REVIEWED BY A REGISTERED PROFESSIONAL ENGINEER BEFORE USE. SC Building Systems
SEE A100 FOR GENERAL NOTES, IMPORTANT SPECIFICATIONS AND WARNINGS. CCMC #12182-L, 12802-L, 13124-L 170, 2nd St. NE
Carman,
** MB
THIS DWG PREPARED FROM COMPUTER IMPUT (LOADS AND DIMENSIONS) SUBMITTED BY TRUSS MFR
(___)___-____ 120 Travail Road Markham, ON L3S 2J1
#%DETAIL?$
�cu

AlOO Notes

ALPINE
> ill)
i�
I I

> AN ITW COMPANY


t�>-- _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ - _ __ _ _ _ - - - - - -�
MnrkhnM,DN / CoqultlnM, BC / Gntlnenu, QC
SPE:ClflCATIDNS• SPECIAL ENGINEERING NDTE:S•
Design stnndnrds conforM to nppllcnble provisions of TPIC, CSA 086 nnd NBCC,BCBC,ABC,nnd CBC Clntest ndopted editions> 1, Handling co.re should be to.ken during shipping and erection of' trusses.
Alpine SysteMs CorporQtlon certifies that trusses Mo.nufo.ctured to Its design o.re suitable for the use specifically Indicated 2. \lornlng• SpeclQl handling CQre should be token during shipping and erection. \le recoMMend seeking
provided thnt• the advice of' a local Professional Engineer.
3. \lornlng1 The configuration/length of' this truss Is such that extreMe caution Must be exercised
1, The truss loading, as well as load transfer Mechanlsl'I, Is Indicated on the drawing, Jn handling and Installation to prevent do.Mage, Refer to BCSI-BlC for recoMMendo.tlons. \le
Recoru"lend seeking the advice of' a local Professional Engineer,
2, The building Mntches the type of building requested by the Mnnufncturer, which Is lndlcnted on the drnwing. 4. ••••••••• \/ARNING ••••••••• DANGER •••••••• Special and extreMe precautions should be
to.ken to Insure that these trusses do not bend More than 3'0' out of' plane during f'o.brlco.tlon,
3, CoMpresslon chords, typically Top Chords, o.re bro.ced using o. continuous rigid dlo.phro.gM sheo.thlng, or o.re bro.ced o.t hnndllng,shipping nnd lnstnllntlon. Speclnl nttentlon Is required so thnt the hnndllng nnd brnclng
Intervals not exceeding 12.5 tlr1es their thickness [18,75' o.c,l, or o.s specified on the Individual design. Tension chords, recOMMendntlons set forth In TPI publlcntlon BCSI-BIC nre strictly ndhered to. Ensure thnt the
typlco.lly BottoM Chords, o.re braced using o. continuous rigid dlo.phro.gM sheo.thlng, or o.re braced o.t lntervo.ls not teMporo.ry and perMo.nent bracing Is o.dequo.te and tho.t trusses are Installed straight and pluMb,
exceeding 80 tlMe their thickness, 10'-0' o,c, MQXIMUM, or as specified on the lndlvlduQl design. All other MeMbers ore to be Be advised tho.t trusses with broken or do.Maged MeMbers or connector plo.tes shall be scrapped
braced as Indicated by the Individual design, Bracing that Is referred to here Is to be securely anchored to prevent and replaced, Repair of' any MeMber Is IMposslble due to the critical nature of' this structure, A
overall MoveMent of the structures as a whole, teMporory support at the center of' the span Is strongly rec0Mr1ended during the erection of'
these trusses and should reMo.ln there until all perMo.nent bracing Is In place. Seek the advice of'
4, A properly designed bracing systeM,Maintaining the trusses In a pluMb position Qnd providing resistance to wind, selsMlc a local Professional Engineer.
loads and sway Is Installed, Bracing appearing on Alpine drawings Is used as a coMponent of the truss and forMs on '5, Truss shall be used In enclosed buildings In non-corrosive envlronMents with adequate ventllo.tlon,
Integral port of' the truss coMponent design. F'allure to provide proper ventllotlon will result In the eventual do.Mage to the coMponent.
6, The bottoM chord of' an attic fro.Me Must be adequately braced by using cross bracing and/or
'5, Proper core and handling of trusses during fabrication,shipping and erection ore the responsibilities of the fabricator strnpplng ns required by the Nntlonnl Building Code,lntest ndopted edition,In conjunction with
and the erectors respectively, Procedures consistent with good workMonshlp and good building practices o.re the appropriate chord size and rooM size,
responsibility of the building contrnctor.

6, Trusses are supported where Indicated on the design sheet o.nd anchored where considered necessary by the designer
of the overall structure, Bearing sizes and bearing details shown on the design ore adequate or More than adequate to HARSH E:NVIRDNME:NTAL CDNDITIDNS•
prevent crushing of' the truss MeMber, This does not, however, take Into account the overall stability of the supporting
structure, Alpine does not design supporting structures, NOTE• If' this truss Is to be used In harsh envlronMento.l conditions,we recoMMend the following•
1, Relative huMldlty Must not exceed 70¼ for More than six consecutive days,
7, Mnterlnh 2, End of' luMber segMents are to be coated with sealant such o.s 'ThoMpsons Water Seal' to
prevent MoveMent of' Moisture through luMber.
A. The luMber used shall be of the size and species,or better,as Indicated on the truss drawing, 3, After fabrication, all connector plates are to recleve two coo.ts of' Glidden Coo.l Tar Epoxy
B, Unless expressly noted, this truss design Is not applicable for use with fire retardant,preservative treated or #5270/5271. All Mnterlnl Is to be npplled nt n rnte of 10.5 MIis wet to nchleve 8.0 MIis dry. Plntes
unseasoned luMber. Must be coMpletely coated to prevent air access to exposed portions of' plate Including teeth
C, The Moisture content of' the luMber shall not exceed 19¼ o.t tlMe of f'o.brlco.tlon, unless otherwise noted, outside the surface of' the wood, $%Lbl:A100.PDF?$

D, Plates used by the fabricator are supplied by Alpine and are of that type,size and gauge o.s Indicated on the 4. Trusses to be Inspected periodically for signs of' corrosion In Metal connector plates, Plates
drawings and placed on both faces of the truss. tho.t becoMe corroded Must be IMMedlo.tely repaired or replaced.
E:, Plnte positioning• Lnternlly centered on the Joint left to right, Chord nnd web MeMber bites nccordlng to Tnble '5, LuMber and plate values have been reduced to take Into account the harsh envlronMento.l
5.1.(7), TPIC 1996/2011 or Tnble 7.1.7,TPIC 2014,unless otherwise specified on plnte positioning tnble or when shown conditions,
on truss drawing,
F. The truss Is Manufactured by an authorized fabricator In accordance with o. design approved by o. registered TD THE BEST CF DUR KND',/LE:DGE: THESE RE:CDMME:NDATIDNS ',/ILL EXTEND SERVICEABLE: LIFE CF THE TRUSS
professional engineer authorized by Alpine, UNDER HARSH E:NVIRDNME:NT CDNDITIDNS, ND ',/ARRANTY DR GUARANTEE: CF ANY KIND IS EXPRESSED DR IMPLIED,
G. Unless otherwise specified on the lndlvlduo.l design sheets, the coMponent Is designed for o. Dry Service Condition, FDLLD',/ MANUFACTURER'S RE:CDMME:NDATIDNS FDR APPLICATIDN CF PRODUCTS USED.
I.e. the In-service overage Moisture content of' the lur1ber Is not to exceed 1'5¼ In any one year Qnd Is never to
exceed 19¾, Fnllure to coMply with this requlreMent will nffect the structurnl Integrity of the coMponent nnd Alpine DUE TD THE CDRRDSIVE: NATURE CF THE E:NVIRDNME:NT IN ',/HICH THIS DESIGN IS TD BE USED,THE
SysteMs will not guarantee the coMponents perforMo.nce. PERFORMANCE: CF THIS FRAME: AND ITS CDNNE:CTIDNS CAN NDT BE GUARANTEED BY ALPINE: SYSTEMS
CDRPDRATIDN,
8, DIMenslons and geor1etry of the lnsto.lled truss Match that of' the design sheet,
9, Brace Loco.tlons and Lengths•

A. ane (1) continuous laterol brace,<CLB) to be placed at the center of the web length,
B, Two C2l CLB's to be plnced nt third points of web length,
C. T-Bro.ce,Scab Brace & L-Broces are to be a MlnlMUM of' 90¼ of the length of' the web.

10. MINIMUM DE:FLE:CTIDN RE:QUIRE:ME:NTSJ


Ho.xlMUM truss deflection shall be based on the greater of' live or dead load deflection for trussesJ 1-1/3 live plus dead E
load deflection for Po.rt 9 Housing and SMo.ll Building o.nd Sectional/Mobile hoMe roof' trusses Live Load or Total
0
u
Load deflection for Po.rt 4 and Port 4 Low HuMo.n Occupancy CF'o.rr1l Trusses Live Load or Total Load
deflection for Po.rt 4 Floor truss designs for Residential and SMo.ll Building occupancy

MAXIMUM DE:FLE:CTIDN shnll be IIMlted ns follows,


A, ',/Ith plnster or gypsuM bonrd celling finish•
- Pnrt 4• LL= L/360 TL= L/240
- Pnrt 9• TL= L/360
B. Dther thnn plnster or gypsuM bonrd celling finish•
- Pnrt 4 Including Low HuMnn Dccupnncy, LL= L/240 TL= L/180
- Pnrt 9• TL= L/360 MAXIMUM ALLD\JABLE: CHDRD CSI'S FDR 4 & 5 PLY GIRDERS,
C, Po.rt 4 floor truss design•
- ',/Ith plnster or gypsuM bonrd celling, LL= L/360 TL= L/240
- Dther thnn plnster or gypsuM bonrd celling• LL= L/240 TL= L/180 TCP DR BDTTDM CHDRD SIZE
D. Cnntllever deflection shnll be IIMlted to length of cnntllever/120.
E. Overhang Deflection - Ho.xlMUM overhang deflection shall be based on total loo.cl and shall be llMlted to overhang FASTENER TYPE 2X6 2X8 2XIO 2X12 Q_
length/120. 1/2'0 Bolts 0,90 0.93 0,94 0,95
F. Top Chord Pnnel Deflection - MnxlMUM top chord pnnel deflection shnll be bnsed on totnl lond nnd shnll be
IIMlted to pnnel length/180. 0.22•0 SIMpson SD\I screws 0.96 0.96 0.97 0.98
G. Bo-ttor1 Chord Panel Deflection - Mo.xlMUl'I bottoM chord panel deflection shall be based on total load and 10/12/2022 0.25'0 RSS GRK screws 0.95 0,96 0,97 0.97
shnll be IIMlted to pnnel length/360,
H. Horlzontnl Deflection nt Supports - MnxlMUM horlzontnl totnl lond deflection shnll not exceed 25 MM, 0.25'0 SIMpson SDS screws 0.95 0,96 0,97 0.97

CCMC 112182-L, 12802-L, 13124-L


n'JARNINGH TRUS:S:ES REQUIRE EXTREME CARE IN FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING REFER TO BCSI BlC (HANDLING, INSTALLING, RESTRAINING AND BRACING>, JOINTLY PRODUCED BY TPIC, TPI AND SBCA, AND AVAILABLE AT W'.Y\JSBGINDIJSIRYCQM/BCS! CANPA FOR BEST PRACTICES PRIOR TD PERFORMING THES:E FUNCTIONS. UNLESS OTHERVJSE INDICATED, TOP
CHORD SHALL HAVE PROPERLY ATTACHED STRUCTURAL PANELS AND BOTTOM CHORD SHALL HAVE A PROPERLY ATTACHED RIGID CEJLING. nIMPORTANTu FURNISH A COPY OF THIS DESIGN TD THE INSTALLATION CONTRACTOR. ALPINE SYSTEMS CORPORATION SHALL NOT BE RESPONSIBLE FOR ANY DEVIATION FROM THIS DESIGN1 ANY FAILURE TO BUILD THE TRUSSES IN CONFORMANCE VITH TPIC1
OR FABRICATING, HANDLING, SHIPPING, INSTALLING AND BRACING OF TRUSSES. DESIGN CONFORMS 'JITH APPLICABLE PROVISIONS OF CSA 086 (CANADIAN STANDARDS ASSDCJATIDN), NBCC, AND TPIC. ALPINE CONNECTORS ARE HADE OF 20GA ASTM A653 GR40 GALV. STEEL EXCEPT AS NOTED APPLY CONNECTORS TD EACH FACE or TRUSS AND, UNLESS OTHERVISE LOCATED ON THIS DESIGN,
POSITION CONNECTORS PER DRA\./INGS 160 A-Z, THE SEAL ON THIS DRA'JING INDICATES ACCEPTANCE OF PROFESSIONAL ENGINEERING RESPONSIBILITY SOLELY FOR THE TRUSS COMPONENT DESIGN SHO'JN THE SUITABILITY AND USE OF THIS COMPONENT FOR ANY SPECIFIC BUILDING IS THE RESPONSIBILITY OF THE BUILDING DESIGNER, PER APPLICABLE TPIC DESIGN STANDARD