VR 32 and Ever Tap Voltage Regulator Instructions Mn225008en
VR 32 and Ever Tap Voltage Regulator Instructions Mn225008en
SERIES
Effective January 2025
MN225008EN Supersedes June 2020
Contents
DISCLAIMER OF WARRANTIES AND LIMITATION MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
OF LIABILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II External Inspection. . . . . . . . . . . . . . . . . . . . . . . . . 25
SAFETY FOR LIFE . . . . . . . . . . . . . . . . . . . . . . . . . . IV Quik-Drive tap-changers . . . . . . . . . . . . . . . . . . . . . 26
EVER-Tap voltage regulator. . . . . . . . . . . . . . . . . . . 27
SAFETY INFORMATION . . . . . . . . . . . . . . . . . . . . . IV
Operational check . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Safety instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . iv
Insulating fluid maintenance. . . . . . . . . . . . . . . . . . 28
INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 EVER-Tap voltage regulator insulating fluid
Read this manual first. . . . . . . . . . . . . . . . . . . . . . . . 1 maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Additional information. . . . . . . . . . . . . . . . . . . . . . . . 1 Sampling insulating fluid. . . . . . . . . . . . . . . . . . . . . 29
Acceptance and initial inspection . . . . . . . . . . . . . . . 1 FR3 insulating fluid application. . . . . . . . . . . . . . . . 29
Handling and storage. . . . . . . . . . . . . . . . . . . . . . . . . 1 Untanking the regulator. . . . . . . . . . . . . . . . . . . . . . 29
Lifting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Retanking the regulator . . . . . . . . . . . . . . . . . . . . . 31
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Leak Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Quality standards. . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SPARE PARTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
PRODUCT INFORMATION. . . . . . . . . . . . . . . . . . . . . 3 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . 32
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . 32
Available options. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Regulator control reverse power flow test. . . . . . . 32
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Voltage regulator ratio test . . . . . . . . . . . . . . . . . . . 33
Pre-installation inspection . . . . . . . . . . . . . . . . . . . . . 5 Voltage regulator potential transformer ratio test. . 34
Systems connections . . . . . . . . . . . . . . . . . . . . . . . . 5 Regulator dry-out procedure. . . . . . . . . . . . . . . . . . 35
Nameplates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Voltage regulator current test. . . . . . . . . . . . . . . . . 35
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Insulation resistance test . . . . . . . . . . . . . . . . . . . . 37
Placing regulator into service . . . . . . . . . . . . . . . . . . 9 Freeing a stalled tap-changer. . . . . . . . . . . . . . . . . 37
! !
SAFETY
FOR LIFE
Safety for life SAFETY
FOR LIFE
Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power™ series products.
We actively promote safe practices in the use and maintenance of our products through our service literature, instructional
training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and
service.
We strongly urge that you always follow all locally-approved safety procedures and safety instructions when working around
high-voltage lines and equipment, and support our “Safety For Life” mission.
Safety information
The instructions in this manual are not intended as a Safety instructions
substitute for proper training or adequate experience in the
safe operation of the equipment described. Only competent Following are general caution and warning statements that
technicians who are familiar with this equipment should apply to this equipment. Additional statements, related to
install, operate, and service it. specific tasks and procedures, are located throughout the
manual.
A competent technician has these qualifications:
• Is thoroughly familiar with these instructions. DANGER
• Is trained in industry-accepted high- and low-voltage safe Hazardous voltage. Contact with hazardous voltage will
operating practices and procedures. cause death or severe personal injury. Follow all locally-
approved safety procedures when working around high-
• Is trained and authorized to energize, de-energize, clear, and low-voltage lines and equipment. G103.3
and ground power distribution equipment.
• Is trained in the care and use of protective equipment WARNING
such as arc flash clothing, safety glasses, face shield,
hard hat, rubber gloves, clampstick, hotstick, etc. Before installing, operating, maintaining, or testing this
equipment, carefully read and understand the contents
Following is important safety information. For safe of this manual. Improper operation, handling, or
installation and operation of this equipment, be sure to read maintenance can result in death, severe personal injury,
and understand all cautions and warnings. and equipment damage. G101.0
WARNING Standards
Eaton’s Cooper Power series regulators are designed and
Equipment Damage. Lift the entire unit only with tank- tested in accordance with the following standards:
mounted lifting lugs. The cover may warp or fracture
and the tank may separate from the cover if the cover- IEEE Std C37.90.1-2012™ standard
mounted lifting eyes are used to lift the entire unit
causing death or severe personal injury and equipment IEEE Std C37.90.2-2004™ standard
damage. IEEE Std C57.13-2016™ standard
IEEE Std C57.15-2017™/IEC 60076-21:2018-12 standard
Lifting IEEE Std C37.91-2021™ standard
When lifting a voltage regulator using an overhead crane IEEE Std C57.131-2012™ standard
to unload, or for installation or deinstallation, it is strongly
recommended that the lift be made by means of a lifting EN 50081-2
strap and spreader bar utilizing the tank-mounted lifting
lugs; see Figure 3 on page 4 for the location of lifting EN 61000-4
lugs. Never lift the entire voltage regulator with the lifting IEC 60068-2
eyes on the cover. The lifting eyes are only to be used to
untank the internal assembly which is attached to the cover. IEC 60214-1
Whether lifting a voltage regulator with a lifting strap and IEC 610255-5
spreader bar or using a lifting strap without a spreader bar,
it is important to perform the lift as vertically as possible
to minimize the possibility of damage to the unit. The Quality standards
maximum angle from vertical of the lifting strap is to be
no more that 25°. The 25° maximum angle applies to both ISO 9001 Certified Quality Management System
2- and 4-lift lug tank designs. The clearance between
lifting straps and any cover-mounted components is to
be a minimum of 3 inches. It is recommended that the
series arrester be removed before lifting to eliminate the
possibility of clearance issues between the arrester and
lifting straps. See Figure 1 for a lifting diagram example.
Product information
Description
VR-32 and EVER-Tap single-phase step-voltage regulators
from Eaton operate to keep voltage levels within
programmed limits to improve power quality and are
compatible with SCADA and automation distribution
systems.
Available in pole-, platform-, and pad-mounted and
substation configurations, VR-32 voltage regulators are
suitable for three- or four-wire overhead and underground
systems. EVER-Tap voltage regulators are manufactured
primarily for installation in substations.
Eaton voltage regulators are regulating auto-transformers. Figure 2. Quick connect/disconnect cable
They regulate rated voltage from 10% raise (boost) to 10%
lower (buck) in 32 approximately 5/8% steps.
The 65 °C rise insulation system and the sealed-tank Available options
construction allow for a bonus capacity 12% above the
55 °C nominal rating without loss of normal insulation Available options include:
life. The bonus capacity is stated on the nameplate. For • Extended-length control cable, lengths up to 120 feet
example, A 167/187 kVA rating indicates a nominal rating of
167 kVA and a bonus capacity rating of 187 kVA.
• Armored control cable
• Shielded control cable
Unit construction, which suspends the internal assembly
from the cover, allows for ease of inspection and • Adjustable galvanized-steel elevating structure
maintenance. • Supplemental external fusing to prevent damage from
Eaton manufactures four types of step-voltage regulators: reverse polarity connection to the external-source
source-side series winding (Type B), load-side series terminals
winding (Type A), series transformer (Type TX), and series • Shunt surge arresters
auto transformer (Type AX). Eaton voltage regulators • Insulating fluid 25°C level sight gauge
are usually equipped with an equalizer winding. The
nameplates located on the tank and control box define the • Insulating fluid thermometer with or without alarm
power circuit. contacts
Cover
Lifting eyes for
untanking
Position indicator
Upper filter press
connection
Cover-ground strap
Ball-type 25 C° insulating
fluid level sight gauge
Control cable with
Quick-Disconnect plug
CL-7 control
Figure 3. External features of the VR-32 and EVER-Tap voltage regulator
6. If the regulator has been stored for some time, test the Ø
Load
dielectric strength of the insulating fluid according to N
Table 5 and Table 6 (page 28).
7. Regulator may be energized at rated voltage (with
caution); you can then perform the ”Operational
check” on page 28. This procedure is optional.
8. A high-potential test may be done to ensure adequate
electrical clearances to ground. This procedure is
optional.
Control
Box
A
Source
Load
C
N
Control
Box
Figure 5. Regulating one phase of a three-phase, four- Figure 6. Regulating a three-phase, three-wire circuit
wire circuit regulator with two regulators (Open Delta)
A
Source
Load
C
N
Figure 7. Regulating a three-phase, four-wire, multi-grounded wye (star) circuit with three regulators (Wye)
A
Source
Load
B
C
Figure 8. Regulating a three-phase, three-wire circuit with three regulators (Closed Delta)
Nameplates Mounting
Two anodized aluminum nameplates are provided as Regulators with over-head bushings can be mounted on
standard; refer to Figure 9 and Figure 10. One nameplate a pole, a cross-arm platform, or an elevating structure.
is placed on the regulator tank. The other is placed on the Regulators are normally provided with either pole-mounting
control box door. Nameplates provide information necessary brackets or a substation base according to their rating. An
for proper control function. Information such as CT ratio, elevating structure can be provided to simplify substation
PT ratio, regulator type, and tap-changer type can be found installation of regulators requiring a specific live part-to-
on the nameplates. When a control is delivered mounted ground clearance.
onto a regulator, the nameplate data will be programmed
into the control at the factory. It is recommended that The regulator control can be mounted on the regulator
this information be verified prior to placing the control and tank or at a point remote from the unit. Various lengths of
regulator into service. When calling Eaton for service or rubber-coated control cables are available up to 120 feet
support-related issues, have the catalog number and serial (36.6 meters).
number found on the nameplate for reference.
DANGER
TO PREVENT INJURY OR DEATH TO PERSONNEL AND
DAMAGE TO EQUIPMENT, THE FOLLOWING STEPS
MUST BE PERFORMED PRIOR TO OPERATING THE
BYPASS SWITCH.
3. The tap changer motor SHALL be disabled before 3. The orange knife switches on back panel should be
performing the bypass operation to prevent properly set for operation:
inadvertent operation of the tap changer motor. Use
these steps to disable the motor:
• V1 for PT closed/pushed in.
• FIRST move the CONTROL FUNCTION switch • V6 for internal differential PT closed/pushed in.
(labeled AUTO/REMOTE-OFF-LOCAL MANUAL) • V2 (if present) for auxiliary winding closed/pushed in.
to the OFF position. Failure to do this FIRST may
result in the tap changer stepping off NETURAL • V8 (if present) for EVER-Tap motor power closed/
immediately upon being energized. pushed in.
• Move the control power switch to OFF. • C for CT shorting Open/pulled out.
• Remove the motor fuse.
4. Apply 120 V (or 240 V if indicated by the decal on the
• On the panel behind the control, open the V1, V6 control) to external source terminals.
and if present the V2 and V8 switches.
5. Lift raise-lower switch to operate tap-changer two or
8. Confirm the voltage regulator has been placed in three steps, then depress raise-lower switch to return
neutral before proceeding by observing these four tap-changer to neutral position; these steps verify
indicators: that the mechanism is functional. When on neutral,
the neutral light will glow continuously and position
a. Neutral light is illuminated continuously and indicator will point to zero or N for Neutral.
brightly.
b. Tap-position indication on the control at FC 12 DANGER
displays 0 for neutral.
TO PREVENT INJURY OR DEATH TO PERSONNEL AND
c. Position indicator dial pointer is pointing directly at DAMAGE TO EQUIPMENT, THE FOLLOWING STEPS
N or 0 for neutral. MUST BE PERFORMED PRIOR TO OPERATING THE
BYPASS SWITCH.
d. Measure the voltage difference between the S
and L bushings using an approved voltmeter or 1. ALWAYS WEAR PROPER PERSONAL PROTECTIVE
the SAFE-TO-BYPASS feature on the CL-7 series EQUIPMENT (PPE) when operating or servicing this
control. The voltage should measure zero or very equipment.
close to zero.
2. The regulator MUST be placed in the NEUTRAL
9. With the regulator in neutral position, disable the motor position. If all of the following indicators do not
operation by taking the following steps: confirm NEUTRAL, the regulator MUST NOT be
bypassed:
a. Set the CONTROL FUNCTION switch to OFF.
• The position indicator pointing to N (neutral).
b. Set the POWER switch to OFF. • The neutral light on the regulator control
c. Open the V1 and V6 knife switches and, if present, illuminated continuously and brightly.
open the V2 and V8 switches. • The control tap-position display indicating 0
d. Remove the 6 Amp motor fuse. (zero).
• The voltage difference measured between the
10. Close load (L) disconnect switch. S and L bushings to be less than 0.25% of the
11. Open bypass switch. The regulator is now energized. system line voltage using a calibrated meter or
the Eaton regulator control SAFE-TO-BYPASS
12. Replace 6 A motor fuse, close the V1 and V6 knife feature.
switches and, if present, the V2 and V8 switches, and
3. The tap changer motor MUST be disabled before
set the POWER switch to INTERNAL.
performing the bypass operation to prevent
13. Refer to Service Information MN225003EN, CL-7 inadvertent operation of the tap changer motor. Use
Voltage Regulator Control Installation, Operation, and these steps to disable the motor:
Maintenance Instructions, for information on the CL-7 • FIRST move the CONTROL FUNCTION switch
series voltage regulator control, including placing the (labeled AUTO/REMOTE-OFF-LOCAL MANUAL)
control into service and initial programming. to the OFF position. Failure to do this FIRST may
result in the tap changer stepping off NETURAL
immediately upon being energized.
Procedure B: Regulator bypass-disconnect switch
• Move the control power switch to OFF.
1. Verify from regulator nameplate that control circuit is • Remove the motor fuse.
connected for proper regulated system voltage.
• On the panel behind the control, open the V1, V6
2. Set CONTROL FUNCTION switch to LOCAL MANUAL and if present the V2 and V8 switches.
and POWER switch to EXTERNAL.
6. Confirm the voltage regulator has been placed in Setting the manual (hard) limit switches
neutral before proceeding by observing these four Note: Refer to “Position indicator and ADD-AMP
indicators:
capability” on page 15 for a complete discussion
a. Neutral light is illuminated continuously and of these features.
brightly.
Before setting the manual limit switches, be sure the new
b. Tap-position indication on the control at FC 12 settings will not conflict with the present tap-changer
displays 0 for neutral. position; see Figure 14. Do not set the switches below the
indicated tap-changer position. For example, if the main
c. Position indicator dial pointer is pointing directly at hand is at step 12 and the change to be made is from plus
N or 0 for neutral. or minus 10% (step 16) to plus or minus 5% (step 8), run
d. Measure the voltage difference between the S and the tap-changer back to step 7 or less, manually. Then set
L bushings. On a de-energized voltage regulator, the limit switches for plus or minus 5% regulation.
this can be done by applying a low voltage (for Limit switches should be set in anticipation of the maximum
example 120 Vac) between the S and SL bushings. deviation of primary voltage. For example, on a circuit
The measured voltage between the S and L where 7200 V is to be maintained, plus or minus 10% will
bushings should be zero or very close to zero. permit voltages between 6480 V and 7920 V to be regulated
Note: Operating the tap changer when applying effectively. For voltages outside this range, the regulator
120 Vac between the S and SL bushings will not be able to return the voltage to the preselected
will create a voltage change of 0.75 Vac level (7200 V). Five percent regulation would accommodate
circuit voltages between 6840 and 7560 V, maintaining 7200
between the S and L bushings for each
V for all voltages in this range.
step.
To set the limit switches:
7. Remove the voltage from external source terminals.
8. With regulator in the neutral position, set CONTROL 1. Unlatch the captive bezel and swing the cover open.
FUNCTION switch to OFF, set POWER switch to OFF, 2. Lift the limit-switch adjustment lever free of the detent
and remove 6 A motor fuse. and slide it to the new setting allowing the lever to
9. For Delta applications only: Close source-load (SL) snap into the detent stop.
disconnect switch. Note: If the ADD-AMP limits have been programmed
10. Close regulator bypass-disconnect switch. The regulator into the control (Soft ADD-AMP) and the limit
is now energized. switches have not been set, it is possible to
manually step the tap-changer beyond the Soft
11. Replace 6 A motor fuse, close the V1 and V6 knife ADD-AMP limit. If the unit is switched back
switches and, if present, the V2 and V8 switches, and
to automatic mode, the control will step the
set POWER switch to INTERNAL.
regulator back to within the Soft ADD-AMP limits
12. Refer to Service Information MN225003EN, CL-7 as set in the control.
Voltage Regulator Control Installation, Operation, and
Maintenance Instructions, for information on the CL-7
series voltage regulator control, including placing the
control into service and initial programming.
provisions. All grounding provisions are located near the Table 2. ADD-AMP adjustments
base of the regulator.
Regulation (%) Current (%)
Nameplates. Each regulator has two laser-etched
nameplates, one mounted on the control enclosure and the ± 10.0 100
other mounted on the regulator tank. The nameplates have ± 8.75 110
the manufacturer code and serial number bar-coded with ± 7.5 120
“3 of 9” coding with a 0.25" minimum height. ± 6.25 135
Pressure-relief device. A pressure-relief device vents at ± 5.0 160
approximately 5 psig.
Tank and Cover. The sealed-tank construction permits The position indicator (see Figure 3 and Figure 14) is
operation at 65 °C AWR without increasing the oxidation mounted on the junction box on the cover of the regulator
rate of the insulating fluid. and is directly connected to the tap-changer by a flexible
The external parts of the tank and control enclosure are drive shaft passing through the junction box and terminal
painted light gray, ANSI® 70 (Munsell 5BG7.0/0.4), and board via a sealing gland.
meet the coating and security requirements of IEEE Std The indicator face is graduated in steps. Drag hands
C57.12.28™-2014 and IEEE Std C57.12.31™-2010 standards. indicate the maximum and minimum positions attained
Also, the inside of the tank and bottom of the cover are during raise and lower operations. The drag hands are reset
primed and/or painted. around the main hand position by operating the drag-hand
An external electrical connection between the cover and reset switch on the control front panel.
tank allows the cover-suspended internal assembly and tank During forward power flow, the main hand of the position
to be grounded together to eliminate voltage differentials indicator will be to the right of the neutral position when
while energized. the regulator is boosting. During reverse power flow, the
Thermometer. Provisions for a tank thermometer are main hand will be to the left of the neutral position when
standard for all voltage regulators with substation bases the regulator is boosting.
(units 167 kVA and above).
The limit switches on the position indicator can be adjusted
Control cable. A multi-conductor neoprene 600 V, –50 °C to limit the maximum and minimum tap positions with
to 105 °C cable with disconnect plugs at each end provides possible settings of raise or lower 8, 10, 12, 14 or 16.
the connection between the internal circuitry of the voltage These limits correspond to percent regulation levels of 5,
regulator and the control. 6 1/4, 7 1/2, 8 3/4, and 10%. The five possible load current
ratings associated with the reduced regulation ranges
Current transformer. An automatic, solid-state CT shorting are summarized in Table 12 (page 41) and Table 13
device protects the internal CT from high voltages due (page 42). Higher regulation ranges are realized in closed
to the control cable being disconnected or cut while the delta application.
voltage regulator is energized.
Internal differential potential transformer (IDPT). The When using the limit switches, a detent stop at each
IDPT provide for a differential voltage measurement setting provides positive adjustment. Settings other than
between the S and L bushings. This measurement is used those stops are not recommended. The raise and lower
by the regulator control for reverse power regulation, SAFE- limits need not be the same value unless reverse power is
TO-BYPASS feature, and enhanced tap position tracking. possible. The regulator will stay within the ADD-AMP limits
set forth by the control or the position indicator, whichever
limit is of a lower regulation percentage.
Position indicator and ADD-AMP capability Note: If Soft ADD-AMP limits have been programmed into
Regulators rated below 668 A include an ADD-AMP the control and the position indicator limit switches
feature which permits additional current-carrying capacity have not been set, it is possible to manually step
at reduced voltage regulation range, as shown in Table 2, the tap-changer beyond these limits. If the unit is
but not to exceed 668 A. The ADD-AMP type adjustment switched back to automatic mode, the control will
is located inside the position-indicator faceplate to prevent step the regulator back to within the Soft ADD-AMP
inadvertent adjustment. In addition, a Soft ADD-AMP limits set in the control.
control feature allows adjustment by way of the keypad or
interface software. An optional ADD-AMP feature maximum
of 875 A is provided when specified for regulators rated Surge protection
438–668 A.
Series arrester
All Eaton voltage regulators are equipped with a bypass
arrester connected across the series winding between
the source (S) and load (L) bushings. This arrester limits
the voltage developed across the series winding during
lightning strikes, switching surges, and line faults. The
series surge arrester can be seen in Figure 3. A heavy-
duty MOV-type series surge arrester of 3 kV offers series A patterned, epoxy-coated insulation paper is used in
winding protection on all regulators except those rated all windings. Prior to assembly of the main core and
22,000 V and greater, which have a 6 kV MOV-type series coil assembly, the windings are baked with sufficient
surge arrester. mechanical pressure exerted on the sides of the coil
winding to maximize a complete bonding of the insulation
Shunt arresters to improve its short-circuit current withstand capabilities.
A shunt arrester is a recommended accessory on Eaton The main core and coil assemblies are of the shell-form
voltage regulators for protection of the shunt winding. The configuration. The series winding on the input (source) side
shunt arrester is a direct-connected arrester mounted on of the regulator (Figure 15) allows all windings (control,
the tank and connected between the bushing and ground shunt and series) to be located in one coil assembly. The
(earth). It is recommended that arresters be applied to all load voltage is monitored by the control winding.
non-grounded bushings. Regulators that have the series winding on the output
For best results, locate these arresters on the mounting (load) side (Figure 16) have a separate potential transformer
pads provided on the tank near the bushing. Connect installed on the load side in lieu of a control winding.
the arrester and the regulator tank to the same ground The control winding or separate potential transformer
connection using the shortest cable possible. Shunt (PT) supplies a voltage for the tap-changer motor and the
arrester application data is listed in Table 3. control sensing circuit. Additional taps are available in the
Table 3. Typical shunt arrester application data a PT for line voltages other than rated voltage.
VR VL
S L
1 2 3 4 5 6 7 8 N
Source Load
E3 C2 C1
E2 CONTROL
E1 V1
E G
SL
Figure 15. Power circuit—series winding located on the source-side, ANSI® Type B
VR VL
S L
N 1 2 3 4 5 6 7 8
Source Load
E3 C2 C1
E2 CONTROL
E1 V1
E G
SL
Figure 16. Power circuit—series winding located on the load-side, ANSI® Type A
S L
6
VR
5
4 E3 C2 C1
Source VL E2 Load
3 CONTROL
2 E1 V1
1 E G
SL
Figure 17. Power circuit – series auto transformer, Type AX (similar characteristics to Type A)
S L
2 E3 C2 C1
Source 3 E2 Load
CONTROL
VL
4 E1 V1
5 E G
VR 6
SL
Voltage circuits Most voltage regulators are installed in circuits with well-
Eaton voltage regulators have provisions for operation at defined power flow from source to load. However, some
system voltages other than the nominal rating, as listed circuits have interconnections or loops in which the direction
in Table 10 (page 39) and Table 11 (page 40). This is of power flow through the regulator may change. For
accomplished by providing taps on the control winding or optimum utility system performance, a regulator installed on
PT. The taps are brought to a terminal board located on top such a circuit should have the capability of detecting reverse
of the tap-changer assembly, under the insulating fluid, and power flow and of sensing and controlling the voltage,
are marked E1, E2, or E3. (See Figure 19.) The connections regardless of the power flow direction. The CL-7 control has
are made with push-on terminals and are easily accessed full reverse power capabilities.
through the hand hole. Refer to Service Information MN225003EN, CL-7 Voltage
Regulator Control Installation, Operation, and Maintenance
Instructions, for more information on the CL-7 series
control, reverse power operation, and source-side voltage
calculation.
The three back-panel potentials (VS, sensing voltage; V7,
E Taps differential voltage; VM, motor and control power voltage)
are all brought directly to the control power switch. When
no IDPT is present, the V7 terminal is connected to the
VS terminal on the control back panel and the control
software then recognizes that a source-side voltage signal
is not present and a calculation is required to determine the
S-bushing voltage.
The power switch has three positions: INTERNAL, OFF,
and EXTERNAL. The internal position powers the control
and motor from the regulator sensing winding, and the
Figure 19. PT tap terminals on a QD3 tap-changer external position permits an external supply for the same
purpose. When the power switch is in the external position,
For voltage regulators equipped with an internal differential the internal supply is disconnected to prevent accidentally
potential transformer (IDPT), “P” tap connections will back-feeding the high-voltage winding and bushings. The
be provided and located either on a separate voltage external-source terminals are prominently located adjacent
transformer or on the tap-changer terminal board. to the voltmeter test terminals.
The PT cannot always provide adjustment of the voltage fine The voltmeter terminals allow the monitoring of the voltage
enough for control or motor use. A tapped autotransformer that is applied to the control. This is the voltage output
is used for fine voltage adjustment. This transformer, the from the RCT and the voltage displayed at FC47 (Voltage
Ratio Correction Transformer (RCT), has input taps at 104, Calibration). During forward power flow, the voltage at these
110, 115, 120, 127, and 133 V. The output tap to the control terminals is the output voltage. During reverse power flow,
and motor is set as 120 V. The RCT is located on the control the voltage at these terminals is the source-side voltage.
back panel (see Figure 11 and Figure 12). From the 6 A fuse, the motor potential provides power
To operate a regulator on a system voltage other than its to the CONTROL FUNCTION switch, the drag-hand reset
nominal rating, the appropriate selection must be made solenoid, the neutral light, and the holding switch (alternate
for the PT, RCT, and IDPT taps and the control must be motor source) circuits.
programmed properly at Function Code (FC) 43 (System
Line Voltage), FC44 (Overall PT Ratio) and FC44 (Internal WARNING
PT Ratio). The nameplate provides settings for common
system voltages (see Figure 9 and Figure 10). Electrocution Hazard. Applying voltage to the voltmeter
terminals on some voltage regulator controls can back-
The internal voltage supply is brought from the tap-changer feed the voltage regulator potential transformer and
terminal board through the junction box and the control create high voltage on the bushings. When applying
cable, into the control box, terminating at the knife switch external power to the voltage regulator control, make
labeled V1. Units equipped with an IDPT will have a V6 sure to open the V1, V6, and if present, the V2 and V8
switch to interrupt this circuit. There may also be a V2 switches on the back panel, apply power to the external
switch to interrupt an auxiliary power winding and a V8 source terminals only and move the POWER switch to
switch provided on EVER-Tap units to interrupt the motor EXTERNAL.
power supply. Opening these knife switches provides a
visible means of removing all power to the control and
motor circuits. From the knife switch, the voltage is ratio
corrected by RCT as previously described.
Current circuit Table 4. Current transformer applications (50 & 60 Hz)
All Eaton voltage regulators are designed with an internal Regulator Current Ratings CT Primary Current
current transformer (CT) (see Figure 20) to provide a current
source for the line-drop compensation calculations, power 50 50
flow direction determination and for metering functions. 75 75
Table 4 provides the application information for the various 100 100
CTs used on Eaton regulators. These CTs provide 200 mA
output for the rated CT primary current. 150 150
167, 200 200
219, 231, 250 250
289, 300 300
328, 334, 347, 400 400
418, 438, 463, 500, 502 500
548, 578, 604, 656, 668 600
833, 875, 1000, 1093 1000
1332, 1503, 1665 1600
2800 3000
Motor circuit
The motor circuit power is brought from the 6 A fuse to
the circuit board through a set of back-to-back diodes to the
CONTROL FUNCTION switch. When this switch is set for
automatic operation, motor power is applied to the relays.
An appropriate relay closure then applies this power to
the tap-changer motor, after first passing through the limit
switch contacts in the position indicator. When the switch
is set for manual operation, the power is transferred to
Figure 20. Internal bushing-mounted current
the momentary toggle switch labeled RAISE/LOWER. By
transformer
actuating this switch in one direction or the other, power
is applied through the limit switch contacts, directly to the
The current developed by the CT is brought through the tap-changer motor, completely bypassing the control circuit
control cable and junction box, into the control box and board. This enables operation of the tap-changer in most
terminates at the knife switch labeled C. Closing the knife circumstances, even if the control cannot be powered up
switch provides a visible means of shorting the CT, thus fully.
allowing the operator to work safely on the current circuitry.
For additional safety measures, the V1, V2, V6, and V8 Also included as a part of the motor circuit is an alternate
knife switches should also be opened. For all regulators with feed to the motor called the holding switch circuit. Located
the quick-disconnect connector (Figure 2), an automatic on the tap-changer are switches which operate off of the
solid-state CT shorting device is located in the junction box. tap-changing mechanism. Motor rotation causes switch
This solid-state device will automatically short the CT when closure (one direction or the other) and establishes a
the cable is disconnected. complete circuit for motor current until the rotation is
complete and the cam drops out. During the time the
At the C switch, one side of the CT is connected to holding switch is closed, motor current is monitored by
the equipment ground and is also routed to the control way of an input on the control circuit board that permits
for termination on the circuit board. The “high” side of the control to detect that a tap change is in process.
the current circuit is brought to the top terminal board The microprocessor uses this information in its decision-
through two removable jumpers and then to the control for making process, as described under Control Operating
connection to the circuit board. Once this current signal is Modes in Service Information MN225003EN, CL-7 Voltage
delivered to the circuit board, it is transformed into a voltage Regulator Control Installation, Operation, and Maintenance
signal and converted into a digital format for processing. Instructions.
Two other circuits that share the 6 A motor source are
the drag-hand reset and neutral light circuits. The drag-
hand reset function is accomplished simply by operating
a momentary membrane switch, which applies power to
the reset solenoid in the position indicator. The neutral
light is energized from a neutral light switch located on the
tap-changer when in the neutral tap position.
Quik-Drive tap-changers
Eaton offers three Quik-Drive tap-changer models (see
Figure 21, Figure 22, and Figure 23). Each device is sized
for a specific range of current and voltage applications and
share many similarities in their construction. The primary
benefits of Quik-Drive tap-changers are: direct motor drive
for simplicity and reliability; high-speed tap selection for
quicker serviceability; and proven mechanical life (one
million operations). Quik-Drive load tap-changers meet
IEEE® and IEC standards for mechanical, electrical, and
thermal performance.
limiting functions. Other motor drive units may be powered EVER-Tap important operational information
and controlled directly by the voltage regulator control. In
either case, the voltage regulator control is responsible for WARNING
initiating a tap change. The motor drive model will be listed
on the voltage regulator nameplate. For all EVER-Tap™ The user of this equipment should be properly trained
manufactured prior to 2020, the voltage regulator was in the operation of voltage regulators. Wiring and
supplied with the ETMD-A motor drive unit. Function Code operation of the EVER-TAP™ voltage regulator is
49 may be used to select the motor drive or tap changer different than other voltage regulators equipped with
model. CL-7 controls. Only attempt to commission and operate
an EVER-Tap™ voltage regulator after thoroughly
The CL-7 voltage regulator control utilizes an additional reading and understanding this document as well as the
actuator board for use with the ETMD-A motor drive unit voltage regulator and control manuals.
to power the tap changer. A 100 µF run capacitor and a 50
µF start capacitor are required for operation of the ETMD-A
with actuator board. Back panel wiring in the control box for EVER-TAP controls and control boxes
the ETMD-A is not compatible with Quik-Drive tap changers. Important information pertaining to a CL-7 control and
The CL-7 will trigger the actuator board to make a tap control box equipped for use with and EVER-Tap voltage
change. If limit switches are not tripped, the actuator board regulator:
energizes the motor. After some rotation of the drivetrain, • EVER-Tap control boxes should only be used on
an operating switch is engaged to signal that the motor is EVER-Tap™ voltage regulators. The ETMD-A motor
responding to the command. Failure to receive this signal drive unit requires a special motor drive control circuitry
within several seconds will cause the actuator board to and capacitor configuration that is different from that
abort the tap change. In approximately 2 seconds, under of Eaton’s Quik-Drive tap changers. The wiring of the
normal operating conditions, the operating switch will be back-panel inside the control box and the wire harness
released, triggering the actuator board to stop the motor to the control cable are not compatible with Quik-Drive
drive unit and signal to the control that the tap change is equipped voltage regulators.
complete.
• Use the CL-7 equipped with an actuator board only
with an ETMD-A motor drive unit on an EVER-Tap™
Operating sequence
voltage regulator. Undesirable performance and unsafe
Within the interval of time the motor drive unit is rotating, operating conditions may result if any other control
the tap changer mechanism drives different linkages to configuration is used.
sequence the switch modules’ operations. First, a bypass
switch opens causing all the load current of one movable • The actuator board interfaces with the motor drive to
contact to flow through the vacuum interrupter. Second, ensure proper actuation of the tap changer.
the vacuum interrupter opens, stopping current through the
movable contact. Third, the movable contact is moved from • The actuator board monitors position limit switches and
one stationary tap to the next tap without electrical arcing operation cycle switches.
because the current was previously interrupted. Fourth, the • Starting and stopping functionality is augmented by the
vacuum interrupter closes and current flow is reinitiated actuator board.
through the movable contact. Finally, the bypass switch
closes causing the load current to be shunted around the
vacuum interrupter. EVER-Tap Internal/external/auxiliary power
Important information pertaining to powering of the CL-7
Reversing switch control when operating an EVER-Tap voltage regulator:
The reversing switch function changes the polarity of the • Two separate internal power circuits exist for the actuator
tapped winding. When an EVER-Tap tap-changer is in the board and CL-7 sensing and power circuits.
neutral position through position 16 Raise, the reversing
switch is in position B. When the tap selector moves • The V1 knife switch powers the VS sensing circuit and
between the neutral position and position 1 Lower, the VM control power circuit.
reversing switch moves between position A and B. • The V8 knife switch powers the actuator board for the
tap changer motor drive.
• Do not short V1 to V8. V1 and V8 are both nominally
120V to ground, however V1 and V8 are opposite phase
resulting in a nominal 240V from V1 to V8.
• Select INTERNAL power on both the CL-7 front panel
and the auxiliary swing panel power switches.
the power input receptacle on the auxiliary swing panel • The actuator board is triggered from the first raise or
inside the control box. lower signal that it receives from the CL-7 and locks out
further input until the end of the tap change cycle, so a
• The control box must be properly grounded. brief actuation of the raise/lower switch in “MANUAL”
• For external power, use a 120 VAC source referenced mode is enough to start and complete a tap change.
to ground. • It is acceptable to hold the raise/lower switch in one
– The neutral terminal is internally connected to position if multiple tap changes are to be made in the
chassis ground. same direction.
– The power source must be capable of supplying • Before reversing the direction of operation of the tap
15 Amps. changer, wait for the completion of a tap change cycle.
• The power input receptacle works with a standard • Due to the longer tap change cycle and differences
NEMA 5-15R extension cord set with normal polarity. in the internal mechanism, the user will notice that
Reversed polarity will short the external power supply the position indicator pointer moves slowly from one
to ground. position to the next compared to the rapid motion
generated by a Quik-Drive tap changer.
• After connecting the power cord, select EXTERNAL
power on both the CL-7 front panel and the auxiliary • If the tap changer fails to operate with the actuator
swing panel power switches to power on the control. board in AUTO or MANUAL mode, check that all wire
harness connections are tight and check the 15A fuse on
• For permanent auxiliary power to the CL-7 control and the actuator board.
actuator board (for example, using substation power)
• In the unlikely event that the tap changer fails to
• Contact the factory for a supplemental wiring move when commanded and/or stalls between taps,
schematic. wait for approximately 10 seconds while the actuator
• Wiring changes will be required on the back panel board resets and then trigger the tap changer to move
to avoid back-feeding the voltage regulator from the in the opposite direction. If the tap changer fails to move
auxiliary power source. again as commanded, there is likely a mechanical jam in
the tap changer or motor drive unit. It is also possible that
the voltage supply and/or temperature are too low.
EVER-Tap with motor drive unit ETMD-A CL-7 control settings
• CL-7 firmware version 1.15.0 or later is required on the Maintenance
CL-7 front panel
• From the CL-7 front panel, use Function Code 49 and The usable life of a regulator will vary depending upon the
select “Eaton ETMD-A”. Alternatively, this setting may be application but in any case, will be extended by periodic
changed using ProView NXG software. inspections and maintenance. Inspection and maintenance
schedules will vary and can be different for the same
• For normal operation using the CL-7 control in AUTO voltage regulator design depending upon system conditions
or LOCAL mode, ensure the actuator board control and loading. The best predictor of future maintenance
switch is in the “AUTO” position. This switch is near the requirements are past experiences.
wire harness connector to the actuator board.
• Emergency manual operation of the tap changer
without a working CL-7 front panel can be performed External Inspection
by moving the actuator board control switch to the • Inspect ground connections to the control box and
“MANUAL” position. A second toggle switch near the tank; take precautions to safely repair and replace any
wire harness of the actuator board is used to manually damaged ground connections.
trigger the actuator board to command “Raise” and
“Lower” operations. • On units installed on wye configured systems, inspect
ground connections to SL bushings; deenergize any unit
• The tap changer actuator board can be disabled by with an ungrounded or poorly grounded SL bushing and
setting the control switch to the “OFF” position between repair the ground connection.
“AUTO” and “MANUAL”.
• From the CL-7 front panel, manual and automatic DANGER
operation is similar to that of a Quik-Drive operation.
For voltage regulators connected in a wye-connected
However, keep these things in mind:
system, an ungrounded SL bushing will be at line
• A complete tap change cycle is approximately 2 voltage. If the ground connection to an SL bushing
seconds under most operating conditions. Cold becomes disconnected, take steps to deenergize the
temperature, especially with a low voltage supply to voltage regulator and reconnect the ground connection.
the control/actuator board, may result in longer cycle Contact with an ungrounded SL bushing will cause
times. death or severe personal injury.
Stationary contacts
• Inspect the arcing tips for excessive erosion.
• Inspect the contact surface for pitting and scoring.
• Replace excessively worn contacts.
Duty Cycle Monitor (DCM) results would be to compare values between subsequent
This feature is not available for the EVER-Tap voltage tests. Unusually rapid buildup of gases from one test to
regulator. another could be a sign of internal problems. Contact the
Voltage Regulator Support group at (866) 975-7347 (from
outside the U.S. and Canada call +1 (262) 896-2591) or
Operational check e-mail questions to [email protected] for further
assistance in evaluating DGA results.
Proper operation of the regulator can be checked without
removing the unit from service. When performing periodic maintenance of voltage
regulators, insulating fluid characteristics should be
To perform an operational check: evaluated. See Table 5 and Table 6 for information on the
characteristics that would be part of the evaluation and the
1. Place the CONTROL FUNCTION switch in LOCAL
levels to be measured against. When the fluid fails to meet
MANUAL.
the requirements shown in the tables, steps should be
2. Manually run the regulator several steps in the raise taken to filter or replace the fluid. These steps should be
direction until the OUT-OF-BAND HIGH LED illuminates performed during normal maintenance intervals.
continuously.
3. Place the CONTROL FUNCTION switch in AUTO/
REMOTE. After the time delay expires, the regulator
EVER-Tap voltage regulator insulating fluid
should return to within the band edge and the OUT-OF- maintenance
BAND HIGH LED should go out. The EVER-Tap voltage regulator is equipped with an arc
4. Again place the CONTROL FUNCTION switch in LOCAL interrupter. The arc occurring during tapping operations
MANUAL. occurs inside of the vacuum bottle. As a result, the
dielectric fluid will not become contaminated in the same
5. Manually run the regulator several steps in the lower way as a conventional voltage regulator. Dissolved gas
direction until the OUT-OF-BAND LOW LED illuminates analysis results from an EVER-Tap voltage regulator can be
continuously. treated like the results from a conventional transformer or
OLTC.
6. Place the CONTROL FUNCTION switch in AUTO/
REMOTE. After the time delay expires, the regulator
should return to within the band edge and the OUT-OF-
BAND LOW LED should go out. Table 5. Envirotemp™ FR3™ Fluid Characteristics
(natural ester a)
7. If the operations check does not complete successfully,
review the troubleshooting section of this manual Characteristic New Used
and refer to Service Information MN225003EN, CL-7 Dielectric Strength (kV) ASTM D1816:
Voltage Regulator Control Installation, Operation, and
2-mm gap ≥ 45 ≥ 40
Maintenance, for more instructions.
1-mm gap ≥ 25 ≥ 23
8. If further assistance is required, contact the Voltage
Interfacial Tension (mNm) ASTM D971-91 — —
Regulator Support group at (866) 975-7347 (from b
outside the U.S. and Canada call +1 (262) 896-2591) or Water (mg/kg) ASTM D1533 ≤ 300
e-mail questions to [email protected]. a Per IEEE Std C57.147™-2008 standard
b Recommended limit is application- and user-specific. Suggested limit would be the same
relative saturation limit used for mineral oil at a given temperature.
Insulating fluid maintenance
The operation of a conventional step voltage regulator
includes switching of a load tap-changer. Switching of this Table 6. Mineral Oil Characteristics (Type II a)
tap-changer will result in a small amount of arcing during Characteristic New Used
each operation. This is different from a typical transformer
or voltage regulator equipped with a vacuum interrupter. Dielectric Strength (kV) ASTM D1816:
Under normal conditions, you would expect no internal 2-mm gap ≥ 45 ≥ 40
arcing in a transformer and as a result, elevated levels of 1-mm gap ≥ 25 ≥ 23
arcing gases are an indication of trouble. For conventional
voltage regulators, arcing occurs inside the tank on every Interfacial Tension (mNm) ASTM D971 ≥ 38 ≥ 25
tap change. As a result, it is expected that gas levels will Water (mg/kg) ASTM D1533 ≤ 20 ≤ 35
build up over time. a Per IEEE Std C57.106™-2006 standard
WARNING
The lifting eyes on the top of the voltage regulator are
to be used for untanking only. Attempting to lift the
entire voltage regulator using the lifting eyes could
cause the tank to separate from the cover and fall to
the ground. This could cause death, personal injury, or
property damage.
WARNING
Personal Injury. Do not rely on the lifting apparatus
when the internal assembly is lifted for inspection or
maintenance. Blocking should be placed between the
cover and the top of the tank when partially untanking
the voltage regulator to keep the assembly from falling,
which can cause death or severe personal injury and
equipment damage.
Retanking the regulator 8. Check and retighten the horizontal, side-channel bolts
through the hand hole; torque to 50 ft-lbs (68 Nm).
Steps for retanking:
9. Properly reseal the hand-hole cover, being careful not to
1. If the core and coil assembly have been out of oil for damage the cover or the gasket.
more than 4 hours, the coil must be dried, as follows:
10. Connect the cover ground strap (see Figure 1).
a. Bake the unit at 100˚C (212˚F) for 24 hours.
11. Connect the control cable to the connector at the
Note: Units equipped with a phenolic tap-changer bottom of the junction box.
must be baked at a maximum temperature
of 66˚C (150˚F). 12. Pull a vacuum on the unit for at least one hour at
2 mm Hg (2 Torr) of vacuum or better after the unit is
Note: A unit can be rebaked a maximum of two completely refilled with fluid.
times over its life.
Note: If vacuum processing is not available, allow the
b. After baking, check all hardware for tightness. entire internal assembly to soak in fluid for at
c. Within four hours after baking, retank the unit and least 24 hours before energizing.
fill it with fluid.
Note: If baking is not possible or practical, see Leak Test
“Regulator dry-out procedure” on page 35 After retanking, a leak test is recommended to ensure that
for an alternative to baking. the cover is properly seal. To perform a leak test, take these
2. Verify that the position indicator shows the present steps:
position of the tap-changer. 1. Ensure that all appropriate plugs, valves, oil level
Note: If the position indicator is not showing the indicators, and thermometers are installed.
present position of the tap-changer, proceed as 2. Ensure that the outside areas of the tank, cover, cover
follows: band, bushings, plugs, valves, and position indicator
a. Remove the indicator cable in the junction box are free of oil.
box from the position indicator shaft after 3. Remove the pressure relief valve and in its place, install
loosening the set screw. a Schrader valve.
b. Rotate the indicator shaft until the proper 4. Apply dry nitrogen to the unit through the Schrader
position is reached; then tighten the set valve to a pressure shown in Table 7.
screw.
Table 7. Tanks Pressures for Leak Testing
c. Verify coordination of the position indicator
with the tap-changer in the neutral position Minimum
(control neutral light on). lbs/psi Time (hours)
3. Check the gasket seat surfaces on the cover and tank, Round Tanks w/Radiators 10 1
and wipe clean. Wipe the gasket and position it on the Round and Square Tanks w/Corrugate (All 7 1
tank lip. Mild Steel Corrugate, Any Stainless Steel
Corrugate Less Than 12”)
4. Loosen the horizontal, side channel bolts to ensure Round and Square Tanks w/ Stainless Steel 5 2
proper seating of the regulator in the tank and proper Corrugate 12” or Larger
cover seal.
The unit is considered to have passed the leak test if the
5. Raise the cover assembly and attached components following requirements have been met:
over the tank. Make certain of proper orientation.
• No more than 0.5 psi pressure loss over the period
6. Lower the unit, rotating the channels counter-clockwise specified in Table 7.
into the tank guides.
• No oil leaks at the welded seams, radiators, and gasket
7. Seat the unit in the tank. Tighten the cover band surfaces above and below the oil line.
or bolts. Torque the cover band to 18 – 22 ft-lbs
(24.4 – 29.8 Nm). Make sure the ends of the cover If the unit does not pass the leak test, steps should be
band do not touch when fully tightened. Torque taken to reseal the tank cover or repair leaks as necessary.
the cover bolts on a square-tanked regulator to Be sure to replace the pressure relief valve after completing
24 – 26 ft-lbs (32.5 – 35.6 Nm). the test.
Note: On round tanks, tap the cover with a rubber
hammer around the edge to assist in providing a
good seal while tightening the cover band.
Refer to the following Service Information documents for V1 V1A V1B V1C Load-Side PT
information on Eaton’s Cooper Power series tap-changer V6 V6A V6B V6C Differential PT
maintenance and replacement parts: C CA CB CC CT Shorting Switch
• MN225072EN, QD3 Quik-Drive Voltage Regulator C2 - - - CT +
Tap-Changer Manual C3 - - - CT +
R1 R3 R-B R-C Motor Raise
• MN225012EN, QD5 Quik-Drive Voltage Regulator
Tap-Changer Manual L1 L3 L-B L-C Motor Lower
G G G G Ground
• MN225011EN, QD8 Quik-Drive Voltage Regulator
Tap-Changer Manual HS HS HSB HSC Holding Switch
Required equipment
• Clamp-on ammeter
• Appropriate cable leads
• 2 – 120 V variable power supplies
Procedure
WARNING
Hazardous Voltage. This procedure must only be
performed on a regulator that has been removed from
service. Failure to comply can cause serious injury or
death.
4. Connect a separate 120 Vac supply to the EXTERNAL Note: On a type B regulator, the difference between
SOURCE terminals on the control front panel. Move the taps will be slightly less than calculated as
the control power switch to the EXTERNAL position to the regulator is tapped toward 16 Lower. This is
operate the tap-changer. normal and inherent in the design of the type B
regulator.
Note: For instruction on connecting the control to
an external source, see Service Information Questions about the described procedure may be directed
MN225003EN, CL-7 Voltage Regulator Control to the Voltage Regulator Support group at (866) 975-7347
Installation, Operation, and Maintenance (from outside the U.S. and Canada call +1 (262) 896-2591)
Instructions. or e-mail questions to [email protected].
5. Increase the voltage on the variac to 120 Vac. This will
provide 12 V on the series winding.
Voltage regulator potential transformer ratio test
120 Vac x 10% regulation = 12 V
Purpose
6. Calculate the change in volts per tap change as follows: The purpose of this test is to verify proper potential
transformer ratio.
series winding volts = 12 = 0.75 V per step
16 steps 16 Required equipment
Note: If 160 Vac is applied between the S and SL • Voltmeter
bushings, the calculations in step 5 and step 6 are • 120 V variable power supply
computed, you will see that a 1.0 volt difference • Appropriate cable leads
between steps will result. Doing this will simplify • Calculator
the ratio check.
Procedure
Table 9. Typical meter readings with 120 Vac
connected between the S and SL bushings
WARNING
Hazardous Voltage. This procedure must only be
Lower Raise
performed on a regulator that has been removed from
16L - 108.0 16R - 132.0 service. Failure to comply can cause serious injury or
15L - 108.75 15R - 131.25 death.
14L - 109.5 14R - 130.5
13L - 110.25 13R - 129.75 WARNING
12L - 111.0 12R - 129.0 Hazardous Voltage. When troubleshooting energized
11L - 111.75 11R - 128.25 equipment, protective gear must be worn to avoid
10L - 112.5 10R - 127.5 personal contact with energized parts. Failure to comply
9L - 113.25 9R - 126.75 can cause serious injury or death.
8L - 114.0 8R - 126.0 1. Remove the unit from service as described in
7L - 114.75 7R - 125.25 “Removal from service” on page 13.
6L - 115.5 6R - 124.5 2. Open the back-panel knife switch marked V1.
5L - 116.25 5R - 123.75
3. Note the correct PT ratio as given for the pinned Load
4L - 117.0 4R - 123.0
Volts on the nameplate under the Internal PT Ratio
3L - 117.75 3R - 122.25 column. The tap setting of the PT can be verified by
2L - 118.5 2R - 121.5 inspecting the tap-changer terminal board connection
1L - 119.25 1R - 120.75 through the hand-hole on the regulator cover. The
Neutral 120 tap-changer terminal board is located on the top of the
tap-changer under oil. The connection will be to E1, E2,
or E3 made by a wire from above the terminal board
7. Operate the tap-changer with the control switch marked E; this should correspond to the PT ratio for the
through all 32 steps from 16 Raise to 16 Lower. voltage pinned on the nameplate.
Record the voltmeter reading at each tap position. The
change in voltage should be almost the same between 4. With the regulator in the neutral position, connect 120
each step (± 0.10 volts). If a substantial difference in Vac between the S (Source) and the SL (Source Load)
any reading exists, then there is a problem with the bushings.
windings or their connection. Readings will be the 5. Using the formula below, determine the expected
same with or without the equalizer winding. output voltage of the PT.
Expected Voltage = 120 Vac/PT Ratio
1. Remove the unit from service as described in tap-changer moves from Neutral to 16 Raise position.
“Removal from service” on page 13. The current will reach its maximum value at a specific
position dependent on the type and rating of the
WARNING regulator. Current reduces to zero when it reaches the
neutral position.
Hazardous Voltage. When troubleshooting energized
equipment, protective gear must be worn to avoid
personal contact with energized parts. Failure to comply
can cause serious injury or death.
2. Conduct this test with the regulator located in the
maintenance shop or other suitable location.
CAUTION
Equipment Damage. When connecting external power to
the voltage regulator control, make sure the polarity of
the power source is correct. Reverse polarity will result
in control damage.
CAUTION
Equipment Damage. Only an AC power supply is to be
used to energize the control externally. Do not use a
DC-to-AC voltage inverter. Failure to comply can cause
excessive harmonics to be generated and result in
damage to the control.
3. Use an external source to power the control and
enable tap-changer operation. See Service Information
MN225003EN, CL-7 Voltage Regulator Control
Installation, Operation, and Maintenance Instructions,
for detailed information on powering the control
externally.
4. Place a jumper, rated for nominal current, between the S
(Source) and L (Load) bushings. Use a clamp-on ammeter Figure 26. Removing jumper between C2 and C3
to measure the current in the jumper during the test.
WARNING
Hazardous Voltage. The regulator tank must be solidly
earth grounded. Failure to comply can
cause severe personal injury and equipment damage.
5. Ground the regulator tank.
6. Close C knife switch on the back panel.
7. Remove the jumper from between the C2 and C3
terminals to the left of the V1 switch, on the back
panel. See Figure 26. Place a milli-ampere meter
between these terminals. See Figure 27.
8. Using a variable voltage source, place approximately
120 V between the L and SL (Source-Load) bushings
until a current value is shown on the clamp-on meter.
9. Open the knife switch C on the back panel. The milli-
ampere meter should indicate a current value based on
the CT ratio shown on the rating plate.
10. Run the voltage regulator through all of the tap Figure 27. Milli-ammeter connection points
positions to check the continuity and reveal any
possible intermittent opens. The current indicated on
the clamp-on meter will increase or decrease as the
Insulation resistance test 6. Using the variac on the tester, bring the voltage up to
the desired test level. Refer to the instructions provided
Purpose with the test equipment for guidelines on voltage test
The purpose of this procedure is to describe the proper levels.
connections and procedure when performing an insulation 7. Read the test value in mega-ohms; then compare the
power factor test on a voltage regulator. reading with the baseline reading:
Required Equipment • If the new reading is lower than the baseline
reading, further testing and evaluation of the
• 120 V variable power supply
insulation is recommended.
• Cable lead jumper rated for nominal current
• Insulation power factor test equipment • If the new reading is the same as or higher than
the baseline reading, no further testing is indicated.
Procedure
Appendix
Connections and voltage levels
Table 10. Tap connections & voltage levels (60 Hz) Table 10. (continued)
Nominal Ratio-Adjusting Data Nominal Ratio-Adjusting Data
Regulator Single- Test Overall Regulator Single- Test Overall
Voltage Phase Internal PT RCT Terminal Potential Voltage Phase Internal PT RCT Terminal Potential
Rating Voltage Tap a Ratio Tap Voltage b Ratio b Rating Voltage Tap a Ratio Tap Voltage b Ratio b
1 2 3 4 5 6 7 1 2 3 4 5 6 7
2500 2500 – 20:1 120 125 20:1 34500 34500 E1/P1 287.5:1 120 120 287.5:1
2400 – 20:1 120 120 20:1 19920 E2/P2 165.5:1 120 120.5 165.5:1
5000 5000 E1/P1 40:1 120 125 40:1 a P taps are used with E taps only on regulators where an internal potential transformer is
4800 E1/P1 40:1 120 120 40:1 used in conjunction with the control winding to provide voltage supplies to the control.
4160 E1/P1 40:1 104 120 34.7:1 See nameplate for verification of this type of control supply.
b Test terminal voltage and overall potential ratio may vary slightly from one regulator to
2400 E2/P2 20:1 120 120 20:1
another. See the regulator nameplate for determining the exact values.
7620 8000 E1/P1 60:1 133 120.5 66.5:1
7970 E1/P1 60:1 133 120 66.5:1
7620 E1/P1 60:1 127 120 63.5:1
7200 E1/P1 60:1 120 120 60:1
6930 E1/P1 60:1 115 120.5 57.5:1
4800 E2/P2 40:1 120 120 40:1
4160 E2/P2 40:1 104 120 34.7:1
2400 E3/P3 20:1 120 120 20:1
13800 13800 E1/P1 115:1 120 120 115:1
13200 E1/P1 115:1 115 120 110.2:1
12470 E1/P1 115:1 104 120 99.7:1
12000 E1/P1 115:1 104 120 99.7:1
7970 E2/P2 57.5:1 133 120 63.7:1
7620 E2/P2 57.5:1 133 120 63.7:1
7200 E2/P2 57.5:1 120 120 57.5:1
6930 E2/P2 57.5:1 120 120 57.5:1
14400 14400 E1/P1 120:1 120 120 120:1
13800 E1/P1 120:1 115 120 115:1
13200 E1/P1 120:1 110 120 110:1
12000 E1/P1 120:1 104 115.5 104:1
7970 E2/P2 60:1 133 120 65.5:1
7620 E2/P2 60:1 127 120 63.5:1
7200 E2/P2 60:1 120 120 60:1
6930 E2/P2 60:1 150 120.5 57.5:1
19920 19920 E1/P1 166:1 120 120 166:1
17200 E1/P1 166:1 104 119.5 143.9:1
16000 E2/P2 120:1 133 120.5 133:1
15242 E2/P2 120:1 127 120 127:1
14400 E2/P2 120:1 120 120 120:1
7970 E3/P3 60:1 133 120 65.5:1
7620 E3/P3 60:1 127 120 63.5:1
7200 E3/P3 60:1 120 120 60:1
ADD-AMP capabilities
Table 12. ADD-AMP capabilities of 60 Hz ratings Table 12. (continued)
Load Current Ratings (A) a Load Current Ratings (A) a
Regulation Range (Wye and Open Delta) Regulation Range (Wye and Open Delta)
± 10% ± 8.75% ± 7.5% ± 6.25% ± 5% ± 10% ± 8.75% ± 7.5% ± 6.25% ± 5%
Rated Rated Regulation Range (Closed Delta) Rated Rated Regulation Range (Closed Delta)
Volts kVA ± 15% ± 13.1% ± 11.3% ± 9.4% ± 7.5% Volts kVA ± 15% ± 13.1% ± 11.3% ± 9.4% ± 7.5%
2500 50 200 220 240 270 320 14400 72 50 55 60 68 80
75 300 330 360 405 480 144 100 110 120 135 160
100 400 440 480 540 640 288 200 220 240 270 320
125 500 550 600 668 668 333 231 254 277 312 370
167 668 668 668 668 668 416 289 318 347 390 462
250 1000 1000 1000 1000 1000 432 300 330 360 405 480
333 1332 1332 1332 1332 1332 500 347 382 416 468 555
416.3 1665 1665 1665 1665 1665 576 400 440 480 540 640
5000 25 50 55 60 68 80 667 463 509 556 625 668
50 100 110 120 135 160 720 500 550 600 668 668
100 200 220 240 270 320 833 578 636 668 668 668
125 250 275 300 338 400 19920 100 50.2 55 60 68 80
167 334 367 401 451 534 200 100.4 110 120 135 160
250 500 550 600 668 668 333 167 184 200 225 267
333 668 668 668 668 668 400 200.8 220 240 270 320
416.3 833 833 833 833 833 500 250 275 300 338 400
7620 b 38.1 50 55 60 68 80 667 335 369 402 452 536
57.2 75 83 90 101 120 833 418 460 502 564 668
76.2 100 110 120 135 160 1000 502 552 602 668 668
114.3 150 165 180 203 240 34500 172.5 50 55 60 68 80
167 219 241 263 296 350 345 100 110 120 135 160
250 328 361 394 443 525 517 150 165 180 203 240
333 438 482 526 591 668 690 200 220 240 270 320
416.3 548 603 658 668 668 a 55/65 °C rise rating on Eaton voltage regulators gives an additional 12% increase in
500 656 668 668 668 668 capacity if the tap-changer’s maximum current rating has not been exceeded. For loading
667 875 875 875 875 875 in excess of the above values, please contact the Voltage Regulator Support group at
(866) 975-7347 (from outside the U.S. and Canada call +1 (262) 896-2591) or e-mail
833 1093 1093 1093 1093 1093 questions to [email protected].
13800 69 50 55 60 68 80 b Regulators are capable of carrying current corresponding to rated kVA when operated at
138 100 110 120 135 160 7200 V.
207 150 165 180 203 240
276 200 220 240 270 320
414 300 330 360 405 480
500 362 398 434 489 579
552 400 440 480 540 640
667 483 531 580 652 668
833 604 664 668 668 668
Wiring diagrams
Figure 28. Typical internal wiring of voltage regulators with a QD3 tap-changer
Figure 29. Typical internal wiring of voltage regulators with QD5 and QD8 tap-changers
12 6
11 5
10 4
9 3
8 2
7 1
Figure 30. Typical internal wiring of EVER-Tap voltage regulator tap changer
46
RECEPTACLE [A] RECEPTACLE-INTERNAL
JUNC/BOX
3/8" MTG STUD B (RED/BLK) (RED/BLK)
1 6
POSITION INDICATOR B (ORG) (ORN)
2 5
B (LT BLU/BLK) (LT BLU/BLK)
D (GRN/BLK) LLS-2 (GRN/BLK) A (GRN/BLK) 3 4
LOWER LIMIT 1 1 B (BLK/WHT) (BLK/WHT)
1 2 C (GRN/BLK) RLS-2 (BLU) A (BLU) 4 3
SWITCH (LLS) 2 2 B (BLK) (BLK)
D (BLU) 5 2
MOLEX 2-PIN MOLEX 2-PIN B (WHT/BLK)
RAISE LIMIT 1 2 PLUG [D] RECEPTACLE [D] 6 1
SWITCH (RLS) C (BLU)
2 J/B 3/8" STUD (WHT) 7 12
P. I. RESET CT (WHT)
SOLENOID (RS) C (ORG/BLK) 8 11
CT PROTECTION D (GRN/BLK) (GRN/BLK)
1 JUNC/BOX CIRCUIT [CT] 9 10
3/8" MTG STUD D (BLU) (BLU)
10 9
CT-C1 (RED) (WHT)
11 8
CT-C2 (GRN) (BLK)
12 7
LLS-1 (GRN/BLK)
RS-1 (ORG/BLK)
A (LT BLU/BLK)
RLS-1 (BLU)
A (RED/BLK)
A (BLK/WHT)
A (WHT/BLK)
A (BLK)
A (RED)
A (GRN)
A (ORG)
J/B 3/8" STUD (WHT)
STUD STUD
MOLEX 10-PIN CC (WHT)
MOLEX 3-PIN
1
VR-32 and EVER-Tap™ Voltage Regulator
2
3
5
7
8
4
6
1
2
3
10
RECEPTACLE [C] RECEPTACLE [B]
1
9
2
3
5
7
8
4
6
1
2
3
10
PLUG [C] PLUG [B]
C2
C1
CC (BLK)
CC (BLU)
CC (RED)
CC (GRN)
CC (ORG)
CC (RED/BLK)
CC (GRN/BLK)
CC (ORG/BLK)
CC (BLK/WHT)
CC (WHT/BLK)
CC (LT BLU/BLK)
POS-7 (BLK)
POS-8 (WHT)
15
12
11
10
9
8
7
6
5
4
3
2
1
NUM
E
12-CONNECTION
C
C
L1
V6
V1
R1
NL
DHR
GRD
GND
MC-2
MC-1
COLOR CHART
RED
BLUE
WHITE
BLACK
GREEN
COLOR
POS-9 (BLU)
POS-5 (ORG)
GROUND (WHT)
POS-6 (RED/BLK)
RED/BLACK
POS-3 (BLK/WHT)
POS-10 (GRN/BLK)
POS-4 (LT BLU/BLK)
BLACK/WHITE
WHITE/BLACK
GREEN/BLACK
LT BLUE/BLACK
GREEN/YELLOW
ORANGE/BLACK
TO CONTROL BOX
VR-32 and EVER-Tap™ Voltage Regulator
RS-1 (ORG/BLK)
CC (ORG/BLK)
CC (RED)
CC (BLK)
RLS-2 (BLU)
CC (ORG)
GROUND
CC (RED/BLK) STUD
CC (GRN)
CC (WHT)
RS-2 (WHT)
12 CONDUCTOR
CONTROL CABLE (CC)
TO CONTROL
MOTOR CC (RED/WHT)
CAPACITOR CC (GRN/WHT)
(NOTE 2)
CC (WHT/BLK)
CC (BLU/BLK)
CC (GRN)
CC (RED)
CC (BLK)
19 (RED)
17 (VIO)
(NOTE 3)
15 (WHT/GRN)
15 (WHT/GRN)
CC (ORG/BLK)
CC (GRN/BLK)
20 (WHT/BRN)
CC (RED/BLK)
13 (WHT/BLU)
13 (WHT/BLU)
CC (BLUE)
CC (WHT)
CC (ORG)
12 (WHT)
12 (WHT)
21 (WHT)
18 (GRN)
18 (GRN)
19 (RED)
14 (BLU)
14 (BLU)
10 (BLK)
16 (BLK)
16 (BLK)
11 (BLK)
17 (VIO)
1 1 1 1
(NOTE 1)
1
2 2 2 2
2 5
DHR
GND
NLG
NLP
VM
OC
104
120
120
127
133
BR
HS
VS
VS
110
110
115
C1
C3
R3
NL
BR
V9
V7
VS
20
21
22
32
L3
V2
V6
V1
R1
R2
C2
C3
V4
G
G
L1
L2
G
G
8
7
6
5
J
C
6
3
3 3 3 7 3
4
TB3
21 (WHT)
RCT (ORG)
RCT (GRN)
RCT (BRN)
RCT (RED)
RCT (BLK)
RCT (BLU)
RCT (YEL)
11 (BLK)
MOV 4 4 4 4
(NOTE 1)
20 (WHT/BRN)
10 (BLK)
COM
104
110
115
120
127
133
RCT1
TAP VOLTAGE
NOTES
1. LEAD 20 (WHT/BRN) CONNECTS VS TO V7 INSTEAD OF
V6-4 TO V7 WHEN A DIFFERENTIAL PT IS NOT PRESENT.
2. CONTROL CABLES CONTAINING 12 CONDUCTORS WILL
HAVE CAPACITOR WIRE COLORS OF BLUE/BLACK AND
BLACK/WHITE.
CONTROL
3. TO RECONFIGURE THE RCT CONNECTION MOVE THE CABLE
WIRE WITH THE WHITE TAG. (CC)
MOTOR
110 110 T
RCT (BRN)
BRAKING
104
10 (BLK)
A
G RCT (BLK) 104 G
G 12 (WHT)
CAPACITOR
CAPACITOR
E
BR 13 (WHT/BLU) COM
R1 AB (GRN/WHT)
R2 14 (BLU)
RCT
VS 16 (BLK)
C2 17 (VIO)
C3 18 (GRN)
4
3
2
1
V1 CC (BLK)
AB (BLU/WHT)
AB (RED/WHT)
AB (RED/WHT)
6
5
AB (GRN/WHT)
CC (RED/WHT)
CC (GRN/WHT)
19 (RED)
4
7 3
2
1
C CC (GRN)
8 17 (VIO)
7 CC (RED)
6
5 AB (YEL) AB (WHT)
J
V9
(CC)
CABLE
V7 20 (WHT/BRN)
CONTROL
AB (WHT)
MOV
BR 13 (WHT/BLU)
3
2
GND
G 12 (WHT)
4
4 3
1 2
1
V2 CC (BLU/BLK)
G CC (WHT)
4
3
2
1
VS 20 (WHT/BRN) V6 CC (WHT/BLK)
VS 16 (BLK)
4
3
2
1
V8 CC (BLK/WHT)
VM
C1 19 (RED) AB (BLU) RLS CC (BLU)
C3 18 (GRN) AB (RED) LLS CC (GRN/BLK)
HS AB (ORG) OCI CC (ORG)
(AB)
3
2
1
L3 15 (WHT/GRN)
NL CC (RED/BLK)
BOARD HARNESS
DHR CC (ORG/BLK)
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2025 Eaton
All Rights Reserved
Eaton is a registered trademark.
Printed in USA For Eaton‘s Cooper Power series product
Publication No. MN225008EN information call 1-877-277-4636 or visit:
All trademarks are property
January 2025 of their respective owners. www.eaton.com/cooperpowerseries.