Manual Bristol Dpc 3330 Display Keyboard User Manual en 133330
Manual Bristol Dpc 3330 Display Keyboard User Manual en 133330
DISPLAY/KEYBOARD ASSEMBLIES
for
RTU 3310, DPC 3330 & DPC 3335
F1 F2 F3 F4 INIT
7 8 9
Local
ALM ALM
4 5 6 I/E ACK for
TOTA L . F L OW . R A T E
1
A/M
OPER DPC 3330
2 3 I/E
1 24 8 . 9 7 6 MC F H ON
? 1 2 3C E ME A E H I ! 0
NEX T B A CK MU L T EX I T DEL ENT
OFF
4 X 20 Display 4 X 20 Display
Remote Only Membrane Keyboard 5 X 5 Membrane Keyboard
R E Y NOL D S GA S S Y S T EM
R E Y NOL D S GA S S Y S T EM
L OC K P O R T S T A T I ON L OC K P O R T S T A T I ON
8 RUN S 8 RUN S
S I GN ON S CROL L S I GN ON S CROL L
F1 F2 F3 F4
F1 F2 F3 F4 INIT
7 8 9 INIT
7 8 9
1 OPER
1 2 3 A/M I/E
2 OPER ON
3 A/M
I/E
ON
0
DEL ENT
OFF
0
-
OFF
DEL ENTER
Bristol Babcock
Bristol Babcock BRISTOL
BABCOCK
Remote for DPC 3330 & DPC 3335 Remote for DPC 3330 & DPC 3335
Bristol Babcock
NOTICE
Copyright Notice
The information in this document is subject to change without notice. Every effort has been
made to supply complete and accurate information. However, Bristol Babcock assumes no
responsibility for any errors that may appear in this document.
Additional copies of instruction manuals may be ordered from the address below per
attention of the Sales Order Processing Department. List the instruction book numbers or
give complete model number, serial or software version number. Furnish a return address
that includes the name of the person who will receive the material. Billing for extra copies
will be according to current pricing schedules.
Copyright© 2005 Bristol Babcock, 1100 Buckingham St., Watertown, CT 06795. No part of
this manual may be reproduced in any form without the express written permission of
Bristol Babcock.
IMPORTANT! READ INSTRUCTIONS BEFORE STARTING!
Be sure that these instructions are carefully read and understood before any
operation is attempted. Improper use of this device in some applications may result
in damage or injury. The user is urged to keep this book filed in a convenient
location for future reference.
These instructions may not cover all details or variations in equipment or cover
every possible situation to be met in connection with installation, operation or
maintenance. Should problems arise that are not covered sufficiently in the text, the
purchaser is advised to contact Bristol Babcock for further information.
The customer should note that a failure of this instrument or system, for
whatever reason, may leave an operating process without protection. Depending
upon the application, this could result in possible damage to property or injury to
persons. It is suggested that the purchaser review the need for additional backup
equipment or provide alternate means of protection such as alarm devices, output
limiting, fail-safe valves, relief valves, emergency shutoffs, emergency switches, etc.
If additional information is required, the purchaser is advised to contact Bristol
Babcock.
ELECTRICAL GROUNDING
A. Bristol warrants that goods described herein and manufactured by Bristol are free
from defects in material and workmanship for one year from the date of shipment
unless otherwise agreed to by Bristol in writing.
B. Bristol warrants that goods repaired by it pursuant to the warranty are free from
defects in material and workmanship for a period to the end of the original warranty
or ninety (90) days from the date of delivery of repaired goods, whichever is longer.
C. Warranties on goods sold by, but not manufactured by Bristol are expressly limited
to the terms of the warranties given by the manufacturer of such goods.
D. All warranties are terminated in the event that the goods or systems or any part
thereof are (i) misused, abused or otherwise damaged, (ii) repaired, altered or
modified without Bristol's consent, (iii) not installed, maintained and operated in
strict compliance with instructions furnished by Bristol, or (iv) worn, injured or
damaged from abnormal or abusive use in service time.
F. No agent of Bristol is authorized to assume any liability for it or to make any written
or oral warranties beyond those set forth herein.
REMEDIES
A. Buyer's sole remedy for breach of any warranty is limited exclusively to repair or
replacement without cost to Buyer of any goods or parts found by Seller to be
defective if Buyer notifies Bristol in writing of the alleged defect within ten (10) days
of discovery of the alleged defect and within the warranty period stated above, and if
the Buyer returns such goods to Bristol's Watertown office, unless Bristol's Water-
town office designates a different location, transportation prepaid, within thirty (30)
days of the sending of such notification and which upon examination by Bristol
proves to be defective in material and workmanship. Bristol is not responsible for
any costs of removal, dismantling or reinstallation of allegedly defective or defective
goods. If a Buyer does not wish to ship the product back to Bristol, the Buyer can
arrange to have a Bristol service person come to the site. The Service person's
transportation time and expenses will be for the account of the Buyer. However,
labor for warranty work during normal working hours is not chargeable.
As you know, a well-trained staff is essential to your operation. Bristol Babcock offers a full
schedule of classes conducted by full-time, professional instructors. Classes are offered
throughout the year at three locations: Houston, Orlando and our Watertown, CT
headquarters. By participating in our training, your personnel can learn how to install,
calibrate, configure, program and maintain any and all Bristol Babcock products and
realize the full potential of your system.
For information or to enroll in any class, contact our training department in Watertown at
(860) 945-2343. For Houston classes, you can also contact our Houston office, at (713) 685-
6200.
BLANK PAGE
A Few Words About Bristol Babcock
For over 100 years, Bristol7 has been providing innovative solutions for the measurement
and control industry. Our product lines range from simple analog chart recorders, to
sophisticated digital remote process controllers and flow computers, all the way to turnkey
SCADA systems. Over the years, we have become a leading supplier to the electronic gas
measurement, water purification, and wastewater treatment industries.
On off-shore oil platforms, on natural gas pipelines, and maybe even at your local water
company, there are Bristol Babcock instruments, controllers, and systems running year-in
and year-out to provide accurate and timely data to our customers.
In addition to the information contained in this manual, you may receive additional assis-
tance in using this product from the following sources:
Many Bristol Babcock software products incorporate help screens. In addition, the software
typically includes a ‘read me’ release notes file detailing new features in the product, as
well as other information which was available too late for inclusion in the manual.
Bristol Babcock's world headquarters are located at 1100 Buckingham Street, Watertown,
Connecticut 06795, U.S.A.
(860) 945-2200
(860) 945-2213 (FAX)
Regular office hours are Monday through Friday, 8:00AM to 4:30PM Eastern Time,
excluding holidays and scheduled factory shutdowns. During other hours, callers may leave
messages using Bristol's voice mail system.
During regular business hours, Bristol Babcock's Application Support Group can provide
telephone support for your technical questions.
For technical questions about ControlWave call (860) 945-2394 or (860) 945-2286.
For technical questions regarding Bristol’s OpenEnterprise product, call (860) 945-3865
or e-mail: [email protected]
For technical questions regarding ACCOL products, OpenBSI Utilities, UOI and all other
software except for ControlWave and OpenEnterprise products, call (860) 945-2286.
For technical questions about Network 3000 hardware, call (860) 945-2502.
The Application Support Group maintains an area on our web site for software updates and
technical information. Go to: www.bristolbabcock.com/services/techsupport/
For assistance in interfacing Bristol Babcock hardware to radios, contact Bristol Babcock’s
Communication Technology Group in Orlando, FL at (407) 629-9463 or (407) 629-
9464.
Questions of a non-technical nature (product orders, literature requests, price and delivery
information, etc.) should be directed to the nearest sales office (listed on the rear cover of
this manual) or to your Bristol-authorized sales representative.
Please call the main Bristol Babcock number (860-945-2200) if you are unsure which office
covers your particular area.
For general information about Bristol Babcock and its products, please visit our site on the
World Wide Web at: www.bristolbabcock.com
Training Courses
Bristol Babcock’s Training Department offers a wide variety of courses in Bristol hardware
and software at our Watertown, Connecticut headquarters, and at selected Bristol regional
offices, throughout the year. Contact our Training Department at (860) 945-2343 for course
information, enrollment, pricing, and scheduling.
D4085
DISPLAY/KEYBOARD ASSEMBLIES
for
RTU 3310, DPC 3330 & DPC 3335
TABLE OF CONTENTS
SECTION TITLE PAGE #
APPENDICES
Note 1: Questionable Data Status requires firmware level AL.00, RMS02, or later.
The ‘local’ Display/Keyboard is comprised of a four line by twenty character liquid crystal
display, with adjustable viewing angle, and a five-by-five membrane key matrix. Each key
has a microswitch for positive tactile feedback. This means that as you firmly depress the
keys, you will feel it click as it engages. The ‘local’ Display/Keyboard is located in the front
panel of the DPC 3330 or RTU 3310 and can be installed at the factory or added later. A
choice of two ‘remote’ Display/Keyboard assemblies are available for use in conjunction with
the DPC 3330 or DPC 3335. These units are designed to be mounted "remotely." The LCD
Display assembly is identical to the one used in the ‘local’ assembly, while the keyboard
section may be either the same five-by-five membrane key matrix used in the ‘local’
Display/Keyboard assembly (see Figures 1, 2, 3 & 22) or the remote only membrane key
matrix shown in Figures 4 & 23.
The Identifier Display is the first display to appear when the ACCOL load begins to
execute. This display will look similar to Figure 6C. Each of the first three lines of the
display contains the text value of a string signal. These string signals are named on the
SELECT terminals of the Keyboard Module (See Figure 5). Since this is the first display
that the user will see, you may want the display to contain general information such as the
node name of the controller or the process that the controller is monitoring.
The bottom line on the display is called the legend line. It shows which function keys are
currently active and their purpose. Function keys are those keys on the Keypad that are
marked ([F1] through [F4]). Function key assignments are preconfigured and cannot be
changed. Using function keys is described in Section 3, Using the Keyboard.
The legend line in Figure 6C shows that the user has two choices: to sign-on (using [F1]) or
scroll (using [F3]).
Once the Keyboard Module has been configured and the Keyboard is operating properly,
you can automatically scroll through a list of signals. Scrolling can be done without
entering a password (discussed in the next step.) The signals in the list are displayed one at
a time and in the same order in which they were entered in the signal list. This list might
contain summary information about the process the RTU/DPC 33XX is controlling.
(Later, we'll discuss other signal lists that can be accessed with the keypad. To distinguish
this list from others, let's call this signal list the Scroll List.)
On the LIST terminal, enter the number of a signal list to be scrolled. (You may also enter a
signal name whose value equals the number of the signal list.) This signal list becomes the
Scroll List. The Scroll List can contain different types of signals (that is, logical, analog and
string). You can create a specific scroll signal list or use any list in the ACCOL load.
Each signal in the Scroll List will be displayed for the number of seconds defined at the
TIME terminal. If you don't specify a time on this terminal, the hold time will be two
seconds. If you signed-on and then started scrolling you will be signed-off in 20 minutes if
no keys are pressed. If this is unacceptable, sign-off (INIT key) before starting scrolling.
Once the Display/Keyboard is operating, a password will be needed to go beyond the initial
displays. These passwords are defined on the PASSWORD_RD and PASSWORD_WT
terminals.
Someone using the password named on the PASSWORD_RD terminal will only be allowed
to read signal information. When the password named on the PASSWORD_WT terminal is
used, that person can also change signal values and other parameters.
Enter a logical alarm signal name on the STATE terminal. This signal will turn ON when a
valid password has been entered. It will be set OFF when the user has signed off. In each
case, an alarm will be reported to notify the network of this activity.
Enter an analog signal name on the STATUS terminal. When the load is executing, the
value of this signal, when read by the PEI, will indicate the present module state. The
signal will assume one of the following codes:
The INPUT terminals are used to define the menu and signal lists to be accessed from the
List Menu. Once the Keyboard is operating, a user who has signed on with a password can
scroll through the names of signal lists and choose a list to read or change.
Up to 255 INPUT terminals are available. Each terminal can contain a signal list number
or signal name. These terminals should be used consecutively, that is, unwired INPUT
terminals should only appear after the last used INPUT terminal and will generate an
'unwired input' message on the display. Unwired terminals between wired terminals will
use memory space. Unwired terminals after the last used terminal do not use memory.
If the terminal is assigned a number, this number will be presented on the List Menu.
When the terminal is assigned a signal name, both the signal name and its value are shown
on the List Menu.
This concludes this section on configuring the Keyboard Module. If you have properly con-
figured the Keyboard Module, you will see the Identifier Display when the ACCOL load
begins to execute.
Note 2 : If your display shows something else, press the [F4] key until you see the words
SIGN-ON and SCROLL on the bottom line.
If your screen is blank, turn the brightness screw clockwise. This screw is located to
the left of the keyboard. If no letters appear, the controller has not been programmed
properly to operate the keypad.
The words SIGN-ON and SCROLL at the bottom of the screen are on the legend line. It
tells you which function keys (that is, key [F1] through [F4]) are active and their purpose at
that time.
Up to four legends can appear on the legend line. The legend on the far left corresponds to
the function of the [F1] key. The assignment for the [F4] key is on the far right. Keys [F2]
and [F3] are described to the left and right of center. When no legend appears, that function
key is not active at that time. For example, in Figure 11 only [F1] and [F3] are active.
SCROLLING
To begin automatic scrolling, press [F3] from the Identifier Display (Figure 7). Signal in-
formation will appear on the screen and remain there for 2 to 10 seconds. The signal name
appears on the first line. Signal value and units appear on the second line and status
appears on the third line. An example is shown in Figure 13.
Figure 13 - Scrolling
When all signals in the list have been displayed, they will be shown again in the same
order.
Press HOLD ([F1]) to halt scrolling and freeze the display. Press GO ([F2]) to resume
scrolling.
SIGNING-ON
To access the List Menu, you must first sign-on with a proper password. From the
Identifier Display (Figure 11), press [F1]. The screen will look like Figure 14A or 14B.
Someone else has already signed on. Go to the paragraph below that starts "Once the
correct password has been entered...".
Enter a password using the 0 to 9 keys. For security, asterisks will appear as you enter
the digits. If you make a mistake, press [F1] and try again. Press [ENT] to enter your
password into the system.
If your password is not recognized, the asterisks will be erased after you press [ENT].
Check your password and try again. After three unsuccessful attempts to sign-on, an
alarm message is generated within the controller and reported to the external network.
Figure 14 - Signing On
When the second line shows READ/WRITE, you can read and write signal parameters.
When it shows READ ONLY you cannot change signal parameters. You are only permitted
to read signal information. If your display shows READ ONLY and you want to change
signal values, sign-off (press the [INIT] key), press [F1] from the Identifier Display, and
enter the password for READ/WRITE access.
Once you have successfully signed on, the legend line will show that you have three options.
You can view and change the time and date of the local clock, access more signal lists, or
return to the Identifier Display. Let's start by setting the local clock.
From the Sign-On Display (Figure 14B), press [F1]. The screen will show the present date
and time and will look like Figure 15. Follow the instructions below to change the time or
date. When you're finished, press [F4] to exit.
From the display shown in Figure 15, press [F1]. Colons (:) will appear on the third line.
Enter the new time there and press [ENT]. Valid times range from 00:00:00 to 23:59:59.
Invalid entries will be ignored. The display will be updated to show the new time.
If you make a mistake while entering the new time, press [CLR] and start again or use
[DEL] to backspace and delete one character at a time.
From the clock display (Figure 15, press [F2]. Slash marks (/) will appear on the third line.
Enter the new date there and press [ENT].
If you make a mistake while entering the new date, press [CLR] and start again or use
[DEL] to back space and delete one character at a time.
The List Menu is another area where signal information can be seen. As explained earlier
in this section, your first opportunity to read signal information is by choosing the SCROLL
function from the Initial Display. Signal name, value and units text are presented from the
Scroll List. This function is available to all users even without signing-on.
To get to the List Menu, choose MENU (press [F2]) from the Sign-On Display (Figure 14B).
The first signal list number in the menu will appear on the first line. If a signal name was
used to name the list in the ACCOL load, the signal name appears on the second line;
other-wise, the display indicates NO NAME.
Press NEXT and BACK to see the other signal lists that are available in the List Menu. The
List Menu can contain up to 255 signal list numbers.
To advance or backup in large increments, enter a one to three digit number on line 3 and
press NEXT or BACK. For example, if the fifth signal is being displayed and you enter the
number 22 and press NEXT, the twenty-seventh signal will appear.
Wraparound will occur for increments exceeding the list length. For example, suppose the
second signal in a 10-signal list is displayed. If the number 11 is entered and NEXT is
pressed, the third signal in the list will be displayed.
To move directly to a list, enter the list number, then press pick.
After READ or CONF has been pressed, the display will show the first signal in the list. An
example is shown in Figure 19. Each time NEXT is pressed the display will show the next
signal in the list. BACK will show the previous signal.
To move in large increments, enter a one to three digit skip count and press NEXT. The dis-
play will skip over that number of signals. The maximum skip count is 255; larger values
default to 255.
From Figure 18, you can change signal parameters by pressing CONF [F2]. Then follow the
directions summarized below (see Note 3).
Note 3: If your display does not contain the legend CONF in the legend line, your password
will only allow you to read signals. If you want to change signal values at this time,
you must first sign-off and then sign-on using the correct password. See your
Systems Engineer for the correct password.
Before making any changes, first check the signal inhibit status field (See Figure 19). When
the display shows ME (manual enable) you can change signal parameters. When it shows
MI (manual inhibit), you cannot alter the parameters of this signal. If the field indicates
MI, press the OPER IE key to change it to ME.
Press CLR to clear the third line. Use the number keys 0 through 9 to enter the new
value. The minus sign and period are also permitted. Press [ENT].
If you make a mistake, press CLR and enter the number again or use the [DEL] key to
erase a character.
Another way to enter new values is by using the arrow up and arrow down keys (located
below the [F4] and [INIT] keys). These keys will raise and lower the value by 1% of the
displayed amount.
Press CLR, then use either the down and up arrow keys or the [0/OFF] and [1/ON] keys
to change the state of a logical signal. If the [0/OFF] and [1/ON] keys are used, you must
also press [ENT].
2. Value - analog value, string value, or logical value. Values which cannot fit in this field will be
shown as asterisks.
Analog values are displayed in floating point format, for example, 0.0125, 99.627, and 1287.66.
When the value cannot be shown in floating point format, scientific format is used
(1.287668E+10 or 1.25E-02 for example).
3. Questionable Data Status - for analog signals, column 1 will be clear if the status is valid. It will
display a question mark if the status is questionable (requires Firmware Level AL.00 or
RMS02 or later).
4. Skip - how far to move in the list when NEXT or BACK is pressed (Default = 1, Max = 255).
CE (Control Enable) means this signal can be updated by the ACCOL program.
CI (Control Inhibit) means the signal cannot be updated by the ACCOL program.
7. Units - units text (for analog signals only), if any units have been defined.
8. Alarm State
! - alarm is unacknowledged
In Read Mode, pressing MULT will display the signal name extension, value, and units for three
signals at one time. These signals include the signal displayed when NEXT was pressed and
the next two signals in the list. Press SNGL [F3] to return to viewing one signal at a time (see
Figure 20).
1) String
SITE.NAME
WEST SUNBURY PUMP STATION
CE ME
2) Analog
TOTAL.FLOW.RATE
1260.578 GALS.
CE MI
3) Logical
FLOW.ALARM
OFF
CE MI AE NA
The first message is a reminder that the first thing you must do to change an analog value
or digital status is to press CLR.
The second message will appear when the signal cannot be changed because it is not in
manual enable (ME) mode.
To acknowledge an alarm:
Press [ALM I/E] key. (Note: This will only inhibit alarm reporting, and not alarm level
detection.)
SIGNING-OFF
Once you have signed-on, use the [INIT] key at any time to sign-off. When this key has
been pressed, the screen will look like Figure 21. Press YES to sign-off. You are signed-off
when the Identifier Display (Figure 6C) appears.
If you do not want to sign-off, press EXIT to leave the Sign-Off Display.
Once you are signed-on an automatic sign-off will occur if 20 minutes has elapsed since the
last key was pressed.
NO INPUT LISTS
Meaning: This may occur when the MENU function is selected. No input lists were
entered during configuration.
UNWIRED INPUT
Meaning: No value has been entered at this INPUT terminal in the ACCOL load.
NON-EXISTENT LIST
Meaning: The list was not found in the load. An invalid signal list number was entered
on the LIST or INPUT terminals.
Remedy: Using the AIC or ABC, enter a valid signal list number on the LIST or INPUT
terminals (See Steps 2 and 5, pages 5 and 8).
NO SCROLL LIST
Remedy: Use the AIC or ABC to enter a value or signal name on the LIST terminal (See
Step 2, page 3).
EMPTY LIST
Meaning: A valid signal list number has been requested but the signal list is empty.
Remedy: Use the AIC or ABC to create a signal list and/or place the appropriate signal
names into the empty list.
STRING SIGNAL:
KEY FUNCTION
Function keys will take on a variety of different functions depending on the
F1, F2, F3,
situation. The function of these keys is listed on the legend line (bottom line) of the
F4
display.
INIT The INIT key is used to terminate the keyboard session and sign-off.
These keys are used to change the value of analog signals in the
0 to 9, -, . CONFIGURATION mode. The 0/OFF and 1/ON keys are used to change the state
of logical signals.
Each press of this key will raise an analog signal value by 1% of the displayed
∆
value or turn a logical signal ON.
Each press of this key will lower an analog signal value by 1% of the displayed
∇
value or turn a logical signal OFF.
ALM I/E Use this key to enable or inhibit alarm signals.
ALM ACK Use this key to acknowledge alarms.
A/M Toggle between AUTO (CE) and MANUAL (CI) with this key.
OPER I/E Toggle between manual inhibit (MI) and enable (ME) with this key.
DEL Use this backspace key to erase digits that have been entered on the keypad.
This key is used to enter new data from the display into the DPC 3330, e.g.,
ENT
password or signal values.
R E Y NOL D S GA S S Y S T EM
L OC K P O R T S T A T I ON
8 RUN S
S I GN ON S CROL L
F1 F2 F3 F4 INIT
7 8 9
ALM ALM
4 5 6 I/E ACK
1 OPER
2 3 A/M I/E
ON
0
DEL ENT
OFF
Bristol Babcock
Appendix DKA of Document D4085
CW_10 4 X 20 DISPLAY-KEYBOARD ASSEMBLY
TABLE OF CONTENTS
SECTION TITLE PAGE #
Section 1 - INTRODUCTION
1.1 DESCRIPTION............................................................................................................................... 1
1.1.1 Resident D-K Assembly .............................................................................................................. 1
1.1 DESCRIPTION
The Display-Keyboard (D-K) Assembly provides a convenient local operator interface. With
this option, the operator can observe and alter certain RTU parameters defined in the
ControlWave Project.
The Display consists of a 4-line, 20 character readout on a 5 x 7 dot matrix LCD screen as
shown in Figure DKA-1. A screen adjustment (contrast) controls the intensity of the
readout. The display presents a variety of menus that allow the user to read or write
parameters, select functions, and create text.
Bristol Babcock Display-Keyboard assemblies provide a built-in, local, user interface for the
ControlWave_10. These assemblies allow an operator or engineer to view and modify
variable values and associated status information, via an ACCOL3 Function Block.
Variables can include inputs, process variables, calculated variables, constants, setpoints,
tuning parameters and outputs used in a measurement or control application. Status bits
include alarm state, alarm acknowledge, control, manual, and questionable data.
A resident Display-Keyboard Assembly is secured to the CW_10 RTU via four screws. The
two top captive screws secure the assembly to swileling stand-offs (hinges) which allow the
panel to be swung out of the way to access I/O boards.
2.1 INSTALLATION
The Resident Display and Keyboard system is assembled to the RTU and does not require
installation.
If your Keypboard has already been set up, Section 2.5 will tell you how to use the
Keyboard and interpret the Display.
In order for the Keyboard and Display to operate, the ControlWave Designer project must
include a properly configured DISPLAY Function Block. Use ControlWave Designer to
configure this function block and assign the parameters according to the four steps covered
in Section 2.4.
Referring to Figure DKA-3, various DISPLAY Function Block Parameters are available.
For information on configuring the Display Function Block, please reference on-line help in
ControlWave Designer.
The Identifier Display is the first display to appear when the Display Function Block is
initialized and begins to execute. This display will look similar to Figure DKA-5. Each of
the first three lines of the display contains the text value of a string variable. These string
variables are created utilizing iaScrnStruct parameters of the Display Function Block (See
Figure DKA-4) and your computer keyboard. Since this is the first display that the user will
see, you may want the display to contain general information such as the node name of the
controller or the process that the controller is monitoring.
The bottom line on the display is called the legend line. It shows which function keys are
currently active and their purpose. Function keys are those keys on the Keypad that are
marked ([F1] through [F4]). Function key assignments are preconfigured and cannot be
changed. Using function keys is described in Section 2.5, Using the Keyboard.
The legend line in Figure DKA-4 shows that the user has two choices: to Log-in (using [F1])
or scroll (using [F2]).
Once the Keyboard is operating properly, you can automatically scroll through a list of
variables created via DISPLAY Function Block Parameters iiList2Scroll and iiListMode.
Scrolling can be done without entering a password. The variables in the list are displayed
one at a time and in the same order in which they were entered in the variable list.
Later, we'll discuss other variable lists that can be accessed with the Keyboard. To
distinguish this list from others, let's call this variable list the Scroll List.
Each variable in the Scroll List will be displayed for the number of seconds defined by the
iiScrollTime parameter. If you don't specify a time for this parameter, the hold time will be
two seconds. If you signed-on and then started scrolling you will be signed-off in 20 minutes
if no keys are pressed. If you don’t want to automatically stop scrolling after 20 minutes,
sign-off (INIT key) before starting scrolling.
The next section describes how to use the Keyboard to access variable information.
Note 1 : If your display shows something else, press the [F4] key until you see the words
Login and Scroll on the bottom line.
The words Login and Scroll at the bottom of the screen are on the legend line. It tells you
which function keys (that is, key [F1] through [F4]) are active and their purpose at that
time.
Up to four legends can appear on the legend line. The legend on the far left corresponds to
the function of the [F1] key. The assignment for the [F4] key is on the far right. Keys [F2]
and [F3] are described to the left and right of center. When no legend appears, that function
key is not active at that time. For example, in Figure DKA-5 only [F1] and [F2] are active.
From the Identifier Display, you have two choices. Pressing [F1] will allow you to sign-on if
you have a password. By pressing [F2] you can activate automatic scrolling through a list of
variables.
2.5.1 Scrolling
To begin automatic scrolling, press [F2] from the Identifier Display (Figure DKA-6).
Variable in-formation will appear on the screen and remain there for 1 to 30 seconds
(default = 2 seconds). The variable name appears on the first line. The variable value
appears on the second line and status information appears on the third line. An example is
shown in Figure DKA-7.
When all variables in the list have been displayed, they will be shown again in the same
order. This is called Single Variable Mode.
Pressing Mlti [F2] activates Multiple Variable Mode. Multiple Variable Mode displays up to
three (3) variables and their values on the screen simultaneously. Pressing Sngl [F2]
terminates Multiple Variable Mode and returns you to Single Variable Mode.
Press HOLD [F1] to halt scrolling. Changing variable values will continue to be displayed.
2.5.2 Signing-On
To access the List Menu, you must first sign-on with a proper password. From the
Identifier Display (Figure DKA-6), press [F1]. The screen will look like Figure DKA-8A or
DKA-8C. If the display looks like Figure DKA-8C:
Someone else has already signed on. Go to the paragraph below that starts "Once you
have successfully signed on,…".
Select the Username (default = system) by using the Up and Down Arrow Keys. If the
Username system is displayed and no other Username is available (i.e., no others have
been assigned), press [ENTER].
Enter a password using the 0 to 9 keys. For security, asterisks will appear as you enter
the digits. If you make a mistake, press [F1] and try again (or use the delete key to
delete the previously pressed key action). The default password is 666666 (used when a
password is not known or no password has been assigned). After typing the password,
press [ENTER].
If your password is not recognized, the asterisks will be erased after you press
[ENTER]. Check your password and try again.
Once the correct password has been entered, the display will look like Figure DKA-8C.
When the second line shows READ/WRITE, you can read and write variable parameters.
When it shows READ ONLY you cannot change variable parameters. You are only permit-
ted to read variable information. If your display shows READ ONLY and you want to
change variable values, sign-off (press the [INIT] key) and log on with a username and
password that provides Read/Write privileges.
Once you have successfully signed on, the legend line will show that you have four options.
D4085 - Appendix DKA CW_10 4-20 Display-Keyboard / Pg.8
You can view and change the time and date of the local clock, access more variable lists,
Scroll, or return to the Identifier Display. Use function keys F1 through F4 to select the
next menu (F1 = Clock, F2 = Menu, F3 = Scroll list & F4 = Exit). Let's start by setting the
local clock.
From the Logged-On Display (Figure DKA-8C), press [F1]. The screen will show the present
date and time and will look like Figure DKA-9. Follow the instructions below to change the
time or date. When you're finished, press [F4] to exit.
From the display shown in Figure DKA-9, press Time [F2]. Colons (:) will appear on the
third line. Enter the new time there and press [ENTER]. Valid times range from 00:00:00 to
23:59:59. Invalid entries will be ignored. The display will be updated to show the new time.
If you make a mistake while entering the new time, use [DEL] to backspace and delete one
character at a time.
From the clock display (Figure DKA-9, press [F1]. Slash marks (/) will appear on the third
line. Enter the new date there and press [ENTER].
If you make a mistake while entering the new date, use [DEL] to back space and delete one
character at a time. Press [F4] to return to the Logged-On Display (Figure DKA-8C).
The List Menu is another area where variable information can be seen. As explained earlier
in this section, your first opportunity to read variable information is by choosing the
SCROLL function from the Initial Display. The variable name and value are presented
from the Scroll List. This function is available to all users even without signing-on.
The List Menu will show other groups of variable which you can choose to read. This in-
formation will be more detailed than the Scroll List.
To get to the List Menu, choose MENU (press [F2]) from the Logged-On Display (Figure
DKA-8C).
The first variable list number in the menu will appear on the second line.
Press PREV (F1) and NEXT (F2) to see the other variable lists that are available in the List
Menu. You can also use the Up and Down Arrow Keys to scroll through the various lists. To
move directly to a list, enter the list number, then press [ENTER].
After READ (F1) or WRITE (F2) has been pressed, the display will show the first variable
in the list. An example is shown in Figure DKA-13. Each time NEXT (F2) is pressed; the
display will show the next variable in the list. PREV (F1) will show the previous variable.
You can also use the Up and Down Arrow Keys to move through a list.
Automatic wraparound occurs in either direction. When you reach the end of the list, [F1]
will display the first variable again. At the top of the list, [F2] will display the last variable.
From Figure DKA-12, you can change variable parameters by pressing F2 [Write]. Then
follow the directions summarized below (see Note 2).
Note 2: If your display does not contain the legend Write in the legend line, your password
will only allow you to read variables. If you want to change variable values at this
time, you must first log-off and then log-on using the correct password. See your
Systems Engineer for the correct password.
Before making any changes, first check the variable inhibit status field (See Figure DKA-
13). When the display shows ME (manual enable) you can change variable parameters.
When it shows MI (manual inhibit), you cannot alter the parameters of this variable. If the
field indicates MI, press the OPER I/E key to change it to ME.
Press CHNG (F3) to clear the third line. Use the number keys 0 through 9 to enter the
new value. The minus sign and period are also permitted. Press [ENTER].
Another way to enter new values is by using the arrow up and arrow down keys (located
below the [F3] key and left of the [INIT] key). These keys will raise and lower the value
by 1% of the displayed amount.
Press CHNG (F3), then use either the down and up arrow keys or the [0/OFF] and
[1/ON] keys to change the state of a logical variable. If the [0/OFF] and [1/ON] keys are
used, you must also press [ENTER].
2. Value - analog value, string value, or logical value. Values which cannot fit in this field will be
shown as asterisks.
Analog values are displayed in floating point format, for example, 0.0125, 99.627, and 1287.66.
When the value cannot be shown in floating point format, scientific format is used
(1.287668E+10 or 1.25E-02 for example).
3. Questionable Data Status - for analog variables, column 1 will be clear if the status is valid. It
will display a question mark if the status is questionable.
CE (Control Enable) means this variable can be updated by the ControlWave project.
CI (Control Inhibit) means the variable cannot be updated by the ControlWave project.
ME (Manual Enable) means the variable can be changed manually.
MI (Manual Inhibit) means the variable cannot be changed manually.
6. Alarm State
! - alarm is unacknowledged
In Read Mode, pressing MULT (F3) will display the variable name extension, value, and units
for three variables at one time. These variables include the variable displayed when NEXT (F2)
was pressed and the next two variables in the list. Press SNGL [F3] to return to viewing one
variable at a time (see Figure DKA-13A).
1) String
SITE_NAME
WEST SUNBURY PUMP STATION
CE ME
2) Analog
TOTAL_FLOW_RATE
1260.578
CE MI
3) Logical
FLOW_ALARM
OFF
CE MI AE NA
To acknowledge an alarm:
2.5.7 Signing-Off
Once you have logged-on, use the [INIT] key at any time to log-off. When this key has been
pressed, the screen will look like Figure DKA-14. Press Yes (F1) to sign-off. You are signed-
off when the Identifier Display (Figure DKA-5) appears.
If you do not want to log-off, press Exit (F4) to leave the Log-Off Display.
Once you are signed-on an automatic sign-off will occur if 20 minutes has elapsed since the
last key was pressed.
KEY FUNCTION
Function keys will take on a variety of different functions depending on the
F1, F2, F3,
situation. The function of these keys is listed on the legend line (bottom line) of the
F4
display.
INIT The INIT key is used to terminate the keyboard session and sign-off.
These keys are used to change the value of analog variables in the
0 to 9, −, • CONFIGURATION mode. The 0/OFF and 1/ON keys are used to change the state
of logical variables.
Each press of this key will raise an analog variable value by 1% of the displayed
∆
value or turn a logical variable ON.
Each press of this key will lower an analog variable value by 1% of the displayed
∇
value or turn a logical variable OFF.
ALM I/E Use this key to enable or inhibit alarm variables.
ALM ACK Use this key to acknowledge alarms.
A/M Toggle between AUTO (CE) and MANUAL (CI) with this key.
OPER I/E Toggle between manual inhibit (MI) and enable (ME) with this key.
DEL Use this backspace key to erase digits that have been entered on the keypad.
This key is used to enter new data from the display into the controller, e.g.,
ENT
password or variable values.
Local F1
7
F2
8
F3
9
F4 INIT
ALM ALM
4 5 6 I/E ACK
{
1 OPER
R E Y NOL D S GA S S Y S T EM 2 3 A/M I/E
ON
L OC K P O R T S T A T I ON
8 RUN S 0
DEL ENT
S I GN ON S CROL L OFF
R E Y NOL D S GA S S Y S T EM
L OC K P O R T S T A T I ON
8 RUN S
S I GN ON S CROL L
F1 F2 F3 F4 INIT
7 8 9
ALM ALM
4 5 6 I/E ACK
1 OPER
2 3 A/M I/E
ON
0
DEL ENT
OFF
BRISTOL
BABCOCK
Remote
Bristol Babcock
Appendix DKB
CW_30 4 X 20 DISPLAY-KEYBOARD ASSEMBLY
TABLE OF CONTENTS
SECTION TITLE PAGE #
Section 1 - INTRODUCTION
1.1 DESCRIPTION............................................................................................................................... 1
1.1.1 Resident (Local) D-K Assembly.................................................................................................. 1
1.1.2 Extended D-K Assembly ............................................................................................................. 1
1.1 DESCRIPTION
The Display-Keyboard (D-K) Assembly provides a convenient local operator interface. With
this option, the operator can observe and alter certain DPC parameters defined in the
ControlWave Project.
The Display consists of a 4-line, 20 character readout on a 5 x 7 dot matrix LCD screen as
shown in Figures DKB-1 & DKB-2. A screen adjustment (contrast) controls the intensity of
the readout. The display presents a variety of menus that allow the user to read or write
parameters, select functions, and create text.
Bristol Babcock Display-Keyboard assemblies provide a built-in, local, user interface for the
ControlWave_30. These assemblies allow an operator or engineer to view and modify
variable values and associated status information, via an ACCOL3 Function Block.
Variables can include inputs, process variables, calculated variables, constants, setpoints,
tuning parameters and outputs used in a measurement or control application. Status bits
include alarm state, alarm acknowledge, control, manual, and questionable data.
The resident (local) Display and Keyboard mount at the front of the chassis and are visible
with the cover in place on DPCs with plastic covers. For DPCs furnished in NEMA-4
enclosures, a front window provides display visibility.
The complete on-board assembly is mounted on a hinged panel. A front view of this
assembly is shown in Figure DKB-1. Loosening the captive screw above the Keyboard
allows the panel to be swung out of the way to access other components.
The hardware of the extended D-K Assembly has the arrangement shown in Figure DKB-3.
This version provides a Resident Module (not shown) in the DPC connected by a ribbon
cable to a Remote (extended D-K Assembly).
The Resident Module is wired to a connector that is accessible through an opening in the
DPC cover. The Resident Module uses the same interface board assembly; however, the
Display and Keypad boards are replaced by a Buffer Board having the appropriate drivers
and interface for the Remote Unit (no PC boards are illustrated).
The Remote Unit of the Extended D-K System is contained in a metal housing having
appropriate openings for the display and keyboard (Figure DKB-2). The screen adjustment
(contrast) is concealed behind a threaded plug. This plug and its o-ring must be replaced
and secured when adjustments are complete.
2.1 INSTALLATION
The Resident (Local) Display-Keyboard system is assembled to the DPC and does not
require installation.
The Remote Unit connects to the CW_30 DPC via a 10-foot, 50-conductor ribbon cable
(Figure DKB-2). One end of the cable plugs into a receptacle at the front of the DPC, and
the other end into a connector at the back of the Display Unit.
Note that the Remote Unit is open at the back and uses the mounting surface as a back
plate. The Remote Unit is designed to mount against a surface such as a cabinet wall. The
cabinet must have a cutout to accommodate the ribbon cable. The unit cutout and drill
dimensions are given in Figure DKB-3.
If you're setting up the Keyboard, follow the configuration instructions provided in Section
2.4 of this appendix.
If your Keyboard has already been set up, Section 2.5 will tell you how to use the Keyboard
and interpret the Display.
In order for the Keyboard and Display to operate, the ControlWave Designer project must
include a properly configured DISPLAY Function Block. Use ControlWave Designer to
configure this function block and assign the parameters according to the four steps covered
in Section 2.4.
Referring to Figure DKB-4, various DISPLAY Function Block Parameters are available.
For information on configuring the Display Function Block, please reference on-line help in
ControlWave Designer.
The Identifier Display is the first display to appear when the Display Function Block is
initialized and begins to execute. This display will look similar to Figure DKB-6. Each of
the first three lines of the display contains the text value of a string variable. These string
variables are created utilizing iaScrnStruct parameters of the Display Function Block (See
Figure DKB-4) and your computer keyboard. Since this is the first display that the user will
see, you may want the display to contain general information such as the node name of the
controller or the process that the controller is monitoring.
The bottom line on the display is called the legend line. It shows which function keys are
currently active and their purpose. Function keys are those keys on the Keyboard that are
marked ([F1] through [F4]). Function key assignments are preconfigured and cannot be
changed. Using function keys is described in Section 2.5, Using the Keyboard.
The legend line in Figure DKB-5 shows that the user has two choices: to Log-in (using [F1])
or scroll (using [F2]).
Once the Keyboard is operating properly, you can automatically scroll through a list of
variables created via DISPLAY Function Block Parameters iiList2Scroll and iiListMode.
Scrolling can be done without entering a password. The variables in the list are displayed
one at a time and in the same order in which they were entered in the variable list.
Enter the number of a variable list to be scrolled. This variable list becomes the Scroll List.
The Scroll List can contain different types of variables (that is, logical, analog and string).
You can create a specific scroll variable list or use any list in the ControlWave Project.
Each variable in the Scroll List will be displayed for the number of seconds defined by the
iiScrollTime parameter. If you don't specify a time for this parameter, the hold time will be
two seconds. If you signed-on and then started scrolling you will be signed-off in 20 minutes
if no keys are pressed. If you don’t want to automatically stop scrolling after 20 minutes,
sign-off (INIT key) before starting scrolling.
The next section describes how to use the Keypad to access variable information.
Note 1 : If your display shows something else, press the [F4] key until you see the words
Login and Scroll on the bottom line.
If your screen is blank, turn the Screen Adjustment Poentiometer clockwise. This
Pot. is located to the left of the Keypboard on Local Units (see Figure DKB-1) or
behind a Plug on Remote Units (see Figure DKB-2). If no letters appear, the control-
ler has not been programmed properly to operate the keypad.
The words Login and Scroll at the bottom of the screen are on the legend line. It tells you
which function keys (that is, key [F1] through [F4]) are active and their purpose at that
time.
Up to four legends can appear on the legend line. The legend on the far left corresponds to
the function of the [F1] key. The assignment for the [F4] key is on the far right. Keys [F2]
and [F3] are described to the left and right of center. When no legend appears, that function
key is not active at that time. For example, in Figure DKB-6 only [F1] and [F2] are active.
From the Identifier Display, you have two choices. Pressing [F1] will allow you to sign-on if
you have a password. By pressing [F2] you can activate automatic scrolling through a list of
variables.
2.5.1 Scrolling
To begin automatic scrolling, press [F2] from the Identifier Display (Figure DKB-7).
Variable in-formation will appear on the screen and remain there for 1 to 30 seconds
(default = 2 seconds). The variable name appears on the first line. The variable value
appears on the second line and status information appears on the third line. An example is
shown in Figure DKB-8.
When all variables in the list have been displayed, they will be shown again in the same
order. This is called Single Variable Mode.
Pressing Mlti [F2] activates Multiple Variable Mode. Multiple Variable Mode displays up to
three (3) variables and their values on the screen simultaneously. Pressing Sngl [F2]
terminates Multiple Variable Mode and returns you to Single Variable Mode.
Press HOLD [F1] to halt scrolling. Changing variable values will continue to be displayed.
2.5.2 Signing-On
To access the List Menu, you must first sign-on with a proper password. From the Identifier
Display (Figure DKB-7), press [F1]. The screen will look like Figure DKB-9A or DKB-9C. If
the display looks like Figure DKB-9C:
Someone else has already signed on. Go to the paragraph below that starts "Once you
have successfully signed on,…".
Select the Username (default = system) by using the Up and Down Arrow Keys. If the
Username system is displayed and no other Username is available (i.e., no others have
been assigned), press [ENTER].
Enter a password using the 0 to 9 keys. For security, asterisks will appear as you enter
the digits. If you make a mistake, press [F1] and try again (or use the delete key to
delete the previously pressed key action). The default password is 666666 (used when a
password is not known or no password has been assigned). After typing the password,
press [ENTER].
If your password is not recognized, the asterisks will be erased after you press
[ENTER]. Check your password and try again.
Once the correct password has been entered, the display will look like Figure DKB-9C.
When the second line shows READ/WRITE, you can read and write variable parameters.
When it shows READ ONLY you cannot change variable parameters. You are only permit-
ted to read variable information. If your display shows READ ONLY and you want to
change variable values, sign-off (press the [INIT] key) and log on with a username and
password that provides Read/Write privileges.
From the Logged-On Display (Figure DKB-9C), press [F1]. The screen will show the present
date and time and will look like Figure DKB-10. Follow the instructions below to change
the time or date. When you're finished, press [F4] to exit.
From the display shown in Figure DKB-10, press Time [F2]. Colons (:) will appear on the
third line. Enter the new time there and press [ENTER]. Valid times range from 00:00:00 to
23:59:59. Invalid entries will be ignored. The display will be updated to show the new time.
If you make a mistake while entering the new time, use [DEL] to backspace and delete one
character at a time.
From the clock display (Figure DKB-10, press [F1]. Slash marks (/) will appear on the third
line. Enter the new date there and press [ENTER].
If you make a mistake while entering the new date, use [DEL] to back space and delete one
character at a time. Press [F4] to return to the Logged-On Display (Figure DKB-9C).
The List Menu is another area where variable information can be seen. As explained earlier
in this section, your first opportunity to read variable information is by choosing the
SCROLL function from the Initial Display. The variable name and value are presented
from the Scroll List. This function is available to all users even without signing-on.
The List Menu will show other groups of variable which you can choose to read. This in-
formation will be more detailed than the Scroll List.
To get to the List Menu, choose MENU (press [F2]) from the Logged-On Display (Figure
DKB-9C).
The first variable list number in the menu will appear on the second line.
Press PREV (F1) and NEXT (F2) to see the other variable lists that are available in the List
Menu. You can also use the Up and Down Arrow Keys to scroll through the various lists. To
move directly to a list, enter the list number, then press [ENTER].
After READ (F1) or WRITE (F2) has been pressed, the display will show the first variable
in the list. An example is shown in Figure DKB-14. Each time NEXT (F2) is pressed; the
display will show the next variable in the list. PREV (F1) will show the previous variable.
You can also use the Up and Down Arrow Keys to move through a list.
Automatic wraparound occurs in either direction. When you reach the end of the list, [F1]
will display the first variable again. At the top of the list, [F2] will display the last variable.
From Figure DKB-13, you can change variable parameters by pressing F2 [Write]. Then
follow the directions summarized below (see Note 2).
Note 2: If your display does not contain the legend Write in the legend line, your password
will only allow you to read variables. If you want to change variable values at this
time, you must first log-off and then log-on using the correct password. See your
Systems Engineer for the correct password.
Before making any changes, first check the variable inhibit status field (See Figure DKB-
14). When the display shows ME (manual enable) you can change variable parameters.
When it shows MI (manual inhibit), you cannot alter the parameters of this variable. If the
field indicates MI, press the OPER I/E key to change it to ME.
Press CHNG (F3) to clear the third line. Use the number keys 0 through 9 to enter the
new value. The minus sign and period are also permitted. Press [ENTER].
Another way to enter new values is by using the arrow up and arrow down keys (located
below the [F3] key and left of the [INIT] key). These keys will raise and lower the value
by 1% of the displayed amount.
Press CHNG (F3), then use either the down and up arrow keys or the [0/OFF] and
[1/ON] keys to change the state of a logical variable. If the [0/OFF] and [1/ON] keys are
used, you must also press [ENTER].
2. Value - analog value, string value, or logical value. Values which cannot fit in this field will be
shown as asterisks.
Analog values are displayed in floating point format, for example, 0.0125, 99.627, and 1287.66.
When the value cannot be shown in floating point format, scientific format is used
(1.287668E+10 or 1.25E-02 for example).
3. Questionable Data Status - for analog variables, column 1 will be clear if the status is valid. It
will display a question mark if the status is questionable.
CE (Control Enable) means this variable can be updated by the ControlWave project.
CI (Control Inhibit) means the variable cannot be updated by the ControlWave project.
ME (Manual Enable) means the variable can be changed manually.
MI (Manual Inhibit) means the variable cannot be changed manually.
6. Alarm State
! - alarm is unacknowledged
In Read Mode, pressing MULT (F3) will display the variable name extension, value, and units
for three variables at one time. These variables include the variable displayed when NEXT (F2)
was pressed and the next two variables in the list. Press SNGL [F3] to return to viewing one
variable at a time (see Figure DKB-14A).
1) String
SITE_NAME
WEST SUNBURY PUMP STATION
CE ME
2) Analog
TOTAL_FLOW_RATE
1260.578
CE MI
3) Logical
FLOW_ALARM
OFF
CE MI AE NA
To acknowledge an alarm:
Press [ALM I/E] key. (Note: This will only inhibit alarm reporting, and not alarm level
detection.)
2.5.7 Signing-Off
Once you have logged-on, use the [INIT] key at any time to log-off. When this key has been
pressed, the screen will look like Figure DKB-15. Press Yes (F1) to sign-off. You are signed-
off when the Identifier Display (Figure DKB-6) appears.
If you do not want to log-off, press Exit (F4) to leave the Log-Off Display.
Once you are signed-on an automatic sign-off will occur if 20 minutes has elapsed since the
last key was pressed.
KEY FUNCTION
Function keys will take on a variety of different functions depending on the
F1, F2, F3,
situation. The function of these keys is listed on the legend line (bottom line) of the
F4
display.
INIT The INIT key is used to terminate the keyboard session and sign-off.
These keys are used to change the value of analog variables in the
0 to 9, −, • CONFIGURATION mode. The 0/OFF and 1/ON keys are used to change the state
of logical variables.
Each press of this key will raise an analog variable value by 1% of the displayed
∆
value or turn a logical variable ON.
Each press of this key will lower an analog variable value by 1% of the displayed
∇
value or turn a logical variable OFF.
ALM I/E Use this key to enable or inhibit alarm variables.
ALM ACK Use this key to acknowledge alarms.
A/M Toggle between AUTO (CE) and MANUAL (CI) with this key.
OPER I/E Toggle between manual inhibit (MI) and enable (ME) with this key.
DEL Use this backspace key to erase digits that have been entered on the keypad.
This key is used to enter new data from the display into the controller, e.g.,
ENT
password or variable values.
Please help us make our documentation more useful to you! If you have a complaint, a
suggestion, or a correction regarding this manual, please tell us by mailing this page with your
comments. It's the only way we know we're doing our job by giving you correct, complete, and
useful documentation.
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
U.S.A. Locations:
Northern Region Gulf Coast Region Western Region Southeast Region
Bristol Babcock Inc. Bristol Babcock Inc. Bristol Babcock Inc. Bristol Babcock Inc.
1100 Buckingham Street 2000 Governor's Circle 1609 South Grove Avenue 317 S. North Lake Blvd.
Watertown, CT 06795 Suite F Suites 106 & 107 Suite 1016
Phone: +1 (860) 945-2381 Houston, TX 77092-8731 Ontario, CA 91761 Altamonte Springs, FL 32701
Fax: +1 (860) 945-2525 Phone: +1 (713) 685-6200 Phone: +1 (909) 923-8488 Phone: +1 (407) 740-7084
Fax: +1 (713) 681-7331 Fax: +1 (909) 923-8988 Fax: +1 (407) 629-2106
International Affiliates:
Canada Mexico United Kingdom Asia Pacific
Bristol Babcock, Canada BBI, S.A. de C.V. Bristol Babcock Ltd. Bristol Babcock, Inc.
234 Attwell Drive Homero No. 1343, 3er Piso Blackpole Road PO Box 1987
Toronto, Ont. M9W 5B3 Col. Morales Polanco Worcester, WR3 8YB Bunbury, Western Australia
Canada 11540 Mexico, D.F. United Kingdom 6231
PH: 416-675-3820 Mexico PH: +44 (0) 1905 856950 PH: +61 (0) 8 9791 3654
FAX: 416-674-5129 PH: (52-55)-52-81-81-12 FAX: +44 (0) 1905 856969 FAX: +61 (0) 8 9791 3173
FAX: (52-55)-52-81-81-09
Victoria, Australia
PH: +61 (0) 3 9384 2171
Calgary Office Villahermosa Office Middle East FAX: +61 (0) 3 8660 2501
Bristol Babcock, Canada BBI, S.A. de C.V. Bristol Babcock Ltd.
3812 Edmonton Trail N.E. Av. Plomo No.2 Blackpole Road
Calgary, Alberta T2E 5T6 Bodega No. 1 - Ciudad Worcester, WR3 8YB
Canada Industrial United Kingdom
PH: 403-265-4808 Villahermosa, Tabasco 86010 PH: +44 (0) 1905 856950
FAX: 403-233-2914 Mexico FAX: +44 (0) 1905 856969
PH: 52-993-353-3142
FAX: 52-993-353-3145
RC Rev: 05-Feb-04