thesis 1 to 3 Sample
thesis 1 to 3 Sample
Proposed two -storey 150 square meter residential building with roofdeck at Brgy. Tinagacan
A Thesis
In Partial Fulfillment
CHRISTOPHER CALMA
November 2024
Chapter I
Proposed two -storey 150 square meter residential building with roofdeck
A residential building serves as a dedicated space for individuals and families to live,
encompassing essential areas for daily activities such as sleeping, cooking, and leisure. Many
houses have traditional designs with rooms serving only one purpose, such as bedrooms,
kitchens, or living rooms. With more people working from home, studying, and spending time
indoors, there is a need for homes that can adapt to different activities. The challenge at hand is
to design a two-storey residential building by creating rooms that can serve multiple functions.
This design should be efficient, comfortable, and meet the needs of families, while following
The client, Mrs. Jelica Llego a teacher wants to build a two-storey residential house with
a roof deck with a floor area of 150 square meters with a total lot area of 5,813 square meter
located at Barangay Tinagacan General Santos City. The design should include rooms that can
change function depending on the family’s needs, such as work, study, or relaxation, while also
being comfortable for living and family gatherings. Ground floor consist of living room,
bedroom, kitchen room, dining room, comfort room and garage that can accommodate a car the
ground. On the second floor consist of office room, storage room, bedroom, multi-functional
room, and also her master bedroom, Both the master bedroom and multi-functional room can
This project aimed to propose a two storey 150 square meter Residential Building with
Roof deck in Barangay Tinagacan, General Santos City that conform with the Philippine Code
and Standards.
Proposed two -storey 150 square meter residential building with roofdeck
3. Estimated Cost.
This project aimed to provide necessary information with regards to the design, structural
analysis, and cost estimate of a proposed two-storey 150 square meter Residential Building with
Roof Deck.
In line with this, the designer believed that this project is of great value to the following:
Client. This study will give client the idea of the design, plans and estimated cost of two storey
Designer. This project helps the designer on how to manage structure plan to gain more ideas
and knowledge about structural analysis and design, and cost analysis of a two-storey apartment
Future Designer. This study could benefit to the future designer or researcher as a guide for
The scope of this project is to provide the Engineering design plans and drawings,
structural design analysis and estimated cost of the two-storey 150 square meter residential
Engineering Design plans and drawings are limited only to provide the following
architectural plans, structural plans, electrical plans and sanitary plans to conform with the
following code. Architectural plans are based on the National Building Code of The Philippines
(NBCP), Structural plans are limited for foundation plan, beam, slab, stairs, and column details
which are based on the National Building Code of The Philippines 2015 (NBCP), in addition,
Electrical plans are limited into the following: lightning layout and power layout are based on
Philippine Electrical Code (PEC 2017), Sanitary plans is limited only to plumbing layout which
the following: seismic analysis and design of slab which are based on the National Structural
Estimated Cost is limited to provide only the total estimated cost and total unit cost of the
building which also includes the total labor cost of the project. Unit based primarily on the prices
were from Department of Public Works and Highways (DPWH) and City Hardware, General
Definition of Terms
To have a better understanding to this study, the following terms are operationally defined.
Propose Two-Storey 150 square meter Residential Building with Roofdeck - This
project refers to a residential house designed to accommodate various activities and functions.
Mrs. Jelica Llego a teacher wants to build a two-storey residential house with a roof deck with a
floor area of 150 square meters with a total lot area of 5,813 square meter located at Barangay
Proposed two -storey 150 square meter residential building with roofdeck
Tinagacan General Santos City. The design should include rooms that can change function
depending on the family’s needs, such as work, study, or relaxation, while also being
comfortable for living and family gatherings. Ground floor consist of living room, bedroom,
kitchen room, dining room, comfort room and garage that can accommodate a car the ground. On
the second floor consist of office room, storage room, bedroom, multi-functional room, and also
her master bedroom, Both the master bedroom and multi-functional room can access the
balcony.
.
Proposed two -storey 150 square meter residential building with roofdeck
CHAPTER II
LITERETURE REVIEW
This chapter presented the different reviews of related studies and literature which are
The following codes were established as standards in the Philippines for structural
analysis and design of a project building, and they acted as a reference for the designer
The P.D. 1096 or National Building Code of The Philippines or NBCP was signed by late
President Ferdinand E. Marcos in 1977. It establishes the minimum standards and requirements
for the construction, occupancy, and maintenance of buildings and structures. Compliance with
the National Building Code (NBCP) is crucial for home and business owners to ensure the
(3) Type III – Type III buildings shall be of masonry and wood construction. Structural
elements may be any of the materials permitted by this Code: Provided, that the building shall be
construction.
it adjoins or has direct access to a public space, yard or street on at least one of its sides. For this
Section, the center line of an adjoining street or alley shall be considered an adjacent property
Proposed two -storey 150 square meter residential building with roofdeck
line. Eaves over required windows shall not be less than 750 millimeters from the side and rear
property lines.
As stated in Section 707. Maximum Height of Buildings, the maximum height and
number of storeys of every building shall be dependent upon the character of occupancy and the
bulk, widths of streets and car parking requirements. The height shall be measured from the
highest adjoining sidewalk or ground surface: Provided, that the height measured from the lowest
adjoining surface shall not exceed such maximum height by more than 3.00 meters: Except, that
towers, spires, and steeples, erected as part of a building and not used for habitation or storage
may extend not to exceed 6.00 meters above the height limits for each occupancy group if of
combustible materials.
a. Dwelling Location and Lot Occupancy - The dwelling shall occupy not more
than ninety percent of a corner lot and eighty percent of an inside lot, and subject
b. Sanitation - Every dwelling shall be provided with at least one sanitary toilet
load of the dwelling and shall be at least 250 millimeters thick and 600
d. Stairs - Stairs shall be at least 750 millimeters in clear width, with a rise of 200
e. Entrance and Exit - There shall be at least one entrance and another one for the
exit.
(a) Subject to the provisions of the Civil Code of the Philippines on Easements of
Light and View, and to the provisions of this part of the Code, every building
ventilation.
(b) All buildings shall face a street or public alley or a private street which has been
duly approved.
(c) No building shall be altered nor arranged so as to reduce the size of any room or
the relative area of windows to less than that provided for buildings under this
(d) No building shall be enlarged so that the dimensions of the required court or yard
Habitable rooms provided with artificial ventilation shall have ceiling heights not less
than 2.40 meters measured from the floor to the ceiling; Provided that for buildings of more than
onestorey, the minimum ceiling height of the first storey shall be 2.70 meters and that for the
second storey 2.40 meters and succeeding storeys shall have an unobstructed typical head-room
clearance of not less than 2.10 meters above the finished floor. Above stated rooms with natural
ventilation shall have ceiling heights not less than 2.70 meters.
a. Rooms for Human Habitations – 6.00 square meters with a least dimension of
2.00 meters;
b. Kitchens – 3.0 square meters with a least dimension of 1.50 meters; c. Bath and
toilet – 1.20 square meters with the least dimension of 0.90 meter.
Rooms intended for any use, not provided with artificial ventilation system, shall be
provided with a window or windows with a total free area of openings equal to at least 10% of
the floor area of the room, provided that such opening shall be not less than 1.00 sq. meter.
However, toilet and bathrooms, laundry rooms and similar rooms shall be provided with
windows or windows with an area not less than 1/20 of the floor area of such rooms, provided
that such opening shall not be less than 240 sq. millimeters. Such window or windows shall open
heating equipment shall be provided with artificial means of ventilation to prevent excessive
accumulation of hot and/or polluted air. Whenever artificial ventilation is required, the
equipment shall be designed and constructed to meet the following minimum requirements in air
changes:
1. For rooms entirely above grade and used for office, clerical, or administrative
machinery rooms, not less than three changes of air per hour shall be provided.
2. For rooms entirely above grade and used as bakeries, hotel or restaurant kitchens,
laundries other than accessory to dwellings, and boiler rooms – not less than ten
3. For auditorium and other rooms used for assembly purposes, with seats or other
accommodations – not less than 0.30 cubic meter of air per minute shall be
4. For wards and dormitories of institutional buildings – not less than 0.45 cubic
meter of air per minute shall be supplied for each person accommodated.
5. For other rooms or spaces not specifically covered under this Section of the Code,
followed.
Proposed two -storey 150 square meter residential building with roofdeck
As per Section 901. General Requirements, all buildings hereafter erected, altered,
remodeled, relocated or repaired for human habitation shall be provided with adequate and
potable water supply, plumbing installation, and suitable wastewater treatment or disposal
system, storm water drainage, pest and vermin control, noise abatement device, and such other
measures required for the protection and promotion of health of persons occupying the premises
(a) Whenever available, the potable water requirements for a building used for human
(b) The quality of drinking water from meteoric, surface or underground sources shall
conform to the criteria set in the latest approved National Standards for Drinking
Water.
(c) The design, construction and operation of deep wells for the abstraction of
Philippines.
(e) The water piping installations inside buildings and premises shall conform to the
wastewater shall be discharged directly into the nearest street sanitary sewer main
criteria set by the Code on Sanitation and the National Pollution Control
Commission.
(b) All buildings located in areas where there are no available sanitary sewerage
system shall dispose their sewage “Imhoff” or septic tank and subsurface
absorption field.
(c) Sanitary and industrial plumbing installations inside buildings and premises shall
(a) Rainwater drainage shall not discharge to the sanitary sewer system.
(b) Adequate provisions shall be made to the drain low areas in buildings and their
premises.
Proposed two -storey 150 square meter residential building with roofdeck
Buildings proposed for construction shall comply with all the regulations and specifications
herein set forth governing quality, characteristics and properties of materials, methods of design
and construction, type of occupancy and classification. All other matters relative to the structural
design of all buildings and other structures not provided for in this Chapter shall conform with
the provisions of the National Structural Code of Buildings, as adopted and promulgated by the
Board of Civil Engineering pursuant to Republic Act Number 544, as amended, otherwise
(a) Subject to the provisions of Articles 684 to 686 of the Civil Code of the Philippines
on lateral and subjacent support, the design and quality of materials used structurally in
(b) Whenever the depth of excavation for any construction is such that the lateral and
affected in a manner that the stability or safety of the same is endangered, the
(c) Excavation and other similar disturbances made on public property shall, unless
condition within 48 hours from the start of such excavation and disturbances by
(1) Footings and foundations shall be of the appropriate type, of adequate size,
and capacity in order to safely sustain the superimposed loads under seismic or any
condition of external forces that may affect the safety or stability of the structure. It shall
be the responsibility of the architect and/or engineer to adopt the type and design of the
(2) Whenever or wherever there exist in the site of the construction an abrupt
change in the ground levels or level of the foundation such that instability of the soil
could result, retaining walls shall be provided and such shall be of adequate design and
(a) Floors shall be of such materials and construction as specified under Chapter 5
Construction.
(b) All floors shall be so framed and secured into the framework and supporting walls
(c) The types of floor construction used shall provide means to keep the beam and
(a) Roof Covering. Roof covering for all buildings shall be either fire-retardant or
construction. The use of combustible roof insulation shall be permitted in all types
directly thereto.
(b) Roof Trusses. All roofs shall be so framed and tied into the framework and
supporting walls so as to form an integral part of the whole building. Roof trusses
shall have all joints well fitted and shall have all tension members well tightened
before any load is placed in the truss. Diagonal and sway bracing shall be used to
brace all roof trusses. The allowable working stresses of materials in trusses shall
In conformity with Chapter 12, Sec. 1207 of PD 1096, The construction of stairs and
exits shall conform to the occupant load requirements of buildings, reviewing stands, bleachers,
and grandstands.
a. Stairs
The stairs shall ensure structural safety for ascent and descent,
occupant load of less than ten (10) may be 750 millimeters wide. Trim
and handrails shall not reduce the required width by more than 100
Proposed two -storey 150 square meter residential building with roofdeck
millimeters. The rise of every step in a stairway shall not exceed 200
millimeters and the run shall not be less than 250 millimeters.
of travel equal to the width of the stairway. Such dimension need not
exceed 1.20 meters when the stairs have a straight run. Landings when
required to be more than 3.00 meters in width shall be provided with not
less than one intermediate handrail for each 3.00 meters of required
within the entire width of the stairway. Handrails shall be placed not less
than 800 millimeters nor more than 900 millimeters above the nosing of
provided at a point not more than 300 millimeters from the side of the
stairway where the treads are narrower but in no case shall any width of
b. Exits
Every building or usable portion thereof shall have at least one exit. In all
The total width of exits in meters shall not be less than the total occupant load served
divided by 165. Such width of exits shall be divided approximately equally among the separate
exits.
c. Doors
Exit door shall swing in the direction of exit travel when serving
occupant load of more than 100; nor shall they be used as a part of fire
assembly, nor equipped with panic hardware. A double acting door shall
be provided with a view panel of not less than 1,300 square centimeters.
Exit door shall be openable from the inside without the use of a key or any special
knowledge or effort: Except, that this requirement shall not apply to exterior exit doors in a
group E or F Occupancy if there is a conspicuous, readily visible and durable sign on or adjacent
to the door, stating that the door is to remain unlocked during business hours. The locking device
Every required exit doorway shall be of a size as to permit the installation of a door not less
than 900 millimeters in width and not less than 2.00 meters in height. When installed in exit
doorways, exit doors shall be capable of opening at least 90 degrees and shall be so mounted that
the clear width of the exitway is not less than 700 millimeters. In computing the required exit
Stairways
Under Chapter 12, Sec. 1207 of PD 1096, the stairs shall ensure structural safety for
ascent and descent, even in cases of emergency. It shall provide sufficient headroom and space
a. Width, stairways serving an occupant load of 50 or less may be 900 millimeters wide.
Trim and handrails shall not reduce the required width by more than 100 millimeters.
b. Rise and run; the rise of every step in a stairway shall not exceed 200 millimeters and
c. Landings, every landing shall have a dimension measured in the direction of travel
equal to the width of the stairway. Such dimension need not exceed 1.20 meters when the stairs
has a straight run. Landings when provided shall not be reduced in width by more than 100
d. Distance between Landings. There shall be no more than 3.60 meters vertical distance
between landings.
e. Handrails Stairways shall have handrails on each side and every stairway required to
be more than 3.00 meters in width shall be provided with not less than one intermediate handrail
for each 3.00 meters of required width. Intermediate handrails shall be spaced approximately
equal within the entire width of the stairway Handrails shall be placed not less than 800
millimeters nor more than 900 millimeters above the nosing of treads, and ends of handrails shall
All electrical systems, equipment and installation mentioned in this Code shall conform to
the provisions of the Philippine Electrical Code, as adopted by the Board of Electrical
Engineering pursuant to Republic Act No. 184 otherwise known as the Electrical Engineering
Law.
The National Structural Code of the Philippines (NSCP 2015) is a Structural design
code that guides structural and civil engineers in designing and assessing buildings and other
structures. The provisions within this code are designed to ensure that structures can withstand
the forces of natural disasters and the loads of the structure (dead load, live load, earthquake
Design Requirement
As stated in Chapter 1 Sec. 104 of NSPC 2015, design shall be in accordance with
Strength Design, Load and Resistance factor Design and Allowable Strength Design
Structural systems and members thereof shall be designed to have adequate stiffness to
limit deflections, lateral drifts and other deformations. The design shall also consider durability,
resistance to exposure to weather, crack control and other conditions that affects the performance
of the building.
accordance with well-established principles of mechanics that take into account equilibrium,
general stability, geometric compatibility and both short term and long term material properties.
Under Chapter 1, Sec. 106, copies of design calculations, reports, plans, specifications
and inspection program for all constructions shall bear the signature and seal of the engineer-in-
record.
a. Design drawings. The drawing shall be drawn to scale on durable paper using
permanent ink and shall be of sufficient clarity to indicate the location and nature of the work
proposed. The drawing shall show complete design with sizes, sections, relative locations and
b. Required Information. The design drawings shall contain, but shall not limited to the
According to Chapter 2, Sec. 203.3.1 of NSCP 2015, when strength design or load and
resistance factor design is used, structures and all portions thereof shall resist the most critical
1.4 (D + F) (203-1)
Where allowable stress or allowable strength design is used, structures and all portions
thereof shall resist the most critical effects resulting from the following combination of loads:
Proposed two -storey 150 square meter residential building with roofdeck
D+F (203-8)
D+H+F+L+T (203-9)
D + H + F + (Lr or R) (203-10)
Under Chapter 2, Sec. 203 of this code, for both allowable stress design and strength
design for concrete, and load and resistance factor design, and allowable strength design for
steel, the special load combination for seismic design shall be used:
Dead load
Stated in Chapter 2, Sec. 204, dead loads consists of the weight of all materials of
construction incorporated into the building or other structure, including but not limited to walls,
floors, roofs, ceilings, stairways, built-in partitions, finishes, cladding and other similarly
The actual weights of materials and constructions shall be used in determining dead loads
for purpose of design. In absence of definite information, it shall be permitted to use the
minimum values. See appendix C for Minimum Densities for Design Load from Materials
Partition Loads
Floors in office buildings and other buildings where partition locations are subject to
change shall be designed to support, in addition to all other loads, a uniformly distributed
Marble 24.5
Live loads
As stated in Chapter 2, Sec. 205 of the NSCP 2016, Live Loads shall be the
maximum loads expected by the intended use or occupancy but in no case shall be less
than the loads required. Floor live loads shall be taken as the minimum live loads of
horizontal projection to be used in the design of buildings for the occupancies listed.
Where uniform floor loads are involved, consideration may be limited to full dead
load on all spans in combination with full live load on adjacent spans and alternate spans.
Proposed two -storey 150 square meter residential building with roofdeck
(a) Floor Live Loads. These loads shall be taken as the minimum live loads of
listed. Special provisions shall be made for machines and apparatus loads.
(b) Distribution of Uniform Floor Loads. Where uniform floor loads are
(d) Special Loads. Provisions shall be made for the special vertical and lateral
(e)
Proposed two -storey 150 square meter residential building with roofdeck
2. Armories -- 7.2 0
Fixed Seats 2.9 0
Movable seats 4.8 0
3. Theaters, assembly
areas, and auditoriums Lobbies and platforms 4.8 0
Stage areas 7.2 0
4. Bowling alleys,
poolrooms, and similar -- 3.6 0
recreational areas
5. Catwalk for
-- 1.9 1.3
maintenance access
6. Cornices and marquees -- 3.6 0
7. Dining rooms and
-- 4.8 0
restaurants
8. Exit facilities -- 4.8 0
General storage and/or
4.8 --
repair
9. Parking Garages and Public parking and ramps 4.8 --
Ramps Private (residential) or
pleasure-type motor 2.4 --
vehicle storage
10. Hospitals Wards and rooms 1.9 4.5
Proposed two -storey 150 square meter residential building with roofdeck
Laboratories and
2.9 4.5
operating rooms
Corridors above ground
3.8 4.5
floor
Reading rooms 2.9 4.5
Stack rooms 7.2 4.5
11. Libraries
Corridors above ground
3.8 4.5
floor
Light 6.0 9.0
Heavy 12.0 13.4
12. Manufacturing
Building corridors above
3.8 9.0
ground floor
Call centers and business
2.9 9.0
processing offices
13. Office Lobbies and ground floor
4.8 9.0
corridors
Other Offices 2.4 9.0
Press rooms 7.2 11.0
14. Printing Plants Composing and linotype
4.8 9.0
rooms
Basic floor area 1.9 0
Exterior balconies 2.9 0
15. Residential
Decks 1.9 0
Storage 1.9 0
Press rooms 7.2 11.0
16. Printing Plants Composing and linotype
4.8 9.0
rooms
Press rooms 7.2 11.0
17. Printing Plants Composing and linotype
4.8 9.0
rooms
Proposed two -storey 150 square meter residential building with roofdeck
to act vertically upon the area projected on a horizontal plane. (Sec. 205.4 of NSCP
2015). Where uniform roof loads are involved in the design of structural members
arranged to create continuity, consideration may be limited to full dead loads on all spans
in combination with full roof live loads on adjacent spans and on alternate spans.
Proposed two -storey 150 square meter residential building with roofdeck
Method 1 Method 2
to less than 100% slope). Arch 0.75 0.70 0.60 0.75 0.06 25
Under Chapter 2, Sec. 208 of NSCP 2015, buildings and other structures and
portions thereof shall be designed to resist all loads due to applicable fluid pressures,
lateral soil pressures,ponding loads and self-straining forces, shown in Section 206.7.
Impact Loads
In reference to Chapter 2, Sec. 206 of NSCP 2015, the live loads specified in section
205.3 shall be assumed to include allowance for ordinary impact conditions. Provisions
shall be made in the structural design for uses and loads that involve unusual vibration
As per the standard of Chapter 2, Sec. 206 of NSCP 2015, Interior walls,
permanent partitions and temporary partitions that exceed 1.8 m in height shall be
designed to resist all loads to which they are subjected but not less than a load, L, of
Wind Loads
Chapter 2 Sec. 207 of NSCP 2015 stated that buildings and other vertical structures
shall be designed and constructed to resist wind loads as specified and presented in
Earthquake Loads
Under Chapter 2, Sec. 208 of NSCP 2015, the purpose of the succeeding
damage that may lead to loss of life and property. These provisions are not intended to
earthquake.
be designed and constructed to resist the effects of seismic ground motions as provided in
this section
b. Basis for Design. The procedures and the limitations for the design of
configuration, structural system and height in accordance with this section. Structures
Ground Motion, considering the inelastic response of the structure and the inherent
Footings
Chapter 3, Section 305 states that footings and foundations shall be constructed of
concrete and masonry shall be of solid material. Foundations supporting wood shall
extend at least 150 mm above the adjacent finish grade Footings shall have a minimum
foundation investigation.
a. Footing Design. Except for special provisions of Section 307 covering the
design of piles, all portions of footings shall be designed in accordance with the structural
provisions of this code and shall be designed to minimize differential settlement when
Proposed two -storey 150 square meter residential building with roofdeck
b. Design Loads. Footings shall be designed for the most unfavorable load effects
due to combination of loads. The dead load is permitted to include the weight of
foundations, footings and overlying fill. Reduced live loads as permitted to be used in the
design of footings.
Zone 4 in accordance with Section 208.4, individual spread footings founded on soil
defined in Section 208.4.3, as Soil profile Type S and Sy shall be interconnected by ties.
Structural Concrete
Chapter 4, Sec. 401.2.2 of NSCP 2105 states that, for all the structural concrete
designs, it should conform to the minimum requirements for the design and construction
NBCP. For structural concrete, fc, specified compressive strength of the concrete, shall
not be less than 17 MPa. No maximum value of f'c shall apply unless restricted by
specific code.
As stated in Chapter 4, Sec. 404 of the said code, the standards of section shall
properties of concrete shall be selected in accordance with section 419 and design
Proposed two -storey 150 square meter residential building with roofdeck
(a) Design Loads. Loads and load combinations considered in design shall be
(b) Structural System and Load Paths. The structural system shall include
structures such as floor and roof construction, both one-way and two- way
(c) Strength. Design strength of a member and its joints and connections, in
terms of moment, axial force, shear, torsion, and bearing shall be taken as
Loads
Conforming to the Chapter 4, Sec. 405, loads shall include self-weight, applied
loads, and effects of restressing, earthquakes, restraint of volume change, and differential
settlement.
(a) Load Factors and Combinations. Required strength U, shall be at least equal to
the effects of factored loads in Table D-1 of Appendix D, with exceptions and additions
Structural Analysis
Under Chapter 4, Sec. 406, this section shall apply to methods of analysis,
modelling of members and structural systems, and calculation of load effects. Members
Proposed two -storey 150 square meter residential building with roofdeck
and structural systems shall be permitted to be modeled in accordance with Section 406.3
and all members and structural systems shall be analyzed for the maximum effects of
loads including the arrangements of live load in accordance with Section 406.4.
(a) Arrangement of Live Load. For two-way slab systems, factored moment
panels.
(c) If L is variable and does not exceed 0.75D, or the nature of L. is such that
406.5.2.
Chapter 4, Sec. 407 of NSCP 2015 contains the following standards and specifications:
(a) Factored Shear. For slabs built integrally with supports V u at the support shall be
shall be provided in all regions where V u > V c . For precast prestressed hollow-
core slabs with untopped h > 315mm A v ,min shall be provided in all regions where
V u > 0.5⌀ V cw .
As stated in Sec. 408 of NSCP 2015, for non-prestressed slabs without interior beams
spanning between supports on all sides, having a maximum ratio of long-to-short span of
2, overall slab thickness h shall not be less than the limits in Table 408.3.1.1, and shall be
at least the value in (a) or (b), unless the calculated deflection limits of section 408.3.2
are satisfied.
Two-Way Slab
Sec. 408.3.1.2
This section shall apply to the design of non-prestressed and slabs reinforced for
flexure in two directions, with or without beams between supports, including Solid slabs,
elements constructed in separate placements but connected so that all elements resist
loads as a unit.
Proposed two -storey 150 square meter residential building with roofdeck
Beams
Sec. 409.1.1.
This section shall apply to the design of non-prestressed and prestressed beams,
including:
Sec. 409.3.1.1.
construction likely to be damaged by large deflections, overall beam h shall satisfy the
limits in Table 409.3.1.1, unless the calculated deflection limits of Section 409.3.2 are
satisfied.
Two-Way Slab
Sec. 408
This section shall apply to the design of non pre-stressed and slabs reinforced for
flexure in two directions, with or without beams between supports, including Solid slabs,
elements constructed in separate placements but connected so that all elements resist
Proposed two -storey 150 square meter residential building with roofdeck
loads as a unit.
Minimum Slab Thickness For non-pre-stressed slabs without interior beams spanning
between supports on all sides, having a maximum ratio of long-to-short span of 2, overall
slab thickness h shall not be less than the limits and shall be at least the value in (a) or
(b), unless the calculated deflection limits of Section 408.3.2 are satisfied:
Columns
For columns with a square, octagonal, or other shaped cross section, it shall be
permitted to base gross area considered, required reinforcement, and design strength on a
circular section with a diameter equal to the least lateral dimension of the actual shape.
Project Specification
Based on the review of codes, the following specifications have been established.
regulations, codes and standards shall form part of the design criteria: NSCP 2015, 7TH
Edition
B. Concrete
C. Steel Reinforcements
The minimum allowable soil bearing pressure at footing level shall be less than
Zone IV
Soil Type = Sd
Structural Analysis
structural systems, and calculation of load effects. Members and structural systems shall
be permitted to be modeled and all members and structural systems shall be analyzed for
a. Arrangement of Live Load - For two-way slab systems, factored moment shall
be calculated.
c. If L is variable and does not exceed 0.75D, or the nature of L is such that all
panels.
appliances, shall be provided to supply the loads. In addition, branch circuits shall be
provided for specific loads where required elsewhere in this Code and for dwelling unit
loads the minimum number of branch circuits shall be determined from the total
calculated load and the size or rating of the circuits used. In all installations, the number
Permissible Loads
In no case shall the load exceed the branch-circuit ampere rating. An individual
brunch circuit shall be permitted to supply any load for which it is rated. A branch circuit
supplying two or more outlets or receptacles shall supply only the loads specified
A 15- und 20-Ampere Branch Circuits. A 15- or 20-ampere branch circuit shall be
supply fused lighting units with heavy-duty lamp holders in any occupancy other than a
dwelling unit(s) or utilization equipment in any occupancy. A rating of any one cord-and-
plug-connected utilization equipment shall not exceed 80 percent of the branch circuit
that are fastened in place in any occupancy. In other than dwelling units, such circuits
shall be permitted to supply fixed lighting units with heavy duty lamp holders, infrared
This section provides acquirements for 123-volt, 15- and 20-ampere reception
outlets. Receptacle wallets required by this section shall be in addition to any receptacle
In every kitchen, family mom, dining room, living room, parlor, library, bedroom,
recreation room, or similar room or area of dwelling units, receptacle outlets shall be
Receptacle Outlets Served. In the kitchen, pantry, breakfast room, dining room, or
similar area of a dwelling it, the two or more 20-ampere small-appliance branch circuits
shall serve all wall and floor receptacle inlet, all countertop outlets and receptacle orders
within 900 mm of the outside edge of each basin. The receptacle outlet shall be located
provided for laundry equipment, shall be installed in each basement and in each attached
garage, and in each detached garage with electric power. Where a portion of the basement
is finished into one or more habitable rooms, each separate unfinished portion shall have
In dwelling units, hallways of 3000 mm or more in length shall have at least one
receptacle outlet. As used in this subsection, the hall length shall be considered the length
habitable room and bathroom. At least one wall switch-controlled lighting outlet shall be
installed in hallways, stairways, attached garages, and detached garages with electric
power.
For dwelling units, attached garages, and detached garages with electric power, at
least one wall switch-controlled lighting outlet shall be installed to provide illumination
on the exterior side of outdoor entrances or exits with grade level access. A vehicle door
Where one or more lighting outlet(s) installed for interior stairways, there shall be
a wall switch at each floor level, and landing level that includes an entryway, to control
the lighting outlet(s) where the stairway between floor levels has six risers or more.
Storage or Equipment Spaces. For attics, under floor spaces, utility rooms, and
basements, at least one lighting outlet containing a switch or controlled by a wall switch
shall be installed where these spaces are used for storage or contain equipment requiring
servicing. At least one point of control shall be at the usual point of entry to these spaces.
The lighting outlet shall be provided at or near the equipment requiring service.
Switch Connections
Three-way and four-way switches shall be wired so that all switching is done only
in the ungrounded circuit conductor. Switches or circuit breakers shall not disconnect the
All switchboards, panel boards, and distribution boards are installed for the
control of light and power circuits. In addition, switches, circuit breakers, and overcurrent
Proposed two -storey 150 square meter residential building with roofdeck
devices used on switchboards, panel boards, and distribution boards, and their enclosures
shall comply with this article and with the requirements. Switchboards and panel boards
Under Chapter 3, Sec. 302 of NPCP, the horizontal drainage pipes shall be run in
practical alignments and at a uniform slope between manholes of not less than 20 mm/m
2% slope due to the following constraints in: (1) excessive depth of the proposed
drainage line; (2) structural and/or geological features of the terrain; and (3) existing
piping shall be made by the use of approved pipe fittings and shall be of the angles
presented by a 22 1/2° bend, 45° bend, 60° bend or other approved fittings of longer
sweeps. Horizontal drainage lines connecting to a vertical stack shall enter through 45° or
60° wye branches, combination wye and 1/8 bend branches, sanitary tee or other
appurtenances and appliances used to receive or discharge liquid wastes or sewage, shall
Per the standards of Chapter 3, Sec. 305 (NPCP), every building where plumbing
fixtures are installed shall have a sewer service connection to a public or private sewer
systems except as provided in Subsection 305.2 of this section. When a Public or Private
Sewer is not available for use, excreta drainage piping from buildings and premises shall
excreta plumbing system, storm drainage system, building drain, building sewer, private
sewage disposal system or parts thereof, shall be located in any lot other than the lot
where the site of the building, structure or premises are served by such facilities. No
manner that the area, clearance, and access requirements of this Code are decreased or
impaired.
Proposed two -storey 150 square meter residential building with roofdeck
Vertical piping shall be secured at sufficiently close intervals to keep the pipes in
alignment and to carry ins weight and contents. Stacks shall be supported at their base as
Bell and Spigot and Hub less pipe shall be supported at every storey or closer, screwed
pipe or Iron Pipe Size (IPS) shall be apported at not less than every other storey thought,
center, lead pipe shall be supported at intervals not exceeding 1.20 meters at centers with
a rigid vertical back-up and Plastic Pipe shall be supported at every one (1) meter
interval.
alignment and prevent sagging. IPS except as provided in other Sections of this Code,
shall the supported at approximately 3.0 meters intervals for piping 19 mm diameter and
smaller and 3.6 meters intervals for piping 25 mm and larger in diameter. Copper Tilting
smaller and 3.0 meters interval for piping 51 mm and larger in diameter. Lead Pipe shall
be supported by stiff metal or wooden hacking for its entire length with hangers properly
spaced. Piping buried in the ground shall be laid on a firm bed for its entire length, except
where concrete cradle support is provided, which is adequate and approved by the
Administrative Authority. Plastic Tube shall be supported by still metal or wood backing
with hangers in its entire length for small size tuhings up to 38 min diameter and without
hackings but with spaced metal hangers at approved spacing fin larger-size tubing’s.
Proposed two -storey 150 square meter residential building with roofdeck
Plumbing Fixtures
dense, durable non-absorbent materials and must have smooth, impervious surface, free
Code, all fixtures shall conform in quality and design to nationally recognized applicable
In Chapter 4, Sec. 403 of NPCP. when any fixture is provided with an overflow
outlet, the waste shall be so arranged that the standing water inside the fixture cannot rise
inside the overflow way when the stopper is closed nor remain inside the overflow way
when the fixture is empty. The overflow pipe from a fixture shall be connected to the
house or inlet side of the fixture trap. Water Closet or Urinal flush tanks shall discharge
into the bowls or wares served by them, but it shall be unlawful to connect such
Based on Chapter 4, Sec. 409 of NPCP, floor drains shall be considered plumbing
fixtures and each drain shall be provided with an approved-type and hinged strainer plate
having the sum of the areas of the small holes of the strainer plate or gross waterway is
equivalent to the cross-sectional area of the tailpiece. Floor drains, floor receptors and
shower drains shall be of an approved type, the body provided with integrally-cast water-
stop outside flange around the body at mid depth and with an inside caulk outlet to
Shower receptors are plumbing fixtures and shall conform to the general
Proposed two -storey 150 square meter residential building with roofdeck
Bathtubs or
Water Closets Lavatories
Type of Building or Urinals (fixtures showers Drinking
(fixtures per (fixtures per
Occupancy per person) (fixtures per Fountain
person) person)
person)
Dwellings
Single Dwelling 1 per dwelling 1 per dwelling 1 per dwelling
Multiple Dwelling or 1 per dwelling 1 per dwelling 1 per dwelling
Department or apartment or apartment or apartment
unit unit unit
As per the standards set forth in chapter 6, Sec. 601 of NPCP, each plumbing
fixture shall be provided with an adequate supply of potable running water, so arranged
as to flush and keep same in dean and healthful conditions without danger of backflow or
flush tank or flushometer valve. Faucets and diverters shall be connected to the hot and
cold water distribution supplies so that the hot water supply is located at Ieft side of the
combination fittings.
Proposed two -storey 150 square meter residential building with roofdeck
In line with Chapter 6, sec. 609 of NPCP, the size of the water meter and the
immediate piping from the meter or from other source of unmetered water supply to the
risers, fixture supply branches, fixture connections, outlets or other uses shall be based on
the total water demand and shall be determined according to the methods and procedures
and/or horizontal drainage pipings shall he determined from the total of all fixture units
connected thereto, and additional, in the case of vertical drainage pipes, in accordance
As stated in Section 704 of the NPCP, drainage piping shall be provided with
approved inlet fittings for fixture connections, correctly located according to the size and
within the distance allowed between a trap and its vent, may be served by a single
vertical drainage pipe, provided that each fixture wastes separately into an approved
double fitting, such as double sanitary tee or double wye and 1/8 bend having inlet
approved fittings and shall be of the angles presented by a 22 1/2'' or 1/16 bend, 45° or
1/8 bend, and 60° or 1/6 bend or other approved fittings of equivalent sweeps.
Proposed two -storey 150 square meter residential building with roofdeck
Each horizontal drainage pipe shall be provided with a clean out at its upper
terminal and each run of piping which is more than 15 meters in total developed length
shall be provided with a clean out and at every 15 meter length or a fraction thereof.
assured throughout all parts of the excreta drainage system by means of vent pipes
this code.
Proposed two -storey 150 square meter residential building with roofdeck
Minimum Horizontal
Seepage pit or
Distance In clear required Building Sewer Septic Tank Disposal Field
cesspool
from:
1. Buildings or
2. Property line
adjoining private
5. Trees - 3m - 3m
6. Seepage pits or
8. On site domestic
main 3m 3m 3m 3m
Proposed two -storey 150 square meter residential building with roofdeck
1 or 2 15 750 (2838)
3 20 1000 (3785)
3
33 1500 (5677.5)
4
5 or 6 45 2000 (7570)
5
55 2250 (8516.3)
6
60 2500 (9462.5)
7
70 2750 (10408.8)
8
80 3000 (11355)
9 90 3250 (12301.3)
Note: Septic tank sizes in this table include sludge storage capacity and the connection disposal
of domestic food waste units without further volume increase.
Philippine Electrical Code (PEC 2000)
Proposed two -storey 150 square meter residential building with roofdeck
Electrical Layout
interconnection wiring.
Power Plan
It is the layout and wiring plans for power on the floor plans drawn to scale, shall
show:
main switchboard, layout of feeders and distribution panels or switches and their
It is the layout and wiring plans for general lighting and receptacle outlets
each room or area. In residences, hotels, apartment houses, and churches, the
illumination level in each room or area need not be shown nor computed
Voltages
Throughout this Code, the voltage considered shall be that at which the circuit
operates. The voltage rating of electrical equipment shall not be less than the nominal
Conductors
otherwise provided in this Code. Where the conductor material is not specified,
the material and the sizes given in this Code shall apply to copper conductors.
Where other materials are used, the size shall be changed accordingly.
Conductor Sizes
Insulation Integrity
Completed wiring installations shall be free from short circuits and from
Wiring Methods
Only wiring methods recognized as suitable are included in this Code. The
Mounting
mounted. Wooden plugs driven into holes in masonry, concrete, plaster, or similar
Cooling
Electrical equipment that depends on the natural circulation of air and convection
principles for cooling of exposed surfaces shall be installed so that room airflow
For equipment designed for floor mounting, clearance between top surfaces and
so that walls or other obstructions do not prevent the free circulation of air
Electrical Connections
identified for the material of the conductor and shall be properly installed and
and copper-clad aluminum), unless the device is identified for the purpose and
where employed, shall be suitable for the use and shall be of a type that will not
Terminals
Proposed two -storey 150 square meter residential building with roofdeck
leads. Connection by means of wire-binding screws or studs and nuts that have
upturned lugs or the equivalent shall be permitted for 5.5 mm2 (2.6 mm dia.) or
smaller conductors. Terminals for more than one conductor and terminals used to
Splices
the use or by brazing, welding, or soldering with a fusible metal or alloy. Soldered
secure without solder and then be soldered. All splices and joints and the free
Temperature Limitations
ratings higher than specified for terminations shall be permitted to be used for
Flash Protection
Proposed two -storey 150 square meter residential building with roofdeck
and motor control centers that are in other than dwelling occupancies and are
practitioner of potential electric arc flash hazards. The marking shall be located so
Clear Space
Working space required by this section shall not be used for storage.
When normally enclosed live parts are exposed for inspection or servicing, the
guarded.
Illumination
Illumination shall be provided for all working spaces about service equipment,
outlets shall not be required where the work space is illuminated by an adjacent light
electrical equipment rooms, the illumination shall not be controlled by automatic means
only.
have access to the space within reach of the live parts. Any openings in
such partitions or screens shall be sized and located so that persons are
not likely to come into accidental contact with the live parts or to bring
surface.
Warning Signs
Entrances to rooms and other guarded locations that contain exposed live
persons to enter.
The walls, roof, floors, and doorways of vaults containing conductors and
equipment over 600 volts, nominal, shall be constructed of materials that have
adequate structural strength for the conditions, with a minimum fire rating of 3
Proposed two -storey 150 square meter residential building with roofdeck
hours. The floors of vaults in contact with the earth shall be of concrete that is not
less than 100 mm thick, but where the vault is constructed with a vacant space or
other stories below it, the floor shall have adequate structural strength for the load
imposed on it and a minimum fire resistance of 3 hours. For the purpose of this
Overcurrent Protection
accordance with Parts 4.30.3, 4.30.4, and 4.30.5. Transformers shall be protected
Device Terminals
attachment of conductors and intended for connection to more than one side of the
circuit shall have terminals properly marked for identification, unless the
and polarized plugs shall have the terminal intended for connection to the
2. If the terminal is not visible, the conductor entrance hole for the
the letter W.
Appliances
device in the line or any line-connected screw shell lampholders, and that are to
plugs and cords with three or more wires (including the equipment grounding
conductor), shall have means to identify the terminal for the grounded circuit
Rating
the maximum permitted ampere rating or setting of the overcurrent device. The
rating for other than individual branch circuits shall be 15, 20, 30, 40, and 50
amperes. Where conductors of higher ampacity are used for any reason, the
ampere rating or setting of the specified overcurrent device shall determine the
circuit rating
Occupancy Limitation
In dwelling units and guest rooms or guest suites of hotels, motels, and
similar occupancies, the voltage shall not exceed 230 volts, nominal, between
less than ¼ hp
Dwelling Units
All 125-volt and/or 250 volts, single-phase, 15- and 20-ampere receptacles
installed in the locations specified in (1) through (8) shall have ground-fault
1. Bathrooms
2. Garages
3. Outdoors
4. Crawl Spaces
5. Unfinished Basements
6. Kitchens
8. Boathouses
Permissible Loads
individual branch circuit shall be permitted to supply any load for which it is
rated. A branch circuit supplying two or more outlets or receptacles shall supply
Cord Connections
attachment plugs are used. Where flexible cords are permitted to be permanently
Appliance Outlets
Outdoor Outlets
grade level, at least one receptacle outlet accessible at grade level and not more than 2
000 mm above grade shall be installed at the front and back of the dwelling.
Laundry Areas
In dwelling units, at least one receptacle outlet shall be installed for the laundry.
Hallways
In dwelling units, hallways of 3 000 mm or more in length shall have at least one
receptacle outlet. As used in this subsection, the hall length shall be considered the length
The largest of the following six selections (load in kVA) shall be included:
1. 100 percent of the nameplate rating(s) of the air conditioning and cooling.
2. 100 percent of the nameplate rating(s) of the heating when a heat pump is used
3. 100 percent of the nameplate ratings of electric thermal storage and other heating
systems where the usual load is expected to be continuous at the full nameplate
4. 100 percent of the nameplate rating(s) of the heat pump compressor and 65
percent of the supplemental electric heating for central electric space heating
systems. If the heat pump compressor is prevented from operating at the same
time as the supplementary heat, it does not need to be added to the supplementary
5. 65 percent of the nameplate rating(s) of electric space heating if less than four
CHAPTER III
PROJECT DESIGN
This chapter presented and discussed the procedures the designer took to create the
engineering drawings, designs, structural analysis, and cost estimate for the proposed
two-story 150 square meter residential building with roof deck, which is where this
The construction of proposed two-storey 150 square meter residential building with
roofdeck will be set within Brgy. Tinagacan, General Santos City, South Cotabato. This
two-storey 150 square meter residential building project aims to deliver a contemporary
Client Information
floor area of 150 square meter in Barangay Tinagacan, General Santos City, on a 5,813
square meters property at Purok 14 , Barangay T inagacan General Santos City. The
client, Mrs. Jelica Llego wants a home that incorporates flexibility for various uses, such
as family gatherings and workspaces, while ensuring compliance with local building
The project will be located in Barangay Tinagacan General Santos City, where the
According to the 2020 census, Tinagacan has a population of 8,344, reflecting steady
growth and development within the City. The site is about 5,813 square meters in size
and it is near the national highway making it a safe and accessible place to build.
According to local government services, the soil type is classified as clay loam, with a
soil bearing capacity of 75 to 200 kPa. This makes the land suitable for constructing a
1. The designer met with the client, Mrs. Jelica Llego, to thoroughly discuss the
details of her proposed project. The meeting was based on the specifications
outlined in the client's land title, as presented in the appendix. During the
architectural design, including the National Building Code of the Philippines, the
Philippine Electrical Code, and the National Structural Code of the Philippines
(2015).
Stage 2:
drawing plan.
b. The plans and drawings approved by the adviser were presented and
c. The revised plans and drawings will be presented to the client for the final
project.
a. The designer will assume for all the structure members to be designed, and
b. The dimension of the design was based on the National Structural Codes in
the Philippines.
3. Cost Estimate
designer was given access to a pricing list from the DPWH cost reference to
b. The designer will survey the Department of Public Works and Highways as
well as other engineering businesses in General Santos City to ascertain the amount of
work required to finish the project; this will offer labor cost information
Procedure
Locale of the Study
Stage 1
Brgy,Tinagacan
Client’s Information and General Santos City
Preference
Cost Estimates
Figure 3.1
Drawing of Design
Plans Structural Analysis
Proposed two -storey 150 square meter residential building with roofdeck
Building.
Proposed two -storey 150 square meter residential building with roofdeck
The design process for the two-storey residential house with roofdeck is around
analysis to verify adherence to building regulations. Over the next 3 weeks, the final
design plan is shaped, reflecting revisions and input from the client. Detailed
drawings, including architectural, structural, electrical, and sanitary plans, are then
completed in 2 weeks. In the final stage, cost estimates for both materials and labor are
meticulously prepared, also taking 2 weeks. This structured progression ensures the
design process is comprehensive and efficient, meeting both technical and regulatory