SSNF1EE.tmp
SSNF1EE.tmp
Calculation Months ................................ Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ............................................ Calculated Space CFM Sizing ........... Individual peak space loads
Total coil load ................................................... 29,8 Tons Load occurs at ................................................ Aug 1400
Total coil load ................................................. 357,3 MBH OA DB / WB .................................................. 90,6 / 77,9 °F
Sensible coil load ............................................ 177,1 MBH Entering DB / WB .......................................... 83,1 / 72,4 °F
Coil CFM at Aug 1400 ..................................... 6881 CFM Leaving DB / WB ........................................... 56,5 / 56,0 °F
Max block CFM ................................................ 6881 CFM Coil ADP ................................................................. 54,4 °F
Sum of peak zone CFM ................................... 6881 CFM Bypass Factor ...................................................... 0,075
Sensible heat ratio .......................................... 0,496 Resulting RH ............................................................. 62 %
CFM/Ton ........................................................ 231,1 Design supply temp. ............................................... 54,5 °F
ft²/Ton ............................................................. 170,4 Zone T-stat Check ................................................ 1 of 1 OK
BTU/(hr·ft²) ....................................................... 70,4 Max zone temperature deviation ............................... 0,0 °F
Water flow @ 10,0 °F rise ............................... 71,50 gpm
Actual max CFM .............................................. 6881 CFM Fan motor BHP ....................................................... 0,00 BHP
Standard CFM ................................................. 6163 CFM Fan motor kW ......................................................... 0,00 kW
Actual max CFM/ft² ........................................... 1,36 CFM/ft² Fan static ................................................................ 0,00 in wg
Calculation Months ................................ Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ............................................ Calculated Space CFM Sizing ........... Individual peak space loads
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
Comedor 1 136,4 Aug 0800 6881 97,3 5075,2 1,36
TABLE 1.1.A. Component Loads For Space "Comedor" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 80,1 °F / 75,4 °F HEATING OA DB / WB 0,0 °F / 0,0 °F
OCCUPIED T-STAT 75,0 °F OCCUPIED T-STAT 70,0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 679 ft² 40391 - 679 ft² - -
Wall Transmission 2350 ft² 13164 - 2350 ft² 54574 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 679 ft² 3516 - 679 ft² 42764 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2030 W 6926 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3600 W 10484 - 0 0 -
People 300 49558 81000 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 12404 4050 0% 0 0
>> Total Zone Loads - 136444 85050 - 97338 0
TABLE 1.1.B. Envelope Loads For Space "Comedor" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
S EXPOSURE
WALL 1356 0,332 - 6125 - 31482
WINDOW 1 89 0,900 1,000 461 1716 5604
WINDOW 2 183 0,900 1,000 947 3527 11515
W EXPOSURE
WALL 994 0,332 - 7040 - 23092
WINDOW 1 146 0,900 1,000 758 12639 9222
WINDOW 2 261 0,900 1,000 1350 22508 16424
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,967 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4251,0 BTU/(hr-CFM)
Site Altitude = 3020,0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,967 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4251,0 BTU/(hr-CFM)
Site Altitude = 3020,0 ft
0,016
0,012
0,010
0,008
0,006
0,004
1 23 4
0,002
0,000
0 10 20 30 40 50 60 70 80 90 100
Temperature ( °F )
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet 0,024
4. Supply Fan Outlet
5. Room Air
0,022
1
0,020
34
0,012
0,010
0,008
0,006
0,004
0,002
0,000
30 40 50 60 70 80 90 100
Temperature ( °F )