INSTALLATION MANUAL
AIR CONDITIONER DEUTSCH
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
PORTUGUÊS
www.lg.com
P/NO : MFL57199003
Ceiling Cassette - 1Way(Art Type) Type Indoor Unit Installation Manual
TABLE OF CONTENTS
Installation Requirements Required Parts Required Tools
Safety Precautions.................4
Installation
2 Indoor Unit
Installation Parts
Installation Parts
ENGLISH
Panel type Grille type
Outlet
Air Inlet
Remote
TEMP
Controller
Remote
TEMP
Controller
Quantity 1 EA 2 EA 8 EA 4 EA 1 SET
Shape
Installation Manual 3
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
■ Be sure to read before installing the air conditioner.
■ Be sure to observe the cautions specified here as they include important items related to safety.
■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the
following indications.
■ Installation
Do not use a defective or under- For electrical work, contact the Always ground the product.
rated circuit breaker. Use this dealer, seller, a qualified electri-
appliance on a dedicated circuit. cian, or an Authorized Service
Center.
• There is risk of fire or electric shock. • Do not disassemble or repair the • There is risk of fire or electric shock.
product. There is risk of fire or elec-
tric shock.
Install the panel and the cover Always install a dedicated cir- Use the correctly rated breaker
of control box securely. cuit and breaker. or fuse.
• There is risk of fire or electric shock. • Improper wiring or installation may • There is risk of fire or electric shock.
cause fire or electric shock.
4 Indoor Unit
Safety Precautions
Do not modify or extend the Do not let the air conditioner Be cautious when unpacking
power cable. run for a long time when the and installing the product.
humidity is very high and a door
ENGLISH
or a window is left open.
• There is risk of fire or electric shock. • Moisture may condense and wet or • Sharp edges could cause injury. Be
damage furniture. especially careful of the case edges
and the fins on the condenser and
evaporator.
For installation, always contact Do not install the product on a Be sure the installation area
the dealer or an Authorized defective installation stand. does not deteriorate with age.
Service Center.
• There is risk of fire, electric shock, • It may cause injury, accident, or • If the base collapses, the air condi-
explosion, or injury. damage to the product. tioner could fall with it, causing prop-
erty damage, product failure, and
personal injury.
Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air
or Oxygen and Do not use Flammable gases. Otherwise, it may cause fire or explosion.
• There is the risk of death, injury, fire or explosion.
■ Operation
Do not store or use flammable gas or combustibles near the product.
• There is risk of fire or failure of product.
Gasolin
Installation Manual 5
Safety Precautions
■ Installation
Always check for gas (refriger- Install the drain hose to ensure Keep level even when installing
ant) leakage after installation or that water is drained away prop- the product.
repair of product. erly.
• Low refrigerant levels may cause • A bad connection may cause water • To avoid vibration or water leakage.
failure of product. leakage.
90˚
Do not install the product where Use two or more people to lift Do not install the product where
the noise or hot air from the out- and transport the product. it will be exposed to sea wind
door unit could damage the (salt spray) directly.
neighborhoods.
• It may cause a problem for your • Avoid personal injury. • It may cause corrosion on the product.
neighbors. Corrosion, particularly on the con-
denser and evaporator fins, could
cause product malfunction or inefficient
operation.
6 Indoor Unit
Installation
Installation
ENGLISH
Read completely, then follow step by step.
200 or more
Ceiling Ceiling board
Ceiling board
300 or less
or more
500 or 500 or
3300 or less
Above 2500
1000
more more
Unit:mm
Floor
In case that the unit is installed near the sea, the installation parts may be corroded
by salt. The installation parts (and the unit) should be taken appropriate anti-corro-
sion measures.
NOTICE
• Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place where it may
not suck oily steam.
2. Avoid installng air conditioner in such
places where cooking oil or iron powder is Air conditioner
generated.
3. Avoid places where inflammable gas is
generated. Take enough
distance
4. Avoid place where noxious gas is Use the ventilation fan
generated. for smoke-collecting
hood with sufficient
5. Avoid places near high frequency capacity.
Cooking table
generators.
Installation Manual 7
Installation
1,385
600 50 1,285 50
Ceiling
40
448
Level gauge
400
306
354
466
1,180
40
250 TT Chassis
1,065
• This air-conditioner uses a drain pump. 600 50 965 50
• Install the unit horizontally using a level
40
gauge.
448
• During the installation, care should be
400
306
354
466
860
taken not to damage electric wires.
40
250
TU Chassis
(unit: mm)
• Select and mark the position for fixing bolts and piping hole.
• Decide the position for fixing bolts slightly tilted to the drain
direction after considering the direction of drain hose.
Ceiling board
• Drill the hole for anchor bolt on the wall.
Ceiling
Hanging bolt Keep the length of the bolt
from the bracket to 40mm
70mm
(W3/8 or M10)
Nut
Flat washer for M10
(W3/8 or M10)
(accessory) Ceiling board Air conditioner body Ceiling board
Spring washer
(M10)
Keep the length of 20~22mm
between the air conditioner bottom
Flat washer for M10 surface and the ceiling surface
(accessory) Paper model Set screw of
Nut for installation paper model (4 pieces)
(W3/8 or M10)
8 Indoor Unit
Installation
Wiring Connection
• Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
ENGLISH
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
Make sure that the screws of the terminal are free from looseness.
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the cir-
cuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to
which the unit is subjected during the course of transportation. Check them and make sure that they are all
tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Confirm the Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the
name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Do not install the leakage breaker in a place which is wet or moist.
Water or moist may cause short circuit.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function
of a overload protection device.
• Proper starting power is not given to the compressor.
Installation Manual 9
Installation
Mesh
Control box cover
Side cover
Robot kit
Decorative panel
fixing screws
(hexagon M6 screws)
(tightening about 20mm)
Decorative panel
Air outlet vane
10 Indoor Unit
Installation
ENGLISH
direction. always remove the paper template.
Mesh
Side cover
Plasma filter
(applied only to plasma model)
Decorative panel
fixing screws
(hexagon M6 screws)
(tightening about 20mm)
Decorative panel
Installation Manual 11
Installation
Drain Piping
• Drain piping must have down-slope (1/50 to 1/100): be sure not to
Upward
provide up-and-down slope to prevent reversal flow. Pipe clamp
routing
• During drain piping connection, be careful not to exert extra force not allowed
on the drain port on the indoor unit. Indoor unit
• The outside diameter of the drain connection on the indoor unit is
32mm.
Piping material: Polyvinyl chloride pipe VP-25 and
Maintenance
pipe fittings drain port
Drain Test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
Feed water Flexible drain hose
(accessory) • Connect the main drain pipe to the exterior
Main and leave it provisionally until the test
drain pipe comes to an end.
• Feed water to the flexible drain hose and
Drain check the piping for leakage.
Drain pump port Glue the joint • Be sure to check the drain pump for normal
Drain hose connection operating and noise when electrical wiring
Use the clip (accessory) is complete.
• When the test is complete, connect the flex-
ible drain hose to the drain port on the
Drain pan indoor unit.
Hanger
Max 300mm distance Hanger bracket
The supplied flexible drain hose should 1~15m 1/50~1/100 slope
not be curved, neither screwed. The Metal
Max 700mm
clamp
curved or screwed hose may cause a leak-
age of water. Flexible drain hose
Insulation
12 Indoor Unit
Installation
ENGLISH
you like to setup.
- Please set it up not to bend because poor setup could take place if setup board bends.
Please set up remote controller board fit to the reclamation box if there is a reclamation box.
Installation Manual 13
Installation
4. Please connect indoor unit and remote controller using connection cable.
Indoor
Unit side
Connecting cable
5. Please use extension cable if the distance between wired remote controller and indoor unit is
more than 10m.
When installing the wired remote controller, do not bury it in the wall.
(It can cause damage in the temperature sensor.)
Do not install the cable to be 50m or above.
(It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of the remote controller side
and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be connected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.
Remote Controller
TEMP
yes
no
TEMP
Remote Controller
no
TEMP
5feet
Remote
Controller
(1.5meters)
no
14 Indoor Unit
Installation
ENGLISH
1. Operation indication screen
2. Set temperature button
• It will set not room temperature but outlet air temperature.
1
3. Fan speed button
10
• Fan Speed have 3 Steps.
9 • Middle and Low step is same
8 2
4. ON/OFF button
3
7 5. Opration mode selection button
4 6. Wireless remote controller receiver
11
• Some products don't receive the wireless signals.
12 5
7. Air flow button
13 6
8. Subfunction button
14 9. Function setting button
15 10. Ventilation button
11. Reservation
12. Up,down,left,right button
• To check the indoor temperature, press button.
13. Room temperature button
• Displays only the room temperature of the remote
controller perception.
• There is no control of room temperature.
Please attach the inform label inside of the door.
Please choose proper language depend on your • In case of fresh air intake unit, displays only the
country. temperature around remote controller.
14. Setting/Cancel button
15. Exit button
※ Some functions may not be operated and displayed depending on the product type.
※ It will display strange value to the room temperature if wired remote controller is not connected.
Installation Manual 15
Installation
16 Indoor Unit
Installation
ENGLISH
Wired remote controller 1 + Standard Indoor Units
GND
Master Slave Slave Slave Signal
12 V
Installation Manual 17
Installation
5. In case of any error occurs at indoor unit, display on the wired remote controller.
Exception of the error indoor unit, an individual indoor unit control possibility.
6. In case of Group Control, it is possible to use following functions.
- Selection of operation options (operation/stop/mode/set temperature)
- Control of flow rate (High/Middle/Low)
- It is not possible at some functions.
Master/Slave setting of indoor units be set possible using a PCB Dip Switch.
It is possible to connect indoor units since Feb. 2009.
In the other cases, please contact LGE.
It can be the cause of malfuctions when there is no setting of master and slave.
2. Group Control 2
Wired remote controllers + Standard Indoor Units
GND
Master Slave Slave Slave Signal
12 V
Master Slave
It is possible to control N indoor units by wired remote controller M units. (M+N≤17 Units)
Set only one indoor unit to Master, set the others to Slave.
Set only one wired remote controller to Master, set the others to Slave.
Other than those, it is same with the Group Control 1.
18 Indoor Unit
Installation
3. Group Control 3
Mixture connection with indoor units and Fresh Air Intake Unit
ENGLISH
LGAP Network System
GND
FAU FAU
Master Slave Master Slave Signal
12 V
Master Master
In case of connecting with standard indoor unit and Fresh Intake Unit, separate Fresh Air Intake
Unit with standard units.
(Because setting temperature are different.)
Installation Manual 19
Installation
4. 2 Remote Control
Wired remote controller 2 + Indoor unit 1
Master
Master Slave
1. It is possible to connect two wired remote controllers with one indoor unit.
2. Every types of indoor unit is possible to connect two remote controller.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
5. In case of any error occurs at indoor unit, display on the wired remote controller.
6. There isnʼt limits of indoor unit function.
❈ Maximum 2wired remote controllers can be connected with 1 indoor unit.
20 Indoor Unit
5. Accessories for group control setting
It is possible to set group control by using below accessories.
ENGLISH
Indoor unit 2 EA +Wired remote controller Indoor unit 1 EA +Wired remote controller 2EA
❈ PZCWRCG3 cable used for connection ❈ PZCWRC2 cable used for connection
Mas te r S lave
PZC WRC 2
PZC WRC G3
Maste r S lave
Maste r
Installation Manual 21