Critical angle threshold using local synchrophasors for real time angular
Critical angle threshold using local synchrophasors for real time angular
See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
IET Generation, Transmission & Distribution
Abstract: An affordable, stable, reliable and sustainable power supply is the need of the hour, keeping in view the journey to a
smart green grid. The present study and derivation of adaptive critical angle threshold (ACAT) contributes to this effect. The
ACAT serves as a key index and an indicator to grid operator in proactive mitigation of angular instability in the grid, which is
seen to be one of the major initiator of blackouts worldwide. The synchrophasor technology enables accurate calculation of
ACAT on real time basis by time synchronised sampling of local voltage and current phasors. The real time calculation makes
the index adaptive to variation in system topologies as well as system vulnerabilities. Furthermore, the local system model
formed for deriving ACAT has less computational burden while capturing the dynamics of external system, without requirement
of intricate power system details. The angular separation of the station bus under supervision can be monitored with respect to
the critical angle and serve as a key indicator for initiation of preventive actions during contingencies. The devised methodology
is tested using standard IEEE test systems as well as a practical 400/220 kV state grid system using ETAP/MATLAB.
IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5888-5898 5888
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2020.0269, Wiley Online Library on [17/01/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
interface. Traditionally, the multi-machine power system stability is predefined set thresholds. The limit has to change adaptively based
evaluated by analysing and solving the swing equation given by on system conditions and changing topology.
IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5888-5898 5889
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2020.0269, Wiley Online Library on [17/01/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 3 ROSE phase angle alarming tool
2.3 Literature review (ii) Aids the operator about characteristics of the power system
transient stability and it's developing trend for initiating auto/
A brief discussion on the importance of wide area monitoring manual preventive actions.
techniques for protection and control system is available in [9]. A
(iii) uses local PMU data of voltage and current phasors for the
study by North American Synchrophasor Initiative (NASPI) [10]
derivation.
discusses how the synchrophasor based phase angle monitoring
tools/applications are utilised by grid operators in utilities (iv) doesnot require the intricate power system network data or
worldwide. The study presents setting of alert threshold consistent generator parameters of the entire system.
with the vulnerability of the grid as one of the hurdles for practical
implementation of the phase angle monitoring tools. A Region of 3 Methodology
Stability Existence (ROSE) tool by V and R Energy is a similar 3.1 Derivation of adaptive critical angle threshold
application [10] which uses user-defined thresholds as seen in Fig.
3. In order to derive the critical angle, the power system under
The alarm thresholds are derived using a base-lining supervision needs to be modelled accurately incorporating the
mechanism for predetermining the minimum and maximum values, effect of all connected incoming and outgoing elements. Existing
i.e. the values are non adaptive to changes in system topologies. transient stability analysis methods rely on estimation of pre and
The study in [11] discusses a real time contingency analysis tool post disturbance dynamic response of grid based on identifying the
using synchrophasor measurements. However, the methodology real-time dynamic model or the power system transfer function.
requires system visibility through more number of PMUs and The measurement-based models available for system identification
depends on the output of a linear state estimator. A transient energy uses state-space and transfer function methodologies. Both the
function based technique for detection and mitigation of transient representations are computation intensive and need intricate power
stability on real time is discussed in [12]. A novel idea of cut-set system details. Hence a simple reliable equivalent system model
angles was introduced in [13] to monitor the static stress of power using local phasor measurements based on the equivalent system
system. WAMS based real-time transient instability detection is model derived in [20] is proposed. As discussed in [20], an
based on perturbed rotor angle trajectory prediction or practical or equivalent source voltage Ek and source impedance Zk is
predicted post-fault trajectories. Accurate prediction of post-fault considered which encompasses the effect of entire power system
trajectory is very important in devising control action schemes. network external to node under study as in Fig. 4. The equivalent
Further, a suitable time period is required in advance to instability system model with voltage source Ek and source impedance Zk will
event so that the mitigating scheme is effective. Also, control hold true, with effect same as that of an external power system
action based on the actual post fault trajectory is not prudent network, if the following equations are satisfied. These equations
without a proper instability detection criterion. Dynamic equivalent imply that voltage phasors and power flows identical to original
network based rotor angle trajectory prediction techniques are system are ensured for the equivalent model formed.
presented in [14–19]. The recent real time transient stability
prediction methods discussed in literature showcase machine (Pm + jQm)∗ = Vm∗ Im
learning based methods [14–16] where decision trees, support
vector machine and neural network techniques are used. However, Im = In
the methodology involves training a classifier based on several (Ek − Vm)
=>
offline simulated faults and results. For a large complex power Zk
network with dynamically changing operating point, the reliability (Vm − Vn)
and practical application of these methodologies require thorough =
Zn
assessment, as it lacks a reliable training data set. In a dynamic
network equivalent model based super-real-time trajectory Zk (Ek − Vm)
=
prediction, the knowledge of network topology or intricate system Zn (Vm − Vn)
parameters is very much necessary. Another method involves rotor
angle trajectory extrapolation using curve fitting methods such as where, Pm and Qm are the incoming real and reactive powers
auto-regression prediction [17], trigonometric function based flowing into the local node. Introducing a complex coefficient
prediction [18] and prediction based on polynomial model [19].
r = (Zk + Zn)/Zn
2.4 Contributions → (1)
Ek = r Vm + (1 − r)Vn
The present study uses the significant information provided by
angular separation and Considering two equilibrium states of the system, the equivalent
source voltage Ek and source impedance Zk will remain same as
(i) Derives an ACAT for the bus phase angle separation by below:
formulating a local equivalent system model encompassing the
effects of external grid. Ek = (r)Vm1 + (1 − r)Vn1 (2)
5890 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5888-5898
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2020.0269, Wiley Online Library on [17/01/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Ek = (r)Vm2 + (1 − r)Vn2 (3) Applying sin2 θ + cos2 θ = 1,
2
Considering two equilibrium states of the system, the equivalent Pn Xeq − QnReq 2 PnReq + Qn Xeq + V n2
source voltage Ek and source impedance Zk will remain same as in + =1 (11)
EkV n EkV n
below.
Solving the above two equations, Ek and r can be found out. This is of the form ax2 + bx + c, where
Knowing value of r and Zn, the source impedance Zk can also be
found out to form the equivalent system model in Fig. 4 as in [20]. a=1
Now, using the equivalent system model, the critical angle b = 2(PnReq + Qn Xeq) − Ek2
threshold is derived. At the node under study, the power Sn is given c = Sn2 Zk2
as
The quadratic equation has single real root V n = V crit at maximum
Sn = Vn In∗ power. At maximum power, the discriminant is equal to 0, i.e.
Ek − Vn ∗
b2 − 4ac = 0. This follows from the fact that the roots of the
= Vn
Zeq equation ax2 + bx + c = 0 are real and equal if b2 − 4ac = 0. Thus,
(6)
where, Zeq = Zk + Zn
= Req + jXeq 2 −b
V crit =
∗ 2
2
(Pn + jQn)(Req + jXeq) = Vn Ek − V n (13)
Ek2 − 2(PnReq + Qn Xeq)
V crit =
Solving and rearranging, 2
L . H . S . = (PnReq + Qn Xeq) + j(QnReq − Pn Xeq) (7) Substituting in (9), critical angle threshold is formulated as,
Pn Xeq − QnReq
R . H . S . = (EkV ncosθkn − V n2 ) − j(EkV nsin θkn) (8) ACAT = θcrit = sin−1 (14)
EkV crit
Where, Vn = V n∠θn, Ek = Ek∠θk, θkn = θk − θn.
The flowchart of the proposed methodology is shown in Fig. 5.
Rearranging and separating the sine and cosine terms in
In the event of an instability, the phase angle separation will
equations (7) and (8),
cross the critical threshold. A distance relay which detects power
swing in transmission lines will enter into a blocking mode
Pn Xeq − QnReq
sin θkn = (9) (typically 2 s as adopted in Indian power system). On detection of
EkV n power swing the last calculated ACAT value can be set as threshold
for detecting instability and further initiating alarm or further
PnReq + Qn Xeq + V n2 preventive protection schemes.
cos θkn = (10)
EkV n
IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5888-5898 5891
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2020.0269, Wiley Online Library on [17/01/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 5 Flowchart of the proposed scheme
4 Results and discussion Now critical angle and voltage thresholds are calculated for bus
8 in the case of an unstable power swing and plotted in Fig. 10. It
The proposed scheme is tested and validated on Western System can be observed that the angular separation oscillates and crosses
Coordinating Council (WSCC) 3-machine, 9-bus and New England critical angle threshold continuously in the event of an unstable
39 bus test systems using ETAP/MATLAB. The relevance of power swing. The critical angle threshold and critical voltage are
ACAT is also brought out using the Northern Kerala blackout calculated for bus 5 and 6 in the case of unstable power swing and
incident explained in [20]. plotted in Fig. 11. The angular separation does not cross the
Case 1, Simulations on WSCC 9 bus system: a symmetrical threshold here even though voltage crosses the threshold,
three phase fault is simulated at 50% of line connecting Bus 5 and indicating preventive action plan initiation has to be at bus 8 to
Bus 7 at 1 s. The fault is cleared by tripping circuit breakers at both contain the impending instability in the system.
ends of line after 80 ms, i.e. at 1.08 s. Load carrying buses - Bus 5, Case 2, Simulations in IEEE 39 bus system a symmetrical three
6 and 8 are monitored. The distance relay in Bus 8 detects a power phase fault is simulated at 50% of line connecting Bus 26 and Bus
swing. The generator real powers and rotor angle plots of all 29 at 1 s. The fault is cleared by tripping circuit breakers at both
generators are shown in Fig. 6a and b. The current and voltage ends of line after 80 ms, i.e. at 1.08 s. The distance relay in Bus 28
plots measured by distance relay at bus 8 is shown in Fig. 6c. detects a power swing. The rotor speed and rotor angle plots of all
From the real power plot, rotor angle plot as well as the voltage generators are shown in Fig. 12. The real power of nearest
and current plots measured by relay at bus 8, a stable power swing generator G9 is shown in Fig. 13. From the real power plot as well
can be inferred. The critical voltage is calculated and is plotted as rotor parameter plots, a stable power swing can be inferred.
along with Bus 8 voltage as shown in Fig. 7. The critical angle The critical angle threshold and critical voltage of Bus 28 is
threshold of Bus 8 is calculated and plotted along with Bus 8 calculated as per equation and plotted as shown in Fig. 14. The
angular separation as shown in Fig. 8a. The critical angle plots of angular separation of Bus 28 is seen to oscillate after fault
bus 5 and bus 6 are shown in Fig. 8b. It can be observed that during clearance but does not exceed the critical angle threshold during
stable power swing, the bus angular separation does not cross the stable power swing. In order to simulate an unstable power swing,
proposed critical threshold ACAT. a symmetrical three phase fault is simulated at 50% of line
In order to simulate an unstable power swing, a symmetrical connecting Bus 26 and Bus 29 at 1 s. The fault is cleared by
three phase fault is simulated at 50% of line connecting Buses 5–7 tripping circuit breakers at both ends of line after 150 ms, i.e. at
at 1 s. The fault is cleared by tripping circuit breakers at both ends 1.15 s. The distance relay in Bus 28 detects a power swing. The
of line after 120 ms, i.e. at 1.12 s. The distance relay in Bus 8 real power generation of all generators are shown in Fig. 15a. The
detects a power swing. The rotor angles of generators 2 and 3 are rotor angles of all generators are shown in Fig. 15b.
shown in Fig. 9b. The real power generation of all generators are An event of unstable power swing can be inferred from the real
shown in Fig. 9a. An event of unstable power swing can be power plot which shows sustained oscillation. Moreover the
inferred from the real power plot which shows sustained diverging pattern of rotor angles also conclude a case of angular
oscillation. Moreover, the diverging pattern of rotor angles also instability. Now critical voltage and critical angle threshold are
conclude a case of an angular instability. The voltage and current calculated for the case of unstable power swing and plotted in Fig.
plots recorded by distance relay in bus 8 is shown in Figs. 9c and d 16. It can be seen that the Bus 28 angular separation crosses the
which also indicate unstable power swing in bus 8.
5892 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5888-5898
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2020.0269, Wiley Online Library on [17/01/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 6 Case 1: Stable Power Swing
(a) Real power of generators, (b) Rotor angles of generators, (c) Voltage and current recorded by distance relay at bus 8
critical angle threshold multiple times in the event of unstable state power grids viz. Andhra Pradesh, Telangana, Karnataka,
power swing. The Bus 28 voltage is also seen to go below the Tamil Nadu, Kerala and Union Territory of Puducherry. 400 kV
critical voltage. Thus, ACAT can serve as an effective criteria to grid network and few 765 and 220 (230) kV inter-state lines form
indicate angular instability in the power system. Hence ACAT can the backbone of State systems transmission interconnections. SR is
be utilised for pre-emptive mitigation of angular instability by a power deficit region. The grid map of Kerala state is shown in
initiating relevant RASs. Fig. 17.
Case 3: the ACAT derived is validated for practical applications A 400/220 kV substation was established in 2012 in Palakkad
by simulating the Northern Kerala blackout incident explained in district of Kerala state as part of System strengthening XI of SR
[20]. During the incident, tripping of two heavily loaded incoming Transmission System. It was planned to facilitate reliable and
lines to Kerala state in India led to voltage collapse and blackout in quality power supply in and around central and northern Kerala
Northern part of the state. Southern Regional (SR) grid in India and to enable a complete development of fast growing industrial
comprising approximately 22% of India's population and 30% of zone in Palakkad. The industrial zone comprises of a proposed
the installed capacity is a large power system comprising of five Palakkad rail coach factory, BEML, manufacturing units of ITI
IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5888-5898 5893
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2020.0269, Wiley Online Library on [17/01/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 9 Case 1: Unstable power swing
(a) Real power generation, (b) Rotor angle of generators, (c) Voltage recorded by distance relay at bus 8, (d) Current recorded by distance relay at bus 8
Ltd, Instrumentation Ltd, BPL etc. The substation is having a state transmission lines, (double circuits (D/C) of Udumalpet
transmission capacity of 630 MVA. The line in line out of inter- (Tamil Nadu)–Trichur (Kerala) 400 kV lines at Palakkad SS),
5894 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5888-5898
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2020.0269, Wiley Online Library on [17/01/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 12 Rotor angle and rotor speed of generators
facilitates drawal of Kerala state share from central sector projects. conditions the voltage profile of Palakkad SS is seen to be low with
Kerala imports power from central pool mainly through 400 kV sometimes voltages going below the Indian Electricity Grid Code
Udumalpet–Palakkad double circuit (D/C) lines. During peak load (IEGC) limit of 95%. The double circuit lines from 400 kV
IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5888-5898 5895
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2020.0269, Wiley Online Library on [17/01/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 16 Critical angle and voltage of Bus 28
Udumalpet to 400 kV Palakkad lines tripped during the blackout 4.1 Discussion
incident (N-2 contingency at Palakkad) causing blackout in
Northern Kerala grid. The results of the three cases (simulations on standard test system
As it had occurred during the actual grid event, a collapse in as well as on real time system with actual data) described above
voltage of entire grid to below IEGC limit of 95% was observed validates the potential use of critical angle threshold as an indicator
from simulation results also. The voltage and frequency plots for of system instability. Real time monitoring tool using angular
all the 400 kV nodes in Kerala state are shown below in Figs. 18a separation against critical angle threshold will aid the system
and b. It can be seen that once the entire supply from central pool operator in the prediction of the onset of transient instabilities. The
to Palakkad station gets cut off, the voltage at Palakkad collapses preventive actions can be initiated accordingly for proactive
gradually. The plot of real power and rotor angle variation at the mitigation of catastrophes. By establishing critical angle threshold
three major generating stations connected to 220 kV system viz. criteria in combination with other events or parameters, remedial
Idukki, Sabarigiri and Lower Periyar is shown in Figs. 18c and d. actions viz. intelligent system separation, load shedding etc. could
Sustained oscillations are observed in the real power generation be initiated. RAS using synchrophasor measurement to monitor
as well as rotor angle and system moves towards instability. The angular separation, implemented in the Peruvian power system, as
Idukki generation was < 600 MW during the actual event as one of a solution to maintain stability is presented in [21]. The RAS was
the generators was out of service. It can be observed that in the implemented to make operation decisions to trip large loads.
event of reduced generation at Idukki hydroelectric project, an N-2 However, for utilising the proposed critical angle threshold tool in
contingency at Palakkad will lead to the important 220 kV stations such time critical applications viz. protection, latency and
in North, Central and South Kerala crossing its critical angle congestion performance need to be assessed thoroughly in a
threshold. The critical angles for all 400 kV stations in Kerala state practical environment. The development of the critical angle
for the said contingency are shown in Table 1. The critical angle threshold tool for special protection schemes in a real time
plots for the important 220 kV stations down-lane to all 400 kV environment for practical application is being taken up as a pilot
substations in Kerala state drawing power from central grid are study in association with the Central Transmission Utility.
calculated and shown as in Fig. 19.
5896 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5888-5898
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2020.0269, Wiley Online Library on [17/01/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 18 Case 3: Grid incident
(a) Voltage at 400 kV nodes, (b) Grid frequency plot, (c) Real power generation, (d) Rotor angles at important generating stations
IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5888-5898 5897
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2020.0269, Wiley Online Library on [17/01/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
identified as a critical indicator of stressed system and it's [6] De La Ree, J., Centeno, V., Thorp, J.S., et al.: ‘Synchronized phasor
measurement applications in power systems’, IEEE Transactions on Smart
proximity to instability. The study presented in this chapter utilises Grid, 2010, 1, (1), pp. 20–27
the equivalent local system model to derive an adaptive limit/ [7] ‘Entso - operations report: Blackout in Turkey on 31st March 2015’
threshold based operational early alert mechanism for phase angle [8] ‘Operational feedback - January 2019’. Available at https://posoco.in
separation across critical nodes. The present work uses the [9] Phadke, A.G., Wall, P., Ding, L., et al.: ‘Improving the performance of power
system protection using wide area monitoring systems’, J. Mod. Power Syst.
significant information provided by synchrophasors from local Clean Energy, 2016, 4, (3), pp. 319–331
PMU to derive an ACAT for the bus voltage phase angle separation [10] Control Room Solutions Task Team Working Document by North American
in order to alert the operator regarding characteristics of the power Synchrophasor Initiative, May 2016
system transient stability and it's developing trend for initiating [11] Nayak, N., Zhang, L., Martin, K., et al.: ‘Practical implementation of
synchrophasor based real-time contingency analysis’. 2018 North American
auto/manual preventive actions. The main constraint for practical Power Symp. (NAPS), Detroit, MI, USA., September 2018
implementation of various phase angle monitoring tools available [12] Bhui, P., Senroy, N.: ‘Real time prediction and control of transient stability
is identifying and updating phase angle alarms and alert thresholds using transient energy function’, IEEE Trans. Power Syst., 2017, 32, (2), pp.
adaptive to grid vulnerabilities. The phase angle of critical nodes 923–934
[13] Dobson, I.: ‘Voltages across an area of a network’, IEEE Trans. Power Syst.,
can be monitored constantly using the ACAT derived and it can be 2012, 27, (2), pp. 993–1002
utilised to generate a visual/audible alarm on crossing the [14] Gomez, F., Rajapakse, A., Annakkage, U., et al.: ‘Support vector machine-
threshold, which is set adaptively, thus aiding quick manual/ based algorithm for post-fault transient stability status prediction using
automatic response. The visualisation of power system stress level synchronized measurements’. 2011 IEEE Power and Energy Society General
Meeting', Fargo, ND, USA., July 2011
using time synchronised low latency and high resolution phase [15] Amraee, T., Ranjbar, S.: ‘Transient instability prediction using decision tree
angle difference measurements are extremely useful for grid technique’, IEEE Trans. Power Syst., 2013, 28, (3), pp. 3028–3037
operators in devising pre-emptive corrective actions viz. [16] Amjady, N., Majedi, S.F.: ‘Transient stability prediction by a hybrid
generation/load control or adjusting generation/load to make the intelligent system’, IEEE Trans. Power Syst., 2007, 22, (3), pp. 1275–1283
[17] Liu, C.-W.: ‘Application of synchronised phasor measurements to real-time
phase angle within limits. The utilisation of ACAT as an initiating transient stability prediction’, IEE Proc. Gener. Transm. Distrib., 1995, 142,
factor for relevant Special Protection Schemes or remedial action (4), p. 355
schemes, keeping in mind time criticality, is to be studied in the [18] Rovnyak, S., Liu, C.-W., Lu, J., et al.: ‘Predicting future behavior of transient
future scope of work. events rapidly enough to evaluate remedial control options in real-time’, IEEE
Trans. Power Syst., 1995, 10, (3), pp. 1195–1203
[19] Liu, C.-W., Thorp, J.S.: ‘New methods for computing power system dynamic
6 References response for real-time transient stability prediction’, IEEE Trans. Circuits
Syst. I, Fundam. Theory Appl., 2000, 47, (3), pp. 324–337
[1] Veloza, O.P., Santamaria, F.: ‘Analysis of major blackouts from 2003 to 2015: [20] Kumar, D.S., Savier, J.S.: ‘Synchrophasor based system integrity protection
classification of incidents and review of main causes’, The Electricity scheme for voltage stability in northern Kerala’. 2018 IEEE Innovative Smart
Journal, 2016, 29, (7), pp. 42–49 Grid Technologies-Asia (ISGT Asia), Suntec City, Singapore, 2018, pp. 634–
[2] UK Energy Research Centre (UKERC). What happened to our electricity 639
system on friday August 9th 2019'. 2019 [21] Jacome, Y., Figueroa, L., Palma, E., et al.: ‘Remedial action scheme based on
[3] Nordrum, A.: ‘Transmission failure causes nationwide blackout in Argentina’. synchrophasor measurements and system angle difference for peru's 500 kv
June 2019 grid’. Proc. of the 43rd Annual Western Protective Relay Conf., Spokane,
[4] Gallucci, M.: ‘Netblocks tracks Venezuela's power outage’. March 2019 WA, 2016
[5] Phadke, A.G., Thorp, J.S.: ‘Synchronized phasor measurements and their
applications’ (Springer, US, 2008)
5898 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5888-5898
© The Institution of Engineering and Technology 2020