TECHNICAL CATALOGUE FOR

C-POWER AIR CIRCUIT BREAKER


Lauritz Knudsen 2
Air Circuit Breakers

Lauritz Knudsen Electrical & Automation Air Circuit Breakers


(ACBs) are specially designed for extreme tropical conditions
and have a proven track record of more than 45 years. Presently
more than 5,00,000 Air Circuit Breakers are being used for
diverse applications. The Air Circuit Breakers provide
technologically driven solutions to meet customer needs.

Complete Selectivity Elegant Design & Rugged Construction

Unique feature of lcu=lcs=lcw for 1 second across the entire › Common door cutout for entire range
range. This ensures complete selectivity for system with time
› Left aligned cutout for all ratings
based discrimination.

Perfect for Indian Conditions Range to Meet Every Customer’s Need

Inherent design to perform in extreme tropical conditions. Various options to choose from
Typical site conditions like high ambient temperature, humidity
› Breaking capacity from 50kA to 100kA
and dusty environment are best handled by ACBs
without compromising on performance and safety. › 3 Pole or 4 Pole configuration
› Fixed or Drawout version
› Auto reset mechanism
Optimal Compactness › Independent manual or stored energy type, manual or
electrically operated mechanism

Designed to ensure › Different terminal orientations : Flat, Horizontal and Vertical

› Low inherent temperature rise


› Adequate interface clearances

Widest Choice of over


Current Protection Releases
› Advance micro-controller based with option of communication
& metering-SR71
› Micro processor based releases-SR18/SR18G/SR18G with
Display and SR18Gi with display & current metering
› Thermo-magnetic release-DN1

Lauritz Knudsen 1
New User Friendly Feature

› Operational Counter will be standard offering from rating


4000A and above

User Friendly Features

› Front accessible over current release settings, telescopic › Extendable Electrical Life:
racking handle and various racking interlocks; no need to
» By replacing the arcing contacts at site, for all ratings
open the panel door
» With changing pole assembly
› Unique ‘Maintenance position’ in drawout type ACBs to
facilitate maintenance & inspection without removing ACB › Programmable SICs: Auxiliary contacts in drawout ACBs are
from the panel programmable for only Service, Only Test, Test and Service,
and All Positions
› Multitap CTs for enhancing protection range in DN1 release
› Protection releases are easily interchangeable at site
› Wide variety of Amperemetric and Voltmetric releases
› Facility for site conversion of manually operated ACBs to
› Fully rated neutral pole for the entire range
electrically operated ACBs
› Lockable sliding shutters to prevent unauthorized access to
› Jaws on breaker facilitate ease of maintenance & replacement
“TRIP” and “CLOSE” push buttons
of contact jaws
› Can be used as an ON / OFF Load Isolator

Safety

› Superior quality engineering grade plastics used for insulation › Variety of Safety Interlocks
purpose; conforms to Glow wire test(Ref: IEC 60695-2-1)
› Easily removable arc chutes without use of any tool
› In-built mechanical anti-pumping to prevent auto-reclosing
› Operating voltage ranges from 10% Un to 110% Un for shunt
of ACB on persisting faults
release ensures intentional tripping even at high voltage
› In-built rating error preventor in drawout ACBs ensure correct drops during short-circuit
rating of drawout portion in corresponding cradle
› Transparent safety shutter offers easy inspection of cradle
› Safety shutters prevent accidental contact with live cradle contacts & reduces the maintenance time
terminals

Conformance to Standards Special Applications

› IEC - 60947 (Part 1 & 2) 690V Application for C-Power ACB


Solution for 690V application available in C-Power Family. For
› IS/IEC - 60947 (Part 1 & 2)
further details please consult our nearest branch office.
› IEC 60695 - 2 - 1
Breakers for Corrosive Environment
› BS EN 60947 - 2 Solution for harsh/corrosive environment available in C-Power
Family. For further details please consult our nearest branch
office.

Lauritz Knudsen 2
Range

Breaking Capacities

Icu = Ics = Icw for 1 sec

Rated Current 400A 630A 800A 1000A 1250A 1600A 2000A 2500A 3200A 4000A 5000A 6300A

CN-CS : E 50kA 50kA 50kA 50kA 50kA 50kA 50kA


Frame-1

CN-CS : S1 50kA 50kA 50kA 50kA 50kA 50kA 50kA 60kA 60kA

Frame-1 Frame-2

CN-CS : C 50kA 50kA 50kA 50kA 55kA 60kA 95kA 95kA

CN-CS : H 65kA 65kA 65kA 65kA 75kA 75kA


75kA 75kA
CN-CS : H2
100kA 100kA
CN-CS : H1/H
Frame-1 Frame-2 Frame-3 Frame-4

Note: 3200A H2 / 4000A H2 will replace 3200A H0 / 4000A H0. Spares for 3200 / 4000 A H0 will be available.

Lauritz Knudsen 3
Technical Data Sheet

400/
Rating (A) 400 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
630

Type Designation E# E# S1 E# S1 C H E# S1 C H E# S1 C H E# S1 C H E# S1 C H S1 C H S1 D H2 H1 H2 H C C C

Rated current (A) at 50°C In 400 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300

Rated operational voltage (V), 50/60Hz Ue *


415 415 415 415 415 415 415 415 415 415 415 415

Rated insulation voltage (V), 50/60Hz Ui 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

No. of poles 3 3 3/4 3 3/4 3 3/4 3 3/4 3 3/4 3 3/4 3/4 3/4 3/4 3/4 3/4

380/415/500V 50 50 50 50 50 50 65 50 50 50 65 50 50 50 65 50 50 50 65 50 50 55 75 60 60 75 60 70 75 100 75 100 70 95 95


Rated ultimate short circuit breaking
Icu
capacity 50/60Hz (kA rms) 690V - - - - - 35 50 - - 35 50 - - 35 50 - - 35 50 - - 40 65 - 40 65 - ∆ 65 85 65 85 ∆ ∆ ∆

380/415/500V 50 50 50 50 50 50 65 50 50 50 65 50 50 50 65 50 50 50 65 50 50 55 75 60 60 75 60 70 75 100 75 100 70 95 95


Rated service short circuit breaking
Ics
capacity 50/60Hz (kA rms) 690V - - - - - 35 50 - - 35 50 - - 35 50 - - 35 50 - - 40 65 - 40 65 - ∆ 65 85 65 85 ∆ ∆ ∆

0.5 sec 50 50 50 50 50 50 65 50 50 50 65 50 50 50 65 50 50 50 65 50 50 55 75 60 60 75 60 70 75 100 75 100 70 95 95


Rated short time
withstand capacity Icw 1 sec 50 50 50 50 50 50 65 50 50 50 65 50 50 50 65 50 50 50 65 50 50 55 75 60 60 75 60 70 75 100 75 100 70 95 95
50/60Hz (kA rms)
3 sec - - 25 - 25 35 50 - 25 35 50 - 25 35 50 - 35 35 50 - 45 50 65 50 55 65 55 ∆ 70 85 70 85 70 ∆ ∆

380/415/500V 105 105 105 105 105 105 143 105 105 105 143 105 105 105 143 105 105 105 143 105 105 121 165 132 132 165 132 154 165 220 165 220 154 209 209
Rated making capacity 50/60Hz (kA
Icm
peak) 690V - - - - - 73.5 105 - - 73.5 105 - - 73.5 105 - - 73.5 105 - - 84 143 - 84 143 - ∆ 143 187 143 187 ∆ ∆ ∆

Rated impulse withstand voltage of


Uimp 8 8 12 8 12 8 12 8 12 8 12 8 12 12 12 12 12 12
main circuit (kV)

Rated impulse withstand voltage of


Uimp 4 4 4 4 4 4 4 4 4 4 4 4
aux. circuit (kV)

Typical opening time (ms) 40 40 40 40 40 40 40 40 40 40 40 40

Typical closing time (ms) 60 60 60 60 60 60 60 60 60 60 60 60

Utilization category B B B B B B B B B B B B

Suitability for isolation            

Fixed                                   

Draw out                                   

Manual                                   

Electrical                                   

Electrical & Mechanical life (operating cycles) ‡ 15000 15000 20000 15000 20000 15000 20000 20000 20000 20000 20000 10000 5000 10000 10000 5000 5000 5000

Electrical life without maintenance 6000 6000 8000 6000 8000 8000 8000 6000 8000 8000 8000 6000 7000 7000 7000 6000 7000 7000 7000 4500 6000 6000 6000 5000 5000 5000 5000 2500 5000 5000 2500 2500 2500

H 385 385 394 385 394 385 394 385 394 385 394 385 - 394 - 394 - 509 ∆ ∆ 509 - -

3 Pole 316 316 326 316 326 316 326 316 326 316 326 316 - 482 - 482 - 636 ∆ ∆ 636 - -
Fixed W
4 Pole - - 414 - 414 - 414 - 414 - 414 - - 628 - 628 - 838 ∆ ∆ 838 - -

D 449 449 443 449 443 431 449 443 431 449 443 431 437 431 437 - 431 - 431 - 518 ∆ ∆ 518 - -
Dimensions (in mm)
H - - 468 - 468 - 468 - 468 - 468 - 468 468 468 468 583 468 468 583 583 583

Draw 3 Pole - - 399 - 399 - 399 - 399 - 399 - 399 555 555 555 711 701 701 711 913 913
W
out 4 Pole - - 487 - 487 - 487 - 487 - 487 - 487 701 701 701 913 909 909 913 1182 1182

D - - 587 - 587 - 587 - 587 - 587 - 587 587 587 612 652 607 607 678 691 691

* Please consult us for application at dc voltages & higher operational voltage ‡ Electrical life = Mechanical life. However, arcing contacts need to be
upto 690V AC. replaced depending upon wear & tear. New H2 range has replaced old HO range
# Available in Control Box version ∆ Please consult us.
5 • Tolerance is +20ms Lauritz Knudsen 4 Lauritz Knudsen 5
Protection Releases

Thermo-magnetic Release Type - DN1

DN1 thermo-magnetic release offers reliable protection against


overload, short-circuit and earth faults via multitap CTs. with
ambient temperature compensation from -5OC to 50OC.

Overload Protection (Phase)


Unique individual phase O/L setting adjustment helps to avoid
the nuisance tripping of ACBs in unbalance load condition (due
to single phase loads) on distribution transformer. Overload
pick-up range: 0.75 to 1 times In
Short-Circuit Protection
Two taps on CTs (working as rating plug) help in selecting
operating threshold. Short-Circuit pickup range: 5.5 and 7.5
times In with minimum impulsion time of 25 ms to prevent
nuisance tripping due to transients
Earth Fault Protection
Offered with auxiliary earth fault release module. Earth-fault
pick-up range: 0.2 to 0.5 times In

Microprocessor Based Release - SR18

Salient Features
› Self-powered & true RMS sensing
› Comprehensive protection
» Overload (Phase), Instantaneous and Short-Circuit
› True Hot & Cold characteristics & switchable thermal memory
› Multi-state LED to indicate
» Power ON condition
» Test mode
› Individual fault annunciation through LEDs
› AN1 module for remote fault indication through LEDs with
changeover contact for each kind of fault
› Provision for Self-diagnostic test (without tripping the breaker)
› Universal Test kit available for testing the release
› Conformance to EMI/EMC standards

Setting Range
Type of Protection
Pick-up Current Time Delay
Ir - 0.5 to 1.0 times In
Overload (Phase) 2.5 sec at 6 times lr
Steps : 0.50, 0.60, 0.65, 0.70, 0.75, 0.80, 0.85, 0.9, 0.95, 1
2 to 10 times In 20 ms to 600 ms
Short-Circuit
Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 Steps : 20, 60, 100, 160, 200, 260 , 300, 400, 500, 600 ms
Instantaneous 6 & 12 In -

Lauritz Knudsen 6
Microprocessor Based Release - SR18G

Salient Features
› Self - powered &True RMS sensing
› True Hot & Cold characteristics & switchable Thermal Memory
› Offers comprehensive protection against Overload - Phase &
Neutral, Short-Circuit, Instantaneous, Earth Fault
› Settable Overload delay
› Settable Instantaneous setting with provision of “OFF”
› I2t ON/OFF for Short-Circuit and Earth Fault protection
› Individual Fault LED indication
› Provision for Self-diagnostic test
› Conformance to EMI/EMC standards
› Testing through Universal Test kit

Setting Range
Type of Protection
Pick-up Current Time Delay

Ir - 0.4 to 1.0 times In 0.2 to 30 sec at 6 times Ir


Overload (Phase)
Steps :0.40, 0.50, 0.60, 0.70, 0.75, 0.80, 0.85, 0.90, 0.95, 1 Steps : 0.2, 0.5, 1, 1.5, 2,3.5, 6, 12, 17, 30 sec

In - 50% to 200% times Ir


Overload (Neutral) Same as Overload (Phase)
Steps : 50%, 100%, 150%, 200%

2 to 10 times In l2t ON = 0.02, 0.1, 0.2, 0.3, 0.4 sec


Short-Circuit
Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 l²t OFF = 0.02, 0.1, 0.2, 0.3, 0.4, sec-

2 to 16 times In
Instantaneous
Steps : 2, 3, 4, 6, 8, 10, 12, 14, 16, OFF

0.2 to 0.6 times In l²t ON = 0.1, 0.2, 0.3, 0.4 sec


Earth fault*
Steps : 0.2, 0.3, 0.4, 0.5, 0.6 l²t OFF = 0.1, 0.2, 0.3, 0.4, 1 sec

*In 3 phase, 4 wire system, Neutral CT is required for earth fault protection

Lauritz Knudsen 7
Microprocessor Based Release - SR18G with display

Salient Features
› Self - powered & True RMS sensing
› True Hot & Cold characteristics & switchable Thermal Memory
› Unique 3 line O-LED display (Organic LED)
› Offers comprehensive protection against Overload - Phase & Neutral, Short-Circuit,
Instantaneous, Earth Fault
› Settable Overload delay
› Settable Instantaneous setting with provision of “OFF”
› I²t ON/OFF for Short-Circuit and Earth Fault protection
› Individual Fault LED indication
› Provision for Self-diagnostic test
› Conformance to EMI/EMC standards
› Testing through Universal Test kit
› Separate version with Zone Selective Interlocking (ZSI) - SR18Gi with display

Setting Range
Type of Protection
Pick-up Current Time Delay

Ir - 0.5 to 1.0 times In 0.2 to 30 sec at 6 times Ir


Overload (Phase)
Steps : 0.50, 0.60, 0.65, 0.70, 0.75, 0.80, 0.85, 0.90, 0.95, 1 Steps : 0.2, 0.5, 1, 1.5, 2, 3.5, 6, 12, 17, 30 sec

IN -50% to 200% times Ir


Overload (Neutral) Same as Overload (Phase)
Steps : 50%, 100%, 150%, 200%
2 to 10 times In l²t ON = 0.02, 0.1, 0.2, 0.3, 0.4 sec
Short-Circuit
Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 l²t OFF = 0.02, 0.1, 0.2, 0.3, 0.4, sec
2 to 16 times In
Instantaneous
Steps : 2, 3, 4, 6, 8, 10, 12, 14, 16, OFF
0.2 to 0.6 times In l²t ON = 0.1, 0.2, 0.3, 0.4 sec
Earth fault*
Steps : 0.2, 0.3, 0.4, 0.5, 0.6 l²t OFF = 0.1, 0.2, 0.3, 0.4, 1 sec

*In 3 phase, 4 wire system, Neutral CT is required for earth fault protection

Lauritz Knudsen 8
Universal Test Kit

Salient Features

› Compatible with following E&A Protection Releases: › ACB test current multiples
» SR protection releases of C-Power ACB family » For O/L, S/C and Inst - 2.5 In to 13 In in steps of 0.05
» UNRS protection releases of U-Power ACB family » For E/F - 0.25 In to 0.70 In in steps of 0.05
» MTX and RC releases of D-Sine MCCB family › MCCB test current multiples
› Operates from 240V AC supply & generates single-phase » For O/L - 2In, 4In, 6In and 8In
voltage test signals » For S/C and Inst - 2.5 In to 13 In in steps of 0.05
› Tests the release for » For E/F - 0.25 In to 0.70 In in steps of 0.05
» Phase fault i.e. for overload, short-circuit, instantaneous › LCD display indicated the trip time (three places after decimal)
and Earth Fault protection

Microprocessor-based Communication-capable Release - SR71

Salient Features
› True RMS sensing
› Offers comprehensive protection for overload, short-circuit, instantaneous,
earth fault and neutral overload
› High resolution backlit LCD display
› Intelligent Pre-trip alarm to prevent system shutdown
› Password protected settings and commands
› MODBUS RTU protocol with intrinsic RS 485 port
› LED indication for POWER ON, different faults and Pre-trip alarm
› 2 sets of storable protection settings
› Last 5 trips & 128 Event records with time & date stamping
› 3 programmable contacts-1 for micro controller failure, 2 for basic fault
annunciation
› 4 relay contacts for indication of exceeding maximum demand,
Pre- trip alarm and control on breaker (closing and opening)
› Rating-plug for precise protection at lower load currents
› Auto-doubling features to prevent nuisance tripping 2
› Selectable I²t based current for short-time and earth fault zones
› Thermal reflectivity enables faster tripping on recurrent overloads
› Inbuilt Zone Selective Interlocking
› Provision for Self-diagnostic test
› Conformance to EMI/EMC standards

Lauritz Knudsen 9
Microprocessor-based Communication-capable Release - SR71

Factory
Parameter Screen Abbreviation Details
Settings

Current Settings (A), Ir = In x .... PICK-UP 0.4 to 1.0 In in steps of 0.05 In 1.0 In

Time Delay, Tr (sec) at 6 x Ir TMS-Tr 0.5-1-2-4-6-12-18-24-30 30 sec


Overload
Pre-trip Alarm Settings PREALAR 0.5 to 0.95 Ir in steps of 0.05 Ir 0.95 Ir
(Phase)
Thermal Reflectivity THM-MEM ON / OFF OFF

Function FUNC Enable / Disable

Current Settings (A), In = Irx .... PICK-UP 0.5-1.0 1.0 Ir


Neutral Fault
Time Delay (sec) DELAY Same as 'Overload (Phase)' 30 sec

Current Settings (A), Isd = In x .... PICK-UP 2 to 10 In in steps of 0.5 In 10 In

l²t OFF DELAY 20-100-200-300-400 400 msec


Time Delay, tsd
(msec) at 10 x In
l²t ON DELAY 20-100-200-300-400 400 msec

Short-Circuit Pre-trip Alarm Settings PREALAR 0.5 to 0.95 Is in steps of 0.05 Is 0.95 Is

l²t l²t ON / OFF

Cold-load Pick-up COLDPIC Enable / Disable Disable

Cold-load Pick-up Delay CP-DLY 0.1 to 10 sec in steps of 0.1 sec 0.1 sec

Function FUNC Enable / Disable Enable


Instantaneous
Current Settings (A), Ii = In x .... PICK-UP 2 to 16 In in steps of 0.1 In 16 In

Function FUNC Enable / Disable Enable

0.1 to 0.6 in steps of 0.05 In for l2t ON 0.6 In


Current Settings (A), Ig = In x .... PICK-UP
0.1 to 0.6 in steps of 0.01 In for l2t OFF

100 to 400 msecs in steps of 100


3 sec
msec for l2t ON
Earth Fault Time Delay (sec), tg DELAY
0.1 to 5 sec in steps of 100 msec for
l2t OFF

Pre-trip Alarm Settings PREALAR 0.5 to 0.95 Ig in steps of 0.05 Ig 0.95 Ig

l²t l²t ON / OFF OFF

Cold-load Pick-up COLDPIC Enable / Disable Disable

Note: Both Protection Groups 1 & 2 carry the same factory settings.

Lauritz Knudsen 10
Additional Protections

Parameter Screen Abbreviation Details Factory Settings


Function FUNC Enable / Disable Disable

Under Current Setting (A) x In PICK-UP 15% to 80% in steps of 5% In 0.8 In


Current Time Delay (secs) DELAY 1 to 255 in steps of 1 second 1 second
Trip / Alarm MODE Either / Both Alarm
Function FUNC Enable / Disable Disable
Current
Current Setting (A) x In PICKUP 10% to 95% in steps of 5% In 0.2 In
Unbalance
Time Delay (secs) DELAY 1 to 10 in steps of 5 secs 2.0 secs
Function FUNC Enable / Disable Disable
Voltage Setting (V) Vs = Vn x .. PICK-UP 105% to 150% in steps of 5% Vn 1.2 Vn
Over
Time Delay (secs) DELAY 0.1 to 100 in steps of 0.1 secs 5.0 secs
Voltage #
Reset Voltage RSTSET 85% to 98% in steps of 1% Vs 0.95 Vs
Trip / Alarm MODE Either / Both Alarm
Function FUNC Enable / Disable Disable
Voltage Setting (V) Vn x .. PICK-UP 45% to 65% in steps of 5% Vn 0.6 Vn
Under
Time Delay (secs) DELAY 0.1 to 5 in steps of 0.1 secs 1 second
Voltage #
Reset Voltage RSTSET 102% to 115% in steps of 1% Vs 1.02 Vs
Trip / Alarm MODE Either / Both Alarm
Function FUNC Enable / Disable Disable
50 to 55Hz for 50Hz in steps of
52.0Hz
0.01Hz
Frequency Setting (Hz) PICK-UP
60 to 62Hz for 60Hz in steps of
Over 61.0Hz
0.01Hz
Frequency #
o.1 to 100 secs in steps of 0.1
Time Delay (secs) DELAY 0.2 secs
second
Drop Off Frequency DRPOFF 0.02 to 0.10Hz in steps of 0.1Hz 0.1Hz
Trip / Alarm MODE Either / Both Alarm
Function FUNC Enable / Disable Disable

Reverse Settings (kW) PICK-UP 0.02 to 0.4 in steps of 0.01 Pn 0.2 Pn


Power # Time Delay (secs) DELAY 1 to 100 in steps of 0.1 secs 2.0 secs
Trip Alarm MODE Either / Both Alarm
Function FUNC Enable / Disable Disable

Phase Settings PICK-UP 123 - 132 123


Sequence # Time Delay (secs) DELAY 0 to 5 in steps of 0.5 secs 2 secs
Trip / Alarm MODE Either / Both Alarm

Breaker Function FUNC Enable / Disable Disable


Failure Time Delay (secs) DELAY 0.05 to 2 secs in steps of 0.01 secs 1.0 second
Function FUNC Enable / Disable Disable
Maximum
Exceed PICK-UP 40 kW - 1600 kW 100 kW
Demand
Step DELAY 10 kW - 1000 kW 10 kW
i-
i -Discrimination Enable / Disable Disable
Discrimination

# Requires SR71-PM module

Lauritz Knudsen 11
Metering

Parameter Screen Abbreviation Details

I Phase, Earth and Neutral

Current Imax Maximum running Current per Phase

%Load Percent Loading

V Phase-Neutral
Voltage#
Vph-Vph Phase-Phase

Frequency # F System Frequency

Power Factor # PF System Power Factor

kW Active Power per Phase and Total (kW)

kVAr Reactive Power per Phase and Total (kVAr)


Power #
kVA Apparent Power per Phase and Total (kVA)

kW Maximum Demand (kW)

kWh Total Active Energy (kWh)

Energy # kVArh Total Reactive Energy (kVArh)

kVAh Total Apparent Energy (kVAh)

I1HAR R-Phase Current Harmonics

Harmonic-Current I2HAR Y-Phase Current Harmonics

I3HAR B-Phase Current Harmonics

V1HAR R-Phase Voltage Harmonics

Harmonic-Voltage # V2HAR Y-Phase Voltage Harmonics

V3HAR B-Phase Voltage Harmonics

Display High Resolution Backlit LCD

# Requires SR71-PM module

Lauritz Knudsen 12
Additional Features

Parameter Screen Abbreviation Details

Auxiliary Power ON P

Overload P

Short-Circuit P

Instantaneous P
LED Indications
Earth Fault P

Neutral Fault P

Trip P

Alarm P

Auxiliary Supply 24V DC

Digital Inputs 4 Nos.

3 Internal + 4 External Relays


Output Relays
240V AC / 5A, 30V DC / 5A (resistive load)

Rating Plug In Multiplier 630-800-1000-1250-2000-3200-5000

Protocol MODBUS RTU


Communication
Link used RS 485

Maintenance Indication I²t based

Pick-up, Alarm, Trip, Date, Time and Cause of Event,


Event Records (128)
voltage and current readings in all phases

Trip Records Last 5 records with date and time stamping,

Testing Self-Diagnostic Test P

Comunication Module (SR71-COM) MODBUS RTU using RS 485

Power Supply Module (UN-PS) Input : 26V to 60V DC, 90 to 300V AC/DC Output : 24V DC
Supplementary Modules
Power Metering Module (SR71-PM) 240V AC, 415V AC

4 Relay Outputs (Breaker OPEN, Breaker CLOSE, Pre


Relay Module (SR71-REL)
Trip alarm and MD Exceed)

No. of Storable Settings 2

Lauritz Knudsen 13
Protection Characteristic

Time-current (DN1) Overload (SR18)

10000 1000

}1.05
1.2
Operating Limits
Thermal

1000

100

100

Zone of Short-Circuit Operation


(M1/M2)
10
Trip Time (s)

Trip Time (s)

10

0.4
0.3
M1
0.2
1
M2
0.1

DN1

25ms

Total Operating Time


Min. Impulsion Time
0.01

0.1
0.71 23 4 5 6 7 8 9 10 20 30 40 50 100 4001 000 11 .2 1.5 23 4 5 6 7 89 10 20

Current Multiples (xIn) Current Multiples (xIr)

Lauritz Knudsen 14
Overload
Short-Circuit (SR18)
(SR18G, SR18G with display/SR18Gi with display)

1 10000

2 10

0.6 0.6
1000
0.5 0.5

0.4 0.4

0.3 0.3 100


0.26

0.2 0.2

Trip Time (s)


10 30s
0.16
17s
12s
Trip Time (s)

6s
0.1 0.1
1 3.5s
2s
1.5s
1s
0.06
0.5s

0.1
0.2s

0.01 trip time ±20%

1 23 4 5 6 7 81 9 0
0.02

Current Multiples (xIn)

0.01
1 23 4 5 6 7 89 10 20 10

Current Multiples (xIn)

Lauritz Knudsen 15
Short-Circuit I²t ON Short-Circuit I²t OFF
(SR18G, SR18G with display/SR18Gi with display) (SR18G, SR18G with display/SR18Gi with display)

10 1

400ms

300ms

1 200ms
Trip Time (s)

Trip Time (s)


400ms 0.1 100ms

300ms

200ms

0.1 100ms

20ms

20ms
0.01 trip time ±40ms
1 10
trip time µ20%
0.01

Current Multiples (xIn) 0 Current Multiples (xIn)

Instantaneous Earth Fault I²t ON


(SR18G, SR18G with display/SR18Gi with display) (SR18G, SR18G with display/SR18Gi with display)

1 10

1
Trip Time (s)

Trip Time (s)

400 ms

300 ms

0.1 200 ms

100 ms

20ms

0.01 trip time +40ms 0.01


trip time ±20%
11 0 100 2 3 45

Current Multiples (xIn) Current Multiples (xIn)

Lauritz Knudsen 16
Earth Fault I²t OFF
(SR18G, SR18G with display/SR18Gi with display)
Overload Curve (SR71)

1 10 000 ,

1000

400ms 100
Trip Time (s)

Trip Time (s)


300ms

10 30 sec
24 sec
18 sec

12 sec
200ms
6 sec
4 sec
1

2 sec
e

1 sec

0.5 sec
Tolerance:
0.1 100ms 0.01 Trip Time: ±20%
trip tim 1.52 3 4 5 69
0.1 1
±40ms
Current Multiples (xIn) Current Multiples (xIn)

Short-Circuit - I²t ON (SR71) Short-Circuit - I²t OFF (SR71)

10,000 10,000

0.6 0.6

1000 1000
1.0 1.0

1.5 1.5

2.0 2.0

100
100 3.0
3.0

4.0

4.0
Trip Time (s)

Trip Time (s)

6.0
6.0
8.0
8.0

9.0 10 9.0
10
10.0
10.0

1
1

0.4
0.4 0.3
0.3
0.2
0.2

0.1 0.1
0.1 0.1

0.02

0.01
0.01 0.05 0.1 1 10 50
0.05 0.11 10 50
Current Multiples (xIn Current Multiples (xIn

Lauritz Knudsen 17
Instantaneous (SR71) Earth Fault - I2t ON (SR71)

10.000 10,000

1000 1000

100 100
Trip Time (s)

Trip Time (s)


10
10

2.0
0.2
0.3
0.4
0.5
3.0
0.6

4.0
1
1 5.0

6.0
0.4s
8.0

10.0

16.0
0.1 0.1s
0.1

0.01
0.8 2.4
0.01 0.05 0.1 1 10 50
0.05 0.11 15 0 0

Current Multiples (xIn) Current Multiples (xIn)

Earth Fault - I2t ON (SR71)

10,000

1000

100
Trip Time (s)

0.2 0.3
0.4
0.5
10 0.6

5.0

1 1.0

0.4s

0.3s

0.2s

0.1 0.1s

0.01
0.05 0.11 10 50

Current Multiples (xIn

Lauritz Knudsen 18
NR Y B

(+24V DC)
1 3 5 AS+ 7 9 11 13 15 E C 81 42 41 J 50 73 70 E

(
(

(
(
(
(

(
(
(
(
(
(
(
(
(
(
(
R
x x x x

CA-1
C11

(
Only for DC
4

(
Electrical
DN1/SR18
SR18G/SR18G+D
anti-pumping
CC NCT MV CP
SR21i/SR71

SR18G+D
F H

Internal Wiring
EA/
EA1

(
ECD

Internal Wiring
81

(
82
Wiring Diagram

(
(

(
(

(
(
(

(
(
(

(
(
(
(
(
(
(
(
(
(
(
(
(

C6
(-24V DC)
@
Load 2 40 6 AS- 8 10 12 14 16 A B D 82 41 42 K 52 55 74 75 71 72 B

Main Protection & Aux Shunt Aux Power Aux Aux Aux Aux Electric U/V Closing Spring Common Separate Shunt Under
Supply
Aux Closing Neutral Electrical
Circuit Control Unit NC Release NC for SR18G NO NC NO NC NO Coil Charging C.T. Release Preventer Charging fault fault trip voltage anti-pumping
with Display Device Indication Indication Indication Indication Indication
Ref no. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

As per order/requirement

The above drawing is for EDO breakers. FCA Limit switch(Shown in breaker reset condition)
1) For MDO/MF versions R Economy Resistor
Ref no. 3, 10, 11 are not applicable C11 Limit switch operates when closing electromagnet is held on
E, B, C, D, A, 15 are applicable only in electrical breakers. C6 ‘Service’ position microswitch for withdrawable circuit breakers
(shown in ‘test’ position)
2) For EF versions
The ref. no. 12, 13, 14, 15, 16, 17, 18, 19, 20, 21 are provided as
per customer requirement. For SR18Gi+D & SR21i release (P&C unit)
SI, SO i discrimination Short circuit i/p & o/p
3) When using AN1 Annunciator Module with SR18G/18Gi (with display releases)
GI, G i discrimination Earth fault i/p & o/p
A) AS+ & AS- always appear after 5,6 nos. of the SIC.
G Earth
B) If 1,2,3,4,5,6 nos. of SICs are not there, AS+ & AS- will appear first.
C) SIC 13 and 14 Nos. are not offered in 3P EDO and 3P MDO standard breakers.

Lauritz Knudsen
19
Accessories

Type Data

Lockable Trip Push


Button (LTPB) Mounted in place of normal trip push button. With this, ACB can be locked in trip
condition. For interlocking, LTPBs are offered in the following combinations:
› 4 different types of keys i.e. AA, BB, CC and DD suitable for 2 I/C & 1 B/C
schemes
› Combination of L, M, N, LM and MN locks, which are suitable for
3 I/C & 2 B/C schemes
› Combination of K, L, M, N, KL, LM and MN locks, which are suitable for
4 I/C & 3 B/C schemes
› Combination of J, K, L, M, N, JK, KL, LM and MN locks, which are
suitable for 5 I/C & 4 B/C schemes

View of the Cradle


Locking in Isolated Position (LIP)The facility of locking the ACB in Isolated
position is available in Drawout
ACBs. This is useful to achieve interlocking between Main & Standby
source. Similar lock is available as LOCK IN ANY POSITION.

Door Interlock
This ensures:
› Unless the panel door is closed, breaker cannot be racked in or out
› Unless the breaker is in Isolated Position, it is not possible to open the
panel door

Door Racking Locking in Racking Interlock


Interlock Interlock ‘Isolated’ This ensures that breaker cannot be racked in/out unless the ACB is in
Position tripped/open condition.

Mechanical Interlock
It is possible to provide “Mechanical Interlock” between two breakers of
the same or different ratings in vertical or horizontal configurations.
Mechanical interlock is available for ACBs upto 4000A by flexible cables
of 2 metres.

Lauritz Knudsen 20
Type Data

C1
Common indication of tripping due to overload, short-circuit and earth faults.
› Provided by micro-switch C1 fitted inside the ACB
› Available as an option in all releases

C2
Separate indication of tripping due to overload, short-circuit and earth faults.
› For release type DN1, this is provided by micro-switch C1
& C2 (C2 fitted inside release)

AN1-Annunciator Module
Remote indication of tripping due to overload, short-circuit and earth faults.
› Can be used with releases type SR18/SR18G/SR21i/SR18G
& SR18Gi with display
› Individual fault indication provided by three separate LEDs for
» Long time faults
» Short time fault/instantaneous fault
» Earth fault
» One potential free contact rated 5A at 230V AC available for each type of fault
› Flush mounting on panel (H-W-D=92mm x 46mm x 105mm)
› Operating voltage: 240V AC

C5
Indication for operation of shunt release or undervoltage release.
› Provided by micro-switch C5 fitted on the shunt release or undervoltage
release

Lauritz Knudsen 21
Type Data Technical Data
Shunt Release › For remote tripping of the Type of
Nominal Power
Operation
breaker Voltage Use consumption
Release Limit
(V) at pick-up
› Shunt release coil is
110 AC 800 VA
short time rated and is 10-130%
disconnected from the circuit EA1 240 AC 800 VA
V
by an auxiliary contact when 415 AC 800 VA
the ACB trips (Refer to wiring 24V DC 32 W
diagram)
48V DC 125 W 65-130%
› Low power consumption EA
110 DC 45 W V
› Two types available: 220 DC 30 W
» EA for DC application
» EA1 for AC application Note: Other voltages available on request

Under Voltage Release › Type MV With no intentional Parameter Specification


time delay Nominal voltage 240V & 415V 50Hz AC,
220V & 415V 60Hz AC,
& 24V DC
Notes: When under voltage
release is provided, the ACB can Pick up (V) 80% Ue
be closed only when supply is Drop off (V) 35-65% Ue
available to the under voltage VA Consumption Pick up - 23 VA
release. Hold on - 8.5 VA
Watt loss 6W

Closing Release Closing release remotely Rated voltage


Power consumption
Range of
closes the circuit breaker if the (Us) operation
mechanism spring is already Pick-up Hold-on
charged. 110V, 50Hz
240V, 50Hz 320 VA 50 VA
220V, 60Hz 85-110%
Us
110V DC,
220V DC
300 W 50 W
24V, 30V,
48V DC

Spring Charging Motor Electrical charging device Rated operational


Power consumption Range of operation
automatically charges the voltage (Ue)
mechanism spring of the 240V AC 320 VA
circuitbreaker. After circuit- 110V DC 154 W 85-110% Ue
breaker closing, the geared
motor immediately recharges 220V DC
the closing spring. Thus
instantaneous reclosing of
the circuit-breaker is possible
following opening operation.

Auxiliary Contacts Two combinations available: Electrical Voltage Rated current


› 2 NO + 2 NC circuit (V) (A)
› 6 NO + 6 NC 24 to 415 AC 16
Resistive
250V DC 1.2
24 to 415 AC 16
Nonresistive
250V DC 1.0 #

# L/R = 15 ms with 2NO or 2NC contacts in series

Lauritz Knudsen 22
OVERALL DIMENSIONS

Fixed Breakers

For 800A to 2500A 3P/4P C/H & 400A to 1600A 3P/4P S1


for Metallic Components

To Remove
340 min Arc Chute
for Insulating Sheet
7

200 min

140 min
36 min A 36 min Door

100 min
20 min Bezel
9

27
26 58 264 26

16
385
394

33

256
4 Hole- Ø12
309

for Mounting
(21)

22
104

68.8
16 16 27
216
Earthing Terminal 30 35
230
20 301 54
2 Holes-Ø6.3 2.6 min
405 86 10

DE E F D
Dimensions (mm)
Ratings CN - CS
A D E F
400/630A S1 3P
800/1000A C/H/S1 3P 326 57 102 -
1250/1600A C/H/S1 3P

400/630A S1 4P
800/1000A C/H/S1 4P 414 56 98 98
1250/1600A C/H/S1 4P
2000/2500A C/H 3P 482 83 154 -
2000/2500A C/H 4P 628 82 150 156

For CN-CS...E 400A-2000A 3P

340 min
Insulator

40 min4 316
+1.0
0 min 20 min
100 min

58 102 102 56 30 min


Z

Rating Type X Y Z
X 400E -1250E 5 150 35.5
1600E 10 145 23.5
385

4 Holes
325
285

Ø12 X
2000E 15 140 23.5
227

216
32

20 20
298
22 137.5
402 21
179.5

Note: All Dimensions are in mm.

Lauritz Knudsen 23
Fixed Breakers

Terminal Terminal Connections


35.5 35.5 23.5 # 23.5

2 Holes-Ø13
3 Holes-Ø13 5 8 10 15
30

15

5 10
30

8 15

15
12.5

227

227
227

227
25 25 25 25 25

150

145

140
147
50 100

400 to 2000E, 800/1000/ 2000/2500C/H Terminal for Terminal for Terminal for 800 C, Terminal for 1600 S1
1250/1600C/H & 400/630 S1 800/1000 S1 1000 C &1250 S1 800/1000 H, 1250/
400/630/800/1000 # 35.5 : For 1250S1 1600 C/H,
/1250/1600S1 2000/2500 C/H

Bezel Fixing Plan for all Fixed Breakers


305
12 Holes-Ø4 101 332
Hinge Hinge
112

Note:
325

A = 89 for 4000C/3200D
363
112

A = 91 for other fixed ACBs


A

112

5.5

11 min 59 294 15 min

Door Drilling for Bezel


Bezel Fixing Plan

For 3200D/4000C 3P/4P for Metallic Components


to Remove
16min 356 min Arc Chute
For Insulating Sheet
200min

B
140min
100min

7
26 58 264 Door
Bezel
27

71

Door Cutout
503

25
509
394

256
309

22
27

68.8

33
Earthing Terminal
21

230 2.6min
16 2 Holes-ø6.3 20 54
27 140
444 85 10
36 min 36 min

4 A 4 6 Holes-ø14
D E E F D
30
26 26
15
70

Terminal
71 Connections 30 50 50
15 160

15 For 3200D/4000C
287
173.5
102

Dimensions (mm)
16 Terminal for 3200D / 4000C Rating CN-CS
16
4 Holes-Ø12 for Mounting A B C E F
Rear View
3200D/4000A C 3P 628 636 112 202 -
3200D/4000A C 4P 830 838 112 202 202

Note: All Dimensions are in mm.

Lauritz Knudsen 24
Drawout Breakers

For 800A to 2500A C/H, 3200A H2/H1, 4000A H2/H, 400A to 3200A S1 3P/4P
for Metallic Components
75 Isolated Position

A 380 min
for Insulating Sheet 51 Test Position

200 min
122
94.5 264 40 max Service Position 7
Door

100
min
64.5 Bezel

26

256
468

397.5
404

M 10

160
46 28
4 74
6

68.8
(10) 54
17.5 min.
20
199.5 6 18.9 max.
538 18 245
8.9 min.

Earthing Terminal
DE FE D
40 40 65 60
64.5
5 5 25 15
10 15 15
308.5

308.5
308.5

308.5
221.5

221.5

221.5

221.5
Terminal for Terminal for Terminal for Terminal for
400/630/800/1000/1250 1250/1600/2500C/H for 3200S1 3200H2/H1
S1 & 800/1000C, 2000C, & 800/1000/2000H, & 4000H2/H
2500S1 1600/2000S1

Dimensions (mm)
Ratings CN - CS
A D E F
400/630/800/1000A C/H/S1 3P
2000A S1 3P 399 97.5 102 -
1250/1600A C/H/S1 3P
400/630/800/1000A C/H/S1 4P
2000A S1 4P 487 96.5 98 98
1250/1600A C/H/S1 4P
2000/2500A C/H 3P
555 123.5 154 -
2500/3200A S1 3P
2000/2500A C/H 4P
701 122.5 150 156
2500/3200A S1 4P
3200A H2/H1 3P
701 148.5 202 -
4000A H2/H 3P
3200A H2/H1 4P
909 151.5 202 202
4000A H2/H 4P

Note: All Dimensions are in mm.

Lauritz Knudsen 25
Drawout Breakers

Flat Terminal Connections


63
50 100
25
25 30 30
19
12.5 10.2 20
10.2 10.2
4 slots 4 Slots 6 Slots

58.4

58.4
8.5 x 9.5

58.4
8.5 x 9.5

38
8.5 x 9.5

38
38
8.5 8.5 8.5

800 - 1000C & 400 - 1250S1 800 - 1000H, 1250/1600C/H & 1600 - 2000S1 2000C
160
106 106 106
33 33 25 25 25 25 25 6 Holes-Ø14
33 33 33 33
17.5
20 20 20
12 12 12

6 Holes-Ø14 6 Holes-Ø14

70
50
67

25
67
43

43
62
38

12.5
6 Holes- Ø14

2500C/H & 2000H 2500S1 3200S1 3200H2/H1 & 4000H2/H

For 3200D/4000/5000/6300C 3P/4P


A For Metallic Components 160
124
25 25 25 25 25
96.5 264 6 Holes-Ø14
400min 17.5
75 Isolated Position
for Insulating Sheet
51 Test Position
200min

40max
100min

Service Position

50

25
102
Terminal for 3200D
28
5

12.5
404

26

Terminal Connections
4000C
6
467

199.5
368

M 10
256

160

FRONT VIEW
(74)

8 Holes-Ø14
28

D E E E D
5

10
20

5 17.5min 217
18.9max
1 615 8.9min

18 245 28 63
583

17.5
SIDE VIEW
40 50 40 43.5

42 Terminal Connections
5000C/6300C

64.5 Earthing Terminal 54 67


7
REAR VIEW Door
Bezel 15 15

160
60 60
Dimensions (mm)
Rating CN-CS 20
A D E 12
256

368

368

6 Holes-
Ø14
3200D/4000C 3P 711 155.5 200
256

256
46
70

3200D/4000C 4P 913 156.5 200


68.8

5000A/6300A 3P 913 187.5 269 10 54


Terminal Connections Terminal for Terminal for
5000A/6300A 4P 1182 187.5 269 3200D 4000A C 5000/6300A C

Note: All Dimensions are in mm.

Lauritz Knudsen 26
Overall Dimensions

Mounting Details

For Horizontal Mounting of all Draw-out Breakers


For 400A to 3200A C/H/ S1 3P/4P 3200 H2/H1, 4000 H2/H 3P/4P

107.5 367.5 40 10 Holes-Ø11


Ratings Type G (mm)
24
800A - 1600A 3P C/H 280.3
400A - 2000A 3P S1 280.3
800A - 1600A 4P C/H 368.3
400A - 2000A 4P S1 368.3
Front 2000 / 2500A 3P C/H 436.3
*G

2000 / 2500A 4P C/H 582.3


2500 / 3200A 3P S1 436.3

24 2500 / 3200A 4P S1 582.3


64.1 3200A 3P H2 / H1 582.3

37
3200A 4P H2/ H1 790.3
20 481
4000A 3P H2/ H 582.3
For 3200D/4000C/5000C/6300C 3P/4P
4000A 4P H2 / H 790.3
592
10 Holes-Ø11
552
25

Dimensions
Ratings CN-CS
A
3200D/4000C 711
A

3200D/4000C 913
5000C/6300C 913
5000C/6300C 1182
25

50
108.5
184.5

Bezel Fixing Plan for all Draw-out Breakers


6 Holes-Ø4 305 332

Hinge Hinge
224
412

450
199

1 5.5
Base of
Cradle

20.5 min A 294 5 min

Door Cutout Door Drilling Bezel


for Bezel Fixing Plan

Note: For 3200A D 3P/4P, 4000A C 3P/4P, 5000C/6300C 3P/4P ACB, A=81.5
Note: All Dimensions are in mm. For other Drawout Breakers A=79.5

Lauritz Knudsen 27
Terminals

Horizontal Terminals
Rear Side
80 80 80 80 110
10

10
15

15

15
308.5

221.5
800 - 1000C 1250 - 1600C/H 2000C 2500C/H 3200 H0/H1/H2
& 800/1000H & 2000H & 4000 H0/H/H2

6 Holes-Ø14
2 Holes-Ø14 3 Holes-Ø144 Holes-Ø146 Holes-Ø14
12.5

20
12.5

16.5

25 25 25 25 25
15

25 25 25

33 33
106
100

160
50

63
25

16.5

12.5 25 12.5 30
12.5 25 12 43

17.5
12.5 25

Vertical Terminals
V S W
U 40

4 HolesT
-Ø O P

R
M N
387.5
X

308.5
221.5

Top

SIDE VIEW REAR VIEW

Ratings M N P Q R S T U V W X
400-1250 S1 & 800-1000 C 10.2 38 20 25 29.2 5 9 65 95 10 58.4
1600-2000 S1 & 1250-1600 C/H
20 40 20 25 29.2 5 9 65 95 10 80
800-1000 H
2000 C 20 40 20 40 29.2 22.5 14 80 110 15 80
2500 S1/ C/H
20 40 20 40 33.5 7.5 14 80 110 15 80
2000 H
3200 S1 30 60 20 40 33.5 7.5 14 80 110 15 120

Note: 1) All Dimensions are in mm. 2) Consult us for other Terminal Orientations.

Lauritz Knudsen 28
Terminals

Vertical Terminals 3200 H2/H1, 4000 H2/H


V S W
U 60.0

6 Holes - ØT Q P Top

R
M NN
387.5
X

308.5
221.5

Side View Rear View

The dimensions for 3200 H2/H1 and 4000 H2/H are as under:

Ratings M N P Q R S T U V W X
3200 H2/H1, 4000A H2/H 30 50 45 40 22.5 95 14 105 135 15 160

Lauritz Knudsen 29
Notes

Lauritz Knudsen 30
Switchgear Training Centres

Pune Lucknow Delhi


Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation
Switchgear Training Centre Switchgear Training Centre Switchgear Training Centre
T-156 / 157, MIDC, C-6 & 7, UPSIDC, A-25, Imperia Complex, First Floor
Bhosari, Pune - 411 026 P. O. Sarojininagar, Mohan Cooperative Industrial Estate
Tel: 020-2712 0037 / 2712 0653 Lucknow - 226 008 Near Sarita Vihar / Mohan Estate Metr o Station
E-mail: STC -PUNE@LK -EA.com Tel: 97944 54455 Main Mathura Road, New Delhi - 110044
E-mail: STC -L [email protected] Tel: 9899020306 / 9720186726 / 9560845094
E-mail: STC -DELHI@LK -EA.com

Kolkata Vadodara Coonor


Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation
Switchgear Training Centre, Switchgear Training Centre Switchgear Training Centre
2nd Floor, Block BN3, Sector V, Behind L&T Knowledge City, Ooty-Coonoor Main Road
Salt Lake City, Near Village Ankhol, Yellanahalli P.O.,
Kolkata - 700091, W est Bengal Vadodara - 390019 The Nilgiris - 643 243
Tel: 7738717893 / 7797795567 Tel: 0265 6147805 / 6147808 Tel: 0423 251 7107
E-mail: STC -K [email protected] E-mail: STC -V [email protected] E-mail: STC -COONOOR@LK -EA.com

Customer Interaction Center (CIC)


Phone no: 022 6932 7800
Web: www.LK-EA.com | e-mail: CIC@LK -EA.com
Electrical Standard
Products (ESP) Offices
HEAD OFFICE

Lauritz Knudsen Electrical & Automation, A/600, Shil-Mahape Road, TTC Industrial Area, MIDC Thane, Navi Mumbai, 400 710, Maharashtra.
Tel: 022-6722 6300 | Fax: 022-6705 1112 | e-mail: [email protected]

BRANCH OFFICES

Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation
C-201, The First Commercial Complex, Shri Daneshwari, 1st Floor, No.10, Fortuna Towers, 2nd Floor, A06/A07, Second Floor,
B/S Keshavbaug Party Plot, Vastrapur, Plot No. 17, 2nd Cross, Near Old Income Rana Pratap Marg, Near NBRI, Grand Chandra Complex, Frazer Road
Ahmedabad - 380 015 Tax Office Road, Vidyanagar, Lucknow - 226 001 Patna - 800 001
Phone No: 022-6932 7800 Hubballi - 580 021 Phone No: 022-6932 7800 Phone No: 022-6932 7800
e-mail: [email protected] Phone No: 022-6932 7800 e-mail: [email protected] e-mail: [email protected]
e-mail: [email protected]

Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation
Wework Central, #36 Infantry Road, AWFIS Space Solutions, Prestige Phoenix, El Dorado Building, 3rd Floor, 6, UrbanWrk, 5th Floor, Sai Radhe,
Bengaluru - 560 001 4th floor, 1405, Umanagar, Begumpet, Venkatraman Street, Chinna Chokkikulam, Raja Bahadur Mill Road, Behind Hotel
Phone No: 022-6932 7800 Hyderabad - 500 016 Madurai - 625 002 Grand Sheraton, Sangamwadi
e-mail: [email protected] Phone No: 022-6932 7800 Phone No: 022-6932 7800 Pune - 411 001
e-mail: [email protected] e-mail: [email protected] Phone No: 022-6932 7800
e-mail: [email protected]

Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation
Under O Launchpad, 4th Floor, Workie, 214 - 2nd Floor, Bestech Business Park, Office No. 211 & 212, Pithalia Plaza,
Unit-434, Esplanade 1, Rasulgarh, Apollo Premier, PU-4, Tower - A, 2nd floor, Sector - 66 KK Road, Near Fafadih Chowk,
Bhubaneswar - 751 010 Scheme No. 54, Vijay Nagar Square, Mohali - 160059 Raipur - 492 001
Phone No: 022-6932 7800 Indore - 452 010 Phone No: 022-6932 7800 Phone No: 022-6932 7800
e-mail: [email protected] Phone No: 022-6932 7800 e-mail: [email protected] e-mail: [email protected]
e-mail: [email protected]

Lauritz Knudsen Electrical & Automation, Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation,
801 Word Level-8, No. 28, Office No. 430, 4th Floor, TC II, Tower B, PRIMA BAY Gate No. 5, DevX 4th Floor, A Wing, Om 9 Square,
SIDCO Industrial Estate, Guindy, Jaipur Electronic Market, Riddhi Siddhi, Saki Vihar Road Powai, 150 Ft Ring Road, Near Nana Mava Circle,
Chennai - 600 032 Gopalpura Bypass, Mumbai - 400 072 Opp Silver Heights,
Phone No: 022-6932 7800 Jaipur - 302 018 Phone No: 022-6932 7800 Rajkot - 360 001
e-mail: [email protected] Phone No: 022-6932 7800 e-mail: [email protected] Phone No: 022-6932 7800
e-mail: [email protected] e-mail: [email protected]

Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation
Playworkz Coworking Space GDR Siddha, Ground Floor, N Road Unnati Building, 2nd Floor, 10th Floor, Titaanium Business,
43 & 44, 3rd Cross, Bistupur, Opposite St. Mary's Church, Automation Campus, A-600, TTC Industrial Bhimrad Road, Althan
Bharathy Colony, Peelamedu, Jamshedpur - 831 001 Area Shil-Mahape Road, Mahape, Surat - 395 017
Coimbatore - 641 004 Phone No: 022-6932 7800 Navi Mumbai - 400 710 Phone No: 022-6932 7800
Phone No: 022-6932 7800 e-mail: [email protected] Phone No: 022-6932 7800 e-mail: [email protected]
e-mail: [email protected] e-mail: [email protected]

Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation
3rd Floor, 1&2 Vijay Park, Business Communication Centre M1 & M2, Mezzanine Floor, 11th Floor, Block-D, Notus IT Park,
Main Chakrata Road, Opp. Anandam, 2nd Floor, Chiramel Chambers, Himalaya Excellency, Sarabhai Campus, Bhailal Amin Marg,
Near Ballupur chowk, Kurisupally Road, Ravipuram, Plot No. C-47, Pratap Nagar Square, Vadodara - 390 023
Dehradun - 248 001 Kochi - 682 015 Nagpur - 440 022 Phone No: 022-6932 7800
Phone No: 022-6932 7800 Phone No: 022-6932 7800 Phone No: 022-6932 7800 e-mail: [email protected]
e-mail: [email protected] e-mail: [email protected] e-mail: [email protected]

Lauritz Knudsen Electrical & Automation Lauritz & Knudsen Electrical & Automation, Lauritz Knudsen Electrical & Automation, Lauritz Knudsen Electrical & Automation
Ground Floor, B-27, 207, 2nd floor, Revolution Complex, 3rd floor, Naga Chambers, 3rd Floor, D/No. 12-1-16,
Biplab Rashbihari Sarani, Station Road, E Ward, Uttam Tower by Viraj Estate , Plot No. 49, Survey No. 1051, Waltair Main Road,
Sector 2A, Bidhan Nagar, Next to Pedestrian Bridge, Sharanpur Road, Visakhapatnam - 530 002
Durgapur - 713 212 Kolhapur - 416 001 Nasik - 422 002 Phone No: 022-6932 7800
Phone No: 022-6932 7800 Phone No: 022-6932 7800 Phone No: 022-6932 7800 e-mail: [email protected]
e-mail: [email protected] e-mail: [email protected] e-mail: [email protected]

Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation Lauritz Knudsen Electrical & Automation
6th Floor, Exotica Greens, A Block, 191, 2nd Floor, BN3, Salt Lake, Sector-V, A-25, 1st Floor, Imperia Complex,
R G Baruah Road, Guwahati Central, Kolkata - 700 091 Mohan Corporative Industrial Estate,
Guwahati - 781 005 Phone No: 022-6932 7800 Near Sarita Vihar Metro Station,
Phone No: 022-6932 7800 e-mail: [email protected] Mathura Road,
e-mail: [email protected] New Delhi - 110 044
Phone no: 022-6932 7800
e-mail: [email protected]

Product improvement is a continuous process. For the latest information and special application,
please contact any of our offices listed here. Product photographs shown for representative purpose only.

Lauritz Knudsen Electrical & Automation, Electrical Standard Product


A/600, Shil-Mahape Road, TTC Industrial Area, MIDC Thane, Navi Mumbai, 400 710,
Maharashtra, Phone No: 022-6722 6300 | Web: www.LK-EA.com

Customer Interaction Center (CIC)


Phone no: 022-6932 7800
Web: www.LK-EA.com | e-mail: [email protected]