The document provides a detailed air system sizing summary for the comedor in the edificio eq I project located in Caracas, Venezuela. It includes calculations for cooling and heating loads, airflow rates, and equipment specifications, indicating a total cooling coil load of 29.8 tons and a maximum airflow of 6881 CFM. The report also outlines the design conditions and psychrometric data for both cooling and heating scenarios.

Uploaded by

Suzam Labrador
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3 views

SSNF1EE.tmp

The document provides a detailed air system sizing summary for the comedor in the edificio eq I project located in Caracas, Venezuela. It includes calculations for cooling and heating loads, airflow rates, and equipment specifications, indicating a total cooling coil load of 29.8 tons and a maximum airflow of 6881 CFM. The report also outlines the design conditions and psychrometric data for both cooling and heating scenarios.

Uploaded by

Suzam Labrador
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Air System Sizing Summary for comedor

Project Name: edificio eq I 03/03/2025


Prepared by: miau 02:45

Air System Information


Air System Name ...................................... comedor Number of zones ......................................................... 1
Equipment Class ...................................... CW AHU Floor Area .......................................................... 5075,2 ft²
Air System Type .......................................... SZCAV Location ........................................ Caracas, Venezuela

Sizing Calculation Information

Calculation Months ................................ Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ............................................ Calculated Space CFM Sizing ........... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ................................................... 29,8 Tons Load occurs at ................................................ Aug 1400
Total coil load ................................................. 357,3 MBH OA DB / WB .................................................. 90,6 / 77,9 °F
Sensible coil load ............................................ 177,1 MBH Entering DB / WB .......................................... 83,1 / 72,4 °F
Coil CFM at Aug 1400 ..................................... 6881 CFM Leaving DB / WB ........................................... 56,5 / 56,0 °F
Max block CFM ................................................ 6881 CFM Coil ADP ................................................................. 54,4 °F
Sum of peak zone CFM ................................... 6881 CFM Bypass Factor ...................................................... 0,075
Sensible heat ratio .......................................... 0,496 Resulting RH ............................................................. 62 %
CFM/Ton ........................................................ 231,1 Design supply temp. ............................................... 54,5 °F
ft²/Ton ............................................................. 170,4 Zone T-stat Check ................................................ 1 of 1 OK
BTU/(hr·ft²) ....................................................... 70,4 Max zone temperature deviation ............................... 0,0 °F
Water flow @ 10,0 °F rise ............................... 71,50 gpm

Supply Fan Sizing Data

Actual max CFM .............................................. 6881 CFM Fan motor BHP ....................................................... 0,00 BHP
Standard CFM ................................................. 6163 CFM Fan motor kW ......................................................... 0,00 kW
Actual max CFM/ft² ........................................... 1,36 CFM/ft² Fan static ................................................................ 0,00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ......................................... 3315 CFM CFM/person ......................................................... 11,05 CFM/person
CFM/ft² ............................................................. 0,65 CFM/ft²

Hourly Analysis Program 5.10 Page 1 of 8


Zone Sizing Summary for comedor
Project Name: edificio eq I 03/03/2025
Prepared by: miau 02:45

Air System Information


Air System Name ...................................... comedor Number of zones ......................................................... 1
Equipment Class ...................................... CW AHU Floor Area .......................................................... 5075,2 ft²
Air System Type .......................................... SZCAV Location ........................................ Caracas, Venezuela

Sizing Calculation Information

Calculation Months ................................ Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ............................................ Calculated Space CFM Sizing ........... Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 6881 6881 1,36 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 136,4 Aug 0800 97,3 5075,2

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
Comedor 1 136,4 Aug 0800 6881 97,3 5075,2 1,36

Hourly Analysis Program 5.10 Page 2 of 8


Air System Design Load Summary for comedor
Project Name: edificio eq I 03/03/2025
Prepared by: miau 02:45

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 90,6 °F / 77,9 °F HEATING OA DB / WB 0,0 °F / 0,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 679 ft² 19403 - 679 ft² - -
Wall Transmission 2350 ft² 14000 - 2350 ft² 54574 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 679 ft² 8095 - 679 ft² 42764 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2030 W 6926 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3600 W 11087 - 0 0 -
People 300 61092 81000 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 12060 4050 0% 0 0
>> Total Zone Loads - 132664 85050 - 97338 0
Zone Conditioning - 130717 85050 - -96181 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 6881 CFM 0 - 6881 CFM 0 -
Ventilation Load 3315 CFM 46366 95174 3315 CFM 96181 0
Supply Fan Load 6881 CFM 0 - 6881 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 177083 180224 - 0 0
Central Cooling Coil - 177083 180233 - 0 0
>> Total Conditioning - 177083 180233 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 3 of 8


Space Design Load Summary for comedor
Project Name: edificio eq I 03/03/2025
Prepared by: miau 02:45

TABLE 1.1.A. Component Loads For Space "Comedor" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 80,1 °F / 75,4 °F HEATING OA DB / WB 0,0 °F / 0,0 °F
OCCUPIED T-STAT 75,0 °F OCCUPIED T-STAT 70,0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 679 ft² 40391 - 679 ft² - -
Wall Transmission 2350 ft² 13164 - 2350 ft² 54574 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 679 ft² 3516 - 679 ft² 42764 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2030 W 6926 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3600 W 10484 - 0 0 -
People 300 49558 81000 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 12404 4050 0% 0 0
>> Total Zone Loads - 136444 85050 - 97338 0

TABLE 1.1.B. Envelope Loads For Space "Comedor" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
S EXPOSURE
WALL 1356 0,332 - 6125 - 31482
WINDOW 1 89 0,900 1,000 461 1716 5604
WINDOW 2 183 0,900 1,000 947 3527 11515
W EXPOSURE
WALL 994 0,332 - 7040 - 23092
WINDOW 1 146 0,900 1,000 758 12639 9222
WINDOW 2 261 0,900 1,000 1350 22508 16424

Hourly Analysis Program 5.10 Page 4 of 8


System Psychrometrics for comedor
Project Name: edificio eq I 03/03/2025
Prepared by: miau 02:45

August DESIGN COOLING DAY, 1400

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 90,6 0,02020 3315 400 46366 95174
Vent - Return Mixing Outlet 83,1 0,01670 6881 1082 - -
Central Cooling Coil Outlet 56,5 0,01053 6881 1082 177083 180233
Supply Fan Outlet 56,5 0,01053 6881 1082 0 -
Cold Supply Duct Outlet 56,5 0,01053 6881 1082 - -
Zone Air - 76,1 0,01344 6881 1716 130717 85050
Return Plenum Outlet 76,1 0,01344 6881 1716 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,967 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4251,0 BTU/(hr-CFM)
Site Altitude = 3020,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 132664 Cooling 130717 76,1 6881 1716 0 0

Hourly Analysis Program 5.10 Page 5 of 8


System Psychrometrics for comedor
Project Name: edificio eq I 03/03/2025
Prepared by: miau 02:45

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 0,0 0,00088 3315 400 -96181 0
Vent - Return Mixing Outlet 15,5 0,00088 6881 408 - -
Central Cooling Coil Outlet 15,5 0,00088 6881 408 0 0
Supply Fan Outlet 15,5 0,00088 6881 408 0 -
Cold Supply Duct Outlet 15,5 0,00088 6881 408 - -
Zone Air - 30,0 0,00088 6881 415 96181 0
Return Plenum Outlet 30,0 0,00088 6881 415 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,967 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4251,0 BTU/(hr-CFM)
Site Altitude = 3020,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -97338 Deadband 96181 30,0 6881 415 0 0

Hourly Analysis Program 5.10 Page 6 of 8


System Psychrometrics for comedor
Project Name: edificio eq I 03/03/2025
Prepared by: miau 02:45

Location: Caracas, Venezuela


Altitude: 3020,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012

0,010

0,008

0,006

0,004

1 23 4
0,002

0,000
0 10 20 30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.10 Page 7 of 8


System Psychrometrics for comedor
Project Name: edificio eq I 03/03/2025
Prepared by: miau 02:45

Location: Caracas, Venezuela


Altitude: 3020,0 ft.
Data for: August DESIGN COOLING DAY, 1400

1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet 0,024
4. Supply Fan Outlet
5. Room Air
0,022
1
0,020

Specific Humidity ( lb/lb )


2 0,018
0,016
5 0,014

34
0,012
0,010
0,008
0,006
0,004
0,002
0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.10 Page 8 of 8