Factorytalk View SE Local Network to Network Distributed
Factorytalk View SE Local Network to Network Distributed
Support Center Get Support Training & Webinars O nline For um My TechConnect wqs_19@yah…
As k a q ues tion... AD
DDD TTO
O F
FAAV
VOOR
RIITTE
ESS
S
SEEA
ARRC
CHH
Summary
Converting a Factorytalk View SE Local / Network Station to a Network Distributed
application
Question
Below are the steps necessary to convert a FactoryTalk View SE L ocal / Network Station to
a Network Distributed SE project. Before starting, please review the 32549 - FactoryTalk
View SE Distributed System Design Considerations and 909024 - FactoryTalk View Site
Edition (SE) Tips and B est Practices T OC .
Answer
Detailed instructions follow: Top
In order to convert a Local / Network Station project to Network Distributed, we first need
a copy of the project itself that we can use to import into the HMI. For our purposes here,
the project that we will use for this will be called "LocalHMI"
(Note: If you are using version 5.0 or lower, please see article 30310 - Backup and Restor e
Utility for RSView 4.0 or FactoryTalk View 5.0 HMI Server for the back up utility. Also r efer to
article 450509 - FactoryTalk View: Legacy Tag Database Conversion Tool for tag database
conversion as well if you are moving to a 64-bit operating system.)
These are the steps to make a backup for Windows 7/Windows Server 2008:
1. Go to ClickStart->AlPrograms->RockwelS oftware->FactorytalkView->Tools-
->HMIServerbackupandrestore.
For Windows 8 /Server 2012, you will go to the Windows Tile screen, click the
magnifying glass in the top right corner and search for "HMIServer"without the
quotes:
2. Once the backup utility opens, you will see the following window, choose "Backup
HMIServer".
3. The following window will then present y ou with a source and destination. Next to the
Sourcesection, click Browse.
4. Once the next windows opens, it should take you right to the HMIProjectsfolder. If it
does not, the folder names are listed below:
For Windows 7/8 & Windows Server 2008/2012, the folder location is:
6. Once the source .SEDfile is chosen, we now need to set the destination folder w hich
for our purposes will be the Desktopfor ease of locating this backup once the import
begins.
7. Then, once the destination folder is set to the Desktop, place a check in the box that
reads ExcludeDatalogFileSetsand click StartBackup. The purpose of this is that if
you have a ton of data logging data, it could cause this utility to take quite some time
to copy and give the impression like it is locked up. The datalog files are not
necessary to do a conversion and if need be, can be copied after the conversion is
done.
8. You should now have a folder on your desktop that matches the name of the HMI
server we backed up.
2. Once Studio is open, you will select NetworkDistributedas the application type.
3. Once the new window appears, enter a name for this new NetworkDistributed
project and click Continue.
4. Once the project is created, this w ould be the time to r emak e any ar eas you might
have had, you can do this by right clicking on the project name at the top of the
explorer tree on the left side of Studio.
5. Give the area a name and say ok. Now it is time to add the HMI server. If you have
areas, then you will right click on that area for the HMI server and go to AddNew
Serverand choose HMIServer.
6. On the following window, the HMI server wizard appears. You will choose Importa
project.
7. The following window is just a warning about RSLinx Enterprise and some legacy
apps, just click OKon this and it moves to the next window.
8. On the following window, you will choose a project type, w hich will be Factory talk
View Site Edition Pr oject (*.SED).
9. On the following window, you will choose which file to import. We will be dir ecting
this to the backup folder we made in the Step 6 of the back up procedure.
10. Once the backup folder is located, br owse into it and choose the pr oject.sed file and
click OK .
11. Once the project is selected and Open is clicked, verify that the project ty pe and .SED
file are the correct names.
12. After you click Next, you will be required to provide a new name for this HMI server.
Be sure this is a unique name and one not already in use. For our pur poses, I have
named this project "Netw orkH MI"
The import process will then begin and once done, y ou should see the Explorer Tr ee on the
left populate with the displays and all other components. Once that is done, try opening a
display for editing and check to ensur e all your components are there. If so, you have
successfully imported this Local / Network Station project into a Netw ork Distributed
project and can now setup a client to connect to it. However, if you use Factorytalk Alar ms
and Events, then you will need to go back to the source system and obtain an XL S export
of the alarms to import into this new pr oject.
3. The next window will just be verifying that y ou have chosen messages and the proper
language. Take the defaults if you are not sure, this will just ensure that the language
will stay what the source has setup and all messages w ill come over.
Note:Languagescanvary,fourourpurposes,wewilluseEnglish(UnitedStates).
4. We will then need to provide a name for the XLS file we are creating and location to
save it. Like the HMI Server backup pr ocedure earlier in this document, we will save
this to the desktop.
5. Once you click Finish, it will then create a .XLS file on the desktop. Take this over to
the system with the new Network Distributed project either with flash drive, over the
network or whatever method is best suited for you. It doesn’t matter how you get the
XLS file to the new system, just as long as we can access without using a network
location like mapped network drive or UNC path name (e.g. \\servername\c$).
Generally, UNC and mapped drives don’t really give problems when importing but it
can, so for this reason you will want to copy it to the local hard drive of the system it is
being imported to. Once the file is there, we are going to repeat Step 1 in this process,
except this time we will choose to import an Excel file rather than export. Rightclick
on the FactorytalkAlarmsandEventserver icon in the explorer tree on the left and choose
ImportandExport.
6. SelectImportalarmconfigurationfromExcelFileandclick Next.
7. The next window will request the file being impor ted. Br owse to the XL S file we made
in steps 1 through 5 and click Next.
8. The next window will ask you whether you want to update existing alarms or import
only new, etc. However, since this is a newly created server, it has no alarms in it yet.
Leave this option on Updateexistingalarmdefinitionsandcreatenewalarm
definitionsfromtheimportfile.
9. If alarms completed the import successfully, you will see the following message:
Import completed successfully
This concludes the Alarm and Event Impor t procedure. Howev er, there is no data server
configured yet and importing the HMI will not r e-create that with the shortcuts
automatically. Because of this, y ou will need to re-create the RSLinx Enterprise or any
other OPC server connections manually. For RSLinx Enterprise, w e simply need to re-
create the data server and re-add the shor tcuts.
1. First, right click your project name from the explorer tree on the top left side. (Same
procedure as what we did from Step 1 of the alarm import procedure).
2. The RSLinx Enterprise proper ties window appears, y ou can take the defaults if you
are not sure what to select but if this data server is meant to run on a separate PC
that the HMI, then specify the system name in the provided area.
3. Click OKto add the RSLinx Enterprise server. You should now see this icon in the
explorer tree on the left. Click the plus sign next to it and you will see Communication
Setup. This is where you need to reconfigure your shor tcuts to the PLC. You will need
to make sure that these shortcut names mimic w hat they were called on the previous
project or the tags addresses won’t evaluate to the right tag addresses properly.
T h is s t u d y s o u r c e w a s d o w n lo a d e d b y 1 0 0 0 0 0 8 0 4 6 1 9 1 6 4
fr o m C o u r s e H e r o . c o m o n 0 5 - 0 3 - 2 0 2 3 0 0 :3 1 : 2 3 G M T - 0 5 :0 0
https://ww w.courseher o.com/file/ 87597428/ Converting-a- Factor ytal k-View- SE-Local-Netw ork- Stati on-to-a-Netw ork-Distri buted-a ppl icationpdf/
This concludes the addition of re-adding the RSLinx Enterprise setup and shor tcuts.
At this point, your project should be conv erted and it will be a matter of changing the CLI
client connecting to this new project.
RA
ATTE
E CO
ONNTTE
ENNTT
Related Answers
Recently V iewed
FactoryTalk View SE : change a FactoryTalk View SE Client Wizard FactoryTalk View SE: Using Newer
Local Station to a SE Networked Client Software With Older
shows no Applications
Station Application
DISCLAIMER
This k nowl edge bas e web site is intended to pr ovi de gener al technical inf orm ation on a particular subj ect or subj ects and is not an ex haustive treatment of suc h subj ects.
Accordingly, the inf ormation in this web site is not intended to constitute application, design, sof twar e or ot her pr of essional engineering advice or ser vices. Bef ore making any
decision or taking any action, w hic h might af f ect your equipm ent, y ou should cons ult a qualified pr of essional advisor.
RO CKWELL AUTO MATIO N DO ES NO T WARRA NT T HE CO MPL ET ENESS, TIMELI NESS O R ACCURACY O F ANY O F THE DA TA CO NTAI NED IN THI S W EB SIT E A ND MAY MAKE C HA NGES
THERETO AT ANY TIME IN ITS SO LE DISC RETIO N WIT HO UT NO TIC E. FURT HER, ALL INFO RMATIO N CO NV EY ED HEREBY IS PRO VIDED TO USERS "AS IS. " IN NO EVENT SHALL
RO CKWELL BE LIABLE FO R ANY DAM AGES O F ANY KIND INCL UDI NG DI RECT, INDI RECT, INCI DENTA L, CO NSEQ UENTIA L, LO SS PRO FIT O R DAMAGE, EV EN IF RO CK W ELL
AUTO MATIO N HA VE BEEN ADVISED O N THE PO SSIBILITY O F SUC H DAMA GES.
RO CKWELL AUTO MATIO N DISCL AIMS ALL W ARRA NTI ES W HET HER EX PRESSED O R IMPLIED I N RESPECT O F THE INFO RMA TIO N (INCL UDI NG SO FTWA RE) PRO VI DED HEREBY ,
INCL UDI NG T HE IMPLI ED WARRA NTI ES O F FITNESS FO R A PARTIC ULA R PURPO SE, MERC HA NT ABILITY, AND NO N-INFRI NGEM ENT. Note that certain jurisdictions do not
countenance the excl usion of implied w arranties; thus, this disclaimer may not apply to you.