Project_1 Grid Connected_Project
Project_1 Grid Connected_Project
PVsyst TRIAL
PVsyst - Simulation report
Grid-Connected System
PVsyst TRIAL
Blackfalds Project - Canada
PVsyst TRIAL
PVsyst TRIAL
Author
PVsyst TRIAL
Project: Project#1 Grid Connected
Variant: New simulation variant
PVsyst V8.0.8
VC0, Simulation date:
21/03/25 12:27
with V8.0.8
PVsyst TRIAL
Geographical Site
Blackfalds Project
Canada
Situation
Latitude
Longitude
Altitude
Time zone
Project summary
52.39 °(N)
-113.81 °(W)
880 m
UTC-5
Weather data
Blackfalds Project
Meteonorm 8.2 (1981-2000), Sat=100% - Synthetic
Jan. Feb. Mar. Apr. May June July Aug. Sep. Oct. Nov. Dec.
Albedo 0.60 0.60 0.60 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.82 0.75
PVsyst TRIAL
System summary
Grid-Connected System No 3D scene defined, no shadings
System information
PV Array Inverters
Nb. of modules 855 units Nb. of units 5 units
Pnom total 547 kWp Total power 500 kWac
Pnom ratio 1.09
Results summary
PVsyst TRIAL
Produced Energy 784.46 MWh/year Specific production 1434 kWh/kWp/year Perf. Ratio PR 89.57 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 4
Loss diagram 5
Predef. graphs 6
Single-line diagram 7
PVsyst TRIAL
PVsyst TRIAL
21/03/25 PVsyst Evaluation mode Page 2/7
Project: Project#1 Grid Connected
Variant: New simulation variant
PVsyst V8.0.8
VC0, Simulation date:
21/03/25 12:27
with V8.0.8
PVsyst TRIAL
Grid-Connected System
Orientation #1
Fixed plane
Tilt/Azimuth 42 / 0 °
General parameters
No 3D scene defined, no shadings
Sheds configuration
No 3D scene defined
Models used
Transposition
Diffuse
Circumsolar
Perez
Perez, Meteonorm
separate
PV Array Characteristics
PV module Inverter
PVsyst TRIAL
Manufacturer Generic Manufacturer Generic
Model CS7N-640MB-AG 1500V Model CSI-100K-T480-GL03-U
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 640 Wp Unit Nom. Power 100 kWac
Number of PV modules 855 units Number of inverters 5 units
Nominal (STC) 547 kWp Total power 500 kWac
Modules 45 string x 19 In series Operating voltage 180-1000 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.09
Pmpp 502 kWp Power sharing within this inverter
U mpp 640 V
I mpp 784 A
PVsyst TRIAL
Total 855 modules Number of inverters 5 units
Module area 2656 m² Pnom ratio 1.09
Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 13 mΩ Loss Fraction -0.4 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s
PVsyst TRIAL
0° 30° 50° 60° 70° 75° 80° 85° 90°
1.000 0.998 0.981 0.948 0.862 0.776 0.636 0.402 0.000
PVsyst TRIAL
21/03/25 PVsyst Evaluation mode Page 3/7
Project: Project#1 Grid Connected
Variant: New simulation variant
PVsyst V8.0.8
VC0, Simulation date:
21/03/25 12:27
with V8.0.8
PVsyst TRIAL
System Production
Produced Energy 784.46 MWh/year
Main results
Specific production
Perf. Ratio PR
1434 kWh/kWp/year
89.57 %
PVsyst TRIAL
Balances and main results
PVsyst TRIAL
March 96.6 41.54 -4.61 144.5 140.9 74.58 73.43 0.929
April 158.3 48.06 3.26 194.9 189.4 97.00 95.58 0.896
May 188.9 62.65 9.93 192.7 186.4 93.66 92.16 0.874
June 188.7 82.36 13.85 177.6 171.0 85.84 84.40 0.868
July 190.7 81.95 16.78 187.5 181.3 89.50 88.05 0.858
August 160.6 64.64 15.14 178.3 173.0 85.72 84.34 0.865
September 113.5 43.24 9.95 154.6 150.7 75.58 74.39 0.879
October 67.6 31.35 3.38 114.6 112.2 58.58 57.64 0.919
November 28.0 17.38 -4.38 55.8 54.6 29.53 28.92 0.948
December 20.0 11.96 -10.40 50.8 49.8 27.68 27.12 0.975
Year 1285.9 517.69 2.79 1600.6 1555.8 797.52 784.46 0.896
Legends
PVsyst TRIAL
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst TRIAL
21/03/25 PVsyst Evaluation mode Page 4/7
Project: Project#1 Grid Connected
Variant: New simulation variant
PVsyst V8.0.8
VC0, Simulation date:
21/03/25 12:27
with V8.0.8
+24.5%
-2.8%
Global horizontal irradiation
Global incident in coll. plane
PVsyst TRIAL
-3.1% PV loss due to temperature
PVsyst TRIAL
0.0% Night consumption
784.46 MWh Available Energy at Inverter Output
784.46 MWh Energy injected into grid
PVsyst TRIAL
PVsyst TRIAL
21/03/25 PVsyst Evaluation mode Page 5/7
Project: Project#1 Grid Connected
Variant: New simulation variant
PVsyst V8.0.8
VC0, Simulation date:
21/03/25 12:27
with V8.0.8
PVsyst TRIAL
PVsyst TRIAL
System Output Power Distribution
PVsyst TRIAL
PVsyst TRIAL
21/03/25 PVsyst Evaluation mode Page 6/7
PVsyst V8.0.8
VC0, Simulation date:
21/03/25 12:27
with V8.0.8
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL