Abb Acs310 Surucu Ariza Ve Hata Kodlari Abb Surucu Servisi

The document provides a comprehensive list of error and fault codes for the ABB ACS310 drive, detailing their causes and recommended actions for resolution. It also highlights the services offered by ADS Engineering, including free fault diagnosis and repair services with a one-year warranty on replaced parts. For support, users can contact ADS Engineering via email or phone.

Uploaded by

mertozer769
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views14 pages

Abb Acs310 Surucu Ariza Ve Hata Kodlari Abb Surucu Servisi

The document provides a comprehensive list of error and fault codes for the ABB ACS310 drive, detailing their causes and recommended actions for resolution. It also highlights the services offered by ADS Engineering, including free fault diagnosis and repair services with a one-year warranty on replaced parts. For support, users can contact ADS Engineering via email or phone.

Uploaded by

mertozer769
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

ABB ACS310 Sürücü Arıza ve Hata Kodları www.adsmuhendislik.com.

tr

ABB ACS310 Sürücü Arıza ve Hata Kodları


ABB ACS310 sürücü arıza kodları dokümanının içeriğinde sürücünüzün uyarı panelinde yer alan hata kodlarıyla
ilgili tüm bilgilere ulaşabilirsiniz.
ADS mühendislik 2000 yılından beri yaptığı ABB sürücü servisi bayiliği sayesinde kazandığı tecrübe ile bütün ABB
sürücülerinin tamirini ve upgared işlemlerini başarıyla yapmaktadır. ADS mühendislik arıza tespit için herhangi bir
ücret talep etmemektedir. Tespit sonrası yollayacağımız rapor ve teklif ile arızanız size bildirilir. Teklifimiz kabul
edilirse gerekli tamir, bakım ve temizlik işlemleri yapılır ve sürücünüz size gönderilir. Tamirde değiştirdiğimiz
parçalar 1 yıl boyunca ADS mühendislik ve ABB garantisi altındadır.
ACS310 sürücü hata kodları ile ilgili destek taleplerinizi [email protected] adresinden bizlere
ulaştırabilir ya da 444 237 4 numaralı telefondan bizlere ulaşabilirsiniz

Alarm messages generated by the drive


CODE ALARM CAUSE WHAT TO DO
2001 OVERCURRENT Output current limit Check motor load.
0308 bit 0 controller is active. Check acceleration time (2202 and
(programmable fault 2205).
function 1610) Check motor and motor cable
(including phasing).
Check ambient conditions. Load
capacity decreases if installation site
ambient temperature exceeds 40 °C.
See section Derating on page 338.
2002 OVERVOLTAGE DC overvoltage Check deceleration time (2203 and
0308 bit 1 controller is active. 2206).
(programmable fault Check input power line for static or
function 1610) transient overvoltage.

2003 UNDERVOLTAGE DC undervoltage Check input power supply.


0308 bit 2 controller is active.
(programmable fault
function 1610)
2004 DIR LOCK Change of direction is Check parameter 1003 DIRECTION
0308 bit 3 not allowed. settings.

2005 IO COMM Fieldbus Check status of fieldbus


0308 bit 4 communication break communication. See chapter
Fieldbus control with the embedded
(programmable fault fieldbus on page 287.
function 3018, 3019)
Check fault function parameter
settings.
Check connections.
Check if master can communicate.
2006 AI1 LOSS Analog input AI1 signal Check fault function parameter
0308 bit 5 has fallen below limit settings.
defined by parameter Check for proper analog control
(programmable fault
3021 AI1 FAULT signal levels.
function 3001, 3021) LIMIT.
Check connections.
2007 AI2 LOSS Analog input AI2 signal Check fault function parameter
0308 bit 6 has fallen below limit settings.
defined by parameter Check for proper analog control
(programmable fault
3022 AI2 FAULT signal levels.
function 3001, 3022) LIMIT.
Check connections.
ABB ACS310 Sürücü Arıza ve Hata Kodları www.adsmuhendislik.com.tr

CODE ALARM CAUSE WHAT TO DO


2008 PANEL LOSS Control panel selected Check panel connection.
0308 bit 7 as active control Check fault function parameters.
location for drive has
(programmable ceased Check control panel connector.
fault function 3002) communicating. Refit control panel in mounting
platform.
If drive is in external control mode
(REM) and is set to accept start/stop,
direction commands or references
through control panel:
Check group 10 START/STOP/DIR
and 11 REFERENCE SELECT
settings.
2009 DEVICE Drive IGBT Check ambient conditions. See also
OVERTEMP temperature is section Derating on page 338.
0308 bit 8 excessive. Alarm limit Check air flow and fan operation.
is 120 °C.
Check motor power against drive
power.
2010 MOTOR TEMP Motor temperature is Check motor ratings, load and
0308 bit 9 too high (or appears to cooling.
be too high) due to Check start-up data.
(programmable fault excessive load,
function Check fault function parameters.
insufficient motor
3005…3009 / 3503) power, inadequate
cooling or incorrect
start-up data.
Measured motor Check value of alarm limit.
temperature has Check that actual number of sensors
exceeded alarm limit corresponds to value set by
set by parameter 3503 parameter 3501 SENSOR TYPE.
ALARM LIMIT.
Let motor cool down. Ensure proper
motor cooling: Check cooling fan,
clean cooling surfaces, etc.
2012 MOTOR STALL Motor is operating in Check motor load and drive ratings.
0308 bit 11 stall region due to eg Check fault function parameters.
excessive load or
(programmable fault
insufficient motor
function power.
3010…3012)
2013 AUTORESET Automatic reset alarm Check parameter group 31
1)
0308 bit 12 AUTOMATIC RESET settings.
2014 AUTOCHANGE PFC Autochange See parameter group 81 PFC
1)
0308 bit 13 function is active. CONTROL, section PFC control
macro on page 110 and section
SPFC control macro on page 111.
2015 PFC I LOCK PFC Interlocks are Drive cannot start
0308 bit 14 active. • any motor (when Autochange is
used)
• the speed regulated motor (when
Autochange is not used).
See parameter group 81 PFC
CONTROL.
2018 PID SLEEP Sleep function has See parameter groups 40 PROCESS
1)
0309 bit 1 entered sleeping PID SET 1… 41 PROCESS PID SET
mode. 2.
ABB ACS310 Sürücü Arıza ve Hata Kodları www.adsmuhendislik.com.tr

CODE ALARM CAUSE WHAT TO DO


2021 START ENABLE 1 No Start enable 1 Check parameter 1608 START
MISSING signal received ENABLE 1 settings.
0309 bit 4 Check digital input connections.
Check fieldbus communication
settings.
2022 START ENABLE 2 No Start enable 2 Check parameter 1609 START
MISSING signal received ENABLE 2 settings.
0309 bit 5 Check digital input connections.
Check fieldbus communication
settings.
2023 EMERGENCY Drive has received Check that it is safe to continue
STOP emergency stop operation.
0309 bit 6 command and ramps Return emergency stop push button
to stop according to to normal position.
ramp time defined by
parameter 2208
EMERG DEC TIME.
2025 FIRST START Motor identification Wait until drive indicates that motor
0309 bit 8 magnetization is on. identification is completed.
This alarm belongs to
normal start-up
procedure.
2026 INPUT PHASE Intermediate circuit DC Check input power line fuses.
LOSS voltage is oscillating Check for input power supply
0309 bit 9 due to missing input imbalance.
power line phase or
(programmable fault Check fault function parameters.
blown fuse.
function 3016)
Alarm is generated
when DC voltage
ripple exceeds 14% of
nominal DC voltage.
2027 USER LOAD Condition defined by See parameter group 37 USER
CURVE 3701 USER LOAD C LOAD CURVE.
0309 bit 10 MODE has been valid
longer than half of the
time set by 3703
USER LOAD C TIME.
2028 START DELAY Start delay in progress See parameter 2113 START DELAY.
0309 bit 11
2030 INLET LOW Pressure at pump/fan Check for a closed valve on the inlet
0309 bit 13 inlet too low side of the pump/fan.
Check piping for leaks.
See parameter group 44 PUMP
PROTECTION.
2031 OUTLET HIGH Pressure at pump/fan Check piping for blocks.
0309 bit 14 outlet too high See parameter group 44 PUMP
PROTECTION.
2032 PIPE FILL Pipe fill in progress See parameters 4421…4426.
0309 bit 15
ABB ACS310 Sürücü Arıza ve Hata Kodları www.adsmuhendislik.com.tr

CODE ALARM CAUSE WHAT TO DO


2033 INLET VERY LOW Pressure at pump/fan Check for a closed valve on the inlet
0310 bit 0 inlet too low side of the pump/fan.
Check piping for leaks.
See parameter group 44 PUMP
PROTECTION.
2034 OUTLET VERY Pressure at pump/fan Check piping for blocks.
HIGH outlet too high See parameter group 44 PUMP
0310 bit 1 PROTECTION.
20381) MOTOR HEATING Motor heating is See parameter 2115 MOT. HEATING
active. SEL.
1)
Even when the relay output is configured to indicate alarm conditions (eg parameter 1401
RELAY OUTPUT 1 = 5 (ALARM) or 16 (FLT/ALARM)), this alarm is not indicated by a relay
output.
ABB ACS310 Sürücü Arıza ve Hata Kodları www.adsmuhendislik.com.tr

Alarms generated by the Basic control panel


The Basic control panel indicates control panel alarms with a code, A5xxx.
ALARM CODE CAUSE WHAT TO DO
5001 Drive is not responding. Check panel connection.
5002 Incompatible Contact your local ABB representative.
communication profile
5010 Corrupted panel parameter Retry parameter upload.
backup file Retry parameter download.
5011 Drive is controlled from Change drive control to the local control mode.
another source.
5012 Direction of rotation is Enable change of direction. See parameter
locked. 1003 DIRECTION.
5013 Panel control is disabled Start from the panel is not possible. Reset the
because start inhibit is emergency stop command or remove the 3-wire
active. stop command before starting from the panel.
See section 3-wire macro on page 105 and
parameters 1001 EXT1 COMMANDS, 1002
EXT2 COMMANDS and 2109 EMERG STOP
SEL.
5014 Panel control is disabled Reset drive fault and retry.
because of drive fault.
5015 Panel control is disabled Deactivate the local control mode lock and retry.
because the local control See parameter 1606 LOCAL LOCK.
mode lock is active.
5018 Parameter default value is Contact your local ABB representative.
not found.
5019 Writing non-zero Only parameter reset is allowed.
parameter value is
prohibited.
5020 Parameter or parameter Contact your local ABB representative.
group does not exist or
parameter value is
inconsistent.
5021 Parameter or parameter Contact your local ABB representative.
group is hidden.
5022 Parameter is write Parameter value is read-only and cannot be
protected. changed.
5023 Parameter change is not Stop drive and change parameter value.
allowed, when drive is
running.
5024 Drive is executing a task. Wait until task is completed.
5025 Software is being uploaded Wait until upload/download is complete.
or downloaded.
5026 Value is at or below Contact your local ABB representative.
minimum limit.
5027 Value is at or above Contact your local ABB representative.
maximum limit.
5028 Invalid value Contact your local ABB representative.
ABB ACS310 Sürücü Arıza ve Hata Kodları www.adsmuhendislik.com.tr

ALARM CODE CAUSE WHAT TO DO


5029 Memory is not ready. Retry.
5030 Invalid request Contact your local ABB representative.
5031 Drive is not ready for Check input power supply.
operation, eg due to low
DC voltage.
5032 Parameter error Contact your local ABB representative.
5040 Parameter download error.
Selected parameter set is Perform upload function before download.
not in current parameter
backup file.
5041 Parameter backup file Contact your local ABB representative.
does not fit into memory.
5042 Parameter download error.
Selected parameter set is Perform upload function before download.
not in current parameter
backup file.
5043 No start inhibit
5044 Parameter backup file Check that file is compatible with drive.
restoring error
5050 Parameter upload aborted Retry parameter upload.
5051 File error Contact your local ABB representative.
5052 Parameter upload has Retry parameter upload.
failed.
5060 Parameter download Retry parameter download.
aborted
5062 Parameter download has Retry parameter download.
failed.
5070 Panel backup memory Contact your local ABB representative.
write error
5071 Panel backup memory Contact your local ABB representative.
read error
5080 Operation is not allowed Switch to the local control mode.
because the drive is not in
the local control mode.
5081 Operation is not allowed Check cause of fault and reset fault.
because of active fault.
5083 Operation is not allowed Check parameter 1602 PARAMETER LOCK
because parameter lock is setting.
on.
5084 Operation is not allowed Wait until task is completed and retry.
because drive is
performing a task.
5085 Parameter download from Check that source and destination drive types
source to destination drive are same, ie ACS310. See the type designation
has failed. label of the drive.
5086 Parameter download from Check that source and destination drive type
source to destination drive designations are the same. See type
has failed. designation labels of the drives.
ABB ACS310 Sürücü Arıza ve Hata Kodları www.adsmuhendislik.com.tr

ALARM CODE CAUSE WHAT TO DO


5087 Parameter download from Check that source and destination drive
source to destination drive information are same. See parameters in group
has failed because 33 INFORMATION.
parameter sets are
incompatible.
5088 Operation has failed Contact your local ABB representative.
because of drive memory
error.
5089 Download has failed Contact your local ABB representative.
because of CRC error.
5090 Download has failed Contact your local ABB representative.
because of data
processing error.
5091 Operation has failed Contact your local ABB representative.
because of parameter
error.
5092 Parameter download from Check that source and destination drive
source to destination drive information are same. See parameters in group
has failed because 33 INFORMATION.
parameter sets are
incompatible.
ABB ACS310 Sürücü Arıza ve Hata Kodları www.adsmuhendislik.com.tr

Fault messages generated by the drive


CODE FAULT CAUSE WHAT TO DO
0001 OVERCURRENT Output current has Check motor load.
(2310) exceeded trip level. Check acceleration time (2202 and
0305 bit 0 2205).
Check motor and motor cable
(including phasing).
Check ambient conditions. Load
capacity decreases if installation site
ambient temperature exceeds 40 °C.
See section Derating on page 338.
0002 DC OVERVOLT Excessive Check that overvoltage controller is on
(3210) intermediate circuit DC (parameter 2005 OVERVOLT CTRL).
voltage. DC Check input power line for static or
0305 bit 1
overvoltage trip limit is transient overvoltage.
420 V for 200 V drives
and 840 V for 400 V Check deceleration time (2203, 2206).
drives.
0003 DEV OVERTEMP Drive IGBT Check ambient conditions. See also
(4210) temperature is section Derating on page 338.
excessive. Fault trip Check air flow and fan operation.
0305 bit 2
limit is 135 °C.
Check motor power against drive
power.
0004 SHORT CIRC Short circuit in motor Check motor and motor cable.
(2340) cable(s) or motor
0305 bit 3
0006 DC UNDERVOLT Intermediate circuit DC Check that undervoltage controller is
(3220) voltage is not sufficient on (parameter 2006 UNDERVOLT
due to missing input CTRL).
0305 bit 5
power line phase, Check input power supply and fuses.
blown fuse, rectifier
bridge internal fault or
too low input power.
0007 AI1 LOSS Analog input AI1 signal Check fault function parameter
(8110) has fallen below limit settings.
defined by parameter Check for proper analog control signal
0305 bit 6 3021 AI1 FAULT levels.
(programmable fault LIMIT.
function 3001, 3021) Check connections.
0008 AI2 LOSS Analog input AI2 signal Check fault function parameter
(8110) has fallen below limit settings.
defined by parameter Check for proper analog control signal
0305 bit 7
3022 AI2 FAULT levels.
(programmable fault LIMIT.
function 3001, 3022) Check connections.
ABB ACS310 Sürücü Arıza ve Hata Kodları www.adsmuhendislik.com.tr

CODE FAULT CAUSE WHAT TO DO


0009 MOT OVERTEMP Motor temperature is Check motor ratings, load and cooling.
(4310) too high (or appears to Check start-up data.
be too high) due to
0305 bit 8 Check fault function parameters.
excessive load,
(programmable fault insufficient motor
function power, inadequate
3005…3009 / 3504) cooling or incorrect
start-up data.
Measured motor Check value of fault limit.
temperature has Check that actual number of sensors
exceeded fault limit set corresponds to value set by parameter
by parameter 3504 3501 SENSOR TYPE.
FAULT LIMIT.
Let motor cool down. Ensure proper
motor cooling: Check cooling fan,
clean cooling surfaces, etc.
0010 PANEL LOSS Control panel selected Check panel connection.
(5300) as active control Check fault function parameters.
location for drive has
0305 bit 9 Check control panel connector.
ceased
(programmable fault Refit control panel in mounting
communicating.
function 3002) platform.
If drive is in external control mode
(REM) and is set to accept start/stop,
direction commands or references
through control panel:
Check group 10 START/STOP/DIR
and 11 REFERENCE SELECT
settings.
0012 MOTOR STALL Motor is operating in Check motor load and drive ratings.
(7121) stall region due to eg Check fault function parameters.
excessive load or
0305 bit 11
insufficient motor
(programmable fault power.
function
3010…3012)
0014 EXT FAULT 1 External fault 1 Check external devices for faults.
(9000) Check parameter 3003 EXTERNAL
0305 bit 13 FAULT 1 setting.
(programmable
fault function 3003)
0015 EXT FAULT 2 External fault 2 Check external devices for faults.
(9001) Check parameter 3004 EXTERNAL
0305 bit 14 FAULT 2 setting.
(programmable
fault function 3004)
0016 EARTH FAULT Drive has detected Check motor.
(2330) earth (ground) fault in Check motor cable. Motor cable length
0305 bit 15 motor or motor cable. must not exceed maximum
(programmable fault specifications. See section Motor
function 3017) connection data on page 348.
Note: Disabling earth fault (ground
fault) may void the warranty.
ABB ACS310 Sürücü Arıza ve Hata Kodları www.adsmuhendislik.com.tr

CODE FAULT CAUSE WHAT TO DO


0018 THERM FAIL Drive internal fault. Contact your local ABB
(5210) Thermistor used for representative.
drive internal
0306 bit 1
temperature
measurement is open
or short circuited.
0021 CURR MEAS Drive internal fault. Contact your local ABB
(2211) Current measurement representative.
0306 bit 4 is out of range.

0022 SUPPLY PHASE Intermediate circuit DC Check input power line fuses.
(3130) voltage is oscillating Check for input power supply
due to missing input imbalance.
0306 bit 5
power line phase or
Check fault function parameters.
blown fuse.
Trip occurs when DC
voltage ripple exceeds
14% of nominal DC
voltage.
0024 OVERSPEED Motor is turning faster Check minimum/maximum frequency
(7310) than highest allowed settings.
0306 bit 7 speed due to Check adequacy of motor braking
incorrectly set torque.
minimum/maximum
speed.
Operating range limits
are set by parameters
2007 MINIMUM FREQ
and 2008 MAXIMUM
FREQ.
0026 DRIVE ID Internal drive ID fault Contact your local ABB
(5400) representative.
0306 bit 9
0027 CONFIG FILE Internal configuration Contact your local ABB
(630F) file error representative.
0306 bit 10
0028 SERIAL 1 ERR Fieldbus Check status of fieldbus
(7510) communication break communication. See chapter Fieldbus
control with the embedded fieldbus on
0306 bit 11 page 287.
(programmable fault Check fault function parameter
function 3018, 3019) settings.
Check connections.
Check if master can communicate.
0029 EFB CON FILE Configuration file Contact your local ABB
(6306) reading error representative.
0306 bit 12
0030 FORCE TRIP Trip command See appropriate communication
(FF90) received from fieldbus module manual.
0306 bit 13
ABB ACS310 Sürücü Arıza ve Hata Kodları www.adsmuhendislik.com.tr

CODE FAULT CAUSE WHAT TO DO


0031 EFB 1 Error from the See chapter Fieldbus control with the
(FF92) embedded fieldbus embedded fieldbus on page 287.
(EFB) protocol
0307 bit 0
application. The
0032 EFB 2 meaning is protocol
(FF93) dependent.
0307 bit 1
0033 EFB 3
(FF94)
0307 bit 2
0034 MOTOR PHASE Motor circuit fault due Check motor and motor cable.
(FF56) to missing motor Check motor thermistor relay (if used).
0306 bit 4 phase or motor
thermistor relay (used
in motor temperature
measurement) fault.
0035 OUTP WIRING Incorrect input power Check input power connections.
(FF95) and motor cable
0306 bit 15 connection (ie, input
power cable is
(programmable fault connected to drive
function 3023) motor connection).
The fault can be
erroneously declared if
the drive is faulty or
the input power is a
delta grounded system
and the motor cable
capacitance is large.
0036 INCOMPATIBLE Loaded software is not Contact your local ABB
SW compatible. representative.
(630F)
0307 bit 3
0038 USER LOAD Condition defined by See parameter group 37 USER LOAD
CURVE 3701 USER LOAD C CURVE.
(FF6B) MODE has been valid
longer than the time
0307 bit 4 set by 3703 USER
LOAD C TIME.
0039 UNKNOWN Option module not Check connections.
EXTENSION supported by the drive
(7086) firmware is connected
to the drive.
0307 bit 5
0040 INLET VERY LOW Pressure at pump/fan Check for a closed valve on the inlet
(8A81) inlet too low side of the pump/fan.
0307 bit 6 Check piping for leaks.
See parameter group 44 PUMP
PROTECTION.
0041 OUTLET VERY Pressure at pump/fan Check piping for blocks.
HIGH outlet too high See parameter group 44 PUMP
(8A83) PROTECTION.
0307 bit 7
ABB ACS310 Sürücü Arıza ve Hata Kodları www.adsmuhendislik.com.tr

CODE FAULT CAUSE WHAT TO DO


0042 INLET LOW Pressure at pump/fan Check for a closed valve on the inlet
(8A80) inlet too low side of the pump/fan.
0307 bit 8 Check piping for leaks.
See parameter group 44 PUMP
PROTECTION.
0043 OUTLET HIGH Pressure at pump/fan Check piping for blocks.
(8A82) outlet too high See parameter group 44 PUMP
0307 bit 9 PROTECTION.
0101 SERF CORRUPT
(FF55)
0307 bit 14
0103 SERF MACRO
(FF55)
0307 bit 14
0201 DSP T1
OVERLOAD
(6100)
Drive internal error Write down fault code and contact
0307 bit 13 your local ABB representative.
0202 DSP T2
OVERLOAD
(6100)
0307 bit 13
0203 DSP T3
OVERLOAD
(6100)
0307 bit 13
0204 DSP STACK
ERROR
(6100)
0307 bit 12
0206 CB ID ERROR
(5000)
0307 bit 11
1000 PAR HZRPM Incorrect frequency Check parameter settings. Check that
(6320) limit parameter setting following applies:
0307 bit 15 • 2007 MINIMUM FREQ <
2008 MAXIMUM FREQ
• 2007 MINIMUM FREQ / 9907
MOTOR NOM FREQ and 2008
MAXIMUM FREQ / 9907 MOTOR
NOM FREQ are within range.
1001 PAR PFC REF NEG Incorrect PFC Check parameter group 81 PFC
(6320) parameters CONTROL settings. Check that
following applies:
0307 bit 15
• 2007 MINIMUM FREQ > 0 when
8123 is ACTIVE or SPFC ACTIVE.
ABB ACS310 Sürücü Arıza ve Hata Kodları www.adsmuhendislik.com.tr

CODE FAULT CAUSE WHAT TO DO


1003 PAR AI SCALE Incorrect analog input Check parameter group 13 ANALOG
(6320) AI signal scaling INPUTS settings. Check that following
applies:
0307 bit 15
• 1301 MINIMUM AI1 <
1302 MAXIMUM AI1
• 1304 MINIMUM AI2 <
1305 MAXIMUM AI2.
1004 PAR AO SCALE Incorrect analog output Check parameter group 15 ANALOG
(6320) AO signal scaling OUTPUTS settings. Check that
following applies:
0307 bit 15
• 1504 MINIMUM AO1 <
1505 MAXIMUM AO1.
1006 PAR EXT RO Incorrect extension Check parameter settings. Check that
(6320) relay output following applies:
0307 bit 15 parameters • MREL relay output extension
module is connected to the drive.
• 1402…1403 RELAY OUTPUT 2 …
RELAY OUTPUT 3 and 1410
RELAY OUTPUT 4 have non-zero
values.
See MREL-01 relay output extension
module user's manual
(3AUA0000035974 [English]).
1012 PAR PFC IO 1 I/O configuration for Check parameter settings. Following
(6320) PFC not complete must apply:
0307 bit 15 • There are enough relays
parameterized for PFC.
• No conflict exists between
parameter group 14 RELAY
OUTPUTS, parameter 8117 NR OF
AUX MOT and parameter 8118
AUTOCHNG INTERV.
1013 PAR PFC IO 2 I/O configuration for Check parameter settings. Following
(6320) PFC not complete must apply:
0307 bit 15 • The actual number of PFC motors
(parameter 8127 MOTORS)
matches the PFC motors in
parameter group 14 RELAY
OUTPUTS and parameter 8118
AUTOCHNG INTERV.
1014 PAR PFC IO 3 I/O configuration for See parameters 8120 INTERLOCKS
(6320) PFC not complete. and 8127 MOTORS.
0307 bit 15 The drive is unable to
allocate a digital input
(interlock) for each
PFC motor.
1015 PAR USER Incorrect voltage to Check parameter 2610 USER
DEFINED U/F frequency DEFINED U1…2617 USER DEFINED
(6320) (U/f) ratio voltage F4 settings.
setting.
0307 bit 15
ABB ACS310 Sürücü Arıza ve Hata Kodları www.adsmuhendislik.com.tr

CODE FAULT CAUSE WHAT TO DO


1016 PAR USER LOAD C Incorrect user load Check parameter settings. Following
(6320) curve parameter must apply:
setting • 3704 LOAD FREQ 1 <
0307 bit 15
3707 LOAD FREQ 2 <
3710 LOAD FREQ 3 <
3713 LOAD FREQ 4 <
3716 LOAD FREQ 5
• 3705 LOAD TORQ LOW 1 <
3706 LOAD TORQ HIGH 1
• 3708 LOAD TORQ LOW 2 <
3709 LOAD TORQ HIGH 2
• 3711 LOAD TORQ LOW 3 <
3712 LOAD TORQ HIGH 3
• 3714 LOAD TORQ LOW 4 <
3715 LOAD TORQ HIGH 4
• 3717 LOAD TORQ LOW 5 <
3718 LOAD TORQ HIGH 5.
1017 PAR SETUP 1 It is not allowed to use Disable frequency output or frequency
(6320) frequency input signal input:
and frequency output • change transistor output to digital
0307 bit 15 signal simultaneously. mode (value of parameter 1804 TO
MODE = DIGITAL), or
• change frequency input selection to
other value in parameter groups
11 REFERENCE SELECT,
40 PROCESS PID SET 1,
41 PROCESS PID SET 2 and
42 EXT / TRIM PID.