SINGLE LINE DIAGRAM

LOAD SCHEDULE
2-38 sq.mm THHN WIRE +
CIRCUIT
LOAD DESCRIPTION QUANTITY
VOLT AMPERE
VOLTAGE AMPERES CIRCUIT RUN WIRE SIZE CONDUIT SIZE
CIRCUIT BREAKER SERVICE DROP 1-14 sq.mm THHN WIRE (G)
NUMBER (VA) AT AF Ø-VOLTAGE

1 LIGHTING 5 - LIGHTING OUTLET 500 230 2.17 2 - 2.0 sq.mm THHN wire 20mmØ PVC 20 AT 50 AF 2P, 230v

125 AT, 60 Hz, 1Ø, 230V, 2P


2 LIGHTING 9 - LIGHTING OUTLET 900 230 3.91 2 - 2.0 sq.mm THHN wire 20mmØ PVC 20 AT 50 AF 2P, 230v
BOLT ON TYPE CIRCUIT BREAKER
3 LIGHTING 5 - LIGHTING OUTLET 500 230 2.17 2 - 2.0 sq.mm THHN wire 20mmØ PVC 20 AT 50 AF 2P, 230v
C1 20 AT 20 AT C2

4 LIGHTING 7 - LIGHTING OUTLET 700 230 3.04 2 - 2.0 sq.mm THHN wire 20mmØ PVC 20 AT 50 AF 2P, 230v
C3 20 AT 20 AT C4

4 LIGHTING 9 - LIGHTING OUTLET 900 230 3.91 2 - 2.0 sq.mm THHN wire 20mmØ PVC 20 AT 50 AF 2P, 230v
C5 30 AT 30 AT C6

4 LIGHTING 10 - LIGHTING OUTLET 1000 230 1.74 2 - 2.0 sq.mm THHN wire 20mmØ PVC 20 AT 50 AF 2P, 230v 40 AT 30 AT
C7 C8

CONVENIENCE 26 - 2 GANG CONVENIENCE OUTLET 2 - 8.0


3.5 sq.mm THHN wire
5 1800 230 7.83 1 - 3.5
2.0 sq.mm THHN wire (G) 20mmØ PVC 30 AT 50 AF 2P, 230v C9 30 AT 30 AT C10
OUTLET WITH GROUND
2 - 8.0 sq.mm THHN wire
6 LAUNDRY OUTLET 1 - LAUNDRY OUTLET 1840 230 8.0 1 - 3.5 sq.mm THHN wire (G) 20mmØ PVC 30 AT 50 AF 2P, 230v spare SPARE SPARE spare

2 - 8.0 sq.mm THHN wire


7 RANGE 1 - RANGE 1840 230 8.0 1 - 3.5 sq.mm THHN wire (G) 20mmØ PVC 30 AT 50 AF 2P, 230v

2 - 8.0 sq.mm THHN wire


8 REFRIGERATOR 1 - REFRIGERATOR 1840 230 8.0 20mmØ PVC 30 AT 50 AF 2P, 230v
1 - 3.5 sq.mm THHN wire (G)
2 - 8.0 sq.mm THHN wire
9 OVEN 1 - OVEN 1840 230 8.0 1 - 3.5 sq.mm THHN wire (G) 20mmØ PVC 30 AT 50 AF 2P, 230v

2 - 8.0 sq.mm THHN wire


10 ELECTRIC SHOWER 1 - ELECTRIC SHOWER 8500 230 37 1 - 3.5 sq.mm THHN wire (G) 20mmØ PVC 30 AT 50 AF 2P, 230v GROUND
2 - 8.0 sq.mm THHN wire
11 ELECTRIC SHOWER 1 - ELECTRIC SHOWER 8500 230 37 1 - 3.5 sq.mm THHN wire (G) 20mmØ PVC 30 AT 50 AF 2P, 230v
DETAILS OF PANEL BOARD
2 - 8.0 sq.mm THHN wire
12 ELECTRIC SHOWER 1 - ELECTRIC SHOWER 8500 230 37 1 - 3.5 sq.mm THHN wire (G) 20mmØ PVC 30 AT 50 AF 2P, 230v SCALE: NTS

13 SPARE

OVERHEAD SERVICE ENTRANCE


14 SPARE

TOTAL 39160 167.77 BUILDING WALL

SECOND FLOOR LINE


GENERAL NOTES DESIGN COMPUTATION & ANALYSIS
1. ALL ELECTRICAL WORKS, HEREIN SHALL BE DONE IN ACCORDANCE WITH THE 2-38 sq.mm THHN
APPLICATION OF DEMAND FACTOR:
REQUIREMENTS OF THE NATIONAL BUILDING CODE, THE PHILIPPINE ELECTRICAL CODE, (167.77 - 12) x 80% = 124.616 + 100% (40) = 164.616 Amperes IN 38mmØ RSC
THE RULES AND REGULATION OF THE LOCAL GOVERNMENT, AND THE REQUIREMENT
OF THE LOCAL ELECTRIC UTILITY. FOR MAIN FEEDER CONDUCTOR:
2. ALL MATERIALS TO BE USED SHALL BE NEW AND OF GOOD QUALITY.
3. LIGHTING BRANCH CIRCUIT SHALL BE 3.5 sq.mm THHN STRANDED WIRE IN 20mmØ PVC USE : 2 - 38 sq.mm THHN CONDUCTOR + METERING CONDUIT PANEL BOARD
PIPE. 1 - 14 sq.mm THHN CODUCTOR (ground) in 35mmØ RMC
4. CONVENIENCE OUTLET CIRCUIT SHALL BE 5.5 sq.mm THHN STRANDED WIRE IN 20mmØ
PVC PIPE. KWHR
5. AIRCON OUTLET CIRCUIT SHALL BE 8.0 sq.mm THHN STRANDED WIRE IN 20mmØ PVC FOR MAIN OVER-CURRENT PROTECTION DEVICE:
PIPE METER
6. MOUNTING HEIGHT OF DEVICE SHALL BE AS FOLLOWS UNLESS NOTED OTHERWISE USE : 125 AT, 60 Hz, 1Ø, 230V, 2P, BOLT-ON TYPE CIRCUIT BREAKER
PANEL BOARD 1500mm ABOVE FINISHED FLOOR
LOCAL SWITCHES 1400mm ABOVE FINISHED FLOOR 1.50m

CONVENIENCE OUTLET 300mm ABOVE FINISHED FLOOR


170mm ABOVE COUNTERS
1.80m

AIRCON OUTLET 2000mm ABOVE FINISHED FLOOR


EMERGENCY LIGHT 300mm BELOW FINISHED CEILING
ELECTRICAL GROUND FLOOR LINE
7. ALL LOCAL SWITCHES TO BE CONNECTED SHALL BE RATED 15 AMPERES
8. ALL ELECTRICAL INSTALLATIONS SHALL BE UNDER THE SUPERVISION OF A DULY
LICENSED ELECTRICAL ENGINEER OR REGISTERED MASTER ELECTRICIAN NATURAL GRADE LINE

1-14 sq.mm BARE COPPER WIRE


IN 15mm O.C.

RISER DIAGRAM 16mmØ x 240mm LENGTH


SCALE: NTS GROUNDING ROD COPPERWELD