Ap60 10 Electrical
Ap60 10 Electrical
The facilities include electrical equipment including all distribution, control and
other related systems, such as lighting, grounding.
The design, performance, testing and inspection for equipment covered by this
project will comply with relevant recommendations, established by the
International Electro technical Commission (IEC).
Continuity of service, taking into accounts the internal failures and external
failures.
The main source of power supply to the plant will be from 30 kV (OHL POLE)
incoming feeders from the Q-FIELD switchgear.
The use of two 100% rated feeders from the switchgear supply enables the plant
to operate during periods of switchgear and transformer maintenance.
The 400V switchboard is configured two sections of bus bars (A, B), each with an
incoming circuit breaker, and with interconnecting bus-ties. The incoming from
transformers TRA-002A/B is NC and the incomer from Emergency Diesel
Generator is NO.
In case of loss of normal power (from the two transformers), the two bus ties will
open and the Emergency Diesel Generator will supply the load prioritaire only
(emergency load).
Tow 30 KV Overhead transmission lines shall be used for transmitting power from
the generating sets located at the GOSP facility to the main substation at the
ALKABIR FIELD.
The 11 KV Overhead lines shall serve to distribute power to the well sites for both
fields and to the wells.
The OHL system shall comprise the following:
Steel pole /Tower
Conductor and earth wire
Cable
Cable protectors, cable terminations
Insulators, bushing and fittings, connectors, steelwork
Line fittings
Isolators
Fuse Isolators
Surge Arrestor
Earthing including earthing wells
Foundations
All other equipment and materials as may be required to form a complete
and proper installation.
Two three phase transformers (with conservator) isolated in mineral oil for indoor
installation. The cooling method is the type ONAN. . The conditions of service will
be compliant CEI354.The transformer shall be confirmed to specification for
power transformers N°: AGO5427-007-01-E-SP-5008:
The oil used should be compliant HN27-S-02, NF C27 - 101 and IEC 296.
The transformer will be equipped with the following accessories:
- A control switch off ± 2x2, 5%
- A gas detection relay with two contacts,
- Thermometer, a thermostat with two contacts,
- Adjustable Rollers in 2 directions, lifting eyes,
- Curator of oil with the drain valve and level indicator,
- Filler cap,
- Acquisition of land
- Nameplates,
- Air dryer’s silica gel,
- Drain valve and sampling device to sample
- equipped with a disconnected fuse.
- Any other useful adjunct filling, emptying, etc.....
Fréquence: 50 Hz.
Couplage: Dyn11.
Two three phase transformers (with conservator) isolated in mineral oil for indoor installation. The
cooling method is the type ONAN. . The conditions of service will be compliant CEI354.The
transformer shall be confirmed to specification for power transformers N°: AGO5427-007-01-E-SP-
5008:
The transformer will be equipped with the following accessories:
A control switch off ± 2x2, 5%
- A gas detection relay with two contacts,
- Thermometer, a thermostat with two contacts,
- Adjustable Rollers in 2 directions, lifting eyes,
- Curator of oil with the drain valve and level indicator,
- Filler cap,
- Acquisition of land
- Nameplates,
- Air dryer’s silica gel,
- Drain valve and sampling device to sample
- Any other useful adjunct filling, emptying, etc.....
The electrical characteristic are:
Fréquence: 50 Hz.
Couplage: Dyn11.
Two three phase transformers (with conservator) isolated in mineral oil for indoor
installation. The cooling method is the type ONAN. . The conditions of service will
be compliant CEI354.The transformer shall be confirmed to specification for
power transformers N°: AGO5427-007-01-E-SP-5008:
The transformer will be equipped with the following accessories:
A control switch off ± 2x2, 5%
- A gas detection relay with two contacts,
- Thermometer, a thermostat with two contacts,
- Adjustable Rollers in 2 directions, lifting eyes,
- Curator of oil with the drain valve and level indicator,
- Filler cap,
- Acquisition of land
- Nameplates,
- Air dryer’s silica gel,
- Drain valve and sampling device to sample
- Any other useful adjunct filling, emptying, etc.....
The electrical characteristic are:
Puissance: 500 KVA.
Fréquence: 50 Hz.
Couplage: Dyn11.
In the event of loss of normal power, the EDG shall start automatically to provide
power supplies to consumers designated as Essential Loads.
The EDG shall be capable of starting from a black start condition and shall be
provided with routine facilities to simulate and test auto-start.
During such test, the generators shall run at load, synchronized with the normal
main supply.
When the normal supply is restored, a temporary parallel through EDG and the
normal main supply will be foreseen.
Automatic transfer schemes shall be provided at the 30kV, 5.5kV and 0.4kV
switchgear in order to switch loads to an alternative feeder in case of failure, or
(only for 0.4kV switchgear) to switch on Emergency Diesel Generator.
Frequency: 50 Hz
Speed: 1500t/mn (auto regulated)
Cos φ : 0,8
Excitation: self-excited
Supply and installation of arrays of solar energy units rated 12 volts and with
sufficient capacity c/w all necessary batteries, inverters, accessories, container,
fencing, in order to meet the required power supply for:
Chemical dosing pumps at Alkabir Field Satellite
C.P system for the 10” trunk line
C.P system for the ten (10) 4” flow lines
The solar Energy Unit rated 12 V, 10 KVA and with a battery cc: type stationary,
sealed lead acid and maintenance free.
A minimum capacity of 200 Ah batteries.
The charge regulator must ensure the protection of equipment and protect the
battery against deep discharge. The charge regulator must be equipped with
warning lights operating status of batteries will be installed on a stand at the
bottom of the envelope outside the box.
a) Station lighting
b) Perimeter street lighting,
c) walkway/access station lighting,
d) Skid lighting,
e) Building interior lighting,
f) Industrial buildings (compressor, pump etc.) lighting,
1.4.7 Earthing
The purpose of the earthing system shall be to protect personnel during normal
and abnormal operating conditions of the plant.
The plant main earthing system shall be designed to provide zero potential
reference for the earthing down of all items of electrical power circuitry requiring
a neutral bond.
All metallic structures, earth, armored cables, conduit, pipe rack, fencing and
electrical equipment shall be permanently and effectively earthed to provide
protection for personnel and equipment.
Armored cables and metallic conduit shall be earthed at both end points.
All relevant equipment such as tanks, vessels, valves, pipes and the like shall be
cross bonded and earthed in such a manner as to render impossible the build up
of static potential. All electrical equipment shall be individually earthed as a
safety measure against hazards arising from failure of the electrical circuitry.
PVC coated earth conductors shall be used above and below ground. The coating
shall be colored yellow/green.