0% found this document useful (0 votes)
33 views6 pages

PNG-EGPP-MEC-DAS-00004 - Jockey Firewater Pumps Datasheets - D01

The document provides datasheets for the Jockey Firewater Pumps as part of the Front-End Engineering Design for the Egbaoma Gas Processing Plant Firewater System Upgrade Project. It includes revision history, change history, and detailed specifications for the pumps, including performance, construction materials, and operational conditions. The document outlines requirements for design, approval, and review processes, emphasizing compliance with relevant standards and specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
33 views6 pages

PNG-EGPP-MEC-DAS-00004 - Jockey Firewater Pumps Datasheets - D01

The document provides datasheets for the Jockey Firewater Pumps as part of the Front-End Engineering Design for the Egbaoma Gas Processing Plant Firewater System Upgrade Project. It includes revision history, change history, and detailed specifications for the pumps, including performance, construction materials, and operational conditions. The document outlines requirements for design, approval, and review processes, emphasizing compliance with relevant standards and specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

PNG GAS LIMITED

FRONT-END ENGINEERING DESIGN FOR EGBAOMA GAS PROCESSING PLANT


FIREWATER SYSTEM UPGRADE PROJECT

JOCKEY FIREWATER PUMPS DATASHEETS

D01 03/10/2024 Issued for Design OUS SAO NUE


A01 20/08/2024 Issued for Approval OUS SAO NUE
R01 15/08/2024 Issued for Review OUS SAO NUE
Rev Date Issued Purpose Prepared By Reviewed By Approved By

Contractor: Sub-Contractor:

Company Facility Discipline Document Sequence Sheet Rev


Document No.:
PNG EGPP MEC DAS 00004 00 D01
FRONT-END ENGINEERING DESIGN FOR EGBAOMA GAS
PROCESSING PLANT FIREWATER SYSTEM UPGRADE PROJECT

Doc. Title:
JOCKEY FIREWATER PUMPS DATASHEETS
PNG GAS LIMITED Doc. No.: Rev. No.
Page 02
PNG-EGPP-MEC-DAS-00004 D01

REVISION HISTORY

REV. DATE DESCRIPTION PREPARED BY REVIEWED BY APPROVED BY

D01 3/10/2024 Issused for Design OUS SAO NUE

A01 20/08/24 Issused for Approval OUS SAO NUE

R01 15/08/24 Issued for Review OUS SAO NUE


Notes

• Revisions for review will be issued as R01, with subsequent come as R02 etc.
• Revisions for approval will be issued as A01, with subsequent updates as A02 etc.
• Revisions for Approved for Design will be issued as D01, with subsequent updates as D02 etc.
• Highlights of sections revised from previous approved issues or reasons for version change are to be listed in the description box

CHANGE HISTORY
DOCUMENT
S/N WHAT CHANGED REASON FOR CHANGE
REVISION
FRONT-END ENGINEERING DESIGN FOR EGBAOMA GAS
PROCESSING PLANT FIREWATER SYSTEM UPGRADE PROJECT

JOB NO. ITEM NO. (P-3803 A/B)

JOCKEY FIREWATER PUMPS DATASHEETS (P-3803 A/B) PURCHASE ORDER NO.

SPECIFICATION NO.
Doc. No: PNG-EGPP-MEC-DAS-00004 REVISION NO. D01 DATE 3/10/2024

1 APPLICABLE TO: PROPOSALS PURCHASE AS BUILT


2 FOR PNG UNIT JOCKEY FIREWATER PUMPS
3 SITE EGBAOMA GAS PROCESSING PLANT SERVICE FIRE WATER
4 NO. REQ 2 TYPE VERTICAL NO. STAGES BY SUPPLIER
5 MANUFACTURER MODEL BY SUPPLIER SERIAL NO. BY SUPPLIER

6 NOTE: FOR INFORMATION TO BE SUPPLIED BY PURCHASER BY MANUFACTURER


MUST BE SUPPLIED BY PURCHASER MUST BE SUPPLIED BY MANUFACTURER
7 GENERAL
8 PUMPS TO OPERATE IN (PARALLEL) NO. MOTOR DRIVEN 2 NO. ENGINE DRIVEN N/A
9 (SERIES) WITH PUMP ITEM NO. (P-3803 A/B) PUMP TAG NO. N/A
10 GEAR ITEM NO. MOTOR ITEM NO. ENGINE ITEM NO. N/A
11 GEAR PROVIDED BY MOTOR PROVIDED BY By Supplier ENGINE PROVIDED BY N/A
12 GEAR MOUNTED BY MOTOR MOUNTED BY By Supplier ENGINE MOUNTED BY N/A
13 GEAR DATA SHT. NO. MOTOR DATA SHT. NO. By Supplier ENGINE DATA SHT. NO. N/A

14 OPERATING CONDITIONS PUMP CONSTRUCTION


15 CAPACITY, NORMAL 6.81 (m³/h) RATED -- (m³/h) NOZZLES SIZE RATING FACING LOCATION
16 OTHER SUCTION 2" VTC 150# RF VTA
17 SUCTION PRESSURE MAX./RATED 1 (barg) DISCHARGE 2" VTC 150# RF VTA

D0110/20DISCHARGE PRESSURE 9.11 (barg) PRESSURE CASING CONNECTIONS


## DIFFERENTIAL PRESSURE 9 (barg) SIZE LOCATION

## HEAD 92.84 (m) NPSHA 8.78 (m) DRAIN VTA VTA


## TOTAL HEAD AT SHUTOFF By Supplier (m) VENT VTA VTA
## TOTAL HEAD AT 150% RATED CAPACITY By Supplier (m) PRESS. GAGE VTA VTA
## POWER 2.13 (KW) CASING MOUNT
## SPLIT-CASE END-SUCTION IN-LINE
## SITE AND UTILITY DATA VERTICAL SHAFT
## LOCATION: MAXIMUM ALLOWABLE CASING PRESSURE
## INDOOR HEATED UNDER ROOF AT 15 °C (barg)
## OUTDOOR UNHEATED PARTIAL SIDES AT NORMAL PUMP TEMPERATURE (barg)
## GRADE MEZZANINE HYDROTEST PRESSURE (barg)
## ELECTRIC AREA CLASSIFICATION BEARING TYPE
## NON-HAZARDOUS SLEEVE ANTIFRICTION
## WINTERIZATION REQ'D TROPICALIZATION REQ'D. BEARING LUBRICATION OIL

## SITE DATA PRESSURE FLOOD RING-OILED


## ALTITUDE SEA LEVEL (m) BAROMETER N/A (m/b) OIL VISCOSITY mm2/s at (°C)
## RANGE OF AMBIENT TEMPS: MIN/MAX. 20 / 40 (°C) IMPELLER DIAMETER
## RELATIVE HUMIDITY: MIN / MAX / 100 (%) RATED (mm) MAX (mm) MIN (mm)
## AREA NOISE CLASSIFICATION IMPELLER MOUNT
## UNUSUAL CONDITIONS: DUST FUMES BETWEEN BEARING OVERHUNG
## OTHER ROTATION (VIEWED FROM COUPLING)
## FIRE WATER CHARACTERISTICS CW CCW
## TYPE TEST HEADER REQUIRED
## FRESHWATER SEAWATER YES NO
## TEMPERATURE, (°C) REMARKS
## MIN 20 NORMAL MAX 40
## SPECIFIC GRAVITY 1.00 AT 40 (°C)
## NOTES:-
##
##
##
##

Datasheet for Jockey Firewater Pumps Page 3 of 6


FRONT-END ENGINEERING DESIGN FOR EGBAOMA GAS
PROCESSING PLANT FIREWATER SYSTEM UPGRADE PROJECT

JOB NO. ITEM NO. (P-3803 A/B)

JOCKEY FIREWATER PUMPS DATASHEETS (P-3803 A/B) PURCHASE ORDER NO.

SPECIFICATION NO.

Doc. No: PNG-EGPP-MEC-DAS-00004 REVISION NO. D01 DATE 3/10/2024

1 PERFORMANCE PUMP ACCESSORIES (CONT)


2 MANUFACTURER TEST HEADER WITH VALVED OUTLETS & CAPS/CHAINS
3 MODEL NO. QUANTITY SIZE
4 SIZE AND TYPE TEST METER ASSEMBLY
5 SPEED TYPE
6 RATED (rpm) MAX. (rpm) MANUFACTURER
7 EFFICIENCY (%) MODEL
8 RATED POWER (KW) FLOW RANGE: FROM TO (m³/h)
9 MAX. POWER, RATED IMPELLER (KW) FLANGE
10 NPSH REQUIRED (m H2O at 3% DROP IN HEAD) TYPE RAISE FACE SIZE
11 RATED HEAD, MAXIMUM IMPELLER (m) FULL FLOW RELIEF VALVE (2.13.1) NOS
12 RATED HEAD, RATED IMPELLER (m) STANDARD: API 526 OTHER
13 TOTAL HEAD AT SHUTOFF (2.2.4) (m) TYPE SPRING LOADED PILOT OPERATED
14 TOTAL HEAD AT 150% RATED CAPACITY (m)
15 MINIMUM CONTINUOUS FLOW (m³/h) WEIGHTS AND DIMENSIONS
16 HORIZONTAL PUMP ONLY (N/A) HORIZONTAL PUMP/DRIVER/SKID (TOTAL WEIGHT)
17 NUMBER OF STAGES DRY (kg) WET (kg)
18 SHAFT DIAMETER VERTICAL PUMP/GEAR/DRIVER/SKID/ACCESSORIES (TOTAL WEIGHT)
19 BOWL (mm) LINE SHAFT (mm) DRY (kg) WET (kg)
20 SHAFT SECTION SKID MOUNTED COMPONENTS
21 LENGTH (mm) QUANTITY LENGTH (mm) WIDTH (mm)
22 COLUMN HEIGHT (mm)
23 DIAMETER (mm) WALL THK (mm)
24 COLUMN JOINTS MATERIALS OF CONSTRUCTION

25 FLANGED THREADED HORIZONTAL PUMPS


26 DOWN THRUST (kg) UP THRUST (kg) CASING CARBON STEEL
27 BOWL (MAXIMUM OD) (mm) IMPELLER STAINLESS STEEL
28 BOWL AND COLUMN ASSEMBLY LENGTH (mm) WEAR RINGS STAINLESS STEEL
29 STRAINER SHAFT STAINLESS STEEL
30 BASKET CONE SHAFT SLEEVE STAINLESS STEEL
31 O.D. (mm) LENGTH (mm) GLAND BY MANUFACTURER
32 % OPEN AREA PACKING BY MANUFACTURER
33 PUMP ACCESSORIES VERTICAL PUMPS
34 AIR RELEASE VALVE NOS PUMP BOWL
35 SIZE TYPE BUSHING
36 CIRCULATION RELIEF VALVE NOS IMPELLER

37 SIZE TYPE WEAR RING


38 SUCTION REDUCER (ECCENTRIC) SHAFT
39 DISCHARGE INCREASER (CONCENTRIC) BEARINGS
40 SUCTION PRESSURE GAGE NOS BEARING SPIDER
41 RANGE (barg) TYPE COLUMN PIPE
42 DISCHARGE PRESSURE GAGE NOS ALL BOLTS
43 RANGE (barg) TYPE STRAINER
44 DISCHARGE PRESSURE SWITCH Yes STUFFING BOX
45 SEALS/PACKING MFR. MODEL PACKING
46 MATERIALS FLUSH PLAN DISCHARGE HEAD
47 NOTE

48 1. BLANK SPACE SHALL BE FILLED BY VENDOR OR SUPPLIER AS APPLICABLE AND APPROVED BY CLIENT VTA : Vendor To Advise
49 VTC : Vendor To Confirm
50 N/A : Not Applicable
51 AMB: Ambient

Datasheet for Jockey Firewater Pumps Page 4 of 6


FRONT-END ENGINEERING DESIGN FOR EGBAOMA GAS
PROCESSING PLANT FIREWATER SYSTEM UPGRADE PROJECT

JOB NO. ITEM NO. (P-3803 A/B)

PURCHASE ORDER NO.


JOCKEY FIREWATER PUMPS DATASHEETS (P-3803 A/B)
SPECIFICATION NO.

Doc. No: PNG-EGPP-MEC-DAS-00004 REVISION NO. D01 DATE 3/10/2024

1 COUPLING DIESEL ENGINE DRIVER (N/A)


2 COUPLING INSTRUMENTATION AND CONTROL
3 TYPE MFR GOVERNOR
4 RATING (KW/100RPM) MFR. MODEL
5 MIN RPM MAX RPM
6 RIGHT ANGLE GEAR OVERSPEED SHUTDOWN DEVICE

7 GEAR MFR. MODEL NO TACHOMETER OIL PRES GAUGE COOLANT TEMP GAUGE
8 GEAR RATIO MAX RPM DIESEL DAY TANK
9 THRUST CAPACITY CAPACITY (L/KW) 5% EXPANSION 5% SUMP
10 MIN (kg) MAX (kg) INSTRUMENTATION Level gauge with low level alarm
11 LUBRICATION
12 PRESSURE FLOOD CONTROLLER
13 EFFICIENCY AT RATED KW AND SPEED (%) SEQUENTIAL START ADJUSTMENT
14 COOLING COIL REQUIRED YES NO ADJUST FROM TO (sec) SET (sec)
15 SERVICE FACTOR (BASED ON THE FOLLOWING): INDIVIDUAL ALARM CONTACTS
16 RATED KW AT RATED SPEED CONTROLLER POWER V PH Hz
17 ACTUAL KW AT MAXIMUM SPEED VOLTMETER REQUIRED AMPSMETER REQUIRED
18 MOTOR DRIVER SPEED INDICATION REQUIRED
19 MANUFACTURER CONTROLLER ALARM OPTIONS
20 NAMEPLATE BRAKE KW AT RPM REQUIRED SETPOINTS ALARM SHUTDOWN
21 HORIZONTAL VERTICAL LOW FUEL LEVEL
22 FRAME LOW OIL PRESSURE
23 SERVICE FACTOR LOW SUCTION PRESSURE
24 VOLTS/PHASE/HERTZ 380 - 415V / 3 HP / 50HZ COOLING WATER TEMP
25 TYPE ENGINE OVERSPEED
26 ENCLOSURE STARTING SYSTEM LOW PRESSURE
27 MINIMUM STARTING VOLTAGE BATTERY CHARGER LOW VOLTAGE
28 TEMPERATURE RISE QA INSPECTIONS AND TESTS
29 FULL LOAD AMPS REVIEW VENDORS QA PROGRAM
30 LOCKED ROTOR AMPS SHOP INSPECTION
31 INSULATION SUBMIT TESTING PROCEDURE
32 STARTING METHOD PERFORMANCE CURVE APPROVAL
33 LUBE SHOP TESTS NON-WIT WIT OBSERVE
34 VERTICAL THRUST CAPACITY HYDROSTATIC
35 DIESEL ENGINE DRIVER (N/A) PERFORMANCE

36 MANUFACTURER NPSH
37 TYPE COMPLETE UNIT TEST
38 NAMEPLATE BRAKE KW AT RPM FIELD TESTS
39 SITE KW AT RPM MINIMUM, RATED AND PEAK (150% RATED) FLOWRATE(11.2.6.2)
40 NUMBER OF CYLINDERS ELECTRIC MOTOR AMPERE DEMAND (11.2.6.3.1)
41 COMPRESSION RATIO ENGINE GOVERNOR (11.2.6.3.3)
42 BORE (mm) STROKE (mm) LOADS START TESTS (11.2.6.4)
43 STARTING SYSTEM CONTROLLER TEST (11.2.7)
44 BATTERY PNEUMATIC NITROGEN BACKUP REMARKS:
45 START GAS PRESS (barg) RATE (Nm3/h)
46 MIN. GAS PRESSURE REQUIRED FOR STARTING (barg)

47 NOTE:
48 1: PUMP SUPPLIER TO PROVIDE DATASHEET, GENERAL ARRANGEMENT DRAWING AND PUMP CURVES FOR COMPANY'S REVIEW AND APPROVAL
48 2:THE JOCKEY FIREWATER PUMPS SHALL BE DESIGN IN ACCORDANCE WITH NFPA 20 AND PNG-EGPP-MEC-SPE-00006_TECHNICAL
49 3:SPECIFICATION FOR MAIN FIREWATER / JOCKEY FIREWATER PUMPS

Datasheet for Jockey Firewater Pumps Page 5 of 6


FRONT-END ENGINEERING DESIGN FOR EGBAOMA GAS
PROCESSING PLANT FIREWATER SYSTEM UPGRADE PROJECT

JOB NO. ITEM NO. (P-3803 A/B)

PURCHASE ORDER NO.


JOCKEY FIREWATER PUMPS DATASHEETS (P-3803 A/B)
SPECIFICATION NO.

Doc. No: PNG-EGPP-MEC-DAS-00004 REVISION NO. D01 DATE 3/10/2024

1
2 APPLICABLE TO: PROPOSALS PURCHASER AS BUILT
3 NOISE & MITIGATION
4 SOUND LEVEL LIMITS FOR THE EQUIPMENT IS SPECIFIED IN TABLES BELOW AND SUPPLIER COMPLETE THESE TABLES.
5 SUPPLIER GIVES ALWAYS NOISE DATA FOR NORMAL DESIGN AND IF ONE NOISE LIMIT IS EXCEEDED
6 SUPPLIER GIVES ALSO A NOISE MITIGATION
7 STANDARDS FOR SOUND LEVEL MEASUREMENT: EEMUA 140, ISO 3740 SERIES, ISO 11200 SERIES, ISO 9614
8 ALL SOUND DATA FOR THESE TABLES ARE:
9 "Lp" : AVERAGE SOUND PRESSURE LEVEL AT 1 METER FROM MAJOR EQUIPMENT BOUNDING SURFACE
10 (DECIBELS REF 0.0002 MICROBAR).
11 "Lpm": MAXIMUM SOUND PRESSURE MEASURED ON BOUNDING SURFACE AT 1 FROM EQUIPMENT
12 "Lw": SOUND POWER LEVELS (DECIBELS REF 10^-12 WATT) (NOTE: Supplier shall fill also these data)
13 FOR INFORMATION TO BE PROVIDED BY VENDOR:
14 MEASURED DATA: YES NO If YES on equivalent equipment, ENCLOSE a diagram showing measured points locations
15 CALCULATED DATA: YES NO If YES, ENCLOSE noise calculation sheet
16 OVERALL SOUND LEVEL DATA IN dBA
17 OVERALL MAX. MANUFACTURER'S ESTIMATED MAXIMUM MANUFACTURER'S GUARANTEED MAX. (Upper Toler. + 0 dBA)

18 PERMISSIBLE NORMAL SPECIAL WITH ACOUSTIC PERMISSIBLE NORMAL SPECIAL WITH ACOUSTIC
19 SOUND LEVEL DESIGN DESIGN TREATMENT SOUND LEVEL DESIGN DESIGN TREATMENT
20 Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw
21
22 Lpm Lpm Lpm Lpm Lpm Lpm Lpm Lpm
23
24 FOR "Lpm" VALUES (Specify locations where Lp is maximum for each proposed design type ):
25
26
27 OCTAVE BAND SOUND LEVEL DATA IN dB dBA
28 IF REQUIRED MANUFACTURER'S ESTIMATED MANUFACTURER'S GUARANTEED
FREQ. in HZ
OCTAVE

29 MAXIMUM MAXIMUM MAXIMUM (Upper Toler. + 0 dB)


30 PERMISSIBLE NORMAL SPECIAL WITH ACOUSTIC NORMAL SPECIAL WITH ACOUSTIC
31 SOUND LEVEL DESIGN DESIGN TREATMENT DESIGN DESIGN TREATMENT
32 Lp Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw
33 31.5
34 63
35 125
36 250
37 500
38 1000
39 2000
40 4000
41 8000
42
43 SUPPLIER FILL IF SPECIAL EMISSIONS CHARACTERISTICS: DISTINCT TONAL CHARACTER IMPULSIVE FLUCTUATING OR INTERMITTENT
44 IF EQUIPMENT INCLUDE SILENCERS: For each silencer, Supplier shall give silencer dynamic insertion loss by octaves bands and sizes (L,W,H)
45 IF EQUIPMENT INCLUDE NOISE ENCLOSURE: Supplier shall give enclosure walls insertion loss by octaves bands with materials description
46
47 DESCRIPTION OF SPECIAL DESIGN:
50 DESCRIPTION OF ACOUSTIC TREATMENT If supplied, Vendor shall include in his offer a noise study with detailed description of noise mitigation
51 and previsional noise map or Lp values at 1 m from equipment for different locations all around the equipment.

Datasheet for Jockey Firewater Pumps Page 6 of 6