PS2 Lecture 4 Unsymmetrical Faults
PS2 Lecture 4 Unsymmetrical Faults
System
Ferdous S. Azad
Assistant Professor,
Department of EEE
Ahsanullah University of Science and Technology
Introduction:
A three-phase system can be analyzed by means of a single-phase equivalent when:
▪ The source voltages are balanced or symmetrical
▪ The electrical parameters of the system are symmetrical
▪ The loads are balanced
Three-phase quantities can be determined from single phase voltages and currents when symmetry is
assumed between phases.
Unbalanced Faults:
Fortescue’s Theorem:
According to Fortescue’s theorem, three unbalanced phasors of a three-phase system
can be resolved into three balanced system of phasors. In other words, any three
unbalanced set of voltages or currents can be resolved into three balanced systems of
voltages or currents, referred to as the system symmetrical components, defined as
follows:
➢Positive Sequence components: three phasors of equal magnitude displaced 120
degrees from each other following the positive sequence
➢Negative Sequence components: three phasors of equal magnitude displaced 120
degrees of each other following the negative sequence.
➢Zero Sequence components: three parallel phasors having equal magnitude and
angle
Fortescue’s Theorem:
The ‘a’ operator:
Symmetrical components in Matrix form:
Symmetrical components for currents:
Symmetrical components for currents:
The equations for the components of voltage drop from point ‘a’ of phase a to the reference bus (or
ground) are, as may be deduced from above figures:
Zero Sequence network of Transformers
• Zero sequence currents can flow in the legs of a star connection only if the star point is
grounded which provides the necessary return path for zero sequence currents.
• No zero sequence currents can flow in the lines connected to a delta connection as no return
path is available for these currents. Zero sequence currents can, however, flow in the legs of a
delta—such currents are caused by the presence of zero sequence voltages in the delta
connection.
Zero Sequence network of Transformers for different configurations:
Zero sequence network related problem:
one-line diagram
zero-sequence network
Zero sequence network related problem:
Try yourself!!!!
Different Unsymmetrical faults:
• For any type of fault on the terminals of the generator, the following
equation can be used