0% found this document useful (0 votes)
16 views

FIT-1211_Manual-CN100-Installation-NonEx-Rev3

The installation manual for the CN-100 Series Electromagnetic Flowmeter provides comprehensive instructions for safe installation, operation, and maintenance of the device. It emphasizes the importance of understanding safety precautions, proper electrical connections, and environmental considerations to ensure optimal performance. The document includes detailed procedures and specifications for installation, troubleshooting, and maintenance of the flowmeter system.

Uploaded by

Sorin Baican
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
16 views

FIT-1211_Manual-CN100-Installation-NonEx-Rev3

The installation manual for the CN-100 Series Electromagnetic Flowmeter provides comprehensive instructions for safe installation, operation, and maintenance of the device. It emphasizes the importance of understanding safety precautions, proper electrical connections, and environmental considerations to ensure optimal performance. The document includes detailed procedures and specifications for installation, troubleshooting, and maintenance of the flowmeter system.

Uploaded by

Sorin Baican
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 33

Electromagnetic Flowmeter

Installation Manual

CN-100 Series

- Revision 3 -
---------------------------------------------------------------------------------------------------------------2

NOTICE: Read this manual before working with the product. For

personal and system safety, and for optimum product


performance, make sure you thoroughly understand the
contents before installing, using, or maintaining this
product.

CAUTION: The products described in this document are NOT

designed for Nuclear qualified applications.

Using non-nuclear qualified products in applications that


require nuclear qualified hardware or products may cause
inaccurate readings.

Procedures and instructions in this manual may require


special precautions to ensure the safety of the personnel
performing the operations.

Information that raises potential safety issues is indicated

by a warning symbol .

Refer to the safety messages listed at the beginning


of each section before performing an operation
preceded by this symbol.
---------------------------------------------------------------------------------------------------------------3

CONTENTS
SECTION 1: INTRODUCTION .............................................................................................. 4
1.1 SYSTEM DESCRIPTION ............................................................................................. 4
1.2 SAFETY MESSAGES ................................................................................................... 4
SECTION 2: INSTALLATION ................................................................................................ 5
2.1 SAFETY MESSAGES ................................................................................................ 5
2.2 WARNINGS ................................................................................................................ 5
2.3 PRE-INSTALLATION ................................................................................................ 5
2.3.1 Identify Options and Configurations ................................................................. 6
2.3.2 Mechanical Considerations ............................................................................... 6
2.4 ELECTRICAL CONSIDERATIONS ......................................................................... 6
2.4.1 Conduit Connections ......................................................................................... 6
2.4.2 Transmitter Input Power .................................................................................... 6
2.4.3 DC Power Requirements ................................................................................... 7
2.4.4 Disconnects ....................................................................................................... 7
2.4.5 Overcurrent Protection ...................................................................................... 7
2.5 ENVIRONMENTAL CONSIDERATIONS ............................................................... 7
2.6 INSTALLATION PROCEDURES ............................................................................. 8
2.6.1 Specifications and Reference Data ( JIS 10K Standard ) .................................. 8
2.6.2 Handling ............................................................................................................ 9
2.6.4 Flowtube Orientation........................................................................................11
2.6.5 Flow Direction................................................................................................. 13
2.6.6 Gaskets ............................................................................................................ 13
2.6.7 Flange Bolts..................................................................................................... 14
2.6.8 Grounding........................................................................................................ 15
2.6.9 Install Conduit ................................................................................................. 18
2.6.10 Power Connections .......................................................................................... 18
2.7 OUTPUT ................................................................................................................... 19
2.7.1 Connect 4–20 mA Loop External Power Source ............................................ 19
2.7.2 Connect Pulse Output ...................................................................................... 19
2.7.3 Connect RS485 Communication ..................................................................... 20
2.8 QUICK START-UP ................................................................................................... 21
2.8.1 Installation Check and Guide .......................................................................... 21
2.9 PRESSURE DROP ................................................................................................... 22
SECTION 3: MAINTENANCE ............................................................................................. 25
3.1 CLEANING .............................................................................................................. 25
3.2 OPERATIVE LIFE .................................................................................................... 25
3.3 PRODUCT DISPOSAL ............................................................................................ 25
SECTION 4: TROUBLESHOOTING................................................................................... 26
4.1 FLOW RATE IS NOT INDICATED......................................................................... 26
4.2 FLOW RATE INDICATED IS NOT CORRECT ..................................................... 27
4.3 FLOW RATE INDICATION IS NOT STABLE ....................................................... 28
---------------------------------------------------------------------------------------------------------------4

SECTION 1: INTRODUCTION

This manual provides instructions for installing, configuring, operating, and


troubleshooting the Model CN-100 Integral Mount Magnetic Flowmeter System.

1.1 SYSTEM DESCRIPTION


A complete magnetic flowmeter system consists of two components: the Model
CN-100 microprocessor-based integral-mount magnetic flowmeter transmitter and a
flowtube. The flowtube is installed in-line with process piping, either vertically or
horizontally. Coils located on opposite sides of the flowtube create a magnetic field,
and conductive liquid moving through the magnetic field generates a voltage that is
detected by two electrodes. The transmitter controls the generation of the magnetic
field and senses the voltage detected by the electrodes. Based on the sensed voltage,
the transmitter calculates a flow rate and produces analog and frequency output
signals proportional to this flow rate.

1.2 SAFETY MESSAGES


Procedures and instructions in this manual may require special precautions to ensure
the safety of the personnel performing the operations. Refer to the safety messages
listed at the beginning of each section before performing any operations.
---------------------------------------------------------------------------------------------------------------5

SECTION 2: INSTALLATION

This section covers the installation procedures for the Model CN-100 Magnetic
Flowmeter System.

2.1 SAFETY MESSAGES


Instructions and procedures in this section may require special precautions to ensure
the safety of the personnel performing the operations. Information that raises potential
safety issues is indicated by a warning symbol. Please refer to the following
safety messages before performing an operation preceded by this symbol.

2.2 WARNINGS
 Explosions could result in death or serious injury:
 Verify that the operating atmosphere of the flowtube and transmitter is consistent
with the appropriate hazardous locations certifications.
 Do not remove the transmitter cover in explosive atmospheres when the circuit is
alive.
 Both transmitter covers must be fully engaged to meet explosion-proof
requirements.
 Failure to follow safe installation and servicing guidelines could result in death
Or serious injury:
 Make sure only qualified personnel perform the installation.
 Do not perform any service other than those contained in this manual unless
qualified.
 High voltage that may be present on leads could cause electrical shock:
 Avoid contact with leads and terminals.

2.3 PRE-INSTALLATION
There are several pre-installation steps that make the installation process easier. They
---------------------------------------------------------------------------------------------------------------6

include identifying the options and configurations that apply to your application,
setting the hardware switches if necessary, and consideration of mechanical, electrical,
and environmental requirements. Please remember that the flowtube liner is
vulnerable to handling damage. Never place anything through the flowtube for the
purpose of lifting or gaining leverage. Liner damage can render the flowtube useless.

2.3.1 Identify Options and Configurations


Standard application of the CN-100 includes control of the flowtube coils and
one or more following configurations or options:
• 4–20 mA Output (DC24V Source)
• Pulse Output
• RS485 Communication (Option)
Be sure to identify the options and configurations that apply to your situation, and
keep a list of them nearby during the installation and configuration procedures.

2.3.2 Mechanical Considerations


The mounting site for the Model CN-100 Integral Mount Transmitter should provide
enough room for secure mounting, easy access to the conduit ports, full opening of the
transmitter covers, and easy readability of the local operator interface (LOI) screen
(see Figure 2-1).The LOI can be rotated in 90° increments. This should be performed
prior to installing the magnetic flowmeter system.

Figure 2-1 Model CN-100 Dimensional Drawings

2.4 ELECTRICAL CONSIDERATIONS


Before making any electrical connections to the Model CN-100, consider the following
standards and be sure to have proper power supply, conduit, and other accessories.

2.4.1 Conduit Connections


The Model CN-100 Integral Mount Magnetic Flowmeter Transmitter has a M6*1.0
conduit connections.
2.4.2 Transmitter Input Power
The Model CN-100 Transmitter is designed to be powered by voltages ranging from
---------------------------------------------------------------------------------------------------------------7

90V to 250V AC(50 to 60 Hz) or 15V–30 V DC. Units powered with an AC power
supply should be connected to standard AC connections for 90V AC or 250V AC.
Units powered by a 15V–30V DC power supply have special considerations.

2.4.3 DC Power Requirements


Units powered with 15V–30V DC may draw up to 2 amps of current. As result, the
input power wire must meet certain gauge requirements. Table 2-1 show the
maximum wire length for corresponding supply voltages, wire gauges, and wire type.

Types of Maximum Length of the Wire


Power supply wires for Each Corresponding Power Supply Source
Wire Milliohms/ft 30 V 24 V 20 V
Gauge Annealed Cu Supply (ft) Supply (ft) Supply (ft)
20 10.15 1230 625 365
18 6.385 1955 990 585
16 4.016 3110 1580 930
14 2.525 4950 2515 1485
12 1.588 7870 3995 2360
10 0.999 12510 6355 3750
Table 2-1 Length of Annealed Copper Wires

2.4.4 Disconnects
The supply wires should be connected to the device through an external disconnect or
circuit breaker. The disconnect or circuit breaker should be clearly labeled and
located near the transmitter.

2.4.5 Overcurrent Protection


Model CN-100 requires overcurrent protection of the supply lines. Maximum rating of
overcurrent devices are as follows:

Power System Fuse Rating


110V AC 250V; 1 Amp, Quick Acting
220V AC 250V; 1 Amp, Quick Acting
18 to 36V DC 250V; 1 Amp, Quick Acting

2.5 ENVIRONMENTAL CONSIDERATIONS


To ensure maximum transmitter life, avoid excessive heat and vibration. Typical
problem areas include high-vibration lines with integrally Mounted transmitters,
warm-climate installations in direct sunlight, and outdoor installations in cold
climates. Because the Model CN-100 System requires external power, access to a
---------------------------------------------------------------------------------------------------------------8

suitable power source must be ensured. Overheating will damage the flowtube. Do not
encapsulate the flowtube with heating elements.

2.6 INSTALLATION PROCEDURES


These installation tasks provide detailed mechanical and electrical installation
procedures.

2.6.1 Specifications and Reference Data ( JIS 10K Standard )


Pressure
Size Outline Size(mm) Flange Size(mm) Weight
Limits
(mm)
(MPa) a b c e D D0 n× A (kg)
10 2.0 200 244 90 10 65 4×15 4
15 2.0 200 244 95 15 70 4×15 4
20 2.0 200 244 100 20 75 4×15 4
25 2.0 200 244 125 25 90 4×19 5
32 2.0 200 248 135 32 100 4×19 7
40 2.0 200 252 140 40 105 4×19 8
50 2.0 200 268 155 50 120 4×19 10
65 2.0 200 270 175 65 140 4×19 15
80 2.0 200 283 185 80 150 8×19 15
100 1.6 250 302 210 100 175 8×19 20
125 1.6 250 320 250 125 210 8×23 22
150 1.6 300 333 280 150 240 8×23 33
200 1.0 350 358 330 200 290 12×23 43
250 1.0 400 387 400 250 355 12×25 82
300 1.0 500 418 445 300 400 16×25 100
350 1.0 500 442 490 350 445 16×25 121
400 1.0 600 467 560 400 510 16×27 145
450 1.0 600 492 620 450 565 20×27 210
500 1.0 600 518 675 500 620 20×27 227
600 1.0 600 569 795 600 730 24×33 250
700 1.0 700 620 905 700 840 24×33 350
---------------------------------------------------------------------------------------------------------------9

2.6.2 Handling
All parts should be handled carefully to prevent damage. Whenever possible, transport
the system to the installation site in the original shipping containers. The flowtube is
shipped with end covers to protect it from mechanical damage and normal
unrestrained distortion. End covers should not be removed until just before
installation. Keep shipping plugs in conduit connections until conduits are connected
and sealed. All flowtube liners are vulnerable to handling damage. Never place
anything through the flowtube for the purpose of lifting or gaining leverage. Liner
damage can render the flowtube useless. Flanged flowtubes have different lifting and
transportation guidance. Refer to Figure 2-2 for correct handling techniques.

Figure 2-2 FlowtubeSupport for Handling


---------------------------------------------------------------------------------------------------------------10

2.6.3 Flowtube Mounting


Physical mounting of a flowtube is similar to installing a typical section of pipe. Only
conventional tools, equipment, and accessories (such as bolts, gaskets, and grounding
hardware) are required.

 Calibration
magnetic flowmeter systems are we ll-calibrated at the factory and need no
further calibration during installation.

 Upstream Downstream Piping


To ensure specific accuracy over widely varying process conditions, install the flowtube
with various installations cases from the electrode plane, as shown in Figure 2-3. This flowtube
placement is usually adequate to allow for disturbances created by elbows, valves, and reducers.

Figure 2-3 Upstream and Downstream Straight Pipe Diameter


* Note : It can be measured a correct flow rate only when a detector is full of fluid inside pipe completely. Make sure
to operate it with fluid in full inside pipe. And it should be no air bubble in fluid of pipe. An air bubble can be
cause a serious hunting problem. It should be removed all of air bubble in fluid of pipe before operating.

 Required pipe length on Piping connections


If various joints are used upstream of the detector outlet, the straight pipe length as show in
Figure 2-3-a is required.
---------------------------------------------------------------------------------------------------------------11

Figure 2-3-a Required straight pipe length on the upstream side


* It follows the regulations of JIS B 7554 and KS B 0612 standards for the straight-pipe length
installation condition of electromagnetic flowmeter.

2.6.4 Flowtube Orientation

 Vertical Installation
Vertical installation allows upward process fluid flow and is generally preferred.
Upward flow keeps the cross-sectional area full, regardless of flow rate. Orientation of
the electrode plane is unimportant in vertical installations.
NOTE :
As shown in Figure 2-4, avoid downward vertical flows where back pressure is
inadequate to ensure that the flowtube remains full.

Figure 2-4 Vertical Flowtube Orientation


---------------------------------------------------------------------------------------------------------------12

Figure 2-4 Vertical Flowtube Orientation


 Horizontal Installation
Horizontal installation should be restricted to low piping sections that are normally
full. Orient the electrode plane to within 45 degrees of horizontal in horizontal
installations. A deviation of more than 45degrees of horizontal would place an
electrode at or near the top of the flowtube–making it more susceptible to insulation
by air or entrapped gas at the top of the flowtube. Figure 2-5.

Figure 2-5 Horizontal Flowtube Orientation

 Incline Installation
An inclined installation, as shown in Figure 2-6, is an acceptable installation
technique. This tends to keep the cross-sectional area full.
NOTE:
As shown in Figure 2-6, avoid declining installations where back pressure is
inadequate to ensure that the flowtube remains full.

Figure 2-6 Incline or Decline Flowtube Orientation


---------------------------------------------------------------------------------------------------------------13

2.6.5 Flow Direction


The flowtube should be mounted so that the FORWARD end of the flow arrow,
shown on the flowtube identification tag, points in the direction of flow through the
tube (see Figure 2-7).

Figure 2-7 Flow Direction


 It can be measured flow rate at both directions such as Forward direction(+) or Reverse
direction(-). It is shown the flow directions on the LCD monitor of converter.

2.6.6 Gaskets
The flowtube requires gaskets at each of its connections to adjacent equipment or
piping. The gasket material selected must be compatible with the process fluid and
operating conditions, and must not damage the liner. (see Figure 2-8).

NOTE:
To avoid possible flowtube damage, do not use metallic or spiral wound gaskets.

FLANGE GASKETS FOR ALL OTHER FLANGE GASKETS WITH NON-ATTACHED


FLOWTUBES GROUNDING RINGS

Figure 2-8 Flange Gaskets


---------------------------------------------------------------------------------------------------------------14

2.6.7 Flange Bolts


Flowtube sizes and torque values for Class 150 and Class 300 flanges are listed in
Table 2-2. Tighten flange bolts in the incremental sequence shown in Figure 2-9.
Correct flange bolt tightening is crucial for proper flowtube operation and life. All
bolts must be tightened in the proper sequence to the specified torque limits. Failure to
observe these instructions could result in severe damage to the flowtube lining and
possible flowtube replacement. Always check for leaks after tightening flange bolts.
All flowtubes require a second torquing 24 hours after initial flange bolt tightening.

1
4 1 8 5

4 3
18 1 9
14 5
2 3 8 11 6 7
16 3 2
20 19
4 15
12 7
1 5 14 1 9
6 13
12 9 10 2 17 8 5

8 3 16 11

4 3
4 7 Torque the flange bolts 12 15
10 11 in increments according to 6 7
6 2 10 2 13
the above numerical sequence.

Figure 2-9 Flange Bolt Torquing Sequence


---------------------------------------------------------------------------------------------------------------15

NOTE:
Torque the flange boltsin increments according to the above numerical sequence.

Nominal Flowtube Size Flange Bolt Torque Specifications in Foot-Pounds

(Inches) (Class 150 Flange) (Class 300 Flange)

0.5 10 10
1 10 10
1.5 17 22
2 25 17
3 45 35
4 35 50
6 60 65
8 80 60
10 70 65
12 80 80
14 100 -
16 90 -
18 125 -
20 125 -
24 150 -
30 150 -
36 200 -

Table 2-2 Flange Bolt Torque Specifications

2.6.8 Grounding
■ General information on ground connections
Observe the following items when grounding the device;
- The flowmeter grounding is one of the most important things for flowmeter installation.
- For plastic pipes or pipes with insulating lining, the grounding is provided by the
grounding ring.
- When stray potentials are present, install a grounding ring upstream and downstream of the
flowmeter sensor.
- For measurement-related reasons, the potential in the station ground and in the pipeline
should be identical.
---------------------------------------------------------------------------------------------------------------16

Important Notice
If the flowmeter sensor is installed in plastic or earthenware pipelines, or in pipelines with an
insulating lining, transient current may flow through the grounding electrode in special cases. In the
long term, it may destroy the sensor, since the ground electrode will turn in degrade electrochemically.
In these special cases, the connection to the ground must be performed using grounding plates. Install a
grounding ring upstream and downstream of the device in this case.

■ Metal pipe with fixed flanges

Use a copper wire (at least 2.5mm²) to establish the ground connection between the sensor,
the pipeline flanges and an appropriate grounding point.

Figure 2-10 : Metal pipe, without liner

 For a pipe which has a coating or painting treatment on a pipe surface, it


should be removed its coating and painting treatment on grounding part
before grounding installation.
---------------------------------------------------------------------------------------------------------------17

■ Plastic pipes, non-metallic pipes or pipes with insulating liner

For plastic pipes or pipes with insulating lining, the ground for the measuring agent is provided
by the grounding ring. If grounding electrodes are used, the grounding ring is not necessary.
a) Install the flowmeter sensor with grounding ring in the pipeline.
b) Connect the terminal lug for the grounding ring and grounding connection on the
flowmeter sensor with the grounding strap.
c) Use a copper wire (at least 2.5mm²) to link the ground connection to a suitable grounding
point.

Figure 2-11 : Plastic pipes, non-metallic pipes or pipes with insulating liner
---------------------------------------------------------------------------------------------------------------18

2.6.9 Install Conduit


Transmitter junction boxes have ports for M20*1.5 conduit connections.
1. Connect the M20*1.5 conduit to the transmitter in accordance with local or plant
electrical codes.
2. Seal unused ports to prevent moisture or other contamination from entering the
junction box.
Do not overtighten metal plugs used to seal wiring compartment ports, overtightening
can damage the housing.

2.6.10 Power Connections


To connect power to the transmitter, complete the following steps:
1. Ensure that the power source and connecting cable meet the requirements outlined
in Table 2-1.
2. Turn off the power source.
3. Open the power terminal cover.
4. Run the power cable through the conduit to the transmitter.
5. Loosen the terminal cable guard for the input power terminals L and N or + and -.
6. Connect the power cable leads as follows:
 For an AC-powered transmitter:
• Connect AC Ground to a grounding lug.
• Connect AC Neutral to terminal N.
• Connect AC Line to terminal L.
 For a DC-powered transmitter:
• Connect DC Ground to a grounding lug.
• Connect + DC.
• Connect – DC.
The DC-powered transmitter has a different terminal block and different
electronics that are not compatible with an AC-powered transmitter.
N
L

FUSE
SW
COMM
ALMH
ALML
POUT

IOUT
IVIN

RXD
TXD
RES

Figure 2-12 Power Connections.


---------------------------------------------------------------------------------------------------------------19

2.7 OUTPUT
If your application of the Model CN-100 includes an externally powered 4–20 mA
loop, or pulse output, certain requirements may apply in addition to those previously
listed. Satisfy these requirements before attempting to install and operate the Model
CN-100.

2.7.1 Connect 4–20 mA Loop External Power Source


The 4–20 mA output loop is powered either internally or externally.

 Internal
The loop may be powered from the transmitter itself. Resistance in the loop
must be 1,000 ohms or less. If a HART-based communicator or a distributed
control system (DCS) is used, it must be connected across a minimum of 250
ohms resistance in the loop.

N
L

FUSE SW
COMM
ALMH
ALML
POUT

IOUT
IVIN

RXD
TXD
RES

(COMM----I OUT TERMINAL)

Figure 2-13 4–20 mA Loop Power Connections.

2.7.2 Connect Pulse Output


The Pulse Output function provides an isolated switch-closure frequency output
signal that is proportional to the flow through the flowtube. The signal is normally
used in conjunction with an external totalizer or control system. If your application
uses the pulse output option, complete the following steps to connect the signal cable
to the transmitter:

1. Ensure that the power source and connecting cable meet the requirements outlined
above and in Table2-1.
2. Turn off the transmitter power sources.
---------------------------------------------------------------------------------------------------------------20

3. Run the signal cable into the transmitter.


4. Connect the two wires that convey switch closure information to the COMM and
POUT terminals.

N
L
FUSE

SW
COMM
ALMH
ALML
POUT

IOUT
IVIN

RXD
TXD
RES
(COMM—POUT TERMINAL)
Figure 2-14 Pulse Output Connections

2.7.3 Connect RS485 Communication


The RS485-Based communication provides a half-duplex, asynchronous media to
transmit data, transmit speed should be 1200bps, 2400bps, 4800bps, 9600bps, 1 start
bit, 8data bit and 1 stop bit, the parity mode should be NONE, EVEN or ODD, all of
above options can be changed in LOI(Section 3: Local Operator Interface) If your
application uses the RS485 communication option, complete the following steps to
connect the signal cable to the transmitter:

1. Ensure that the power source and connecting cable meet the requirements outlined
above and in Table2-1.
2. Turn off the transmitter power sources.
3. Run the signal cable into the transmitter.
4. Connect the two wires that to the RS485 data +(TXD) and –(RXD) terminals.
N
L

FUSE
SW
COMM
ALMH
ALML
POUT

IOUT
IVIN

RXD
TXD
RES

Figure 2-15 RS485 Connections


---------------------------------------------------------------------------------------------------------------21

2.8 QUICK START-UP


Once the magnetic flowmeter system is installed and communication is established, final
configuration of the transmitter must be completed. You may perform these functions
with the LOI ,Specific instructions regarding these functions are provided in (Section 3:
Local Operator Interface) To initiate a basic flowmeter system start-up, only two
parameters are required:
1. Set Units
2. Output Range
If your application of the magnetic flowmeter system involves more advanced functions
such as multidrop or pulse output, additional configuration steps may be required to
enable full functionality. See (Section 3: Local Operator Interface)

2.8.1 Installation Check and Guide


Use this guide to check new installations of Magnetic Flowmeter Systems that
appear to malfunction.
 Before You Begin
Be sure that power to your system is off before beginning these checks.
 Transmitter
1. Check for correct flowtube line size entered in the software.
(The line size value is listed on the flowtube nameplate.)
2. Check that the analog range of the transmitter matches the analog range in the
control system.
 Flowtube
1. For horizontal flow installations, ensure that the electrodes are in a plane such that
they remain covered by process fluid.
2. For vertical or inclined installations, ensure that process fluid is flowing up into
the flowtube to keep the electrodes covered by process fluid.
3. Ensure that the grounding straps on the flowtube are connected to grounding rings,
lining protectors, or the adjacent pipe flanges. Improper grounding will cause
erratic operation of the system.
---------------------------------------------------------------------------------------------------------------22

 Process Fluid
1. Process fluid conductivity should be 5 mhos per centimeter, minimum.
2. Process fluid must be free of air and gasses.
3. Flowtube should be full of process fluid.

2.9 PRESSURE DROP


If the CN-100 is installed properly according to the installation manual, the pressure drop
can not result because there is no obstacle in the flowtube.

2.10 SOME SPECIAL TIPS

A. For using a valve on the upstream side of flowmeter


Do not use any position valve or control valve if there is a valve on the upstream
side of flowmeter. If it is required to use, it should be installed at the distance of
20D at least between the valve and the flowmeter on the upsteam pipe.
---------------------------------------------------------------------------------------------------------------23

B. Maintaining the flowmeter for long time


Remove the electric power when it is not used over 30 days.
---------------------------------------------------------------------------------------------------------------24

C. For setting the flow-zero


It is essential to have a calibration for flow-zero setting on site.
---------------------------------------------------------------------------------------------------------------25

SECTION 3: MAINTENANCE

3.1 CLEANING
The adhesion might be caused in the detector pipe when using it for a long term when
the fluid including the electro-conductive solid etc. is measured, and it causes the
instruction decrease. Please clean the flowmeter if there is found any abnormal
matters such as phenomenon of decreasing a flow-rate instruction which may cause
the adhesion in the flowmeter pipes while using it.
Please clean the electrodes (2pcs) of flowmeter with soft brush, sponge, cloth
moistened with alcohol, etc. after being moved to a stable place with good ventilation
and remove the adhesion thing from the electrodes. The flowmeter may indicate a
normal value by removing the adhesion. Use always new packing when it is mounting
the flowmeter in the pipeline again.

3.2 OPERATIVE LIFE


The operative life of CN-100 is 5 years from the date of delivery. The life of the
flowmeter differs depending on the environmental conditions and the way it was
used. To extend the life of the flowmeter, inspect and clean the flowmeter
periodically. If it will be used with mixed NaCLO fluid, it will be shortened life-time
as half from its operative life-time.

3.3 PRODUCT DISPOSAL


The electromagnetic flowmeter must be disposed of, according to the rules and
regulations of your local government. Especially if you dispose of electrolytic
capacitors to replace parts, have it done by an agency which is licensed to handle
industry waste materials.
---------------------------------------------------------------------------------------------------------------26

SECTION 4: TROUBLESHOOTING
If a problem occurs while using the CN-100, follow the flowcharts described below.

4.1 FLOW RATE IS NOT INDICATED

START

Check if the power supplies are NO Use the correct power supplies
correct for each device. for each device.

YES

Check if it is correct to install the NO


Install the power and I/O cables
powers and I/O cables. correctly. Refer to 2.4.

YES

Check if it is burnt the fuse in the YES Replace the fuse with a new
converter. one.

NO

Check if it is correct to set up the NO Set up the flow-range correctly.


flow-Range. Refer to the converter manual.

YES

Check if the flow direction matches NO Set the flow direction matches
with the arrow-mark on the flow- with the arrow-mark correctly.
meter.

YES

Contact our website and send


us email (www.fckoreains.com)
---------------------------------------------------------------------------------------------------------------27

4.2 FLOW RATE INDICATED IS NOT CORRECT


START

Check if it is correct to set up NO Set it up correctly.


the flow-Range. Refer to the converter manual.

YES

Check if it is correct to set up NO


Adjust the zero point correctly.
the zero point. Refer to the converter manual.

YES

Check if the excitation current value NO Set it up again correctly.


is correct as stated tag on the flow Refer to the converter manual.
direction.

YES
Check if it is contaminated inside Clean up inside of the
YES
wall of the flowmeter pipes. flowmeter pipe completely.
NO

NO
Check if it is correct the output load- Change an earth-grounding
NO properly so that the output load
resistance as specified.
resistance is less than 750ohm.

YES
Check if two load resistors are YES Connect the two load-resistors
connected to the output in parallel. in series, if necessary.

NO

Is accuracy calculated as follows? Calculate it again correctly as


(Measured flow rate-Actual flow rate) NO
X 100 shown on the left table.
Actual flow rate

YES

Contact our website and send


us email (www.fckoreains.com)
---------------------------------------------------------------------------------------------------------------28

4.3 FLOW RATE INDICATION IS NOT STABLE

START

Check if it is set the power supply NO Use the proper power-supply


voltage correctly within the within the specified range.
specified range.

YES
Check if it is connected the cables NO Connect each cable securely to
securely. the terminal board.

YES
Check if the flowmeter is grounded Ground the flowmeter with a
with 100ohm or less ground NO copper braid or wire for good
resistance. earth ground.

YES

Check if it is filled up with fluid NO Fill up with fluid inside of pipe


inside of pipe lines completely. line completely all the time.

YES

Check if there is any air bubble YES It must remove any air bubble
inside of flowmeter. inside of flowmeter completely
S before operating.
NO

Check if there are any YES Install the flowmeter away from
high-voltage, large current cables or equipment producing
equipment near the flowmeter. electromagnetic or electro static
interference.

NO

Contact our website and send


us email (www.fckoreains.com)
Issued date : 26th JAN 2018

How to operate the converter


1. How to use the main function

forward direction Reverse direction Total integration


integration integration

* Press one time * Press one time * Press one time

Present % against Fluid velocity(FLS)


Empty pipe-ratio(MTP)
Max flow-rate(FQP)

* Press one time * Press one time * Press one time

* NOTE *

Each time you press the botton , it is circulated and displayed in order as shown above.
2. How to input the password to enter the parameter

1. Turn on the power 2. Press one time 3. Program Version 4. Get Parameters Set

5. Press two times 6. Press one time 7. Password Screen 8. Press one time

9. Press one time 10. Press one time 11. Press one time 12. Press two times

13. Press one time 14. Press one time 15. Press one time 16. Press two times

17. Press two times 18. Press one time 19. Enter the menu
3. How to change a menu item

1. Entering screen for 2. It can be changed an item by 3. It can be changed an item by


Parameter Menu fffpressing one time fffpressing one time

4. It can be changed an item by 5. It can be changed an item by 6. It can be changed an item by


fffpressing one time fffpressing one time fffpressing one time

* NOTE *

There are 54 items for flow meter function of electromagnetic flowmeter. Each time you press the
botton , it is circulated and displayed in order.
4. How to change the flow setting way( For example)

2. Press two times in


1. Enter a"Flow Range" item 3. Press one time
order to move botton

6. Press one time to


4. It can be adjusted increasing 5. It can decreasing values by
move the right and adjust
values by pressing pressing
increasing or decreasing values

7. After setting it, press 9. It returns to a flow range


a few time to go 8. Press one time
item again

11. It will be returned to the


10. Press a few time to normal operating condition if it
move press one time
ELECTRO - MAGNETIC FLOW METER

4. Measuring Range
In the normal industry application, it is better to set the measured medium speed as 2~4m/s, under the special
situation, the minimum speed should be more than 0.2m/s and maximum speed less than 8m/s, if there are solid
granules in liquid, the usual speed should be less than 3m/s for purpose to avoid the over-attrition between lining
and electrical poles. For viscid liquid, the speed can choose as 2m/s, the fast flow speed makes for the automatic
elimination of obstructive substances glued on poles, therefore improve the inspection’s preciseness.

Flow range
Minimum Maximum
Size (mm)
Velocity Flow rate Velocity Flow rate
(m/s) (m3/h) (m/s) (m3/h)
10A 0.08 2.82
15A 0.19 6.35
20A 0.34 11.29
25A 0.53 17.64
32A 0.87 28.91
40A 1.36 45.71
50A 2.12 70.58
65A 3.58 119.28
80A 5.43 180.68
100A 8.48 282.32
125A 13.25 441.12
150A 19.08 636.21
200A 33.91 1129.27
250A 52.99 1764.48
300A 0.2 76.30 10.0 2540.86
12 350A 103.86 3458.39
400A 135.65 4517.08
450A 171.68 5716.93
500A 211.95 7057.94
600A 305.21 10163.43
700A 415.42 13833.55
800A 542.59 18068.31
900A 686.72 22867.71
1000A 847.80 28231.74
1200A 1220.83 40653.71
1400A 1661.69 55334.21
1600A 2170.37 72273.25
1800A 2746.87 91470.84
2000A 3391.20 112926.96

Graph Illustration of Diameter, Flow Speed and Volume of Flowmeter

300 350
32 100 250 400
40 65 200 450
10 15 25 50 80 150 mm
Flow velocity (m/s)

1.0

0.3

0.1
10 -2 10 -1 1 10 1 10 2 10 3 10 4
3
Flow volume (m /h)

You might also like