0% found this document useful (0 votes)
58 views4 pages

RCD Application Inverter Au

The document outlines the application of Residual Current Devices (RCD) in HUAWEI's SUN2000 series solar inverters for the Australian market. It specifies the inverter models and their compatibility with RCD type A limits, detailing the required protection limits according to IEC 62109-2: 2011. The document emphasizes that the integrated Residual Current Monitoring Unit (RCMU) in the inverters prevents direct residual current feed into the grid.

Uploaded by

nachofp.alq
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
58 views4 pages

RCD Application Inverter Au

The document outlines the application of Residual Current Devices (RCD) in HUAWEI's SUN2000 series solar inverters for the Australian market. It specifies the inverter models and their compatibility with RCD type A limits, detailing the required protection limits according to IEC 62109-2: 2011. The document emphasizes that the integrated Residual Current Monitoring Unit (RCMU) in the inverters prevents direct residual current feed into the grid.

Uploaded by

nachofp.alq
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Doc.

Code

RCD Application in HUAWEI Solar Inverter for


Australia

Issue 01

Date 2020-06-22

HUAWEI TECHNOLOGIES CO., LTD.


Product Description

Copyright © Huawei Technologies Co., Ltd. 2013. All rights reserved.


No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions


and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.

All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees
or representations of any kind, either express or implied.

The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base

Bantian, Longgang

Shenzhen 518129

People's Republic of China

Website: http://enterprise.huawei.com
Product Description

RCD Application in HUAWEI Solar Inverter for Australia

Manufacture Name: HUAWEI Technologies Co.,Ltd


Address: HUAWEI Industrial Base, Bantian, Longgang District, 518129, Shenzhen, China
Product Description: SUN2000 Series Inverter
Inverter Model: SUN2000L-2/3/4/4.6/5KTL,
SUN2000-2/3/4/4.6/5/6KTL-L1,
SUN2000-5/6KTL-M0,
SUN2000-5/6KTL-M1,
SUN2000-8/10/12/15/17/20KTL-M0,
SUN2000-8/10/12/15/17/20KTL-M2
SUN2000-29.9/36KTL,
SUN2000-50KTL-M0,
SUN2000-100KTL-M1
According to IEC 62109-2: 2011, a residual current monitoring unit (RCMU) is required for
inverters without simple separation between the grid and the photovoltaic generator. The
SUN2000 series inverters have such an integrated RCMU. Due to the inverters’ circuit
design, they can’t feed in direct residual current into the grid.
If the standard take as a basis for the building of PV system or the grid company requests
a separate RCD (Residual Current Device), a residual current device RCD type A can be
used for all SUN2000 series inverters.
Regarding the internal RCMU protection limits (which is 300mA or higher according to IEC
62109-2: 2011), from SUN2000 inverters’ point of view, a RCD type A with a limit of
300mA or higher would be fine (as shown on following table). With this limit a premature
switch off of the external RCD would not happen.

SUN2000 inverters with type A RCD limit:


Inverter Model Type A RCD Limit
SUN2000L-2/3/4/4.6/5KTL 100 mA
SUN2000-2/3/4/4.6/5/6KTL-L1 100 mA
SUN2000-5/6KTL-M0 100 mA
SUN2000-5/6KTL-M1 100 mA
SUN2000-8/10/12/15/17/20KTL-M0 300 mA
SUN2000-8/10/12/15/17/20KTL-M2 300 mA
SUN2000-29.9/36KTL 300 mA
Product Description

SUN2000-50KTL-M0 500 mA
SUN2000-100KTL-M1 900 mA