Final_Question_2
Final_Question_2
KATHMANDU UNIVERSITY
End Semester Examination
April, 2024
SECTION “A”
[20 Q. * 0.5 = 10 marks]
Choose the most appropriate function
1. Which circuit breaker/s will operate for fault at F in the system given below?
Figure 1.
a) B3, B4
b) B5,B6
c) B4
d) B2, B3, B4, B5
2. A generating station with a step up transformer (Delta-Wye grounded) is connected to a line. The
transmission line has three phase conductors and two over-head ground wires. A ground fault
occurs at one of the phase conductor. The ground current will return to source through
a) Ground
b) Ground and Two Overhead ground wires
c) Healthy phase
d) Ground and One Overhead ground wire
3. Which kind of protection equipment is commonly used in secondary side of a 11kV transformer?
a) Liquid filled fuse
b) MCCB
c) Dropout fuse
d) HRC fuse
4. A current transformer has 5VA, 5P20 written in its name plate. The information it conveys are:
a) Rated burden: 3%, Composite error: 10, Accuracy limiting factor = 10, Metering class CT
b) Rated burden: 10VA, Composite error: 5%, Accuracy limiting factor = 20, Protective class
CT
c) Rated burden: 5VA, Composite error: 5%, Accuracy limiting factor = 20, Protective class CT
d) Rated burden: 10VA, Composite error: 3%, Accuracy limiting factor = 10, Metering class CT
5. An overcurrent relay is to be used for protection of a three-phase line connecting Bus A and Bus B
as shown in Figure 2. What should the value of plug setting/pickup for the relay?
6. Which distance relay provides the best performance under arcing fault?
a) Impedance relay
b) Mho relay
c) Reactance relay
d) Elliptical relay
8. A ground fault occurs at phase c shown in Figure 3. The system phase voltage is 220V. What will
be the rms voltage at phase-a under this fault condition?
a) 0V
b) 220√3𝑉
c) 220√2𝑉
d) 220𝑉
9. The time-current characteristics of two over-current relays installed in a system (Figure 4) is given
in Figure 5. A fault is applied at line connecting Bus B and C resulting in a fault current of 7000A.
Are the relays properly coordinated for this fault?
a) Yes
b) No
c) Voltage transformer information is not provided
d) Current transformer information is not provided
Figure 4. System
11. A lightning arrestor (LA) is to be put in an ungrounded power system of 132kV. What should be
the minimum voltage rating of the LA?
a) 115kV
b) 135kV
c) 200kV
d) 80 kV
12. An Electrical supervisor is given four earthing design results for a generation substation. Which
final design should the supervisor choose?
(a)
Tolerable touch Actual Touch Tolerable step Actual Step Resistance
voltage (V) Voltage (V) voltage (V) Voltage (V) (Ω)
1500 1800 1100 500 1
(b)
Tolerable touch Actual Touch Tolerable step Actual Step Resistance
voltage (V) Voltage (V) voltage (V) Voltage (V) (Ω)
1500 800 1100 500 0.5
(c)
Tolerable touch Actual Touch Tolerable step Actual Step Resistance
voltage (V) Voltage (V) voltage (V) Voltage (V) (Ω)
1500 1000 1100 500 10
(d)
Tolerable touch Actual Touch Tolerable step Actual Step Resistance
voltage (V) Voltage (V) voltage (V) Voltage (V) (Ω)
1500 800 300 500 1
13. Which of the following bus bar scheme is the most reliable?
a) Single bus bar with sectionalization
b) Main and transfer bus scheme
c) Double bus double breaker scheme
d) One and Half breaker scheme
15. What factors should be considered before using differential relay for power transformer protection?
a) Phase shift and Voltage ratio between primary and secondary
b) Phase shift and Current ratio between primary and secondary
c) CT error
d) None of the above
20. 100% stator earth fault relay for generator protection requires:
a) Overcurrent protection
b) Inrush protection
c) Third Harmonic voltage relay
d) Differential protection
Marks Scored:
KATHMANDU UNIVERSITY
End Semester Examination
April, 2024
SECTION “B”
[5 Q * 8 = 40 marks]
Attempt ANY FIVE questions. Each question carries 8 marks. Symbols have their usual meanings. Urgent
appropriate assumptions are permissible. Marks are indicated inside brackets. Some important formulae
and data are given after the questions section.
(b) Describe the working principle, advantages, and disadvantages of a SF6 circuit breaker. [4]
2. (a) Design the differential protection for a three-phase, 50 Hz transformer with the following
nameplate ratings: 50 MVA, 11 kV/132 kV, delta- star. [5]
(b) Draw the transformer connection, wiring diagram of relay and current transformer for Question
2(a). [3]
3. (a) Obtain three zone settings for a mho relay of 80 deg MTA with the impedance diagram
(showing all three zones) using the following data:
CT 200/1A, PT 220kV/110V.
Impedance for the first line is 2+j4 ohms (primary), Impedance for the second line is 2+j4 ohms
(primary) and the impedance for the third line is 2+j4 ohms (primary).
The first zone covers 80% of the first section, the second zone covers the first line and 50% of the
second line and the third zone covers the first and second line and 50% of the third line. [5]
(b) Compare different types of distance protection based on their application and limitations. [3]
5. (a) Develop a detailed single line diagram for a 3MW hydropower generating station with a
11/220kV step-up transformer. [2]
(b) Calculate the size of all equipment’s used for Question 5 (a). [6]
6. Justify the following statements [1*8=8]
(a) Numerical relays allow adaptive protection of power system.
(b) Residual current circuit breaker interrupts power supply in a matter of milli-seconds during
earth fault.
(c) Ground fault currents at lower voltage level can be smaller than the normal rated current.
(d) Ungrounded neutral system is rarely used in the modern power sector.
(e) IDMT relays must be used for proper circuit breaker coordination in a radial
transmission lline.
(f) Transformer protection relay must have third harmonic restraint capability.
(g) Explain the working of a converter substation.
(h) Double bus double breaker has the highest reliability.
Table 1. 11kV cable rating data