General Faults
Table 28 lists and describes the general faults.
20 dc undervolt DC link undervoltage. DC link voltage below 250V Contact Satcon Service
for more than 1 second.
21 dc ground fault DC ground overcurrent detected by ground Contact Satcon Service
impedance monitoring device.
22 ln overvlt slow Line overvoltage slow. Line voltage above 120% of None. This fault is automatically cleared when the
rated for more than 1 second. line voltage drops below the trip level.
23 ln overvlt fast Line overvoltage fast. Line voltage above 110 % of None. This fault is automatically cleared when the
rated for more than 0.16 second. Automatically line voltage drops below the trip level.
cleared when the line voltage drops below the trip
level.
24 ln undrvlt slow Line undervoltage slow. Line voltage below 88% of None. This fault is automatically cleared when the
rated for more than 1 second. Automatically line voltage rises above the trip level.
cleared when the line voltage rises above the trip
level.
25 ln undrvlt fast Line undervoltage fast. Line voltage below 50% of None. This fault is automatically cleared when the
rated for more than 0.16 second. Automatically line voltage rises above the trip level.
cleared when the line voltage rises above the trip
level.
26 volt unbalance Line voltage unbalance (IEC unbalance) Contact Satcon Service
27 line over freq Line over frequency. Line frequency more than 0.5 None. This fault is automatically cleared when the
Hz above rated for more than 0.16 second. frequency drops below the trip level.
Automatically cleared when the frequency drops
below the trip level.
28 under freq slow Line under frequency slow. Line frequency more None. This fault is automatically cleared when the
than 0.7 Hz below rated for more than 0.16 second. frequency rises above the trip level.
Automatically cleared when the frequency rises
above the trip level
29 under freq fast Line under frequency fast. Line frequency more None. This fault is automatically cleared when the
than 3.0 Hz below rated. Automatically cleared frequency rises above the trip level.
when the frequency rises above the trip level.
30 Not used
31 Reserved
32 Reserved
DPCB Faults
Table 29 lists and describes the Digital Processing Circuit Board (DPCB) faults.
Table 29 DPCB Faults
Hardware Faults
Table 30 lists and describes the hardware faults.
Inverter Faults
Table 31 lists and describes the inverter faults.
Temperature faults
Table 32 lists and describes the temperature faults.
Table 32 Temperature Faults
Warning Messages
Table 33 lists and describes the warning messages.
NOTE
Warning messages do NOT cause the PVS unit to shut down.