The EH Series includes models EH-1725-HA-UD and EH-2000-HA-UD, featuring a maximum DC voltage of 1500V and high efficiency up to 99%. Both models support on-grid and off-grid operations with adjustable AC voltage ranges and have robust protection ratings (IP65). They are designed for a wide operating temperature range and include various communication ports for integration.

Uploaded by

wsp015526
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
16 views

66baf511a969d

The EH Series includes models EH-1725-HA-UD and EH-2000-HA-UD, featuring a maximum DC voltage of 1500V and high efficiency up to 99%. Both models support on-grid and off-grid operations with adjustable AC voltage ranges and have robust protection ratings (IP65). They are designed for a wide operating temperature range and include various communication ports for integration.

Uploaded by

wsp015526
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

EH Series Model EH-1725-HA-UD EH-2000-HA-UD

DC Parameters
Power Conversion System (Central PCS, 1500V) Max. DC voltage 1500V

Max. DC current 1936A 2245A


Features
Battery voltage range 1000~1500V
Max. efficiency up to 99% IP65 protection degree
Number of DC input 1
Full reactive power four-quadrant capability Black start ability
AC parameters (On-Grid)
Support VSG function Three level topology
AC output power 1897.5kVA@30℃,1725kVA@45℃ 2200kVA@30℃, 2000kVA@45℃
Millisecond-level power response to EMS/SCADA Use alone or in combination with MV station
Nominal AC voltage 690V,3W+PE

AC voltage range 607~759V (Adjustable)

PCS Max. AC output current 1588A@30℃,1443A@45℃ 1841A@30℃, 1674A@45℃

Nominal grid frequency 50/60Hz

Harmonic (THDi) <1.5% (100% load)

Power factor range -1~+1

AC parameters (Off-Grid)

Nominal AC voltage 690V,3W+PE

AC voltage range 607-759V(Adjustable)

AC voltage distortion <1.5% (100% linear load)

DC voltage component <0.5% Un (Linear balance load)

Unbalanced load capacity 100%

Nominal grid frequency 50/60Hz

General Data

Isolation mode Transformerless

Max. efficiency 99%

Circuit Diagram European efficiency 98.5%

Ingress protection rating IP65

Operating temperature range -40~+60℃(>45℃ derating)


soft start
DC Fuse LC Filter AC breaker Relative humidity 0~100% (no condensing)
BAT + DC AC
U
EMI DC Load
DC/AC EMI V Max. altitude 5000m (>3000m derating)
Break Switch
Filter
BAT _ Filter W
DC Fuse
soft start
Cooling method Forced air cooling
PE PE

DC SPD Communication port RS485/CAN/Ethernet/Bluetooth


AC SPD
Dimensions (W*D*H) 1150×1435×2350mm

Weight 1400kg

© 2024 SINENG ELECTRIC CO., LTD. All RIGHTS RESERVED. SUBJECT TO CHANGE WITHOUT NOTICE.