BXUV.D957 - UL Product Iq
BXUV.D957 - UL Product Iq
D957 | UL Product iQ
See General Information for Fire Resistance Ratings - CAN/ULC-S101 Certified for Canada
Design Criteria and Allowable Variances
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL
Certification (such as Canada), respectively.
https://iq.ulprospector.com/es/profile?e=13928 1/9
16/4/25, 20:05 BXUV.D957 | UL Product iQ
1. Beam — W12X14, W8X28, W8x24 or W6x12, min size, see Items 6A through 6E.
1A. Steel Joists — (Not shown) — As an alternate to Item 1 — May be either uncoated or provided with a shop coat of paint.
Composite or noncomposite. Welded or bolted to end supports. Designed per S.J.I. specifications for a max design stress of 30 ksi.
The top chords shall consist of two angles measuring 1-1/4 by 1-1/4 by 0.127 in. thick. Bottom chords shall consist of two round
bars measuring 0.566 in. in diam. or two angles measuring 1 by 1 by 0.125 in. thick. Bearing plates shall consist of two angles
measuring 1-1/2 by 2 by 0.188 in. thick and 5-1/16 in. long. Web members shall consist of 0.565 in. diam bars. The min depth and
weight shall be 8 in. and 4.9 lb/ft, respectively.
1B. Steel Joists — (Not shown) — As an alternate to Item 1 — Composite or noncomposite and welded or bolted to end
supports. May be uncoated or provided with a shop coat of paint. Designed per S.J.I. specifications for a max design stress of
30,000 psi. Top chords shall consist of two angles measuring 1-1/2 by 1-1/2 by 0.156 in. thick. Bottom chords shall consist of two
round bars measuring 0.675 in. in diam. or two angles measuring 1 by 1 by 0.125 in. thick. Bearing plates shall consist of two
angles measuring 2 by 2 by 0.192 in. thick and shall be min 4-15/16 in long. The second web member at each end shall consist of
0.654 in. diam round bar. All remaining web members, including the end web members, shall consist of 0.774 in. diam round bars.
Bridging per S.J.I. specifications is required when noncomposite joists are used.
1C. Steel Joists — (Not shown) — As an alternate to Item 1 — Composite or noncomposite, welded or bolted to end supports.
May be uncoated or provided with a shop coat of paint. Designed per S.J.I. specifications for a max design stress of 30,000 psi. Top
chords shall consist of two angles measuring 1-1/2 by 1-1/2 by 0.156 in. thick. Bottom chord shall consist of two round bars
measuring 0.675 in. in diam. or two nangles measuring 1 by 1 by 0.125 in. thick. The second web member at each end shall consist
of 0.654 in. diam round bar. All remaining web members, including the end web members, shall consist of 0.774 in. diam round
bars. Bridging per S.J.I. specifications is required when noncomposite joists are used.
https://iq.ulprospector.com/es/profile?e=13928 2/9
16/4/25, 20:05 BXUV.D957 | UL Product iQ
1D. Steel Joists — (Not shown) — As an alternate to Item 1 — May be either uncoated or provided with a shop coat of paint.
Composite or noncomposite. Welded or bolted to end supports. Designed per S.J.I. specifications for a max design stress of 30 ksi.
The top chords shall consist of two angles measuring 1-1/4 by 1-1/4 by 0.127 in. thick. Bottom chords shall consist of two round
bars measuring 0.566 in. in diam. or two angles measuring 1 by 1 by 0.125 in. thick. Bearing plates shall conform to S.J.I.
specifications . Web members shall consist of 0.565 in. diam bars. The min depth and weight shall be 8 in. and 4.9 lb/ft
respectively.
2. Normal Weight or Lightweight Concrete — Normal weight concrete, carbonate or siliceous aggregate, 3500 psi compressive
strength, vibrated. Lightweight concrete, expanded shale or slate aggregate by rotary-kiln method or expanded clay aggregate by
rotary-kiln or sintered-grate method, 3000 psi compressive strength, vibrated, 4 to 7 per cent entrained air.
Restrained Concrete Concrete Unit Concrete
Assembly Rating Hr (Type) Weight pcf Thkns In.
3A. Negative Reinforcement — (Not Shown) - Optional - For floor spans with concrete cast continuous over the supporting
beams. Deformed bars designed to resist the support moments of the concrete slab in accordance with the latest ACI Building
Code Specifications.
4. Steel Floor and Form Units* — Composite or non-composite, 1-1/2, 1-5/8 , 2 or 3 in. deep galv units or 4-1/2 in. deep non-
composite galv units. Fluted units may be phos/ptd. Min gauges are 22 MSG for fluted and 20/20 for cellular and partial cellular
units. The following combinations of units may be used:
(1) All 24, 26, 28 or 36 in. wide cellular or partial cellular.
(3) One or two 3 in. deep, 12 in. wide, 18/18 MSG min cellular alternating with 3 in. deep fluted or other cellular.
(4) Any blend of fluted and 24, 26, 28 or 36 in. wide cellular or partial cellular.
(5) Corrugated, nom 1-5/16 or 2 in. deep, 30 in. wide, 24 MSG min galv units with shear wires factory welded to deck corrugations. Welded to
supports 12 in. OC through welding washers. For shear wire spacing of 8 in. or less the steel deck stress shall not exceed 20 KSI. For shear wire
spacing greater than 8 in. OC but less than or equal to 12 in. OC steel deck stress shall not exceed 12 KSI.
ASC STEEL DECK, DIV OF ASC PROFILES L L C — 36 in. wide Types 2WH-36, 2WHS-36, 2WHF-36, 2WHF-36A, 3WxH-36, 3WxHF-36, 3WxHF-
36A, 3WH-36, 3WHF-36, 3WHF-36A, BH-36, BHN-36, BHN-35-1/4, 3W-36, 3WF-36. All units may be galvanized or Prime Shield. Non-cellular
decks may be vented designated with a "V" suffix to the product name. Cellular deck top and bottom sections may be riveted together
(designated with "Fr") vs. arc spot welded, "F".
https://iq.ulprospector.com/es/profile?e=13928 3/9
16/4/25, 20:05 BXUV.D957 | UL Product iQ
CANAM GROUP INC — 24 in. wide Type P-2432 composite or 36 in. wide Type P-3623, P-3606, P-3615 and 24 in wide Type P-2432
composite, Type P-3606 and P-3615 non-composite; 24 or 36 in. wide Type 3 in. LOK-Floor; 36 in. wide Types 1.5B, 1.5BI, 1.5BL and 1.5BL; 24
in. or 36 in. wide, Type LF2, vented Types LF2 and LF3.
CANAM STEEL CORP — 12 or 24 in. wide, Types 1-1/2, 2, or 3 in. LOK-Floor and LOK-Floor Cell; 36 in. wide, Types 2 or 3 in. LOK-Floor and
LOK-Floor Cell; 24, 30 or 36 in. wide, Type 1-1/2 in. B-LOK and B-LOK Cell; 24 in. wide, Types N-LOK and N-LOK Cell.
CHIA TEH CONSTRUCTION MATERIAL CO LTD — 24 or 36 in. wide Mac-Lok 3; 24 in. wide CFD-3.
DECK WEST INC — 36 in. wide Type B-DW, Inverted B-DW, BA-DW, Inverted BA-DW, 2-DW or 3-DW. Side joints of Type 2-DW and 3-DW
may be fastened together with min 1 in. long No. 12 x 14 self-drilling, self-tapping steel screws 36 in. OC.
EPIC METALS CORP — 24 in. wide Types EC150, EC150 inverted, EC300, EC366, ECP150, ECP300, ECP366, Epicore A, 2.0 ECA; 30 in. wide Types
ECB150, ECBR150; 36 in. wide Types EC156, EC266, ECP266.
INTSEL STEEL EAST LLC — 36 in. wide Types 1.5" COMPOSITE/FLOOR, 2" COMPOSITE/FLOOR, 3" COMPOSITE/FLOOR.
KAM INDUSTRIES LTD, DBA CORDECK — 24 in. wide, Types 2 or 3 in. WDR.
MARLYN STEEL DECKS INC — Type 1.5 CF, 2.0 CF or 3.0 CF.
NEW MILLENNIUM BUILDING SYSTEMS L L C — 24 or 36 in. wide Types 2.0CD, 3.0CD, 2.0CFD, 3.0CFD, 3.0CFDES; 24, 30 or 36 in. wide
Types 1.5CD, 1.5CDI, 1.5CDR, 1.5CFD. Fluted units may be phos/painted or galvanized.
ROOF DECK INC — 36 in. wide Types LOK-1-1/2, LOK-1-1/2R; 24 in. wide Types LOK-2, LOK-3.
STEEL MASTERS INTERNATIONAL DEPENDABLE STEEL — 36 in. wide Types 2WH-36, 3WH-36. Units may be phos/painted or galvanized.
VERCO DECKING INC - A NUCOR CO — — FORMLOK™ deck types PLB, B, BR, PLN3, N3, PLN, N, PLW2, W2, PLW3, W3. Units may be
galvanized, phos./ptd., or mill finish. Units may be cellular or acoustical cellular, with the suffix "CD" or "CD-AC" added to the product name,
respectively. All non-cellular deck may be vented or non-vented.12 in. wide PLW2, W2, PLW3 or W3 units may be blended with 24 or 36 in.
wide PLW2, W2, PLW3 or W3 units, respectively; or Types PLN3-CD, N3-CD, PLN3.
VULCRAFT, DIV OF NUCOR CORP — 24, 30 or 36 in. wide, Type 1.5 VL, 1.5VLI, 1.5PLVLI, 1.5VLP, 1.5PLVLP; 24 or 36 in. wide, Types 2VLI,
2.0PLVLI, 3VLI, 3.0PLVLI, 2VLP, 2.0PLVLP, 3VLP, 3.0PLVLP. 36 in. wide Types 1.5 SB, 1.5 SBR; 24 or 36 in wide Types 2.0 SB, 3.0 SB, 36 in. wide
Type High Strength 1.5 SBI, 36 in. wide Type High Strength 1.5 SBN; Units may be phos/ptd.
Spacing of welds attaching units to supports shall be 12 in. OC for 12, 24, 36 in. wide units, four welds per sheet for 30 in. wide units. 6 in. OC
for 18 in. wide and Sec. 12 units. Unless specified otherwise for specific units types, adjacent units button-punched or welded together 36 in.
OC along side joints. For 3 Hr Rating, units with overlapping type side joints welded together 24 in. OC max.
When a superimposed load of 250 PSF is desired the spacing of welds or button-punches shall not exceed 24 in. OC along side joints.
Alternate Construction — Noncomposite units of the same type listed above may be used provided allowable loading is calculated on the
basis of noncomposite design.
The Unrestrained Assembly Rating is equal to the Unrestrained Beam Rating (See Item 6) for a max 3 Hr and is limited to the following units
and limitations:
(a) 1-1/2, 2 and 3 in. deep, 24 in. wide, 22 MSG or thicker fluted with clear spans not more than 7 ft, 8 in.
(b) 1-1/2, 2 and 3 in. deep, 24 in. wide, 20 MSG or thicker fluted with clear spans not more than 8 ft, 8 in.
https://iq.ulprospector.com/es/profile?e=13928 4/9
16/4/25, 20:05 BXUV.D957 | UL Product iQ
(c) 1-1/2 and 2 in. deep, 24 in. wide, 16 MSG or thicker fluted and 18/18 MSG or thicker cellular with clear spans not more than 9
ft, 11 in.
(d) 3 in. deep, 36 in. wide, 18 MSG or thicker fluted and 24 in. wide, 20/18 MSG or thicker cellular with clear spans not more than
13 ft, 2 in.
For assemblies utilizing 3-1/4 in. lightweight concrete topping with a max Restrained Assembly Rating of 2 Hr, the Unrestrained Assembly
Rating is equal to the Unrestrained Beam Rating (See Item 6) and is limited to the following floor units and spans:
(a) 1-1/2, 2 and 3 in. deep, 24 or 36 in. wide, 22 MSG fluted and 20/20 MSG cellular with clear spans not more than 9 ft, 6 in.
(b) 2 and 3 in. deep, 24 or 36 in. wide, 20 MSG fluted and 20/20 MSG cellular with clear spans not more than 10 ft, 0 in.
(c) 3 in. deep, 24 in. wide, 20 MSG fluted and 20/20 MSG cellular with clear spans not more than 13 ft, 2 in.
5. Joint Cover — (Use with fluted units optional — Not Shown) — 2 in. wide cloth adhesive tape applied following the contour of
the units.
6. Spray-Applied Fire Resistive Materials* — Applied by mixing with water according to instructions on each bag of material.
Mixture can be spray or trowel applied in one or more coats. The thickness of the mixture is dependent on the type of floor unit.
See table below for appropriate thickness. When fluted steel deck is used and the fire protection thickness selected is based on all
fluted deck, the area between the steel deck and the top flange of the steel beam shall be filled. When fluted steel deck is used
and the steel beam is sprayed with the thicknesses applicable to cellular or blended units, the area between the steel deck and the
top flange of the steel beam shall be plugged. The steel surfaces must be clean and free of dirt, loose scale and oil. Min avg
density of 44 pcf with min ind value of 40 pcf for Types PFM2 or F5. Min avg density of 44 pcf with min ind value of 42 pcf for
Types PFTG or F5T. For method of density determination, refer to Design Information Section, Sprayed Material.
2 2 15/16 1-1/4
2 3 1-5/16 1-1/2
3 1-1/2 5/8 1
3 2 15/16 1-1/4
3 3 1-15/16 1-1/2
*This thickness applies when optional Item 12 or 13 are used over 3-1/4 in. lightweight concrete topping.
FLAMTECHNIC CO LTD — Types PFM2 or PFTG. Types PFM2 and PFTG investigated for exterior use.
MOY YUAN INDUSTRIAL LTD — Types PFM2 or PFTG. Types PFM2 and PFTG investigated for exterior use.
ETEX MIDDLE EAST LLC — Types PFM2 or PFTG. Types PFM2 and PFTG investigated for exterior use.
PROMAT INC — Types F5, F5T, PFM2 and PFTG investigated for exterior use.
PROMAT AUSTRALIA PTY LTD — Type PFM2, investigated for exterior use.
PROSTAR CONTRACT SERVICES PTE LTD — Types PFM2 or PFTG. Types PFM2 and PFTG investigated for exterior use.
https://iq.ulprospector.com/es/profile?e=13928 5/9
16/4/25, 20:05 BXUV.D957 | UL Product iQ
SHIN SUNG MINERAL CO LTD — Types PFM2 or PFTG. Types PFM2 and PFTG investigated for exterior use.
6A. Spray-Applied Fire Resistive Materials* — Alternate to Item 6. Applied by mixing with water in accordance with instructions
on each bag and applied in one or more coats to a final thickness as shown in table below to steel beam surface which is free of
dirt, oil or scale. When fluted steel deck is used and the fire protection thickness selected is based on all fluted deck, the area
between the steel deck and the top flange of the steel beam shall be filled. When fluted steel deck is used and the steel beam is
sprayed with the thicknesses applicable to cellular or blended units, the area between the steel deck and the top flange of the
steel beam shall be plugged.
Min average and min individual density is 17.5 and 16 pcf, respectively, for Types PC3C, F3, RS or DS. Min average and min individual density
of 22 and 19 pcf, respectively, for Types PC4C or F4. For method of density determination, refer to Design Information Section. The thickness
of the material on the Structural Members (Item 1, 1C, or 1D) shall be as follows:
*This thickness applies when optional Item 12 or 13 are used over 3-1/4 in. lightweight concrete topping.
6B. Spray-Applied Fire Resistive Materials* — Alternate to Item 6. Applied by spraying with water, in one coat to a final
thickness as shown above and in table below to steel beam surface which is free of dirt, oil or scale. When fluted steel deck is used
and the fire protection thickness selected is based on all fluted deck, the area between the steel deck and the top flange of the
steel beam shall be filled. When fluted steel deck is used and the steel beam is sprayed with the thicknesses applicable to cellular
or blended units, the area between the steel deck and the top flange of the steel beam shall be plugged. Use of adhesive is
optional. Min avg untamped density is 13 pcf with min ind untamped density of 11 pcf for Types FC or DF. Tamping is optional.
For method of density determination, refer to Design Information Section. The thickness of the Spray-Applied Fire Resistive
Materials on the Structural Members (Item 1, 1A, or 1B) shall be as follows:
Protection Mtl Thknson Structural Member In.
Joist Joist
W8x28 W12x14 Item 1A Item 1B
W8x28 When When When When
Restrained Unrestrained When Deck Deck Deck Deck
Assembly Beam Deck Is Blend Is Is Fluted Is Fluted
Rating Rating Concrete Is All or All All Cellular Cellular
Hr Hr Type Fluted Cellular Fluted or Blend or Blend
https://iq.ulprospector.com/es/profile?e=13928 6/9
16/4/25, 20:05 BXUV.D957 | UL Product iQ
*May be reduced to 3/4 in. for the 1-1/2 hr Unrestrained Beam Rating when the material is sprayed 2 in. beyond the beams's top flange and
no reduction in thickness is made at the tips of the bottom flange.
**This thickness applies when optional Item 12 or 13 are used over 3-1/4 in. lightweight concrete topping.
+Thickness of Spray-Applied Fire Resistive Materials may be reduced to one half of this thickness on the lower flange tips of the steel beam.
++ - When bottom chords consist of 1 by 1 by 0.125 in. thickn steel angles, the thickness of spray-applied fire resistive material shall be
increased by 1/4 in. on the bottom chord only.
6C. Mastic and Intumescent Coatings* — As an alternate to Items 6 through 6B. For use with fluted steel floor and form units
only. Min. size W8x24 or W6x12 beams shall be primed with a phenolic modified alkyd primer at a thickness of 1 mil. Coating
spray or brush applied in accordance with the manufacturer's instructions at the min dry thickness as shown in the table below.
The thickness shown below includes the 1 mil of primer. Flutes above beam to be completely filled with minimum 6 pcf mineral
wool insulation, or the top flange of the beam to be protected with the same thickness of coating as required on the beam.
Unrestrained Restrained
Minimum Dry Minimum Dry Beam Assembly
Thickness mils Thickness mm Beam Size Rating Hr Rating Hr
53 1.34 W8x24 1 2
73 1.83 W6x12 1 2
6D. Mastic and Intumescent Coatings* — As an alternate to Items 6 through 6C. For use with normal weight concrete. Min. size
W8x28 beams shall be primed with a phenolic modified alkyd primer at a thickness of 1 mil. Coating spray or brush applied in
accordance with the manufacturer's instructions at the min dry thickness as shown in the table below. The thickness shown below
https://iq.ulprospector.com/es/profile?e=13928 7/9
16/4/25, 20:05 BXUV.D957 | UL Product iQ
includes the 1 mil of primer. The top surface of the top flange where fluted units are used must be protected with the coating
material at the same min dry thickness at a min distance of 1 in. (25 mm) inward from the flange tip on both sides of the beam.
Mineral wool insulation optional above top surface of the beam.
Unrestrained Restrained
Minimum Dry Minimum Dry Steel Floor Beam Assembly
Thickness mils Thickness mm Units Rating Hr Rating Hr
PROMAT FIRE & INSULATION PRIVATE LTD — Type PS3, Investigated for Interior General Purpose.
7. Shear Connector Studs — Optional — Studs, 3/4 in. diam by 3 in. long, for 1-1/2 in. deep form units to 5-1/4 in. long for 3 in.
deep form units, headed type or equivalent per AISC specifications. Welded to the top flange of the beam through the steel form
units.
8. Lath Hanger — (Not Shown) — Optional — For use in caged beams with Items 6 or 6A Galv steel 6 SWG min diam spaced 27
in. O. C.
9. Clips — (Not Shown) — Optional — For use in caged beams with Items 6 or 6A No. 24 MSG spring steel pushed on to top and
bottom flanges of beam spaced 6 in. O. C. max
10. Metal Lath — (Not Shown) — Optional — or use in caged beams with Items 6 or 6A 3/8 in. diamond mesh or rib lath, 3.4 lbs
per sq yd expanded steel attached to beam with clips spaced 6 in. OC max; or tied to lath hangers with 18 SWG galv steel wire
spaced 6 in. OC max.
11. Electrical Inserts — (Not Shown) — Classified as "Outlet Boxes and Fittings Classified for Fire Resistance*."
12. Mineral and Fiberboards* — (Optional, not shown). Applied over concrete floor with no restriction on board thickness. When
mineral and fiber boards are used, the unrestrained beam rating shall be increased by a minimum of 1/2 hr. See Mineral and
Fiber Board (CERZ) category for names of manufacturers.
13. Foamed Plastic* — (Optional, not shown). Consisting of polyisocyanurate or urethane roof insulations. Applied over concrete
floor with no restrictions on thickness. When polyisocyanurate or urethane insulation is used, the unrestrained beam rating shall
be increased by a minimum of 1/2 hr. See Foamed Plastic (CCVW) for list of manufacturers.
14. Insulating Concrete — (Optional, not shown) — Various types of insulating concrete prepared and applied as follows:
A. Vermiculite Concrete - Blend 6 to 8 cu ft of Vermiculite Aggregate* to 94 lb Portland cement and air entraining agent. Min thickness of 2 in.
as measured to the top surface of the structural concrete or foamed plastic (Item 15) when it is used. See Vermiculite Aggregate (CJZZ)
category for names of Classified companies.
B. Cellular Concrete-Roof Topping Mixture* - Concentrate mixed with water and Portland cement per manufacturer's specifications. Min.
thickness of 2-in. as measured to the top surface of the structural concrete or foamed plastic (Item 15) when it is used. Cast dry density and
28-day min compressive strength of 190 psi as determined with ASTM C495-66.
CELCORE INC — Type Celcore with cast dry density of 31 (+ or - 3.0) pcf or Type Celcore MF with cast dry density of 29 (+ or - 3.0) pcf.
ELASTIZELL CORP OF AMERICA — Type II, with a cast dry density of 39 (+ or - 3.0) pcf.
https://iq.ulprospector.com/es/profile?e=13928 8/9
16/4/25, 20:05 BXUV.D957 | UL Product iQ
SIPLAST INC — Mix #1, Cast dry density of 32 (+ or -) 3 pcf.
C. Cellular Concrete-Roof Topping Mixture* - Foam concentrate mixed with water, Portland cement and UL Classified Vermiculite Aggregate
per manufacture's application instructions. Cast dry density of 33 (+ or -) 3 pcf and 28 day compressive strength of min 250 psi as determined
in accordance with ASTM C495-86.
ELASTIZELL CORP OF AMERICA — Type II. Mix #1 of cast dry density 39 (+ or -) 3.0 pcf, Mix #2 of cast dry density 40 (+ or -) 3.0 pcf, Mix #3
of cast dry density 47 (+ or -) 3.0 pcf.
D. Perlite Concrete - 6 cu ft of Perlite Aggregate* to 94 lb of Portland Cement and 1-1/2 pt air entraining agent. Min thickness 2 in. as
measured to the top surface of structural concrete or foamed plastic (Item 15A) when it is used.
See Perlite Aggregate (CFFX) in Fire Resistance Directory for names of Classified companies.
15. Foamed Plastic* — (Optional - Not shown) — For use only with vermiculite (Item 14A) or cellular (Item 14B) concretes-Rigid
polystyrene foamed plastic insulation having slots and/or holes sandwiched between vermiculite or cellular concrete slurry which
is applied to the normal or lightweight concrete surface and vermiculite or cellular concrete topping (Item 14A or 14B).
See Foamed Plastic* (BRYX) category in Building Materials Directory or Foamed Plastic* (CCVW) Category in Fire Resistance Directory for
list of Classified companies.
15A. Foamed Plastic* — (Not Shown) — For use only with cellular or perlite concrete. Nominal 24 by 48 in. polystyrene foamed
plastic insulation boards having a density of 1.0 (+ or - 0.1) pcf, encapsulated within concrete topping. Each insulation board shall
contain six nominal 3 in. diameter holes oriented in two rows of three holes each with the holes spaced 12 in. OC transversely and
16 in. OC longitudinally.
See Foamed Plastic* (BRYX) category in Building Materials Directory or Foamed Plastic* (CCYW) category in Fire Resistance Directory for
list of Classified companies.
16. Roof Covering Materials* — (Optional, not shown) — Consisting of materials compatible with insulations described herein
which provide Class A, B or C coverings. See Built-Up Roof Covering Materials in Building Materials Directory.
17. Insulated Concrete — (Optional, not shown) — various types of insulated concrete prepared and applied in the thickness
indicated.
A. Perlite Concrete — Mix consists of 6.2 cu ft Perlite Aggregate* to 94 lbs of Portland cement and 1-1/2 pt air entraining agent.
Compressive strength 80 psi min.
See Perlite Aggregate (CFFX) category for names of Classified companies.
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL
Certification (such as Canada), respectively.
Last Updated on 2024-08-02
La presencia del nombre de una empresa o producto en esta base de datos no garantiza por sí misma que los productos así identificados
hayan sido fabricados bajo el servicio de seguimiento de UL. Solo aquellos productos que lleven la marca UL deben considerarse como
certificados y garantizados bajo el servicio de seguimiento de UL. Busque siempre la marca en el producto.
UL permite la reproducción del material contenido en el directorio de certificación en línea sujeta a las siguientes condiciones: 1. La
información de la guía, las asambleas, las construcciones, los diseños, los sistemas y/o certificaciones (archivos) deben presentarse en su
totalidad y de forma no engañosa, sin ninguna manipulación en los datos (o dibujos). 2. Debe aparecer la declaración "Reimpreso desde el
directorio de certificaciones en línea con permiso de UL" junto al material extraído. Además, el material reimpreso debe incluir una nota de
derechos de autor en el siguiente formato: "©2025 UL LLC."
https://iq.ulprospector.com/es/profile?e=13928 9/9