0% found this document useful (0 votes)
28 views4 pages

Bs 7835 Xlpe LSZH 6 35 11kv Cable

The document provides specifications for the BS 7835 XLPE LSZH 6.35/11 (12)kV Cable, which is designed for power networks and installations where fire safety is a concern. It includes details on its construction, electrical characteristics, and compliance with various standards, including BSI KITEMARK™ testing. Additionally, it outlines the cable's sustainability commitments and regulatory compliance with directives such as RoHS and REACH.

Uploaded by

Tomas Hudač
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views4 pages

Bs 7835 Xlpe LSZH 6 35 11kv Cable

The document provides specifications for the BS 7835 XLPE LSZH 6.35/11 (12)kV Cable, which is designed for power networks and installations where fire safety is a concern. It includes details on its construction, electrical characteristics, and compliance with various standards, including BSI KITEMARK™ testing. Additionally, it outlines the cable's sustainability commitments and regulatory compliance with directives such as RoHS and REACH.

Uploaded by

Tomas Hudač
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Click here for more information:

elandcables.com | BS 7835 XLPE LSZH 6.35/11 (12)kV Cable

BS 7835 XLPE LSZH 6.35/11 (12)kV Cable

Eland Product Group: A9M

APPLICATION BSI KITEMARK™ TESTED


Power cables for power networks, underground, outdoors and
in cable ducting. For installation where fire, smoke emission Cables are tested and verified by
The Cable Lab® to confirm they meet
and toxic fumes create a potential threat to life and equipment. Cable Testing
Verification
the quality standards required of the
KITEMARK™
BSI Cable Testing Verification Kitemark™.
KM 662609

CHARACTERISTICS
Voltage Rating Uo/U (Um) STANDARDS
6.35/11 (12)kV BS 7835, IEC/EN 60228,
Temperature Rating
Low Smoke Zero Halogen to IEC/EN 61034-1/2, IEC/EN 60754-1/2,
Fixed: 0°C to +90°C
Flame Retardant acc. to IEC/EN 60332-1-2, IEC/EN 60332-3-24
Minimum Bending Radius
Single core - Fixed: 15 x overall diameter THE CABLE LAB®
3 core - Fixed: 12 x overall diameter AN ISO/IEC 17025 AND IECEE CBTL ACCREDITED FACILITY
(Single core 12 x overall diameter and 3 core 10 x overall diameter where bends are
positioned adjacent to a joint or termination provided that the bending is carefully controlled Our world-class testing facility assures the quality and compliance of this cable
by the use of a former) through a continuous and rigorous testing regime.

CONSTRUCTION
Conductor
Class 2 stranded copper conductor
SUSTAINABILITY COMMITMENT
Conductor Screen We are on a journey to Net Zero.
Semi-conductive XLPE (Cross-Linked Polyethylene) We've committed to near-term emissions reductions and a net-zero target with the
Science Based Targets initiative and we're a signatory to the United Nations Global
Insulation Compact Sustainable Development Goals.
XLPE (Cross-Linked Polyethylene) Learn more about embodied carbon and our carbon emissions reduction actions,
our comprehensive recycling services, and wider ESG activities for sustainable
Insulation Screen operations at: www.elandcables.com/company/about-us/esg-sustainability
Semi-conductive XLPE (Cross-Linked Polyethylene)

Metallic Screen
Individual or overall copper tape screen

Filler
PET (Polyethylene Terephthalate) fibres
REGULATORY COMPLIANCE
Separator This cable meets the requirements of the RoHS Directive 2015/65/EU and
Binding tape Reach Directive EC 1907/2006. RoHS compliance has been tested and
confirmed by The Cable Lab®.
Bedding
LSZH (Low Smoke Zero Halogen)

Armour
Single core: AWA (Aluminium Wire Armoured)
Multi-core: SWA (Steel Wire Armoured)

Sheath
LSZH (Low Smoke Zero Halogen)

Sheath Colour
Red Black

UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com


International T +44 20 7241 8740 | F +44 20 7241 8700 | [email protected] technicalspecification | 1 of 4
Click here for more information:
elandcables.com | BS 7835 XLPE LSZH 6.35/11 (12)kV Cable

DIMENSIONS
ELAND PART NO. NO. OF NOMINAL CROSS NOMINAL DIAMETER NOMINAL
CORES SECTIONAL AREA mm WEIGHT
mm2 kg/km
Under Armour Over Armour Overall

A9M11KV01050*L 1 50 21.7 24.9 28.5 1200


A9M11KV01070*L 1 70 23 26.2 30 1500
A9M11KV01095*L 1 95 24.7 27.9 31.7 1600
A9M11KV01120*L 1 120 26.7 29.9 33.9 2100
A9M11KV01150*L 1 150 27.5 31.5 35.7 2500
A9M11KV01185*L 1 185 29.3 33.3 37.5 2900
A9M11KV01240*L 1 240 31.6 35.6 40 3600
A9M11KV01300*L 1 300 34.6 38.6 43 4300
A9M11KV01400*L 1 400 37 41 45.8 5200
A9M11KV01500*L 1 500 40.5 45.5 50.5 6500
A9M11KV01630*L 1 630 44.6 49.6 54.8 8000
A9M11KV01800*L 1 800 48.8 53.8 59.2 9850
A9M11KV011000*L 1 1000 53.5 58.5 64.3 12100
A9M11KV03035*L 3 35 41.6 46.6 51.6 4700
A9M11KV03050*L 3 50 44.4 49.4 54.6 5300
A9M11KV03070*L 3 70 48.1 53.1 58.5 6300
A9M11KV03095*L 3 95 52 57 62.6 7300
A9M11KV03120*L 3 120 55.6 60.6 66.6 8400
A9M11KV03150*L 3 150 58.6 63.6 69.8 9600
A9M11KV03185*L 3 185 62.7 67.7 74.1 11000
A9M11KV03240*L 3 240 68.1 74.4 81.2 14000
A9M11KV03300*L 3 300 73.5 79.8 87 16600
A9M11KV03400*L 3 400 78.3 84.6 92.2 20000

* Designates the sheath colour. For each Eland Cables part number replace with the colour code as listed below. e.g. A9M11KV01050RDL = 50mm² Red

COLOUR CODES
COLOUR Red Black
CODE RD BK

UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com


2 of 4 | technicalspecification International T +44 20 7241 8740 | F +44 20 7241 8700 | [email protected]
Click here for more information:
elandcables.com | BS 7835 XLPE LSZH 6.35/11 (12)kV Cable

CONDUTORS
Class 2 Stranded Conductors for Single Core and Multi-Core Cables

NOMINAL CROSS NOMINAL DIAMETER MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC


SECTIONAL AREA mm ohms/km
mm2
Circular Circular Compacted Shaped Annealed Copper Conductor

Plain Wires
Cu Al Cu Al Cu Al

50 19 19 6 6 6 6 0.387
70 19 19 12 12 12 12 0.268
95 19 19 15 15 15 15 0.193
120 37 37 18 15 18 15 0.153
150 37 37 18 15 18 15 0.124
185 37 37 30 30 30 30 0.0991
240 37 37 34 30 34 30 0.0754
300 61 61 34 30 34 30 0.0601
400 61 61 53 53 53 53 0.047
500 61 61 53 53 53 53 0.0366
630 91 91 53 53 53 53 0.0283
800 91 91 53 53 - - 0.0221
1000 91 91 53 53 - - 0.0176

ELECTRICAL CHARACTERISTICS
Current Carrying Capacity

NO. OF NOMINAL CROSS CONTINUOUS CURRENT RATING


CORES SECTIONAL AREA Amps
mm2 In Ground In Ducts In Air

Trefoil Flat Trefoil Flat Trefoil Flat

1 50 220 230 220 220 250 300


1 70 270 280 260 270 310 370
1 95 320 335 305 325 375 460
1 120 360 380 340 370 430 530
1 150 410 430 375 410 490 600
1 185 455 485 410 460 550 690
1 240 520 560 470 540 650 820
1 300 580 640 500 610 740 940
1 400 650 730 530 690 840 1100
1 500 710 830 570 780 930 1280
1 630 760 940 620 890 1040 1480
1 800 810 1060 660 990 1140 1690
1 1000 860 1170 690 1090 1230 1900
3 35 170 170 150 150 175 175
3 50 210 210 180 180 220 220
3 70 250 250 215 215 270 270
3 95 300 300 255 255 330 330
3 120 340 340 290 290 380 380
3 150 380 380 330 330 430 430
3 185 430 430 370 370 490 490
3 240 500 500 430 430 570 570
3 300 540 540 470 470 650 650
3 400 625 625 525 525 755 755

UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com


International T +44 20 7241 8740 | F +44 20 7241 8700 | [email protected] technicalspecification | 3 of 4
Click here for more information:
elandcables.com | BS 7835 XLPE LSZH 6.35/11 (12)kV Cable

DE-RATING FACTORS
AIR TEMPERATURE °C 25 30 35 40 45 50 55
DE-RATING FACTOR 1.00 0.96 0.92 0.88 0.83 0.78 0.73

GROUND TEMPERATURE °C 10 15 20 25 30 35 40
DE-RATING FACTOR 1.03 1.00 0.97 0.93 0.89 0.86 0.82

GROUND THERMAL
RESISTIVITY km/W
0.9 1.0 1.2 1.5 2.0 2.5 3.0

DE-RATING FACTOR 1.06 1.04 1.00 0.92 0.82 0.74 0.68

DEPTH OF LAYING m 0.80 1.00 1.25 1.50 1.75 2.00 2.50


DE-RATING FACTOR 1.00 0.97 0.95 0.94 0.93 0.91 0.90

The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is
believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.

UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com