8071D Operating Manual
8071D Operating Manual
Contents
Introduction ......................................................................................................5
1.1 Scope of Manual .................................................................5
1.2 Safety ...............................................................................5
1.3 Typographical Conventions...................................................6
Description.........................................................................................................7
2.1 Overview ...........................................................................7
2.2 Features............................................................................7
2.3 Interfaces..........................................................................8
2.4 Model Number Identification............................................... 10
2.5 Controls and Indicators ..................................................... 11
2.6 Menu Structure ................................................................ 12
2.7 Alarm Messages ............................................................... 15
Installation ......................................................................................................17
3.1 Dimensions...................................................................... 17
3.2 Installation Guidance Notes................................................ 18
3.3 Mounting the Controller ..................................................... 19
3.4 Electrical Connections........................................................ 19
3.5 Configure the Controller .................................................... 21
Quick Start Guide ..........................................................................................23
4.1 Install the Controller ......................................................... 23
4.2 Normal Display................................................................. 23
4.3 Menu Navigation and Changing Values................................. 23
4.4 Configure the Controller. ................................................... 25
4.5 Set the Operating Parameters ............................................ 25
Operation..........................................................................................................27
5.1 Normal Operation ............................................................. 27
5.2 Level Inhibit..................................................................... 28
5.3 Parameter Set Switching.................................................... 28
5.4 Setpoint Switching ............................................................ 28
5.5 Operator Level Settings ..................................................... 29
5.6 Parameter Level Settings ................................................... 30
Configuration Settings ................................................................................33
6.1 Analogue Inputs ............................................................... 34
6.2 Controller ........................................................................ 37
6.3 Generator ........................................................................ 38
6.4 Limit Comparators ............................................................ 39
6.5 Outputs........................................................................... 43
6.6 Binary Functions............................................................... 45
6.7 Display............................................................................ 46
6.8 Timer.............................................................................. 47
6.9 Interfaces........................................................................ 48
Contents
Introduction
Section 1
Introduction
Contents
Para Page
1.1 Scope of Manual......................................................................... 5
1.2 Safety....................................................................................... 5
1.3 Typographical Conventions .......................................................... 6
1.3.1 Pushbuttons .................................................................... 6
1.3.2 Displays ......................................................................... 6
1.3.3 Factory Settings .............................................................. 6
1.2 Safety
Certain operations within this manual are potentially hazardous and could
cause injury to personnel or equipment damage if the instructions are not
carried out exactly as described. Where a significant potential hazard exists,
the following text appears immediately before steps in the procedure that
present a particular hazard:
WARNING
A Warning identifies a hazard that could cause injury to personnel.
The text of the warning describes the hazard and details of the
precautions that must be applied before the next step of the procedure
is carried out.
Introduction
CAUTION
A Caution identifies a hazard that could cause damage to equipment.
The text of the caution describes the hazard and details of the
precautions that must be applied before the next step of the
procedure is carried out.
Note
A Note contains supplementary information that may be useful to the
Operator and may appear before or after a particular step in the procedure.
1.3.1 Pushbuttons
The following conventions are used throughout this Manual when referring to
the operation of the pushbuttons on the 8071D Controller. A plus “+” sign
between two pushbuttons means press and hold both pushbuttons together.
1.3.2 Displays
When referring to the seven segment displays in the text, it is represented as
follows.
e.g. 59.4 , disp
Description
Section 2
Description
Contents
Para Page
2.1 Overview................................................................................... 7
2.2 Features ................................................................................... 7
2.3 Interfaces.................................................................................. 8
2.3.1 Assignment of Inputs and Outputs ..................................... 9
2.4 Model Number Identification ...................................................... 10
2.5 Controls and Indicators ............................................................. 11
2.6 Menu Structure ........................................................................ 12
2.7 Alarm Messages ....................................................................... 15
2.1 Overview
The 8071D controller is an instrument for controlling temperature, pressure
and other process variables and can be used as 2-state, 3-state, modulating or
continuous controller.
A high contrast, multicolour LED displays process value, setpoint and operator
prompting. Operation, parameter setting and configuration is achieved using
four pushbuttons on the front panel.
2.2 Features
• Max. two programmable Analogue inputs
• Four programmable setpoints, two parameter sets
• Four limit comparators
• Two timer functions
• Two self-optimization procedures
• RS485 interface
Description
2.3 Interfaces
Fig 1 shows the 8071D controller interfaces with the optional items shown in
shaded boxes.
Outputs
• Binary output 1 and 2 – Changeover relay contacts (not used).
• Binary output 3 and 4 – 12 V dc logic outputs which can be configured
to indicate a number of events. They are normally used as the main
controller outputs (actuator control signals).
• Analogue output 5 and 6 (optional) – Standard 4-20 mA outputs
which can be configured to represent a number of parameters within the
controller.
• 23 V, 30 mA DC Supply – Used for the analogue input power supply if a
powered 4-20 mA input is required.
Description
Binary Inputs
There are two binary inputs (1 and 2). The factory set functions are setpoint
and parameter set switching as follows:
6 6
Binary Input 1 10 10
7 7
Binary Input 2 10 10
Description
For example:
Setpoint Z2 Z1
1 0 0
2 0 1
3 1 0
4 1 1
0 = contact open/Off
1 = contact closed/On
Binary Outputs
Binary outputs 3 and 4 are factory set for Controller output 1 and 2. These
signals are normally used for controlling the actuator.
If required, other functions may be assigned (see Section 6.5.1, page 43).
8071D 1 2 0 D -AA
Inputs
Input 1 = PT100, Input 2 = not fitted 0
Input 1 = PT100, Input 2 = 4-20mA 1
Input 1 = 4-20mA, Input 2 = not fitted 2
Input 1 = 4-20mA, Input 2 = 4-20mA 3
Outputs
Output 1 = SSR, Output 2 = not fitted 0
Output 1 = 4-20mA, Output 2 = not fitted 1
Output 1 = 4-20mA, Output 2 = 4-20mA 2
Communications
None 0
RS422/RS485 1
Direct/Reverse acting
Direct D
Reverse R
Description
Item Description
Upper display Four digit, red, 7 segment display.
The parameter displayed can be configured (see Sect
6.7, page 46). The default is process temperature.
Lower display Four digit, green 7 segment display.
The parameter displayed can be configured (see Sect
6.7, page 46). The default is Setpoint 1 value.
Setpoint indicators Indicates which setpoint value is displayed in the
lower display. (SP1, SP2, SP3 or SP4).
16 Segment display Two digit, green, 16 segment display.
Indicates the units of the lower display value.
Status indicators Eight yellow icons show the status of the following.
Description
• Operator Level
• Parameter Level
• Configuration Level
Operator Level
Enables the setting of setpoints and the read only display of a various
parameters (see Fig 3).
Parameter Level
Enables the operator to set the operating parameters of the controller
(see Fig 3).
Configuration Level
Enables the operator to set up the mode of the controller (see Fig 4).
Description
Configuration
See Fig 4 for
Menu
Description
Description
Description
Installation
Section 3
Installation
Contents
Para Page
3.1 Dimensions ............................................................................. 17
3.2 Installation Guidance Notes ....................................................... 18
3.3 Mounting the Controller ............................................................. 19
3.4 Electrical Connections ............................................................... 19
3.4.1 Terminal Strip 1............................................................. 19
3.4.2 Terminal Strip 2............................................................. 20
3.4.3 Terminal Strip 3............................................................. 21
3.5 Configure the Controller ............................................................ 21
3.1 Dimensions
Installation
Installation
CAUTION
To prevent damage to the controller, terminals not documented in the
following table must not be connected.
The electrical connections to the 8071D controller are made with screw
terminals on the rear face. There are three terminal strips numbered 1 to 3
and contain the following connections.
The following figure details the connections used for each configured option
together with the relevant part number (see Sect 2.4, page 10).
Installation
Installation
Installation
Section 4
Para Page
4.1 Install the Controller ................................................................. 23
4.2 Normal Display ........................................................................ 23
4.3 Menu Navigation and Changing Values ........................................ 23
4.4 Configure the Controller. ........................................................... 25
4.5 Set the Operating Parameters .................................................... 25
This section details the basic, minimum instructions to set up the controller for
use.
Menu Navigation
Fig 11 illustrates the method of navigating through the menu system using the
four pushbuttons on the front panel of the controller.
Button Action
PGM Move down through the menu to the next level
EXIT Move up through the menu to the level above.
S Move backwards through items in the same menu level.
T Move forwards through items in the same menu level.
Changing Values
After navigating to the required parameter, the pushbuttons have different
functions to enable changes to be made.
Button Action
PGM Select the displayed parameter for editing. The parameter
flashes when selected.
EXIT Cancel the editing of a parameter without saving the change.
S Increase the value of a parameter.
Press and hold to increment automatically.
T Decrease the value of a parameter.
Press and hold to decrement automatically.
Note
When a parameter is changed, it is automatically accepted and saved after
two seconds with no action required by the operator.
To reject a change without saving it, press EXIT within two seconds of the
change.
To accept and save the change immediately, press PGM within two seconds
of the change.
• Operator Level
# Setpoint 1 0pr – proc - sp1
• Configuration Level
# Input sensor type Conf – Inp – Inp – sens (see Section 6.1).
# Linearization Conf – Inp – Inp – lin (see Section 6.1).
# Temperature units Conf – Inp – In12 – Unit (see Section 6.1).
Note
All the parameters in this procedure are located in para – par1.
1 Set the following parameter level values.
# Proportional band 1 pb1 = 0
# Derivative time dt = maximum
# Reset time rt = maximum
2 Allow the controller to run and measure the Cycle time (the time between
maximum values displayed in the upper display).
3 Set the following parameters.
# Reset time rt = Cycle time + 20%
# Derivative time dt = 0
4 Gradually increase the Proportional band 1 (pb1) parameter until the
system stabilises.
5 Gradually increase the Derivative time (dt) parameter to a maximum of
20% of Reset time (rt) to stop overshoot.
Note
To change the setpoint value, in the Normal display, press S to increase or T
to decrease.
Operation
Section 5
Operation
Contents
Para Page
5.1 Normal Operation ..................................................................... 27
5.1.1 Change the Setpoint....................................................... 27
5.1.2 Manual Mode................................................................. 28
5.2 Level Inhibit ............................................................................ 28
5.3 Parameter Set Switching ........................................................... 28
5.4 Setpoint Switching.................................................................... 28
5.5 Operator Level Settings ............................................................. 29
Note
The figure above shows that Binary output 4 is active which is configurable
but normally represents controller output 2.
Operation is automatic with no operator intervention required.
Operation
1 From the Normal display, press PGM and T together for more than five
seconds.
2 When Code is displayed, press PGM - Code flashes.
3 Press the S and T buttons to set the required value.
Operation
Proc
Note
The User (USEr) and Program (Pro) menus are not used.
Operation
Two sets of parameters can be stored and are switched by Binary Functions. See
Section 2.3.1, page 9.
Operation
Note
The parameters Pb2, Cy2, HyS2 and y2 refer to the second controller output
for a 3-state or modulating controller.
The decimal place of some parameters depends on the decimal place setting
in the displays.
The parameter display on the instrument depends on the controller type
selected. See Section 6.2.
Operation
Configuration Settings
Section 6
Configuration Settings
Contents
Para Page
6.1 Analogue Inputs ....................................................................... 34
6.2 Controller ................................................................................ 37
6.3 Generator................................................................................ 38
6.4 Limit Comparators .................................................................... 39
6.5 Outputs .................................................................................. 43
6.5.1 Binary Outputs - 0utl ...................................................... 43
6.5.2 Analogue Outputs – 0uta ................................................. 44
6.6 Binary Functions ...................................................................... 45
6.7 Display ................................................................................... 46
6.8 Timer ..................................................................................... 47
6.9 Interfaces................................................................................ 48
Configuration Settings
Configuration Settings
Configuration Settings
In12
Configuration Settings
6.2 Controller
inverse:
The controller output Y is > 0 when the
process value is smaller than the setpoint
(e. g. heating).
direct:
The controller output Y is > 0 when the
process value is larger than the setpoint
(e. g. cooling).
Inhibit InHa 0 Enabled
manual mode 1 inhibited
If the manual mode is inhibited, changing
over to “manual” is not possible from the
keys or via the binary input.
Manual Hand -100…101 Defines the controller output level after
output 101 changing over to manual mode.
101 = last output
Range output R0ut -100…+100 Output on over/underrange.
0 101 = last output
Configuration Settings
6.3 Generator
This menu is not used
Configuration Settings
Limit comparators (threshold monitors, limit contacts) can be used to monitor an input
variable (process value for the limit comparator) against a fixed limit or another
variable (the setpoint for the limit comparator). When a limit is exceeded, a signal can
be output or an internal controller function initiated.
Four limit comparators are available which can be set to the following functions.
lk1 lk5
lk2 lk6
lk3 lk7
lk4 lk8
Note
In the case of the limit comparator functions lk7 and lk8, the measurement
that is set is monitored with respect to a fixed value AL.
Configuration Settings
Configuration Settings
c) Stabilized condition
The limit comparator again operates in
accordance with its function.
Configuration Settings
Configuration Settings
6.5 Outputs
Configuration Settings
Configuration Settings
Configuration Settings
6.7 Display
Configuration Settings
6.8 Timer
Configuration Settings
6.9 Interfaces
MODbus – r422
Setting Display Value range Description
factory setting
Protocol Prot 0 MODbus
1 MODbus integer
Baud rate Bdrt 0 9600 bps
1 19200 bps
2 38400 bps
Data format Dft 0 8 data bits, 1 stop bit, no parity
1 8 data bits, 1 stop bit, odd parity
2 8 data bits, 1 stop bit, even parity
3 8 data bits, 2 stop bits, no parity
Device adr 0…255 Address in data network
address 1
Communications Interface
Section 7
Communications Interface
Contents
Para Page
7.1 Description .............................................................................. 49
7.1.1 Master-Slave Principle .................................................... 49
7.1.2 Transmission mode (RTU) ............................................... 50
7.1.3 Device Address.............................................................. 50
7.1.4 Timing of the communication........................................... 50
7.1.5 Timing of a Data Request ................................................ 52
7.1.6 Structure of the data blocks ............................................ 53
7.1.7 Error Handling ............................................................... 53
7.2 Functions ................................................................................ 54
7.2.1 Read n Words................................................................ 55
7.2.2 Write one word.............................................................. 55
7.2.3 Write n words................................................................ 56
7.3 Address Tables......................................................................... 57
7.3.1 Process Data ................................................................. 58
7.3.2 Setpoints ...................................................................... 61
7.3.3 Controller Parameters..................................................... 62
7.3.4 Configuration ................................................................ 63
7.3.5 Program Transmission .................................................... 64
7.3.6 Commands ................................................................... 65
7.3.7 Device Identification....................................................... 66
7.1 Description
Communications Interface
Note
A maximum of 31 slaves can be addressed via the RS422/485 interface.
Two forms of data exchange can be distinguished:
• Broadcast Instruction by the master to all slaves, via the device address
0. The connected slaves do not respond. A specific setpoint can, for
example, be transmitted to all slaves. In such a case, the correct
acceptance of the values by the slaves should be checked by a
subsequent readout of the setpoint.
A data request with device address 0 is meaningless.
The character transmission time (the time taken to transmit one character)
depends on the baud rate and the data format that is used (stop bits and
parity bit).
Communications Interface
For a data format with 8 data bits, no parity bit and one stop bit, this is:
Response of slave
transmission time = n characters * 1000 * x bits/(baud rate)
Example
Communications Interface
Note
A minimum response time can be set in the controller, under the menu item
“Interface”. This preset time is the minimum time which will be waited
before an answer is transmitted (0 - 500 ms). If a smaller value is set, then
the response time may be longer than the preset value (because the
internal processing time is longer), the controller answers as soon as the
internal processing is completed. A preset time of 0 ms means that the
controller answers with the maximum possible speed.
The minimum response time which can be set is required by the RS485
interface in the master, in order to switch over the interface driver from
transmit to receive. This parameter is not required for the RS422 interface.
t2 is the time is needed by the controller, to switch over from transmit back to
receive. This is the waiting time which the master has to observe before
presenting a new data request. This time must always be observed, even when
the new data request is directed to another device.
RS422 interface: t2 = 1 ms
RS485 interface: t2 = 10 ms
Communications Interface
# invalid function
# invalid parameter address
# write access to parameter denied
Example:
Date request:
01 02 40 00 00 04 CRC16
Response:
01 83 02 CRC16
Communications Interface
Checksum (CRC16)
The checksum (CRC16) serves to recognize transmission errors. If an error is
identified during evaluation, the corresponding device does not respond.
CRC = 0xFFFF
CRC = CRC XOR ByteOfMessage
For (1 to 8)
CRC = SHR(CRC)
If (flag shifted right = 1)
then else
CRC = CRC XOR 0xA001
While (not all ByteOfMessage processed);
Example:
07 03 00 CE 00 02 A5 92
CRC16
Response: (CRC16 = 0xADF5)
07 03 04 00 00 41 C8 AD F5
Word 1 Word 2 CRC16
Interface
7.2 Functions
The following functions are available:
Communications Interface
• Date request
Slave Function Address Word Checksum
address 0x03 or 0x04 number CRC16
(max 127)
1 byte 1 byte 2 bytes 2 bytes 2 bytes
• Response
Slave Function Number of Word Checksum
address 0x03 or 0x04 bytes read value(s) CRC16
1 byte 1 byte 1 byte x byte(s) 2 bytes
• Example
Read the two controller setpoints
Data request:
01 03 31 00 00 04 4AF5
Response:
• Instruction
Slave Function Word Word value Checksum
address 0x06 address CRC16
1 byte 1 byte 2 bytes 2 bytes 2 bytes
• Response
Slave Function Word Word value Checksum
address 0x06 address CRC16
1 byte 1 byte 2 bytes 2 bytes 2 bytes
Communications Interface
• Example
Write limit for limit comparator 1 = 275
01 06 00 77 80 00 5810
01 06 02 6F 80 00 5810
01 06 00 78 43 89 F945
01 06 00 78 43 89 F945
• Instruction
Slave Function Address Word Byte Word Checksum
address 0x10 of first number number value(s) CRC16
word (max
127)
• Response
Slave Function Address of Word Checksum
address 0x10 first word number CRC16
1 byte 1 byte 2 bytes 2 bytes 2 bytes
• Example
Write proportional band Pb1 = 20 of second parameter set
Instruction:
01 10 30 14 00 02 04 00 00 41 A0 9979
Response:
01 10 30 14 00 02 0ECC
Communications Interface
Byte sequence
Because of the platform-dependent representation of floating-point numbers
and long values, the bytes must be arranged in the sequence that is
appropriate for MODbus.
Please find out in which sequence float values are stored in your system (PC,
PLC etc.).
PC (master) 00 80 3B 45
MODbus 80 00 45 3B
Byte 1 2 3 4
Communications Interface
PC (master) 03 02 01 00
MODbus 00 01 02 03
Byte 1 2 3 4
Communications Interface
Communications Interface
Communications Interface
7.3.2 Setpoints
Address Data type/ Access Signal designation
bit number
0x3100 FLOAT R/W Setpoint W1
0x3102 FLOAT R/W Setpoint W2
0x3104 FLOAT R/W Setpoint W3
0x3106 FLOAT R/W Setpoint W4
Note
The setpoint limits will not be checked when setpoints are altered via the
interface.
Write operations to these parameters result in them being saved to the
EEPROM. These memory chips only have a limited amount of write cycles
(about 10000), this is why this function can be switched off in the case of
frequent programming. The parameter values are then saved to the volatile
memory (RAM) only and are lost after a supply failure.
Communications Interface
Note
Write operations to these parameters result in them being saved to the
EEPROM. These memory chips only have a limited amount of write cycles
(about 10000), this is why this function can be switched off in the case of
frequent programming. The parameter values are then saved to the volatile
memory (RAM) only and are lost after a supply failure.
Communications Interface
7.3.4 Configuration
Address Data type/ Access Signal designation
bit number
0x0077 FLOAT R/W Limit comparator 1, limit AL
0x0079 FLOAT R/W Limit comparator 1, switching differential
0x007B INT R/W Limit comparator 1, switch-on delay
0x007C INT R/W Limit comparator 1, switch-off delay
0x007D FLOAT R/W Limit comparator 2, limit AL
0x007F FLOAT R/W Limit comparator 2, switching differential
0x0081 INT R/W Limit comparator 2, switch-on delay
0x0082 INT R/W Limit comparator 2, switch-off delay
0x0083 FLOAT R/W Limit comparator 3, limit AL
0x0085 FLOAT R/W Limit comparator 3, switching differential
0x0087 INT R/W Limit comparator 3, switch-on delay
0x0088 INT R/W Limit comparator 3, switch-off delay
0x0089 FLOAT R/W Limit comparator 4, limit AL
0x008B FLOAT R/W Limit comparator 4, switching differential
0x008D INT R/W Limit comparator 4, switch-on delay
0x008E INT R/W Limit comparator 4, switch-off delay
0x008F FLOAT R/W Ramp function, slope
0x00B9 INT R/W Alarm text (1-2)
0x00BA INT R/W Alarm text (3-4)
Note
Write operations to these parameters result in them being saved to the
EEPROM. These memory chips only have a limited amount of write cycles
(about 10000), this is why this function can be switched off in the case of
frequent programming. The parameter values are then saved to the volatile
memory (RAM) only and are lost after a supply failure.
Communications Interface
Note
Write operations to these parameters result in them being saved to the
EEPROM. These memory chips only have a limited amount of write cycles
(about 10000), this is why this function can be switched off in the case of
frequent programming. The parameter values are then saved to the volatile
memory (RAM) only and are lost after a supply failure.
Communications Interface
7.3.6 Commands
Address Data type/ Access Signal designation
bit number
0x006F INT R/W Binary functions "Program controller"
Bit 1 R/W Program pause (=0x0002)
Bit 2 R/W Program canceled (=0x0004)
Bit 3 R/W Program start (=0x0008)
Bit 8 R/W Segment change (=0x0100)
0x0070 INT R/W Binary functions "Controller"
Bit 1 R/W Pause program (=0x0002)
Bit 2 R/W Cancel ramp (=0004)
Bit 4 R/W Activate manual mode (=0x0010)
Bit 5 R/W Automatic mode (=0x0020)
Bit 6 R/W Controller off (=0x0040)
Bit 7 R/W Start autotuning (=0x0080)
Bit 13 R/W Cancel autotuning (=0x2000)
0x0071 INT R/W Binary functions "Operation"
Bit 4 R/W Display off with key inhibit (=0x010)
Bit 5 R/W Acknowledge limit comparators (=0x0020)
Bit 6 R/W Text display (=0x0040)
0x0072 INT R/W Binary functions "Timer"
Bit 1 R/W Pause timer 1 (=0x0002) (only via interface)
Bit 2 R/W Cancel timer 1 (0=0004)
Bit 3 R/W Start timer 1 (=0x0008)
Bit 9 R/W Pause timer 2 (=0x0200) (only via interface)
Bit 10 R/W Cancel timer 2 (0=0400)
Bit 11 R/W Start timer 2 (=0x0800)
0x0073 INT R/W Setpoint switching (0=off) 1 – 4 = W1-W4
0x0074 INT R/W Parameter set switching (0=off)
1=P1
2=P2
0x3200 FLOAT W/O Setpoint
0x3202 FLOAT W/O Process value
0x3004 FLOAT W/O Math 1
0x3006 FLOAT W/O Math 2
0x3008 INT W/O Logic 1+2
Bit 0 W/O Logic 1 (=0x0081)
Bit 1 W/O Logic 2 (=0x0082)
Bit 7 W/O Activation (=0x0080)
Communications Interface
Section 8
Para Page
8.1 Calibration............................................................................... 67
8.2 Auto Tuning............................................................................. 68
8.3 Check the Tuning ..................................................................... 72
8.4 Maintenance ............................................................................ 72
8.4.1 Clean the front panel...................................................... 72
8.4.2 Replace the Controller .................................................... 73
8.4.3 Return Components to the Manufacturer ........................... 73
8.1 Calibration
For accurate processing, it is important that the Controller interprets the value
of the analogue input(s) correctly. To achieve this, analogue signals as close
as possible to each end of the input range are fed into the controller. At each
value, the Controller is adjusted to display the required value.
Fig 13 Calibration
Procedure
WARNING
If the Controller is installed and connected into the system, the
appropriate precautions must be taken to isolate the electrical supply
before connecting/disconnecting analogue inputs.
• Oscillation
• Step response
Oscillation Method
The controller selects one of two procedures (a or b), depending on the size of
the control deviation:
Autotuning can be started from any system status, and can be repeated as
often as is required. The controller outputs (continuous, relay, solid-state), the
controller standby output and the step size (min. 10%) have to be defined.
Note
With output type “solid-state”, the cycle time during autotuning is reduced
to 8 x the sampling cycle time.
With the “relay” output type, care has to be taken that the process value is
not influenced by the cycle time, since otherwise autotuning can not be
completed successfully.
Solution: Reduce the cycle time Cy, until the process value is no longer
influenced. (Manual mode can be used for the adjustment)
Start Autotuning
Note
The controller output types must be defined for autotuning – see Section
6.2.
Press S and T (simultaneously > two seconds “tUnE” is shown, flashing, in the
lower display
Cancel autotuning
Cancel with S and T (simultaneously)
8.4 Maintenance
There are no user-serviceable parts inside the controller. For rapid spares and
service support, contact the manufacturer at the address shown on the back
cover of this Manual.
WARNING
The power supply to the
Controller must be switched
off and isolated before the
Controller is removed from
its housing.
Note
When refitting the Controller
module, ensure that the
latches below the knurled
areas are fully engaged.
Fig 14 Controller Module
CAUTION
Components of the Controller are susceptible to damage by
electrostatic discharge. When returning components to the
manufacturer, the rules of EN 100 015 “Protection of electrostatically
endangered components” must be observed. Use only the approved
packaging material for transport.
Please note that we cannot be held liable for any damage caused by
ESD (electrostatic discharges).
Accessories
Section 9
Accessories
Contents
Para Page
9.1 8072D Controller ...................................................................... 75
9.1.1 Description ................................................................... 75
9.1.2 Installation ................................................................... 79
9.1.3 Operation ..................................................................... 82
9.1.4 Maintenance ................................................................. 82
9.2 8073C Relay Module ................................................................. 85
9.2.1 Description ................................................................... 85
9.2.2 Installation ................................................................... 85
9.2.3 Maintenance ................................................................. 88
9.3 47581L001 Solid State Relay ..................................................... 89
9.3.1 Description ................................................................... 89
9.3.2 Installation ................................................................... 89
9.3.3 Maintenance ................................................................. 90
9.1.1 Description
The 8072D controller incorporates an 8071D PID controller and two solid state
relays with outputs that feed directly to the electrically actuated AMOT G-
Valve. With a standard DIN rail mounted terminal connections and requiring
only a power supply and temperature input, the 8072D provides a complete,
compact control solution.
Accessories
The main component is the 8071D controller which is fully described in Section
2.
Accessories
Accessories
Accessories
9.1.2 Installation
Dimensions
Accessories
Accessories
WARNING
Two holes for the mounting of the
controller are located under the flap
that covers the terminal connections.
The power supply to the controller
must be isolated before the flap is
lifted to prevent electric shock to
personnel.
Electrical Connections
Electrical connections to the 8072D are made through terminal connections
beneath the hinged flap as follows:
Accessories
9.1.3 Operation
Refer to Section 5 for the operation instructions for the 8071D controller. The
ON/OFF switch isolates the power supply to the 8071D controller and the
actuator outputs.
9.1.4 Maintenance
Note
Throughout this procedure the “controller” refers to the 8071D controller
unless stated otherwise.
Accessories
Note
The panel is manufactured in two parts which need to be separated to
expose the SSR mounting screws.
Accessories
Note
SSR 1 has the earth tag attached.
1.9 Remove the two screws, nuts and washers securing the SSR to the
panel.
1.10 Remove the SSR.
2 Fit a replacement SSR as follows:
2.1 Secure the SSR to the panel with the two screws, nuts and washers.
Ensure the earth tag is reconnected if fitting SSR1.
2.2 Reconnect the wires to the SSR.
2.3 Align the two parts of the panel and insert the switch into position.
2.4 Refit the 8071D controller and reassemble the 8072D controller.
Please note that we cannot be held liable for any damage caused by
ESD (electrostatic discharges).
Accessories
9.2.1 Description
The 8073C is a dual, solid state relay module designed to control mains
actuator voltages from either low voltage dc or ac input signals.
The principal use for the 8073C is as an alternative to solid state relays for
converting the logic outputs of an 8071D or relay outputs of a different
controller into drive voltages for an electrically driven G-Valve actuator.
Two LEDs on the printed circuit board (see Fig 22 page 87) indicate that a DC
control signal is active:
Features
• Zero-crossing switching.
• Relay and logic level inputs.
• IP67 enclosure.
9.2.2 Installation
Dimensions
Accessories
Four mounting holes are provided in each corner of the module under the
cover securing screws.
Determine the cable entry position, punch out the required blank and fit the
cable gland.
Accessories
Electrical Connections
Electrical Interface
CAUTION
Damage will be caused to the module if both the DC and AC control
inputs are energised simultaneously. Connect only the AC or DC
control inputs. Do not connect both inputs on the same installation.
Accessories
9.2.3 Maintenance
There are no user-serviceable parts inside the module. For rapid spares and
service support, contact the manufacturer at the address shown on the back
cover of this Manual.
Accessories
9.3.1 Description
The 47581L001 solid state relay (SSR) normally operates at approx 5A (G-
Valve electric actuator) but can operate up to 25A with suitable heatsinking. It
has significantly higher performance than standard relays, providing excellent
transient protection and switching life. The arcing associated traditional relays
is completely eliminated due to zero volt switching.
Dimensions
9.3.2 Installation
Electrical Interface
The relay is designed for use with the 8071D controller and is connected as
follows:
Accessories
9.3.3 Maintenance
There are no user-serviceable parts inside the relay. For rapid spares and
service support, contact the manufacturer at the address shown on the back
cover of this Manual.
Technical Data
Section 10
Technical Data
Contents
Para Page
10.1 8071D Controller ...................................................................... 91
10.2 8072D Controller ...................................................................... 94
10.3 8073C Relay Module ................................................................. 95
Inputs
The change between Pt100, thermocouples and 4 – 20mA can be configured in
the software.
Technical Data
Standard Signal
Voltage 2 - 10 V
input resistance RIN > 100 kΩ
Current 4 - 20 mA, voltage drop ≤ 1.5 V
Heating current 0 - 50mA ac
Resistance transmitter min 100 Ω, max. 4 kΩ
Binary Inputs
Floating contacts
Outputs
Relay (changeover)
contact rating 3 A at 230 V ac resistive load
contact life 350,000 operations at rated load / 750,000
operations at 1 A
Current (option)
output signals 4 - 20mA
load resistance Rload ≤ 500 Ω
Technical Data
Electrical Data
Housing
MODbus Interface
Technical Data
Power requirement
Analogue input
Environmental
Alarm outputs
Weight
Technical Data
Power requirements
Logic inputs
Voltage range 5 to 30 V dc
Drive current < 20 mA
Outputs
Environment
Weight
Technical Data
AMOT Shanghai
Rm A8-671 Jiahua Business Center
808 Hongqiao Road
Shanghai 200030
China
AMOT Singapore
10 Eunos Road 8 #12-06
Singapore Post Centre
Singapore 408600
www.amot.com