array_parameter_tool_13 (2)
array_parameter_tool_13 (2)
Min Temp -26 C Module width 3.28 ft Module/string Isc (series) 9.44 A
module height 6.54 ft Isc continous current multiplier 1.25 see (a)
Voc 46.43 V Nom Isc 11.8 A
Ref temp 25 C Rack width 28 modules Isc irradiance correction 1.25 see (b)
Rack height 2 modules Max Isc string 14.75 A
Temp Coeff of Voc -0.0029 per deg C Max Isc rack, at CB 29.5 A
Temp delta -51 Rack width 91.84 ft Allowed current CB 400 A
temp correction 1.15 Rack height 13.08 ft Max current per CB 354 A
Voc corrected 53.297 Strings per CB 27.11864
Frame width 1.38 in Number of CB per array 11
String voltage/CB in voltage 1500 V Actual strings per CB 24 ****
String size 28.1442
string size ( series ) 28 modules
String voltage calculated 1492.3 V
(a) NEC690.8(B)(1) requires overcurrent device ratings shall not be less than 125% of the maximum currents calculated - continous current multiplier.
(b) NEC690.8(A)(1) requires another 125% correction multiplier before the applicaton of other correction factors.
The irradiance correction factor is a multiplier for the current output of a solar panel. Panels can have power spikes with higher solar irradiance.
Thus the total current correction factors are 156%
(c) The total component area includes the racks and inverter skid. Does not include negligable area of converter boxes or recombiners.
(rack area)(118)+(inv skid area)
(d) Referenced from true north. Azimuth is measured clockwise from true north to the point on the horizon directly below the object.
** Access road included
*** Assumes 6x6 configuration & 16 ft spacing between arrays.
**** Except CB6 and CB7 ,see CB & Inverter Sheet (this xlsx)
Power per Rack 18.2 kW Ground Coverage Ratio (GCR) 0.5064 see( c)
1
MAY1602 ISU Senior Design
Combiner Box (CB) Currents
Array Layout
551.04 ft
91.84 ft
12.63 ft
508.69 ft
4
5
16.00 ft
6 7
10
11
12.00 ft
Legend
Rack Combiner Box with identification number
2
MAY1602 ISU Senior Design
Conductors
Conductors Max Isc (A) Type Material Temp (degC) AWG Cable Rating (A) Minimum Depth Fuse
String Conductor 14.75 Free Air Copper 75 12 35 NA 15
Rack to CB - Jumper 29.5 Free Air Copper 75 10 50 NA 30
CB to Inverter - DC feeder 354 Buried Aluminum 75 700 375 30 inch 355 see (a)
Xformer to Collector 116 Buried Aluminum 75 1\0 120 36 inch (*) see (b)
(a) 1500 V conductor must be buried at least 30 inches , NEC310 Table 300.50 pg157
(a) 34.5kV conductor must be buried at least 36 inches, NEC310 Table 300.50 pg157
6
4.86 4.81
4.36
4
0
1 2 3 4 5 6 7 8 9 10 11 12
Month
3.18
2.94
3
2.05
2 1.74
0
1 2 3 4 5 6 7 8 9 10 11 12
Month