0% found this document useful (0 votes)
6 views56 pages

Controlador Serie 4300

The FDC-4300 is a self-tuning fuzzy/PID process and temperature controller featuring a user-configurable menu, high accuracy inputs and outputs, and various programmable functions. It supports multiple input types, including thermocouples and RTDs, and offers advanced control features such as auto-tuning and bumpless transfer. The manual includes detailed sections on installation, programming, calibration, troubleshooting, and specifications.

Uploaded by

Alonso Pavez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
6 views56 pages

Controlador Serie 4300

The FDC-4300 is a self-tuning fuzzy/PID process and temperature controller featuring a user-configurable menu, high accuracy inputs and outputs, and various programmable functions. It supports multiple input types, including thermocouples and RTDs, and offers advanced control features such as auto-tuning and bumpless transfer. The manual includes detailed sections on installation, programming, calibration, troubleshooting, and specifications.

Uploaded by

Alonso Pavez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 56

User's Manual

FDC-4300
Self-Tune Fuzzy / PID
Process / Temperature Controller
CONTENTS
Page No
Chapter 1 Overview
1-1 Features ------------------------------------------------------------------------- 3
1-2 Ordering Code ---------------------------------------------------------------- 4
1-3 Programming Port and DIP Switch --------------------------------------- 5
1-4 Keys and Displays ------------------------------------------------------------ 6
1-5 Menu Overview -------------------------------------------------------------- 7
1-6 Parameters Description ----------------------------------------------------- 8

Chapter 2 Installation
2-1 Unpacking ---------------------------------------------------------------------- 15
2-2 Mounting ------------------------------------------------------------------------ 15
2-3 Wiring Precautions ----------------------------------------------------------- 16
2-4 Power Wiring -------------------------------------------------------------------- 17
2-5 Sensor Installation Guidelines --------------------------------------------- 17
2-6 Thermocouple Input Wiring ------------------------------------------------ 18
2-7 RTD Input Wiring --------------------------------------------------------------- 18
2-8 Linear DC Input Wiring ------------------------------------------------------- 19
2-9 CT / Heater Current Input Wiring ------------------------------------------ 19
2-10 Output 1 Wiring ------------------------------------------------------------ 20
2-11 Output 2 Wiring ------------------------------------------------------------- 21
2-12 Event Input Wiring ----------------------------------------------------------- 22
2-13 Alarm 1 Wiring --------------------------------------------------------------- 22
2-14 Alarm 2 Wiring --------------------------------------------------------------- 22
2-15 RS-485 -------------------------------------------------------------------------- 23
2-16 Analog Retransmission ---------------------------------------------------- 23
2-17 RS-232 ------------------------------------------------------------------------- 24

Chapter 3 Programming Special Functions


3-1 Rearrange User Menu ------------------------------------------------------- 25
3-2 Dwell Timer ---------------------------------------------------------------------- 26
3-3 Manual Control---------------------------------------------------------------- 26
3-4 Failure Transfer ----------------------------------------------------------------- 27
3-5 Signal Conditioner DC Power Supply ----------------------------------- 27
3-6 Bumpless Transfer ------------------------------------------------------------- 28
3-7 Self-Tuning ---------------------------------------------------------------------- 29
3-8 Auto-Tuning -------------------------------------------------------------------- 30
3-9 Manual Tuning ---------------------------------------------------------------- 32
3-10 Pump Control --------------------------------------------------------------- 35
3-11 Sleep Mode ----------------------------------------------------------------- 36
3-12 Remote Lockout ------------------------------------------------------------ 36
3-13 Heater Break ----------------------------------------------------------------- 37
3-14 Reload Default Parameters -------------------------------------------- 37

Chapter 4 Calibration ---------------------------------------------------- 38


Chapter 5 Error Codes and Troubleshooting ----------------------- 42

Chapter 6 Specifications ----------------------------------------------- 45

Appendix
A-1 Menu Existence / Your Settings ----------------------------------- 48
A-2 Warranty --------------------------------------------------------------- 51
2
UM4300-August-2024
Chapter 1 Overview
Unique
1 1 Features Valuable

Two function complexity levels " Soft-start " ramp and dwell timer
User menu configurable Programmable inputs( thermocouple, RTD, mA, VDC )
Adaptive heat-cool High accuracy 18-bit input A DAnalog input for remote set point and CT
High accuracy 15-bit output D A Event input for changing function & set point
Fast input sample rate (5 times / second) Programmable digital filter
dead band Hardware lockout + remote lockout protection
Pump control Loop break alarm
Fuzzy + PID microprocessor-based control Heater break alarm
Automatic programming Sensor break alarm + Bumpless transfer
Differential control RS-485, RS-232 communication
Auto-tune function Analog retransmission
Self-tune function Signal conditioner DC power supply
Sleep mode function A wide variety of output modules available
EMC / CE EN50081-1 & EN50082-2 Safety UL / CSA / CE / RoHS IEC1010 1

FDC-4300 Fuzzy Logic plus PID microprocessor-based controller, incorporates a bright,


easy to read 4-digit LED display, indicating process value. The Fuzzy Logic technology
enables a process to reach a predetermined set point in the shortest time, with the
minimum of overshoot during power-up or external load disturbance. The units are
housed in a 1/4 DIN case, measuring 96 mm x 96 mm with 53 mm behind panel
depth. The units feature three touch keys to select the various control and input
parameters. Using a unique function, you can put at most 5 parameters in front of user
menu by using SEL1 to SEL5 contained in the setup menu. This is particularly useful to
OEM's as it is easy to configure menu to suit the specific application.

FDC-4300 is powered by 11-28 or 90 - 264 VDC / AC supply, incorporating a 2 amp.


control relay output and dual 2 amp. alarm relays output as standard whereby
second alarm can be exceptionally configured into second output for cooling
purpose or dwell timer. Alternative output options include SSR drive, triac, 4 - 20 mA
and 0 - 10 volts. FDC-4300 is fully programmable for PT100, thermocouple types J, K, T,
E, B, R, S, C, P, 0 - 20mA, 4 -20mA and voltage signal input, with no need to modify the
unit. The input signals are digitized by using a 18-bit A to D converter. Its fast sampling
rate allows the FDC-4300 to control fast processes such as pressure and flow. Self tune
is incorporated. The self- tune can be used to optimize the control parameters as soon
as undesired control result is observed. Unlike auto-tune, Self-tune will produce less
disturbance to the process during tuning, and can be used any time.

The function of Fuzzy Logic is to adjust PID parameters internally in order to make
manipulation output value MV more flexible and adaptive to various processes.
PID + Fuzzy Control has been proven to be an efficient method to improve the control
stability as shown by the comparison curves below:

PID control when properly tuned

PID + Fuzzy control

Temperature

Set point

Figure 1.1 Fuzzy PID


Enhances Control
Warm Up Load Disturbance Stability

Time

UM4300-August-2024
3
1 2 Ordering Code

FDC-4300 -
Power Input 1 2 3 4 5 6 7 8 9
4: 90 - 264 VAC, 50/60 HZ
5: 11 - 26 VAC or VDC
9: Special Order Specials
Standard
Signal Input Alarm 1 Leave Blank
1: Standard Input 0: None AA-ZZ Consult
Input 1 - Universal Input 1: Relay Form C
Alarm 2 Factory
Thermocouple: J, K, T, E, B, 2A / 240VAC 0: None
R, S, C, PLII 9: Special order 1: Relay Form A Options
RTD: PT100 DIN, PT100 JIS 2A / 240VAC
9: Special order 0: None
Current: 4 - 20mA, 0 - 20 mA. 1: Nema 4X
Voltage: 0 - 1V, 0 - 5V, 1 - 5V, Output 1
0 - 10V Communications
Input 2 - CT and Analog Input 0: None
0: None
CT: 0 - 50 Amp. AC Current 1: Relay Form A
1: RS-485
Transformer** 2A/240VAC
2: RS-232
2: Pulsed voltage to
Analog Input: 4 - 20 mA, 3: Retransmit 4-20mA/0-20mA *
0 - 20mA, 0 - 1V, 0 - 5V, drive SSR, 5V/30mA
4: Retransmit 1 - 5V / 0 - 5V *
1 - 5V, 0 - 10V. 3: Isolated
5: Retransmit 0 - 10V
Input 3 - Event Input ( EI ) 4 - 20mA / 0 - 20mA*
Output 2 9: Special order
4: Isolated 1 - 5V / 0 - 5V
9: Special Order
5: Isolated 0 - 10V
* 0: None
6: Triac Output 1: Relay Form A 2A/240VAC
Example 1A / 240VAC,SSR 2: Pulsed voltage to
Standard Model: C: SSR Drive 14VDC@40ma drive SSR, 5V / 30mA
FDC-8300-41111010 9: Special order 3: Isolated 4 - 20mA / 0 - 20mA*
90 - 264 operating voltage 4: Isolated 1 - 5V / 0 - 5V *
Input: Standard Input 5: Isolated 0 - 10V
Output 1: Relay 6: Triac Output, 1A / 240VAC, SSR
Output 2: Relay 7: Isolated 20V / 25mA DC
Alarm 1: Form A Relay Output Power Supply
Alarm 2: Form A Relay 8: Isolated 12V / 40 mA DC
RS- 485 Communication Interface Output Power Supply
Options: None 9: Isolated 5V / 80mA DC
Output Power Supply
C: SSR Drive 14VDC @40ma
Accessories A: Special order
CT94-1 = 0 - 50 Amp. AC Current Transformer
Range set by front keyboard
OM95-3 = Isolated 4 - 20 mA / 0 - 20 mA Analog Output Module * Need
OM95-4 = Isolated 1 - 5V / 0 - 5V Analog Output Module ** HeatertoBreak
order an accessory CT94-1 if
detection is required.
OM95-5 = Isolated 0 - 10V Analog Output Module
OM94-6 = Isolated 1A / 240VAC Triac Output Module ( SSR ) Related Products
DC94-1 = Isolated 20V / 25mA DC Output Power Supply
DC94-2 = Isolated 12V / 40mA DC Output Power Supply SNA10A = Smart Network Adaptor for Third
DC94-3 = Isolated 5V / 80mA DC Output Power Supply Party Software, Converts 255
CM94-1 = Isolated RS-485 Interface Module channels of RS-485 or RS-422 to
CM94-2 = Isolated RS-232 Interface Module RS-232 Network
CM94-3 = Isolated 4 - 20 mA / 0 - 20 mA Retransmission Module
CM94-4 = Isolated 1 - 5V / 0 - 5V Retransmission Module
CM94-5 = Isolated 0 - 10V Retransmission Module
CC94-1 = RS-232 Interface Cable (2M)
OM94-7 = SSR Drive 14 VDC @ 40ma
Um8300 = FDC-8300 User's Manual
4
UM4300-August-2024
1 3 Mini Jumper and DIP Switch

Rear Front
Terminal Panel

ON DIP

1234

Figure 1.2 Access Hole


Access Hole Overview

The programming port is used to connect to


P10A hand-held programmer for automatic
programming, also can be connected to ATE
system for automatic testing & calibration.

DIP Switch
:ON :OFF

1 2 3 4

TC, RTD, mV

Input 1 0-1V, 0-5V, 1-5V, 0-10V


Select
0-20 mA, 4-20 mA

All parameters are Unlocked

Only SP1, SEL1 SEL5 * are unlocked Table 1.1 DIP Switch
Lockout
Only SP1 is unlocked Configuration

All Parameters are locked

Factory Default Setting


The mini jumper ( programming port ) is used for off-line automatic setup and testing
procedures only. Don't attempt to make any connection to these jumpers when the
unit is used for a normal control purpose.
When the unit leaves the factory, the DIP switch is set so that TC & RTD are selected for
input 1 and all parameters are unlocked.
Lockout function is used to disable the adjustment of parameters as well as operation
of calibration mode. However, the menu can still be viewed even under lockout

* SEL1- SEL5 represent those parameters which are selected by using SEL1, SEL2,...SEL5
parameters contained in Setup menu. Parameters been selected are then allocated at
the beginning of the user menu.
5
UM4300-August-2024
1 4 Keys and Displays
The unit is programmed by using three keys on the front panel. The available key functions are listed in following table.
Table 1.2 Keypad Operation
TOUCHKEYS FUNCTION DESCRIPTION

Press and release quickly to increase the value of parameter.


Up Key
Press and hold to accelerate increment speed.

Press and release quickly to decrease the value of parameter.


Down Key
Press and hold to accelerate decrement speed.

Scroll Key Select the parameter in a direct sequence.

Allow access to more parameters on user menu, also used to Enter manual
Press mode, auto-tune mode, default setting mode and to save calibration data
Enter Key
for at least 3 seconds during calibration procedure.

Press Reset historical values of PVHI and PVLO and start to record the peak process
Start Record Key
for at least 6 seconds value.

Press Reverse Scroll Key Select the parameter in a reverse sequence during menu scrolling.

Press Mode Key Select the operation Mode in sequence.

Reset the front panel display to a normal display mode, also used to leave
Press Reset Key the specific Mode execution to end up the auto-tune and manual control
execution, and to quit the sleep mode.

Press The controller enters the sleep mode if the sleep function ( SLEP ) is enabled
Sleep Key
for at least 3 seconds ( select YES ).

By entering correct security code to allow execution of engineering programs.


Press Factory Key This function is used only at the factory to manage the diagnostic reports.
The user should never attempt to operate this function.

Upper Display, to display process value,


menu symbol and error code etc. How to display a 5-digit number ? Power On Sequence
For a number with decimal point the
display will be shifted one digit right:
1.) Display segments OFF for 0.5 secs.
-199.99 will be displayed by -199.9
Out 1 LED
Process Unit 4553.6 will be displayed by 4553 2.) Display segments ON for 2.0 secs
Indicator
Out 2 LED
3.) Display Program Code for 2.5 secs
Lower Display, For a number without decimal point 4.) Display Date Code for 1.25 secs.
Alm 1 LED to display set point the display will be divided into two
Alm 2 LED value,parameter 5.) Display S/N for 1.25 secs
alternating phases:
value or control
output value etc. -19999 will be displayed by:
FDC-4300
3 Buttons for ease Program Code
of control setup
and set point
adjustment.

Figure 1.4 Front Panel Description 45536 will be displayed by: Program Version
Program No.
Table 1.3 Display Form of Characters
Date Code
A E I N S X
B F J O T Y
-9999 will be displayed by:
C G K P U Z
Date (31'st)
c H L Q V ? Month (December)
Year (1999)
D h M R W =
: Confused Character
6 UM4300-August-2024
1 5 Menu Overview
PV Value User
SV Value Menu *2
Press to enter Setup Mode. Press to select parameter. The upper SEL1
SEL2
display indicates the parameter symbol, and the lower display indicates the SEL3
selection or the value of parameter. SEL4
SEL5

for 3
Setup seconds
Menu *1 *1
FUNC TIME
COMM A1SP
PROT A1DV
ADDR A2SP
BAUD A2DV
Hand (Manual) DATA RAMP
for 3 seconds
PARI OFST
Control STOP REFC
Mode AOFN SHIF
H AOLO PB1
C AOHI TI1
IN1 TD1
IN1U CPB
DP1 DB
Auto-tuning IN1L SP2
Mode IN1H PB2
IN2 TI2
Press for 3 seconds to enter
the auto-tuning mode IN2U TD2
DP2 O1HY
IN2L A1HY
IN2H A2HY
OUT1 PL1
O1TY PL2
Display CYC1
Mode O1FT
OUT2
PVHI O2TY
PVLO CYC2
H O2FT Display Go Home
C A1FN
DV
The menu will revert to
A1MD
PV1 A1FT
PV/SV display after keyboard
Default PV2 is kept untouched for
A2FN
Setting PB A2MD 2 minutes except Display
FILE TI
Mode for
A2FT Mode Menu and Manual
TD EIFN
3 seconds Mode Menu. However, the
CJCT PVMD
To execute the PVR menu can revert to PV / SV
FILT
default setting PVRH
program SELF display at any time by
PVRL SLEP pressing and .
SPMD
Calibration SP1L
Mode SP1H
SP2F
AD0 SEL1
ADG SEL2
V1G SEL3
CJTL SEL4
CJG SEL5
REF1
SR1
*1: The flow chart shows a complete listing of all parameters.
MA1G
For actual application the number of available parameters
V2G
depends on setup conditions, and should be less
MA2G
than that shown in the flow chart. See Appendix A-1 for the
existence conditions of each parameter.
Apply these modes will break the control loop and change *2: You can select at most 5 parameters put in front of the
some of the previous setting data. Make sure that if the user menu by using SEL1 to SEL5 contained at the bottom
system is allowable to use these modes. of setup menu.
7
UM4300-August-2024
1 6 Parameter Description
Table 1.4 Parameter Description
Contained Basic Parameter Display Parameter
Range Default
in Function Notation Format Description Value
Set point 1 100.0 C
SP1 Low: SP1L High: SP1H (212.0 F)
TIME Dwell Time Low: 0 High: 6553.5 minutes 0.0
Alarm 1 Set point 100.0 C
A1SP See Table 1.5, 1.6 (212.0 F)
-200.0 C 200.0 C 10.0 C
A1DV Alarm 1 Deviation Value Low: (-360.0 F) High: ( 360.0 F) (18.0 F)
100.0 C
A2SP Alarm 2 Set point See Table 1.5, 1.7 (212.0 F)
-200.0 C 200.0 C 10.0 C
A2DV Alarm 2 Deviation Value Low: (-360.0 F) High: ( 360.0 F) (18.0 F)
Ramp Rate 500.0 C
RAMP Low: 0 High: (900.0 F) 0.0

OFST Offset Value for P control Low: 0 High: 100.0 % 25.0


Reference Constant for High:
REFC Specific Function Low: 0 60 2
-200.0 C High: 200.0 C
SHIF PV1 Shift (offset) Value Low: (-360.0 F) ( 360.0 F) 0.0

PB1 Proportional Band 1 Value Low: 0 High: 500.0 C 10.0 C


(900.0 F) (18.0 F)
User TI1 Integral Time 1 Value Low: 0 High: 1000 sec 100
Menu
TD1 Derivative Time 1 Value Low: 0 High: 360.0 sec 25.0
Cooling Proportional Band 1 High: 255 % 100
CPB Value Low:
Heating-Cooling Dead Band High:
DB Negative Value= Overlap Low: -36.0 36.0% 0
37.8 C
SP2 Set point 2 See Table 1.5, 1.8 (100.0 F)
Proportional Band 2 Value 500.0 C 10.0 C
PB2 Low: 0 High: (900.0 F) (18.0 F)
TI2 Integral Time 2 Value Low: 0 High: 1000 sec 100

TD2 Derivative Time 2 Value Low: 0 High: 360.0 sec 25.0


Output 1 ON-OFF Control 55.6 C
O1HY Hysteresis Low: 0.1 High: ( 100.0 F) 0.1

Hysteresis Control of Alarm 1 10.0 C


A1HY Low: 0.1 High: (18.0 F) 0.1

Hysteresis Control of Alarm 2 10.0 C


A2HY Low: 0.1 High: (18.0 F) 0.1

PL1 Output 1 Power Limit Low: 0 High: 100 % 100

PL2 Output 2 Power Limit Low: 0 High: 100 % 100

0 : Basic Function Mode


FUNC Function Complexity Level 1
1 : Full Function Mode

0 : No communication function

1 : RS-485 interface

2 : RS-232 interface

3 : 4 - 20 mA analog retransmission
output
Setup
COMM Communication Interface 4 : 0 - 20 mA analog retransmission 1
Menu
Type output

5 : 0 - 1V analog retransmission
output

6 : 0 - 5V analog retransmission
output

7 : 1 - 5V analog retransmission
output
8 : 0 - 10V analog retransmission
output

PROT COMM Protocol Selection 0 : Modbus protocol RTU mode 0

8 UM4300-August-2024
Table 1.6 Parameter Description
Contained Basic Parameter Display Parameter
Range Default
in Function Notation Format Description Value
Address Assignment of Digital High: 255
ADDR COMM Low: 1

0 : 0.3 Kbits/s baud rate

1 : 0.6 Kbits/s baud rate

2 : 1.2 Kbits/s baud rate

3 : 2.4 Kbits/s baud rate

4 : 4.8 Kbits/s baud rate

BAUD Baud Rate of Digital COMM 5 : 9.6 Kbits/s baud rate 5

6 : 14.4 Kbits/s baud rate

7 : 19.2 Kbits/s baud rate

8 : 28.8 Kbits/s baud rate

9 : 38.4 Kbits/s baud rate

Data Bit count of Digital 0 : 7 data bits


DATA 1
COMM 1 : 8 data bits

0 : Even parity

PARI Parity Bit of Digital COMM 1 : Odd parity 0

2 : No parity bit

Stop Bit Count of Digital 0 : One stop bit


STOP 0
COMM
1 : Two stop bits
Setup
Menu
0 : Retransmit IN1 process value

1 : Retransmit IN2 process value

2 : Retransmit IN1 IN2 difference


process value

3 : Retransmit IN2 IN1 difference


process value

AOFN Analog Output Function 4 : Retransmit set point value 0

5 : Retransmit output 1 manipulation


value

6 : Retransmit output 2 manipulation


value

7 : Retransmit deviation(PV-SV)
Value
Analog Output Low Scale 0C
AOLO Value Low: -19999 High: 45536 (32.0 F)
Analog Output High Scale High: 45536 100.0 C
AOHI Value Low: -19999 (212.0 F)
0 : J type thermocouple

1 : K type thermocouple

2 : T type thermocouple

3 : E type thermocouple
1
IN1 IN1 Sensor Type Selection 4 : B type thermocouple
(0)
5 : R type thermocouple

6 : S type thermocouple

9
UM4300-August-2024
Table 1.6 Parameter Description
Contained Basic Parameter Display Parameter
Range Default
in Function Notation Format Description Value
7 : C type thermocouple

8 : P type thermocouple

9 : PT 100 ohms DIN curve

10 : PT 100 ohms JIS curve

11 : 4 - 20 mA linear current input


1
IN1 IN1 Sensor Type Selection 12 : 0 - 20 mA linear current input (0)
13 : 0 - 1V linear Voltage input

14 : 0 - 5V linear Voltage input

15 : 1 - 5V linear Voltage input

16 : 0 - 10V linear Voltage input

17 : Special defined sensor curve

0 : Degree C unit
0
IN1U IN1 Unit Selection 1 : Degree F unit
(1)
2 : Process unit

0 : No decimal point

1 : 1 decimal digit
DP1 IN1 Decimal Point Selection 1
2 : 2 decimal digits

3 : 3 decimal digits
Setup
Menu
IN1L IN1 Low Scale Value Low: -19999 High: 45536 0

IN1H IN1 High Scale Value Low: -19999 High: 45536 1000

0 : IN2 no function

1 : Current transformer input

2 : 4 - 20 mA linear current input

3 : 0 - 20 mA linear current input

IN2 IN2 Signal Type Selection 4 : 0 - 1V linear voltage input 1

5 : 0 - 5V linear voltage input

6 : 1 - 5V linear voltage input

7 : 0 - 10V linear voltage input

IN2U IN2 Unit Selection Same as IN1U 2

DP2 IN2 Decimal Point Selection Same as DP1 1

IN2L IN2 Low Scale Value Low: -19999 High: 45536 0

IN2H IN2 High Scale Value Low: -19999 High: 45536 1000

0 : Reverse (heating ) control action


OUT1 Output 1 Function 0
1 : Direct (cooling) control action

0 : Relay output
1 : Solid state relay drive output
2 : Solid state relay output

O1TY Output 1 Signal Type 3 : 4 - 20 mA current module 0

UM4300-August-2024 10
Table 1.6 Parameter Description
Contained Basic Parameter Display Parameter
Range Default
in Function Notation Format Description Value
4 : 0 - 20 mA current module

5 : 0 - 1V voltage module

O1TY Output 1 Signal Type 6 : 0 - 5V voltage module 0


7 : 1 - 5V voltage module

8 : 0 - 10V voltage module

CYC1 Output 1 Cycle Time Low: 0.1 High: 100.0 sec 18.0
Select BPLS ( bumpless transfer ) or 0.0 ~ 100.0
Output 1 Failure Transfer % to continue output 1 control function as the unit BPLS
O1FT Mode fails, power starts or manual mode starts.

0 : Output 2 no function

1 : PID cooling control 0


OUT2 Output 2 Function

2 : DC power supply module


installed

O2TY Output 2 Signal Type Same as O1TY 0

CYC2 Output 2 Cycle Time Low: 0.1 High: 100.0 sec 18.0
Select BPLS ( bumpless transfer ) or 0.0 ~ 100.0
Output 2 Failure Transfer % to continue output 2 control function as the unit
O2FT Mode BPLS
fails, power starts or manual mode starts.

0 : No alarm function
Setup
Menu 1 : Dwell timer action

2 : Deviation high alarm

3 : Deviation low alarm

4 : Deviation band out of band alarm

5 : Deviation band in band alarm

6 : IN1 process value high alarm

7 : IN1 process value low alarm


A1FN Alarm 1 Function 2
8 : IN2 process value high alarm

9 : IN2 process value low alarm

10 : IN1 or IN2 process value high


alarm
11 : IN1 or IN2 process value low
alarm
12 : IN1 IN2 difference process value
high alarm
13 : IN1 IN2 difference process value
low alarm
14 : Loop break alarm

15 : Sensor break or A-D fails

0 : Normal alarm action

1 : Latching alarm action


A1MD Alarm 1 Operation Mode 0
2 : Hold alarm action

3 : Latching & Hold action

UM4300-August-2024 11
Table 1.6 Parameter Description
Contained Basic Parameter Display Parameter
Range Default
in Function Notation Format Description Value
0 : Alarm output OFF as unit fails
Alarm 1 Failure Transfer
A1FT Mode 1
1 : Alarm output ON as unit fails

A2FN Alarm 2 Function Same as A1FN 2

A2MD Alarm 2 Operation Mode Same as A1MD 0


A2FT Alarm 2 Failure Transfer Same as A1FT
Mode 1
0 : Event input no function

1 : SP2 activated to replace SP1

2 : PB2, TI2, TD2 activated to replace


PB1, TI1, TD1

3 : SP2, PB2, TI2, TD2 activated to


replace SP1, PB1, TI1, TD1

4 : Reset alarm 1 output

EIFN Event Input Function 5 : Reset alarm 2 output 1

6 : Reset alarm 1 & alarm 2

7 : Disable Output 1

8 : Disable Output 2

9 : Disable Output 1 & Output 2

10 : Lock All Parameters

11 : Selects remote setpoint active


Setup
Menu
0 : Use PV1 as process value

1 : Use PV2 as process value


PVMD PV Mode Selection 2 : Use PV1 0
PV2 (difference) as
process value
3 : Use PV2 PV1 (difference) as
process value

0 : 0 second time constant

1 : 0.2 second time constant

2 : 0.5 second time constant

3 : 1 second time constant

4 : 2 seconds time constant


Filter Damping Time
FILT 2
Constant of PV : 5 seconds time constant
5

6 : 10 seconds time constant

7 : 20 seconds time constant

8 : 30 seconds time constant

9 : 60 seconds time constant

0 : Self tune function disabled


Self Tuning Function
SELF 0
Selection 1 : Self tune function enabled

0 : Sleep mode function disabled


Sleep mode Function
SLEP 0
Selection 1 : Sleep mode function enabled

12 UM4300-August-2024
Table 1.6 Parameter Description
Contained Basic Parameter Display Parameter
Range Default
in Function Notation Format Description Value
0 : Use SP1 or SP2 (depends on EIFN)
as set point
1 : Use minute ramp rate as set point

2 : Use hour ramp rate as set point


SPMD Set point Mode Selection 0
3 : Use IN1 process value as set point

4 : Use IN2 process value as set point

5 : Selected for pump control


Low: -19999 High: 45536 0C
SP1L SP1 Low Scale Value (32.0 F)
SP1 High Scale Value Low: -19999 High: 45536 1000.0 C
SP1H (1832.0 F)
0 : set point 2 (SP2) is an actual value
SP2F Format of set point 2 Value 0
1 : set point 2 (SP2) is a deviation
value
0 : No parameter put ahead

1 : Parameter TIME put ahead

2 : Parameter A1SP put ahead

3 : Parameter A1DV put ahead

4 : Parameter A2SP put ahead

5 : Parameter A2DV put ahead

6 : Parameter RAMP put ahead

7 : Parameter OFST put ahead


Setup
Menu 8 : Parameter REFC put ahead 0
SEL1 Select 1'st Parameter
9 : Parameter SHIF put ahead

10 : Parameter PB1 put ahead

11 : Parameter TI1 put ahead

12 : Parameter TD1 put ahead

13 : Parameter CPB put ahead

14 : Parameter DB put ahead

15 : Parameter SP2 put ahead

16 : Parameter PB2 put ahead

17 : Parameter TI2 put ahead

18 : Parameter TD2 put ahead

SEL2 Select 2'nd Parameter Same as SEL1 0

SEL3 Select 3'rd Parameter Same as SEL1 0

SEL4 Select 4'th Parameter Same as SEL1 0

SEL5 Select 5'th Parameter Same as SEL1 0

AD0 A to D Zero Calibration -360 High: 360


Coefficient Low:
A to D Gain Calibration -199.9 High: 199.9
ADG Coefficient Low:
Calibration Voltage Input 1 Gain
Mode V1G Low: -199.9 High: 199.9
Calibration Coefficient
Menu
Cold Junction Low
CJTL Temperature Calibration Low: -5.00 C High: 40.00 C
Coefficient

UM4300-August-2024 13
Table 1.6 Parameter Description
Contained Basic Parameter Display Parameter
Range Default
in Function Notation Format Description Value
Cold Junction Gain -199.9 199.9
CJG Calibration Coefficient Low: High:

Reference Voltage 1
REF1 Calibration Coefficient for Low: -199.9 High: 199.9
RTD 1

Calibration Serial Resistance 1


Mode SR1 Calibration Coefficient for Low: -199.9 High: 199.9
Menu RTD 1
mA Input 1 Gain Calibration -199.9 High: 199.9
MA1G Coefficient Low:

V2G Voltage Input 2 Gain


Calibration Coefficient Low: -199.9 High: 199.9
MA2G mA Input 2 Gain Calibration -199.9 High: 199.9
Coefficient Low:
Historical Maximum Value of Low: -19999 High: 45536
PVHI PV
Historical Minimum Value of -19999 High: 45536
PVLO PV Low:

MV1 Current Output 1 Value Low: 0 High: 100.00 %

MV2 Current Output 2 Value Low: 0 High: 100.00 %


Current Deviation (PV-SV) Low: -12600 High: 12600
DV Value
PV1 IN1 Process Value Low: -19999 High: 45536
Display
Mode PV2 IN2 Process Value Low: -19999 High: 45536
Menu
Current Proportional Band High: 500.0 C
PB Low: 0 (900.0 F)
Value
TI Current Integral Time Value Low: 0 High: 4000 sec
Current Derivative Time Low: 0 High: 1440 sec
TD Value
Cold Junction Compensation High:
CJCT Temperature Low: -40.00 C 90.00 C

PVR Current Process Rate Value Low: -16383 High: 16383

PVRH Maximum Process Rate Value Low: -16383 High: 16383

PVRL Minimum Process Rate Value Low: -16383 High: 16383

Input Type J_TC K_TC T_TC E_TC B_TC R_TC S_TC


-120 C -200 C -250 C -100 C
Range Low (-184 0C 0C 0C
F) (-328 F) (-418 F) (-148 F) (32 F) (32 F) (32 F)
1000 C 1370 C 400 C
Range High (1832 900 C 1820 C 1767.8 C 1767.8 C
F) (2498 F) (752 F) (1652 F) (3308 F) (3214 F) (3214 F)
Table 1.5 Input ( IN1 or IN2 ) Range
Input Type N_TC L_TC PT.DN PT.JS CT Linear ( V, mA)
or SPEC
-250 C -200 C -210 C -200 C
Range Low (-418 0 Amp
F) (-328 F) (-346 F) (-328 F) -19999

Range High (2372 C


1300 900 C 700 C 600 C 90 Amp
F) (1652 F) (1292 F) (1112 F) 45536

14 UM4300-August-2024
Chapter 2 Installation

Dangerous voltages capable of causing death are sometimes


present
in this instrument. Before installation or beginning any troubleshooting
procedures the power to all equipment must be switched off and isolated.
Units suspected of being faulty must be disconnected and removed to a
properly equipped workshop for testing and repair. Component replacement

To minimize the possibility of fire or shock hazards, do not expose this


instrument to rain or excessive moisture.

Do not use this instrument in areas under hazardous conditions such


as excessive shock, vibration, dirt, moisture, corrosive gases or oil. The
ambient temperature of the areas should not exceed the maximum rating

2 1 Unpacking
Upon receipt of the shipment remove the unit from the carton and inspect the
unit for shipping damage.
If any damage due to transit , report and claim with the carrier.
Write down the model number, serial number, and date code for future reference
when corresponding with our service center. The serial number (S/N) and date
code (D/C) are labeled on the box and the housing of control.

2 2 Mounting
Make panel cutout to dimension shown in Figure 2.1.

Take both mounting clamps away and insert the controller into panel cutout.
Install the mounting clamps back. Gently tighten the screws in the clamp till the
controller front panels is fitted snugly in the cutout.
3.62 “
92 mm

Panel Cutout

Figure 2.1 Mounting Dimensions

Panel
3.62 “
92 mm
2.08”
53 mm

15
UM4300-August-2024
2 3 Wiring Precautions
* Before wiring, verify the label for correct model number and options. Switch
off the power while checking.

* Care must be taken to ensure that maximum voltage rating specified on the
label are not exceeded.

* It is recommended that power of these units to be protected by fuses or circuit


breakers rated at the minimum value possible.

* All units should be installed inside a suitably grounded metal enclosure to


prevent live parts being accessible from human hands and metal tools.

* All wiring must conform to appropriate standards of good practice and local
codes and regulations. Wiring must be suitable for voltage, current, and
temperature rating of the system.

* Beware not to over-tighten the terminal screws.


* Unused control terminals should not be used as jumper points as they may
be internally connected, causing damage to the unit.

* Verify that the ratings of the output devices and the inputs as specified in
Chapter 6 are not exceeded.

* Electric power in industrial environments contains a certain amount of noise in


the form of transient voltage and spikes. This electrical noise can enter and
the form of transient voltage and spikes. This electrical noise can enter and
adversely affect the operation of microprocessor-based controls. For this
reason we strongly recommend the use of shielded thermocouple extension
wire which connects the sensor to the controller. This wire is a twisted-pair
construction with foil wrap and drain wire. The drain wire is to be attached to
ground at one end only.

7.0mm max.
3.2mm min.
Figure 2.2 Lead Termination

90-264 VAC
47-63 Hz
1 L 11
Alarm 2
15 VA 2 N 12
+ 3 C 13 AO+
TX1
OP1
4 NO 14 AO
TX2
+ 5 C 15 +
OP2 AI, CT
6 NO 16 Figure 2.3 Rear Terminal
7 C 17
EI Connection Diagram
+ A
Alarm 1 8 18 RTD
NO NC + +
9 19 B
V
COM 10 20 B

ALL RELAY CONTACTS:


16 RESISTIVE 2A/240VAC
UM4300-August-2024
2 4 Power Wiring
The controller is supplied to operate at 11-28 VAC / VDC or 90-264VAC.Check
that the installation voltage corresponds with the power rating indicated on the
product label before connecting power to the controller.
Fuse
90 ~ 264 VAC or
11 ~ 26 VAC / VDC

Figure 2.4
1 11
Power Supply Connections
2 12
3 13
4 14
5 15
6 16
7 17
8 18
9 19
10 20

This equipment is designed for installation in an enclosure which provides


adequate protection against electric shock. The enclosure must be connected
to earth ground.

Local requirements regarding electrical installation should be rigidly observed.


Consideration should be given to prevent from unauthorized person access to
the power terminals.

2 5 Sensor Installation Guidelines

Proper sensor installation can eliminate many problems in a control system.


The probe should be placed so that it can detect any temperature change
with minimal thermal lag. In a process that requires fairly constant heat
output, the probe should be placed closed to the heater. In a process where
the heat demand is variable, the probe should be closed to the work area.
Some experiments with probe location are often required to find this
optimum position.

In a liquid process, addition of a stirrer will help to eliminate thermal lag.


Since the thermocouple is basically a point measuring device, placing more
than one thermocouple in parallel can provide an average temperature
readout and produce better results in most air heated processes.

Proper sensor type is also a ver y important factor to obtain precise


measurements. The sensor must have the correct temperature range to
meet the process requirements. In special processes the sensor might need
to have different requirements such as leak-proof, anti-vibration, antiseptic,
etc.

Standard sensor limits of error are A4degrees F (A 2degrees C ) or 0.75% of


sensed temperature (half that for special ) plus drift caused by improper
protection or an over-temperature occurrence. This error is far greater than
controller error and cannot be corrected on the sensor except by proper
17
selection and replacement.
UM4300-August-2024
2 6 Thermocouple Input Wiring
Thermocouple input connections are shown in Figure 2.5. The correct type of
thermocouple extension lead-wire or compensating cable must be used for the
distance between the controller and the thermocouple, ensuring that the correct
polarity is observed throughout. Joints in the cable should be avoided, if possible.

If the length of thermocouple plus the extension wire is too long, it may affect the
temperature measurement. A 400 ohms K type or a 500 ohms J type thermocouple
lead resistance will produce 1 degree C temperature error approximately.

1 11
2 12
ON
1

3 13
2

4 14
3

5 15
Figure 2.5
6 16
4

Thermocouple Input Wiring


7 17
8 18
DIP Switch +
9 19
10 20

Thermocouple

2 7 RTD Input Wiring


RTD connection are shown in Figure 2.6, with the compensating lead connected
to terminal 12. For two-wire RTD inputs, terminals 12 and 13 should be linked. The
three-wire RTD offers the capability of lead resistance compensation provided that
the three leads should be of same gauge and equal length.

Two-wire RTD should be avoided, if possible, for the purpose of accuracy. A


0 . 4 o h m l e a d r e s i s t a n c e o f a t w o -w i r e R T D w i l l p r o d u c e 1 d e g r e e C
temperature error.

1 11 1 11
2 12 2 12
3 13 3 13
4 14 4 14
5 15 5 15
Figure 2.6
ON
1

6 16 6 16
RTD Input Wiring
2

7 17 7 17
RTD
3

8 18 8 18
9 19 9 19
4

10 20 10 20
RTD
DIP Switch
18 Three-wire RTD Two-wire RTD

UM4300-August-2024
2 8 Linear DC Input Wiring
DC linear voltage and linear current connections for input 1 are shown in Figure
2.7 and Figure 2.8 .

DC linear voltage and linear current connections for input 2 are shown in Figure
2.9 and Figure 2.10 .

Figure 2.7 Figure 2.8


Input 1 Linear Voltage Wiring Input 1 Linear Current Wiring

1 11

ON
1 11
ON

1
1

2 12 2 12

2
2

3 13 3 13

3
3

4 14 4 14

4
4

5 15 5 15

DIP Switch 6 16 DIP Switch 6 16


7 17 7 17
8 18 8 18

+
+
9 19 9 19
10 20 10 20

0~1V, 0~5V 0~20mA or


1~5V, 0~10V 4~20mA

Figure 2.9 Figure 2.10


Input 2 Linear Voltage Wiring Input 2 Linear Current Wiring

1 11 1 11
2 12 2 12
3 13 3 13
4 14 4 14

+
+

5 15 5 15
6 16 6 16
7 17 7 17
0~1V, 0~5V 0~20mA or
8 18 8 18
1~5V, 0~10V 4~20mA
9 19 9 19
10 20 10 20

2 9 CT / Heater Current Input Wiring

1 11
2 12
Figure 2.11
3 13
CT Input Wiring for
4 14
Single Phase Heater
+

5 15
6 16
7 17
8 18
9 19
10 20 CT Signal Input *Total current CT94-1 not to
exceed 50 A RMS. 19
UM4300-August-2024
2 10 Output 1 Wiring
Max. 2A
Resistive
Load 120V/240V 0 - 20mA,
Mains Supply Load
4 - 20mA
Maximum Load
+
500 ohms
1 11 1 11
2 12 2 12
3 13
+ 3 13
4 14 4 14
5 15 5 15
6 16 6 16
7 17 7 17
8 18 8 18
9 19 9 19
10 20 10 20

Relay Output Linear Current

0 - 1V, 0 - 5V Load
1 - 5V, 0 - 10V
+ Minimum Load
1 11
10 K ohms
1 11
2 12 2 12
+ +
3 13 3 13
4 14 4 14
5 15 5 15
5VDC@30ma or
14VDC @40ma 6 16 6 16
Pulsed Voltage 7 17 7 17
8 18 8 18
9 19 9 19
10 20 10 20

Pulsed Voltage to Drive SSR Linear Voltage

Max. 1A / 240V
Load 120V /240V
Mains Supply

1 11
2 12
3 13
4 14
5 15
6 16
Figure 2.12
7 17
Output 1 Wiring
8 18
9 19
10 20

Triac (SSR) Output


Direct Drive
20
UM4300-August-2024
2 11 Output 2 Wiring
Max. 2A
Resistive
Load 0 - 20mA, Maximum Load
120V/240V Load
4 - 20mA 500 ohms
Mains Supply
+

1 11 1 11
2 12 2 12
3 13 3 13
4 14 4 14
5 15
+ 15
5
6 16 6 16
7 17 7 17
8 18 8 18
9 19 9 19
10 20 10 20

Relay Output Linear Current

0 - 1V, 0 - 5V Load Minimum Load


1 - 5V, 0 - 10V 10 K ohms
+

1 11 1 11
5VDC@30ma or 2 12 2 12
14VDC @40ma 3 13 3 13
Pulsed Voltage 4 14 4 14
+ +
5 15 5 15
6 16 6 16
7 17 7 17
8 18 8 18
9 19 9 19
10 20 10 20

Pulsed Voltage to Drive SSR Linear Voltage

Max. 1A / 240V
Load 120V /240V
Mains Supply

Figure 2.13
1 11 Output 2 Wiring
2 12
3 13
4 14
5 15
6 16
7 17
8 18
9 19
10 20

Triac (SSR) Output


Direct Drive 21

UM4300-August-2024
2 12 Event Input wiring

1 11 1 11
2 12 2 12
3 13 3 13
4 14 4 14
5 15 5 15 Figure 2.14
6 16 6 16 Event Input Wiring
7 17 7 17
+
8 18 8 18
9 19 9 19
10 20 10 20

Open Collector Switch Input


Input
The event input can accept a switch signal as well as an open collector signal. The
event input function ( EIFN ) is activated as the switch is closed or an open collector
( or a logic signal ) is pulled down.

2 13 Alarm 1 Wiring
Max. 2A resistive
Load 120V/240V
Mains Supply Figure 2.15
Alarm 1 Wiring
1 11
2 12
3 13 NOTE: Alarm 1 is a Form C Relay
4 14 Terminal 7 - Com
5 15
Relay Output Terminal 8 - N.O.
6 16
Alarm 1 Terminal 9 - N.C.
7 17
Example shows load wired across
8 18
9 19
Com and N.O. Contact
10 20

2 14 Alarm 2 Wiring
Max. 2A
Resistive
1 11 Load 120V/240V
2 12 Mains Supply
3 13
Relay Output
4 14
5 15
6 16
Figure 2.16
7 17
Alarm 2 Wiring
8 18
9 19
10 20
22
UM4300-August-2024
2 15 RS-485

Figure 2.18
RS-485 to RS-232
RS-485 Wiring
1 11 network adaptor
2 12
3 13
TX1 RS-232
4 14 TX1
5 15 TX2
TX2
SNA10A or
SNA10B
PC
6 16
7 17
8 18
9 19
Figure 2.17
10 20
RS-485 Wiring
Twisted-Pair Wire

1 11 1 11
2 12 TX1 2 12
3 13 TX1
3 13
4 14 4 14
5 15 TX2 5 15 TX2
6 16 6 16
7 17 7 17
8 18 8 18
9 19 9 19 Terminator
10 20 10 20 220 ohms / 0.5W
End unit of limk
Max. 247 units can be linked

2 16 Analog Retransmission Figure 2.18 Analog


Retransmission Wiring

1 11
0 - 20mA, 1 11 1 - 5 V, 0 - 5V
2 12
4 - 20mA 2 12 0 - 10V
+

3 13 3 13
4 14 4 14
+

5 15 5 15
6 16 Load 6 16
7 17 7 17
8 18 8 18
+

9 19 9 19
Load Load
10 20 10 20
+

Load
Retransmit Current
+

Retransmit Voltage
+

Do not exceed 500 ohms total load Load Minimum load must be greater than 10K ohms. Load

Output typically used for Indicators PLC's Recorders Data loggers Inverters etc.
23
UM4300-August-2024
2 17 RS-232

1 11
2 12 PC
3 TX1 13
4 TX2 14
5 15
Figure 2.19
6 16 RS-232 Wiring
7 17
8 18 9-pin
9 19 RS-232 port
10 COM 20

CC94-1

If you use a conventional 9-pin RS-232 cable instead of CC94-1, the cable
must be modified according to the following circuit diagram.

To DTE ( PC ) RS-232 Port

1 DCD
BTC-4300
1 2 RD
6
TX1 RD 3 TD Figure 2.21
TX1 13 2
7 4 DTR Configuration of RS-232
TX2 TD 3
TX2 14 8 5 GND Cable
4
9
6 DSR
COM GND 5 7 RTS
COM 10
8 CTS
9 RI
Female DB-9

24
UM4300-August-2024
Chapter 3 Programming Special Functions
This unit provides an useful parameter " FUNC " which can be used to
select the function complexity level before setup. If the Basic Mode ( FUNC
= BASC ) is selected for a simple application, then the following functions
are ignored and deleted from the full function menu:
RAMP, SP2, PB2, TI2, TD2, PL1, PL2, COMM, PROT, ADDR, BAUD, DATA, PARI,
STOP, AOFN, AOLO, AOHI, IN2, IN2U, DP2, IN2L, IN2H, EIFN, PVMD, FILT, SLEP,
SPMD and SP2F.

Basic Mode capabilities: If you don't need:


(1) Input 1: Thermocouple, RTD, Volt, mA (1) Second setpoint
(2) Input 2: CT for heater break detection (2) Second PID
(3) Output 1: Heating or Cooling ( Relay, SSR, SSRD, Volt, mA ) (3) Event input
(4) Output 2 : Cooling ( Relay, SSR, SSRD, Volt, mA ), DC Power supply. (4) Soft start (RAMP)
(5) Alarm 1: Relay for Deviation, Deviation Band, Process, Heater Break, Loop (5) Remote set point
Break, Sensor Break, Latch, Hold or Normal Alarm. (6) Complex process value
(6) Alarm 2: Relay for Deviation, Deviation Band, Process, Heater Break, Loop (7) Output power limit
Break, Sensor Break, Latch, Hold or Normal Alarm. (8) Digital communication
(7) Dwell Timer (16) Hardware Lockout (9) Analog retransmission
(8) Heater Break Alarm (17) Self-Tune (10) Power shut off (Sleep Mode)
(9) Loop Break Alarm (18) Auto-Tune (11) Digital filter
(10) Sensor Break Alarm (19) ON-OFF, P, PD, PI, PID Control (12) Pump control
(11) Failure Transfer (20) User Defined Menu (SEL) (13) Remote lockout
(12) Bumpless Transfer (21) Manual Control then you can use Basic Mode.
(13) PV1 Shift (22) Display Mode
(14) Programmable SP1 Range (23) Reload Default Values
(15) Heat-Cool control (24) Isolated DC Power Supply

3 1 Rearrange User Menu


The conventional controllers are designed with a fixed parameters' scrolling. If SEL1
you need a more friendly operation to suit your application, the manufacturer
will say " sorry " to you. The FDC-4300 has the flexibility for you to select those
parameters which are most significant to you and put these parameters in the SEL2
front of display sequence.
SEL1 : Selects the most significant parameter for view and change.
SEL2 : Selects the 2'nd significant parameter for view and change. SEL3
SEL3 : Selects the 3'rd significant parameter for view and change.
SEL4 : Selects the 4'th significant parameter for view and change.
SEL5 : Selects the 5'th significant parameter for view and change. SEL4
Range : NONE, TIME, A1.SP, A1.DV, A2.SP, A2.DV, RAMP, OFST,
REFC, SHIF, PB1, TI1, TD1, C.PB, DB, SP2, PB2, TI2, TD2
When using the up-down key to select the parameters, you may not obtain
SEL5
all of the above parameters. The number of visible parameters is dependent
on the setup condition. The hidden parameters for the specific application are
also deleted from the SEL selection.
Example : SEL1 selects TIME Now, the upper display scrolling becomes :
SEL2 selects A2.DV
SEL3 selects OFST
SEL4 selects PB1 PV
SEL5 selects NONE

25

UM4300-August-2024
3 2 Dwell Timer
Alarm 1 or alarm 2 can be configured as dwell timer by selecting TIMR for
A1FN or A2FN, but not both, otherwise Er07 will appear. As the dwell timer is
configured, the parameter TIME is used for dwell time adjustment.
The dwell time is measured in minute ranging from 0 to 6553.5 minutes.
O n c e
the process reaches the set point the dwell timer starts to count from zero
u n t i l

PV
Error Code
SP1

If alarm 1 is configured as dwell timer, A1SP, A1DV, A1HY and A1MD are hidden.
Same case is for alarm 2.

A1 or A2
Time Example :
TIME Set A1FN=TIMR or A2FN=TIMR but not both.
Adjust TIME in minutes
ON
A1MD ( if A1FN=TIMR ) or A2MD ( if A2FN=TIMR ) is ignored in this case.
OFF If a form B relay is required for dwell timer, then order form B alarm 1 and
configure A1FN. Form B relay is not available for alarm 2.
Time
Timer starts

Figure 3.1 Dwell Timer Function

3 3 Manual Control
The manual control may be used for the following purposes:
( 1 ) To test the process characteristics to obtain a step response as well as an
impulse response and use these data for tuning a controller.
( 2 ) To use manual control instead of a close loop control as the sensor fails or
the controller's A-D converter fails. NOTE that a bumpless transfer can not
be used for a longer time. See section 3-6.
( 3 ) In certain applications it is desirable to supply a process with a constant
demand.

Operation:
Press until ( Hand Control ) appears on the display. Means
Press for 3 seconds then the upper display will begin to flash and the lower MV1=38.4 %
display will show . The controller now enters the manual control mode. for OUT1 ( or Heating )
Pressing the lower display will show and alternately where
indicates output 1 ( or heating ) control variable value MV1 and Means
indicates output 2 ( or cooling ) control variable value MV2. Now you can use MV2=7.63 %
up-down key to adjust the percentage values for H or C. for OUT2 ( or Cooling )

The controller performs open loop control as long as it stays in manual control Exception
mode. The H value is exported to output 1 ( OUT1 ) and C value is exported to If OUT1 is configured as ON-OFF control
output 2 provided that OUT2 is performing cooling function ( ie. OUT2 selects ( ie. PB1=0 if PB1 is assigned or
COOL ). PB2=0 if PB2 is assigned by event input ),
Exit Manual Control the controller will never perform
To press keys the controller will revert to its previous operating mode manual control mode.
( may be a failure mode or normal control mode ).
26 UM4300-August-2024
3 4 Failure Transfer
Failure Mode Occurs as :
The controller will enter failure mode as one of the following conditions occurs:
1. SB1E
1. SB1E occurs ( due to the input 1 sensor break or input 1 current below 1mA
2. SB2E
if 4-20 mA is selected or input 1 voltage below 0.25V if 1-5 V is selected ) if
3. ADER
PV1, P1-2 or P2-1 is selected for PVMD or PV1 is selected for SPMD.
2. SB2E occurs ( due to the input 2 sensor break or input 2 current below 1mA Failure Transfer of outout 1 and output 2
if 4-20 mA is selected or input 2 voltage below 0.25V if 1-5 V is selected ) if occurs as :
PV2, P1-2 or P2-1 is selected for PVMD or PV2 is selected for SPMD. 1. Power start ( within 2.5 seconds )
3. ADER occurs due to the A-D converter of the controller fails. 2. Failure mode is activated
3. Manual mode is activated
Output 1 Failure Transfer, if activated, will perform : 4. Calibration mode is activated
1. If output 1 is configured as proportional control ( PB1 = 0 ), and BPLS is
selected for O1FT, then output 1 will perform bumpless transfer. Thereafter Failure Transfer of alarm 1 and alarm 2
the previous averaging value of MV1 will be used for controlling output 1. occurs as :
2. If output 1 is configured as proportional control ( PB1 = 0 ), and a value of 1. Failure mode is activated
0 to 100.0 % is set for O1FT, then output 1 will perform failure transfer.
Thereafter the value of O1FT will be used for controlling output 1. Failure Transfer Setup :
3. If output 1 is configured as ON-OFF control ( PB1 = 0 ), then output 1 will be 1. O1FT
driven OFF if O1FN selects REVR and be driven ON if O1FN selects DIRT. 2. O2FT
3. A1FT
Output 2 Failure Transfer, if activated, will perform : 4. A2FT
1. If OUT2 selects COOL, and BPLS is selected for O1FT, then output 2 will
perform bumpless transfer. Thereafter the previous averaging value of MV2
will be used for controlling output 2. Exception: If Loop Break (LB) alarm or
2. If OUT2 selects COOL, and a value of 0 to 100.0 % is set for O2FT, then sensor Break (SENB) alarm is
output 2 will perform failure transfer. Thereafter the value of O1FT will be configured forA1FN or A2FN, the alarm1/ 2
used for controlling output 2. will be switched to ON state independent
Alarm 1 Failure Transfer is activated as the controller enters failure mode. of the setting of A1FT/ A2FT. If Dwell Timer
Thereafter the alarm 1 will transfer to the ON or OFF state preset by A1FT. (TIMR) is configured for A1FN/A2FN,
the alarm 1/ alarm2
Alarm 2 Failure Transfer is activated as the controller enters failure mode. will not perform failure transfer.
Thereafter the alarm 2 will transfer to the ON or OFF state preset by A2FT.

3 5 Signal Conditioner DC Power Supply


Three types of isolated DC power supply are available to supply an external transmitter
or sensor. These are 20V rated at 25mA, 12V rated at 40 mA and 5V rated at 80 mA.
The DC voltage is delivered to the output 2 terminals.

Two-line 1 11
Set
Transmitter 2 12
OUT2 = DC Power Supply
3 13
4 14
+ +
5 15
6 16
7 17
8 18
+ 4 - 20mA
9 19
10 20
Figure 3.26
DC Power Supply Applications

Caution:
Don't use the DC power supply beyond its rating current to avoid damage.
Purchase a correct voltage to suit your external devices. See ordering code in section 1-2. 27
UM4300-August-2024
3 6 Bumpless Transfer
The bumpless transfer function is available for output 1 and output 2 ( provided Bumpless Transfer Setup :
that OUT2 is configured as COOL ). 1. O1FT = BPLS
2. O2FT = BPLS
Bumpless Transfer is enabled by selecting BPLS for O1FT and/or O2FT and
activated as one of the following cases occurs :
Bumpless Transfer Occurs as :
1. Power starts ( within 2.5 seconds ).
1. Power Starts ( within 2.5 seconds )
2. The controller enters the failure mode. See section 3-4 for failure mode
2. Failure mode is activated
descriptions.
3. Manual mode is activated
3. The controller enters the manual mode. See section 3-3 for manual mode
4. Calibration mode is activated
descriptions.
4. The controller enters the calibration mode. See Chapter 4 for calibration
mode descriptions.
As the bumpless transfer is activated, the controller will transfer to open-loop
control and uses the previous averaging value of MV1 and MV2 to continue
control.

Without Bumpless Transfer

PV Power interrupted
Sensor break
Set point
Figure 3.3 Benefits of Bumpless
Large Transfer
deviation
Time
Since the hardware and software need time to be initialized, the control is
abnormal as the power is recovered and results in a large disturbance to
the process. During the sensor breaks, the process loses power.

With Bumpless Transfer

PV Power interrupted
Sensor break
Set point
Load varies
Small
deviation

Time

After bumpless transfer configured, the correct control variable is applied Warning :After system fails,
immediately as the power is recovered, the disturbance is small. During the never depend on bumpless
sensor breaks, the controller continues to control by using its previous value. If
transfer for a long time,
the load doesn't change, the process will remain stable. Thereafter, once the
load changes, the process may run away. Therefore, you should not rely on a
otherwise it might cause a
bumpless transfer for a longer time. For fail safe reason, an additional alarm problem to the system to run
should be used to announce the operator when the system fails. For example, away.
a Sensor Break Alarm, if configured, will switch to failure state and announces
the operator to use manual control or take a proper security action when the
system enters failure mode.
28 UM4300-August-2024
3 7 Self Tuning
The Self-tuning which is designed by using an innovative algorithm provides Self-tune Menu
an alternative option for tuning the controller. It is activated as soon as SELF
is selected with YES. When Self-tuning is working, the controller will change its
working PID values and compares the process behavior with previous cycle. Selects
If the new PID values achieve a better control, then changing the next PID
values in the same direction, otherwise, changing the next PID values in Disable Self-tuning
reverse direction. When an optimal condition is obtained, the optimal PID or
values will be stored in PB1, TI1, TD1 or PB2, TI2, TD2 which is determined by
Event Input conditions. When Self-tuning is completed, the value of SELF will Enable Self-tuning
be changed from YES to NONE to disable self-tuning function.

When the Self-tuning is enabled, the control variables are tuned slowly so Default
that the disturbance to the process is less than auto-tuning. Usually, the Self- SELF=NONE
tuning will perform successfully with no need to apply additional auto-

Exceptions: The Self-tuning will be disabled as soon as one of the following


conditions occurs:
1. SELF is selected with NONE.
2. The controller is used for on-off control, that is PB=0.
3. The controller is used for manual reset, that is TI=0.
4. The controller is under loop break condition.
5. The controller is under failure mode (e.g. sensor break).
6. The controller is under manual control mode.
7. The controller is under sleep mode.
8. The controller is being calibrated.

If the self-tuning is enabled, the auto-tuning can still be used any time. The
self-tuning will use the auto-tuning results for its initial values.

Benefits of Self-tuning: Benefits of Self-tune:


1. Unlike auto-tuning, Self-tuning will produce less disturbance to the 1. Less disturbance to the process.
2. process. 2. Perform PID control during tuning
Unlike auto-tuning, Self-tuning doesn't change control mode during tuning period.
3. period. It always performs PID control. 3. Available for ramping set point
Changing set point during Self-tuning is allowable. Hence, Self-tuning can control and remote set point
be used for ramping set point control as well as remote set point control control.
where the set point is changed from time to time.

Operation:
The parameter SELF is contained in setup menu. Refer to Section 1-5 to
obtain SELF for initiating a self-tuning.

29
UM4300-August-2024
3 8 Auto Tuning
The auto-tuning process is performed at set point.
The process will oscillate around the set point during tuning process.
Set a set point to a lower value if overshooting beyond the normal
process value is likely to cause damage.
The auto-tuning is applied in cases of :
* Initial setup for a new process
* The set point is changed substantially from the previous auto-tuning
value
* The control result is unsatisfactory
Operation : Applicable Conditions :
1. The system has been installed normally. PB1=0, TI1=0 if PB1,TI1,TD1
2. Use the default values for PID before tuning. assigned
The default values are : PB1=PB2=18.0 F
TI1=TI2=100 sec, TD1=TD2=25.0 sec, Of course, you can use other PB2=0, TI2=0, if PB2, TI2, TD2
reasonable values for PID before tuning according to your previous assigned
experiences. But don't use a zero value for PB1 and TI1 or PB2 and
TI2, otherwise, the auto-tuning program will be disabled.
3. Set the set point to a normal operating value or a lower value if
overshooting beyond the normal process value is likely to cause
damage.
4. Press until appears on the display.

5. Press for at least 3 seconds. The upper display will begin to flash
and the auto-tuning procedure is beginning.

NOTE :
Any of the ramping function, remote set point or pump function, if used,
will be disabled once auto-tuning is proceeding.
Procedures:
The auto-tuning can be applied either as the process is warming up
( Cold Start ) or as the process has been in steady state ( Warm Start ).
See Figure 3.4.

If the auto-tuning begins apart from the set point ( Cold Start ), the Pre-tune Function Advantage:
unit enters Warm-up cycle. As the process reaches the set point Consistent tuning results can be
value, the unit enters waiting cycle. The waiting cycle elapses a obtained
double integral time ( TI1 or TI2, dependent on the selection, ) then it
enters a learning cycle. The double integral time is introduced to
allow the process to reach a stable state. Before learning cycle, the
unit performs pre-tune function with a PID control. While in learning
cycle the unit performs post-tune function with an ON-OFF control.
Learning cycle is used to test the characteristics of the process. The
data are measured and used to determine the optimal PID values.
At the end of the two successive ON-OFF cycles the PID values are
obtained and automatically stored in the nonvolatile memory.
After the auto-tuning procedures are completed, the process display
will cease to flash and the unit revert to PID control by using its new
PID values.
During pre-tune stage the PID values will be modified if any unstable
phenomenon which is caused by incorrect PID values is detected.
Without pre-tune stage, like other conventional controller, the tuning
result will be strongly related to the time when the auto-tuning is
applied. Hence different values will be obtained every time as auto-
tuning is completed without pre-tune. It is particularly true when the
auto-tuning are applied by using cold start and warm start.
30 UM4300-August-2024
Auto-tuning Auto-tuning
Begins Complete

Warm-up Waiting
PV
Cycle Cycle Learning Cycle New PID Cycle
=2 Integral
Time
Set Point Figure 3.4
Auto-tuning Procedure
Pre-tune Stage Post-tune Stage

PID Control ON-OFF Control PID Control

Time
Cold Start

Auto-tuning Auto-tuning
Begins Complete
Pre-tune Stage
Waiting
PV
Cycle Learning Cycle New PID Cycle
=2 Integral
Time
Set Point
Pre-tune
Stage Post-tune Stage

PID Control ON-OFF Control PID Control

Time
Warm Start

If the auto-tuning begins near the set point ( warm start ), the unit passes the
warm-up cycle and enters the waiting cycle. Afterward the procedures are
same as that described for cold start.

Auto-Tuning Error
If auto-tuning fails an ATER message will appear on the upper display in cases of : Auto-Tuning Error
If PB exceeds 9000 ( 9000 PU, 900.0 LF or 500.0 LC ).
or if TI exceeds 1000 seconds.
or if set point is changed during auto-tuning procedure.
or if event input state is changed so that set point value is changed.
Solutions to
1. Try auto-tuning once again.
2. Don't change set point value during auto-tuning procedure.
3. Don't change event input state during auto-tuning procedure.
4. Use manual tuning instead of auto-tuning. ( See section 3-20 ).
5. Touch any key to reset message.
31
UM4300-August-2024
3 9 Manual Tuning
In certain applications ( very few ) using both self-tuning and auto-tuning to
tune a process may be inadequate for the control requirement, then you
can try manual tuning.
Connect the controller to the process and perform the procedures
according to the flow chart shown in the following diagram. Figure 3.5
Manual Tuning
Procedure
Use initial PID values
to control the process

Wait and Examine Wait and Examine


the Process the Process

Is Is
No steady state No steady state
reached ? reached ?

Yes Yes
Does No Does
the process No the process
oscillate ? oscillate ?

Yes Yes
1 Flag 0 Flag PB1 PBu
Oscillating period Tu

2PB1 PB1 0.5PB1 PB1


Load new PID values
1.7 PBu PB1
Tu TI1
0.3 Tu TD1
Wait and Examine
the Process

Is
END
No steady state
reached ?

Yes
Does
the process No NOTE :
oscillate ? The final PID values can't be zero.
If PBu=0 then set PB1=1.
Yes If Tu < 1 sec, then set TI1=1 sec.

No No
Flag=0 ? Flag=1 ?

Yes Yes
1.6PB1 PB1 0.8PB1 PB1

The above procedure may take a long time before reaching a new steady state
since the P band was changed. This is particularly true for a slow process. So
the above manual tuning procedures will take from minutes to hours to obtain
optimal PID values.
32 UM4300-August-2024
The PBu is called the Ultimate P Band and the period of oscillation Tu is
called the Ultimate Period in the flow chart of Figure 3.5 . When this occurs,
the process is called in a critical steady state. Figure 3.6 shows a critical
steady state occasion.

If PB=PBu
PV the process sustains to oscillate
Figure 3.6 Critical Steady
Set point State

Tu

Time

If the control performance by using above tuning is still unsatisfactory, the


following rules can be applied for further adjustment of PID values :

ADJUSTMENT SEQUENCE SYMPTOM SOLUTION


Slow Response Decrease PB1 or PB2
(1) Proportional Band ( P )
PB1 and/or PB2 High overshoot or
Increase PB1 or PB2
Oscillations
Slow Response Decrease TI1 or TI2
(2) Integral Time ( I )
TI1 and/or TI2 Instability or
Increase TI1 or TI2 Table 3.2 PID Adjustment Guide
Oscillations

Slow Response or
(3) Derivative Time ( D ) Decrease TD1 or TD2
Oscillations
TD1 and/or TD2
High Overshoot Increase TD1 or TD2

CPB Programming : The cooling proportional band is measured by % of PB with range 1~255. Initially set 100%
for CPB and examine the cooling effect. If cooling action should be enhanced then decrease CPB, if cooling
action is too strong then increase CPB. The value of CPB is related to PB and its value remains unchanged
throughout the self-tuning and auto-tuning procedures.

Adjustment of CPB is related to the cooling media used. For air is used as cooling media, adjust CPB at 100(%).
For oil is used as cooling media, adjust CPB at 125(%). For water is used as cooling media, adjust CPB at
250(%).

DB Programming: Adjustment of DB is dependent on the system requirements. If more positive value of DB


( greater dead band ) is used, an unwanted cooling action can be avoided but an excessive overshoot over
the set point will occur. If more negative value of DB ( greater overlap ) is used, an excessive overshoot over the
set point can be minimized but an unwanted cooling action will occur. It is adjustable in the range -36.0% to
36.0 % of Pb1
( or PB2 if PB2 is selected ). A negative DB value shows an overlap area over which both outputs are active. A
positive DB value shows a dead band area over which neither output is active.

UM4300-August-2024
33
Figure 3.25 shows the effects of PID adjustment on process response.

P action

PV PB too narrow

Perfect

Set point
Figure 3.7 Effects of PID
Adjustment

PB too wide

Time

I action
TI too high
PV

Set point

Perfect
TI too low

Time

D action

TD too low
PV
Perfect Figure 3.8 (Continued )
Effects of PID Adjustment
Set point

TD too high

Time
34
UM4300-August-2024
3 10 Pump Control
Pump Control function is one of the unique features of FDC-4300. Using this PUMP: A Cost Effective
function the pressure in a process can be controlled excellently. The yet Perfect Solution
pressure in a process is commonly generated by a pump driven by a
variable speed motor. The complete system has the following
characteristics which affects the control behavior: 1, The system is very
noisy. 2, The pressure is changed very rapidly. 3, The pump characteristics is
ultra nonlinear with respect to its speed. 4, The pump can't generate any
more pressure as its speed is lower than half of its rating speed. 5, An
ordinary pump may slowly lose the pressure even if the valves are
completely closed.
Obviously a conventional controller can't fulfill the conditions mentioned
above. Only the superior noise rejection capability in addition to the fast
sampling rate owned by FDC-4300 can realize such application. To
achieve this, set the following parameters in the setup menu:
FUNC=FULL Key menu
EIFN=NONE SPMD
PVMD=PV1 SP2F
FILT=0.5 REFC
SELF=NONE
SP2
SPMD=PUMP
SP2F=DEVI

and program the following parameters in the user menu:

REFC= Reference constant


SP2= A negative value is added to SP1 to obtain the set point for idle
state

Since the pump can't produce any more pressure at lower speed, the Pump Control Features:
pump may not stop running even if the pressure has reached the set point. 1. Minimum oscillation of pressure
If this happens, the pump will be over worn out and waste additional 2. Rapidly stabilized
power. To avoid this, the FDC-4300 provides a Reference Constant REFC in 3. Guaranteed pump stop
the user menu. If PUMP is selected for SPMD, the controller will periodically 4. Programmable pump stopping
test the process by using this reference constant after the pressure has interval
reached its set point. If the test shows that the pressure is still consumed by
the process, the controller will continue to supply appropriate power to the
pump. If the test shows that the pressure is not consumed by the process,
the controller will gradually decrease the power to the pump until the
pump stops running. As this happens, the controller enters idle state. The
idle state will use a lower set point which is obtained by adding SP2 to SP1
until the pressure falls below this set point. The idle state is provided for the
purpose of preventing the pump from been restarted too frequently. The
value of SP2 should be negative to ensure a correct function.

The pump functions are summarized as follows:


1. If the process is demanding material ( ie. lose pressure ), the controller
will precisely control the pressure at set point.
2. If the process no longer consumes material, the controller will shut off the
pump as long as possible.
3. The controller will restart the pump to control the pressure at set point as
soon as the material is demanded again while the pressure falls below a
predetermined value ( ie. SP1+SP2 ).

35

UM4300-August-2024
Programming Guide:
1. Perform auto-tuning to the system under such condition that the material
( ie. pressure ) is exhausted at typical rate. A typical value for PB1 is about
2
10 Kg/cm , TI1 is about 1 second, TD1 is about 0.2 second.
2. If the process oscillates around set point after auto-tuning, then increase
PB1 until the process can be stabilized at set point. The typical value of PB1
is about half to two times of the range of pressure sensor.
3. Increase FILT ( Filter ) can further reduce oscillation amplitude. But a value
of FILT higher than 5 ( seconds ) is not recommended. A typical value for FILT
is 0.5 or 1 .
4. Close the valves and examine that if the controller can shut off the pump
each time. The value of REFC is adjusted as small as possible so that the
controller can shut off the pump each time when all the valves are closed. A
typical value for REFC is between 3 and 5.
5. An ordinary pump may slowly lose the pressure even if the valves are
completely closed. Adjust SP2 according to the rule that a more negative
value of SP2 will allow the pump to be shut off for a longer time as the valves
2
are closed. A typical value for SP2 is about -0.50 Kg/cm .

3 11 Sleep Mode
To Enter Sleep Mode: Sleep Mode Features:
FUNC selects FULL to provide full function. Shut off display
SLEP selects YES to enable the sleep mode. Shut off outputs
Press for 3 seconds, the unit will enter its sleep mode. Green Power
During sleep mode: Replace Power Switch
(1) Shut off all display except a decimal point which is lit periodically.
(2) Shut off all outputs and alarms. Setup Menu
To Exit Sleep Mode: FUNC=FULL
(1) Press to leave the sleep mode. SLEP=YES
(2) Disconnect the power.
Default: SLEP=NONE,
Sleep Function can be used to replace a power switch to reduce the system cost.
Sleep mode is disabled.
Note: If the Sleep mode is not required by your system, the SLEP should select
NONE to disable sleep mode against undesirable occurrence.

3 12 Remote Lockout
The parameters can be locked to prevent from being changed by using Remote Lockout:
either Hardware Lockout (see Section 1-3) or Remote Lockout or both. If 1.Connect external switch to terminal
you need the parameters to be locked by using an external switch 16 and 17 .
(remote lockout function), then connect a switch to terminals 16 and 17 2. Set LOCK for EIFN
and choose LOCK for EIFN. 3. Lock all parameters

If remote lockout is configured, all parameters will be locked as the


external switch is closed. When the switch is left open, the lockout
condition is determined by internal DIP switch (hardware lockout, see
Section 1-3).
Hardware Lockout: Can be used only during initial setup.
Remote Lockout: Can be used any time.
36
UM4300-August-2024
3 13 Heater Break Alarm
A current transformer ( parts No. CT94-1 ) should be installed to detect the Heater Break Alarm 1
heater current if a heater break alarm is required. The CT signal is sent to Setup : IN2 = CT
input 2, and the PV2 will indicate the heater current in 0.1 Amp. resolution. A1FN = PV2.L
The range of current transformer is 0 to 50.0 Amp. A1MD = NORM
A1HY = 0.1
Adjust : A1SP
Trigger levels : A1SP A1/2 A1HY

Heater Break Alarm 2


Example: Setup : IN2 = CT
A furnace uses two 2KW heaters connected in parallel to warm up the process. A2FN = PV2.L
The line voltage is 220V and the rating current for each heater is 9.09A. If we A2MD = NORM
want to detect any one heater break, set A1SP=13.0A, A1HY=0.1 A2HY = 0.1
A1FN=PV2.L, A1MD=NORM, then Adjust : A2SP
Trigger levels : A2SP A1/2 A2HY
Limitations :
1. Linear output can't use heater break
alarm.
No heater breaks 1 heater breaks 2 heaters breaks 2. CYC1 should use 1 second or
longer to detect heater current reliably.
Alarm ! Alarm !

20 30 20 30 20 30
Figure 3.9
10 40 10 40 10 40
Heater Break Alarm
A A A
0 50 0 50 0 50

3 14 Reload Default Values


The default values listed in Table 1.4 are stored in the memory as the
product leaves the factory. In certain occasions it is desirable to retain
these values after the parameter values have been changed. Here is a
convenient tool to reload the default values.
Operation
Press several times until . Then press . The upper FILE 0
display will show .Use up-down key to select 0 to 1. If LC unit is LC Default File
required, select 0 for FILE and if LF unit is required, select 1 for FILE. Then
Press for at least 3 seconds. The display will flash a moment and the FILE 1
default values are reloaded. LF Default File

CAUTION
The procedures mentioned above will change the previous setup data.
Before doing so, make sure that if it is really required.

37
UM4300-August-2024
Chapter 4 Calibration
Do not proceed through this section unless there is a definite need to
re-calibrate the controller. Otherwise, all previous calibration data will be
lost. Do not attempt recalibration unless you have appropriate calibration
equipment. If calibration data is lost, you will need to return the controller
to your supplier who may charge you a service fee to re-calibrate the
controller.

Entering calibration mode will break the control loop. Make sure that if
the system is allowable to apply calibration mode.

Equipments needed before calibration:


(1) A high accuracy calibrator ( Fluke 5520A Calibrator recommended )
with following functions:
0 - 100 mV millivolt source with +/-0.005 % accuracy
0 - 10 V voltage source with +/-0.005 % accuracy
0 - 20 mA current source with +/-0.005 % accuracy
0 - 300 ohm resistant source with +/-0.005 % accuracy
(2) A test chamber providing 25 C ambient
(Optional) High CJC calibration requires
a test chamber providing +50C ambient

The calibration procedures described in the following section are a step by step
manual procedures.

ATTENTION: A unit requires a 30 minute warm up BEFORE Calibration can be


Initiated.

UM4300-August-2024
38
Manual Calibration Procedures

* Perform step 1 to enter calibration mode.


Step 1. Set the lockout DIP switch to the unlocked condition ( both switches
3 and 4 are off ).
Press both scroll and down keys and release them quickly. The
operation mode menu will appear on the display. Repeat the operation
several times until appear on the display.
Press scroll key for at least 3 seconds , the display will show
and the unit enters calibration mode . The output 1 and output 2 use
their failure transfer values to control.

* Perform step 2 to calibrate Zero of A to D converter and step 3 to


calibrate gain of A to D converter. The DIP switch is set for T/C input.

Step 2. Short terminals19 and 20 , then press scroll key for at least 3 seconds. DIP Switch Position
ON
The display will blink a moment and a new value is obtained.
T/C input
Otherwise, if the display didn't blink or if the obtained value is equal to 1 2 3 4
-360 or 360, then the calibration fails.
Step 3. Press scroll key until the display shows . Send a 60mV signal
to terminals 19 and 20 in correct polarity . Press scroll key for at
least 3 seconds . The display will blink a moment and a new value is
obtained . Otherwise , if the display didn't blink or if the obtained value
is equal to -199.9 or 199.9, then the calibration fails.

* Perform step 4 to calibrate voltage function ( if required ) for input 1.

Step 4. Change the DIP switch for the Voltage input. Press scroll key until DIP Switch Position
ON
the display shows . Send a 10 V signal to terminals 19 and
0 10V input
20 in correct polarity. Press scroll key for at least 3 seconds . The 1 2 3 4

display will blink a moment and a new value is obtained . Otherwise,


if the display didn't blink or if the obtained value is equal to -199.9 or
199.9 , then the calibration fails.

* Perform both steps 5 and 6 to calibrate RTD function ( if required )


for input 1.
Step 5. Change the DIP switch for the RTD input . Press scroll key until the DIP Switch Position
ON
display shows . Send a 100 ohms signal to terminals 18, 19
RTD input
and 20 according to the connection shown below: 1 2 3 4

18
100 ohms
19 FDC-4300 Figure 6.1
20 RTD Calibration

Press scroll key for at least 3 seconds . The display will blink a
moment, otherwise the calibration fails.
39
UM4300-August-2024
Step 6. Press scroll key and the display will show . Change the
ohm's value to 300 ohms .Press scroll key for at least 3 seconds.
The display will blink a moment and two values are obtained for SR1
and REF1 (last step). Otherwise, if the display didn't blink or if any
value obtained for SR1 and REF1 is equal to -199.9 or 199.9 ,
then the calibration fails.

* Perform step 7 to calibrate mA function ( if required ) for input 1.


Step 7. Change the DIP switch for mA input. Press scroll key until the display DIP Switch Position
shows .Send a 20 mA signal to terminals 19 and 20 in ON

correct polarity. Press scroll key for at least 3 seconds . The display mA input
1 2 3 4
will blink a moment and a new value is obtained . Otherwise , if the
display didn't blink or if the obtained value is equal to -199.9 or 199.9,
then the calibration fails.

* Perform step 8 to calibrate voltage as well as CT function ( if required )


for input 2.
Step 8. Press scroll key until the display shows . Send a 10 V signal to
terminals 15 and 16 in correct polarity. Press scroll key for at least 3
seconds . The display will blink a moment and a new value is obtained .
Otherwise , if the display didn't blink or if the obtained value is equal
to -199.9 or 199.9 , then the calibration fails.

* Perform step 9 to calibrate mA function ( if required ) for input 2.


Step 9. Press scroll key until the display shows . Send a 20 mA signal
to terminal 15 and 16 in correct polarity. Press scroll key for at least
3 seconds . The display will blink a moment and a new value is obtained .
Otherwise , if the display didn't blink or if the obtained value is equal to
-199.9 or 199.9, then the calibration fails.

* Perform step 10 to calibrate offset of cold junction compensation, if


required. The DIP switch is set for T/C input.
Step 10. Setup the equipments according to the following diagram for DIP Switch Position
calibrating the cold junction compensation. Note that a K type ON

TC input
thermocouple must be used. 1 2 3 4

5520A K+
19
Calibrator FDC-4300
K-TC 20 Figure 6.2
K
Cold Junction
Stay at least 20 minutes in still- Calibration Setup
air room
room temperature 25 +/- 3 C

The 5520A calibrator is configured as K type thermocouple output


with
internal compensation. Send a 0.00 C signal to the unit under

40 UM4300-August-2024
The unit under calibration is powered in a still-air room with
temperature 25 +/-3C. Stay at least 20 minutes for warming up. The
DIP Switch is located at TC input .
Perform step 1 stated above, then press scroll key until the display
shows . Apply up/down key until value 0.00 is obtained .
Press scroll key at least 3 seconds. The display will blink a moment
and a new value is obtained . Otherwise , if the display didn't blink
or if the obtained value is equal to -5.00 or 40.00, then the calibration
fails.

* Perform step 11 to calibrate gain of cold junction compensation if


required, otherwise , perform step 11N to use a nominal value for the
cold junction gain if a test chamber for calibration is not available.

Step 11.Setup the equipments same as step 10. The unit under calibration is
powered in a still-air room with temperature 50A3 BC. Stay at least 20
minutes for warming up . The calibrator source is set at 0.00 C with
internal compensation mode.

Perform step 1 stated above , then press scroll key until the display
shows . Apply up/down key until value 0.0 is obtained. Press
scroll key for at least 3 seconds . The display will blink a moment and
a new value is obtained. Otherwise , if the display didn't blink or if
the obtained value is equal to -199.9 or 199.9, then the calibration
fails.
This setup is performed in a high temperature chamber, hence it is
recommended to use a computer to perform the procedures.

Perform step 1 stated above , then press scroll key until the display
shows . Apply up/down key until value 0.1 is obtained.
Press scroll key for at least 3 seconds. The display will blink a moment
and the new value 0.0 is obtained. Otherwise , the calibration fails.

It is not recommended to use this step 11N, since the cold


junction gain is not able to achieve rated accuracy by this step.

* Final step
Set the DIP switch to your desired position ( refer to section 1-3 ).

41
UM4300-August-2024
Chapter 5 Error Codes & Troubleshooting
This procedure requires access to the circuitry of a live power unit. Dangerous accidental contact with line
voltage is possible. Only qualified personnel are allowable to perform these procedures. Potentially lethal
voltages are present.

Troubleshooting Procedures :
(1) If an error message is displayed, refer to Table 5.1 to see what cause it is and apply a corrective action to the
failure unit.
(2) Check each point listed below. Experience has proven that many control problems are caused by a defective
instrument.
Open or shorted heater circuit
* Line wires are improperly connected *
Open coil in external contactor
* No voltage between line terminals *
Burned out line fuses
* Incorrect voltage between line terminals *
Burned out relay inside control
* Connections to terminals are open, missing or loose *
Defective solid-state relays
* Thermocouple is open at tip *
Defective line switches
* Thermocouple lead is broken *
Burned out contactor
* Shorted thermocouple leads *
* Short across terminals *
Defective circuit breakers

(3) If the points listed on the above chart have been checked and the controller does not function properly, it is
suggested that the instrument be returned to the factory for inspection.
Do not attempt to make repairs without qualified engineer and proper technical information . It may create
costly damage. Also , it is advisable to use adequate packing materials to prevent damage in transportation.

42 UM4300-August-2024
Table 5.1 Error Codes and Corrective Actions
Error Display
Symbol Error Description Corrective Action
Code
Illegal setup values been used: PV1 is used for both PVMD Check and correct setup values of PVMD and SPMD. PV
1 and SPMD. It is meaningless for control. and SV can't use the same value for normal control
Illegal setup values been used: PV2 is used for both PVMD
2 Same as error code 1
and SPMD. It is meaningless for control
Illegal setup values been used: P1-2 or P2-1 is used for Check and correct setup values of PVMD and SPMD.
PVMD while PV1 or PV2 is used for SPMD. Dependent Difference of PV1 and PV2 can't be used for PV while PV1
3 values used for PV and SV will create incorrect result or PV2 is used for SV
of control

Illegal setup values been used: Before COOL is used for Check and correct setup values of OUT2, PB1, PB2, TI1,
OUT2, DIRT ( cooling action ) has already been used for TI2 and OUT1. IF OUT2 is required for cooling control, the
4 OUT1, or PID mode is not used for OUT1 ( that is PB1 or control should use PID mode ( PB = 0, TI = 0 ) and OUT1
PB2 = 0, and TI1 or TI2 = 0 ) should use reverse mode (heating action), otherwise, don't
use OUT2 for cooling control

Illegal setup values been used: unequal IN1U and IN2U or Check and correct setup values of IN1U, IN2U, DP1, DP2,
unequal DP1 and DP2 while P1-2 or P2-1 is used for PVMD PVMD, SPMD, A1FN or A2FN. Same unit and decimal point
5 or, PV1 or PV2 is used for SPMD or, P1.2.H, P1.2.L, D1.2.H should be used if both PV1 and PV2 are used for PV, SV,
or D1.2.L are used for A1FN or A2FN. alarm 1 or alarm 2.

Illegal setup values been used: OUT2 select =AL2 but Check and correct setup values of OUT2 and A2FN. OUT2
6 will not perform alarm function if A2FN select NONE.
A2FN select NONE
Illegal setup values been used: Dwell timer (TIMR) is Check and correct setup values of A1FN and A2FN. Dwell
7 selected for both A1FN and A2FN. timer can only be properly used for single alarm output.
Correct the communication software to meet the protocol
10 Communication error: bad function code requirements.
11 Communication error: register address out of range Don't issue an over-range register address to the slave.

12 Communication error: access a non-existent parameter Don't issue a non-existent parameter to the slave.

14 Communication error: attempt to write a read-only data Don't write a read-only data or a protected data to the slave.
Communication error: write a value which is out of range to
15 a register Don't write an over-range data to the slave register.

1.The PID values obtained after auto-tuning procedure are


out of range. Retry auto-tuning.
2.Don't change set point value during auto-tuning
Fail to perform auto-tuning function procedure.
26
3. Don't change Event input state during auto-tuning
procedure.
4.Use manual tuning instead of auto-tuning.

29 EEPROM can't be written correctly Return to factory for repair.

Input 2 ( IN2 ) sensor break, or input 2 current below 1 mA


38 if 4-20 mA is selected, or input 2 voltage below 0.25V if Replace input 2 sensor.
1 - 5V is selected

Input 1 ( IN1 ) sensor break, or input 1 current below 1 mA


39 if 4-20 mA is selected, or input 1 voltage below 0.25V if Replace input 1 sensor.
1 - 5V is selected

40 A to D converter or related component(s) malfunction Return to factory for repair.

UM4300-August-2024 43
Table 5.2 Common Failure Causes and Corrective Actions

Symptom Probable Causes Corrective Actions


- Clean contact area on PCB
1) Keypad no function -Bad connection between PCB & keypads - Replace keypads
- No power to instrument - Check power line connections
2) LED's will not light - Power supply defective - Replace power supply board
3) Some segments of the display or - LED display or LED lamp defective - Replace LED display or LED lamp
LED lamps not lit or lit erroneously. - Related LED driver defective - Replace the related transistor or IC chip

- Analog portion or A-D converter defective - Replace related components or board


4) Display Unstable - Thermocouple, RTD or sensor defective - Check thermocouple, RTD or sensor
- Intermittent connection of sensor wiring - Check sensor wiring connections

- Wrong sensor or thermocouple type, wrong - Check sensor or thermocouple type and if
5) Considerable error in temperature input mode selected. proper input mode was selected
indication - Analog portion of A-D converter defective - Replace related components or board

6) Display goes in reverse direction


( counts down scale as process warms ) - Reversed input wiring of sensor - Check and correct
- No heater power ( output ), incorrect output - Check output wiring and output device
device used - Replace output device
7) No heat or output - Output device defective - Replace output fuse
- Open fuse outside of the instrument
8) Heat or output stays on but indicator - Output device shorted, or power service - Check and replace
reads normal shorted

- CPU or EEPROM ( non-volatile memory ) - Check and replace


9) Control abnormal or operation incorrect defective. Key switch defective - Read the setup procedure carefully
- Incorrect setup values

- Suppress arcing contacts in system to


- Electromagnetic interference ( EMI ), or eliminate high voltage spike sources.
10) Display blinks; entered values change Separate sensor and controller wiring from
by themselves Radio Frequency interference ( RFI )
- EEPROM defective " dirty " power lines, ground heaters
- Replace EEPROM

44 UM4300-August-2024
Chapter 6 Specifications
Power
Input 2
90 264 VAC, 47 63 Hz, 15VA, 7W maximum
11 26 VAC / VDC, 15VA, 7W maximum Resolution : 18 bits
Sampling Rate : 1.66 times / second
Input 1 Maximum Rating : -2 VDC minimum, 12 VDC maximum
Resolution : 18 bits Temperature Effect : A1.5uV/ C for all inputs except
Sampling Rate : 5 times / second mA input
Maximum Rating : -2 VDC minimum, 12 VDC maximum A3.0uV/ C for mA input
( 1 minute for mA input ) Common Mode Rejection Ratio ( CMRR ): 120dB
Temperature Effect : +/-1.5uV/ C for all inputs except Normal Mode Rejection Ratio ( NMRR ): 55dB
mA input
Sensor Break Detection :
+/-3.0uV/ C for mA input
Below 1 mA for 4-20 mA input,
Sensor Lead Resistance Effect :
below 0.25V for 1 - 5V input,
T/C: 0.2uV/ohm
unavailable for other inputs.
3-wire RTD: 2.6 C/ohm of resistance difference of two
leads Sensor Break Responding Time : 0.5 second
2-wire RTD: 2.6 C/ohm of resistance sum of two leads
Burn-out Current : 200 nA Characteristics:
Common Mode Rejection Ratio ( CMRR ): 120dB Accuracy Input
Type Range
Normal Mode Rejection Ratio ( NMRR ): 55dB @ 25 C Impedance
Sensor Break Detection :
Sensor open for TC, RTD and mV inputs, 0 50.0 A +/-2 % 302 K
CT94-1
below 1 mA for 4-20 mA input, of Reading
below 0.25V for 1 - 5 V input,
0.8V
unavailable for other inputs. mA -3mA 27mA +/-0.05 % 70.5 +
input current
Sensor Break Responding Time :
Within 4 seconds for TC, RTD and mV inputs, V -1.3V 11.5V +/-0.05 % 302 K
0.1 second for 4-20 mA and 1 - 5 V inputs.
Characteristics: Input 3 (Event Input )
Accuracy Input Logic Low : -10V minimum, 0.8V maximum.
Type Range
@ 25 C Impedance Logic High : 2V minimum, 10V maximum
-120 C 1000 C External pull-down Resistance : 400 K maximum
J +/-2 C 2.2 M
( -184 F 1832 F ) External pull-up Resistance : 1.5 M minimum
-200 C 1370 C Functions : Select second set point and/or PID,
K +/-2 C 2.2 M reset alarm 1 and/or alarm 2,
( -328 F 2498 F )
-250 C 400 C disable output 1 and/or output 2,
T +/-2 C 2.2 M remote lockout.
( -418 F 752 F )
-100 C 900 C
E +/-2 C 2.2 M Output 1 / Output 2
( -148 F 1652 F )
+/-2 C Relay Rating : 2A/240 VAC, life cycles 200,000 for
0 C 1820 C
B ( 200 C 2.2 M resistive load
( - 32 F 3308 F )
1820 C ) Pulsed Voltage : Source Voltage 5V,
0 C 1767.8 C +/-2 C current limiting resistance 66 .
R 2.2 M
( - 32 F 3214 F )
0 C 1767.8 C Linear Output Characteristics
S +/-2 C 2.2 M
( - 32 F 3214 F )
Type Zero Span Load
0 C 2300 C Tolerance Tolerance Capacity
C +/-2 C 2.2 M
( 32 F 4200 F )
0 C 1395 C 4-20 mA 3.8-4 mA 20-21 mA 500 max.
P ( 32 F 2543 F ) +/-2 C 2.2 M 0-20 mA 0 mA 20-21 mA 500 max.
PT100 -210 C 700 C 0 5V 0V 5 5.25 V 10 K min.
+/-0.4 C 1.3 K
( DIN ) ( -346 F 1292 F )
PT100 -200 C 600 C 1 5V 0.95 1 V 5 5.25 V 10 K min.
+/-0.4 C 1.3 K
( JIS ) ( -328 F 1112 F ) 0 10 V 0V 10 10.5 V 10 K min.
mV -8mV 70mV +/-0.05 % 2.2 M
mA -3mA 27mA +/-0.05 % 70.5
UM4300-July-2024
45
V -1.3V 11.5V +/-0.05 % 302 K
Linear Output Resolution : 15 bits
Resolution : 15 bits Accuracy : +/-0.05 % of span +/-0.0025 %/ C
Output Regulation : 0.01 % for full load change Load Resistance :
Output Settling Time : 0.1 sec. ( stable to 99.9 % ) 0 - 500 ohms ( for current output )
Isolation Breakdown Voltage : 1000 VAC 10 K ohms minimum ( for voltage output )
Temperature Effect : +/-0.0025 % of SPAN / C Output Regulation : 0.01 % for full load change
Output Settling Time : 0.1 sec. (stable to 99.9 % )
Triac ( SSR ) Output Isolation Breakdown Voltage : 1000 VAC min.
Rating : 1A / 240 VAC Integral Linearity Error : +/-0.005 % of span
Inrush Current : 20A for 1 cycle Temperature Effect : +/-0.0025 % of span/ C
Min. Load Current : 50 mA rms Saturation Low : 0 mA ( or 0V )
Max. Off-state Leakage : 3 mA rms Saturation High : 22.2 mA ( or 5.55V, 11.1V min. )
Max. On-state Voltage : 1.5 V rms Linear Output Range :0-22.2mA(0-20mA or 4-20mA)
Insulation Resistance : 1000 Mohms min. at 500 VDC 0-5.55V ( 0 - 5V, 1 - 5V )
Dielectric Strength : 2500 VAC for 1 minute 0 - 11.1 V ( 0 - 10V )

DC Voltage Supply Characteristics ( Installed at Output 2 ) User Interface


Dual 4-digit LED Displays : Upper 0.55" ( 14 mm ),
Type Tolerance Max. Output Ripple Isolation
Lower 0.4 " ( 10 mm )
Current Voltage Barrier
Keypad : 3 keys
20 V +/-0.5 V 25 mA 0.2 Vp-p 500 VAC Programming Port :For automatic setup, calibration
12 V +/-0.3 V 40 mA 0.1 Vp-p 500 VAC and testing
0.05 Vp-p 500 VAC Communication Port : Connection to PC for
5V +/-0.15 V 80 mA
supervisory control

Alarm 1/ Alarm 2 Control Mode


Alarm 1 Relay : Form C Rating Output 1 : Reverse ( heating ) or direct ( cooling )
2A/240VAC, life cycles 200,000 for action
resistive load. Output 2 : PID cooling control, cooling P band 1~
Alarm 2 Relay : Form A, Max. rating 2A/240VAC, 255% of PB
life cycles 200,000 for resistive load. ON-OFF : 0.1 - 100.0 ( F ) hysteresis control
Alarm Functions : Dwell timer, ( P band = 0 )
Deviation High / Low Alarm, P or PD : 0 - 100.0 % offset adjustment
Deviation Band High / Low Alarm, PID : Fuzzy logic modified
PV1 High / Low Alarm, Proportional band 0.1 ~ 900.0 F.
PV2 High / Low Alarm, Integral time 0 - 1000 seconds
PV1 or PV2 High / Low Alarm, Derivative time 0 - 360.0 seconds
PV1-PV2 High / Low Alarm, Cycle Time : 0.1 - 100.0 seconds
Loop Break Alarm, Manual Control : Heat (MV1) and Cool (MV2)
Sensor Break Alarm. Auto-tuning : Cold start and warm start
Alarm Mode : Normal, Latching, Hold, Latching / Hold. Self-tuning : Select None and YES
Dwell Timer : 0 - 6553.5 minutes Failure Mode : Auto-transfer to manual mode while
sensor break or A-D converter damage
Data Communication Sleep Mode : Enable or Disable
Interface : RS-232 ( 1 unit ), RS-485 ( up to 247 units ) Ramping Control : 0 - 900.0 F/minute or
Protocol : Modbus Protocol RTU mode 0 - 900.0 F/hour ramp rate
Address : 1 - 247 Power Limit : 0 - 100 % output 1 and output 2
Baud Rate : 0.3 ~ 38.4 Kbits/sec Pump / Pressure Control : Sophisticated functions
Data Bits : 7 or 8 bits provided
Parity Bit : None, Even or Odd Remote Set Point : Programmable range for voltage
Stop Bit : 1 or 2 bits or current input
Communication Buffer : 50 bytes Differential Control : Control PV1-PV2 at set point

Analog Retransmission
Functions : PV1, PV2, PV1-PV2, PV2-PV1, Set Point, Digital Filter
MV1, MV2, PV-SV deviation value Function : First order
Output Signal : 4-20 mA, 0-20 mA, 0 - 1V, 0 - 5V, Time Constant : 0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60
1 - 5V, 0 - 10V seconds programmable
46
UM4300-August-2024
Environmental & Physical
Operating Temperature : -10 C to 50 C
Storage Temperature : -40 C to 60 C
Humidity : 0 to 90 % RH ( non-condensing )
Insulation Resistance : 20 Mohms min. ( at 500 VDC )
Dielectric Strength : 2000 VAC, 50/60 Hz for 1 minute
2
Vibration Resistance : 10 - 55 Hz, 10 m/s for 2 hours
2
Shock Resistance : 200 m/s ( 20 g )
Moldings : Flame retardant polycarbonate
Dimensions : 96mm(W) X 96mm(H) X 65mm(D),
53 mm depth behind panel
Weight : 255 grams

Approval Standards
Safety : UL/cUL File# E197216 QUYX-QUYX7
CE EN61010-1 (IEC1010-1)
RoHS Compliant EN61010-1

Protective Class :
IP65 for panel with additional option
IP50 for panel without additional option
IP20 for terminals and housing with protective cover.
All indoor use only.
EMC: EN61326
The color codes used on the thermocouple extension leads are shown in below

Thermocouple Cable Color Codes

Thermocouple Cable British American German French


Type Material BS ASTM DIN NFE

Copper ( Cu ) + white + blue + red + yellow


T Constantan blue red brown blue
( Cu-Ni ) * blue * blue * brown * blue

Iron ( Fe ) + yellow + white + red + yellow


J Constantan blue red blue black
( Cu- Ni ) * black * black * blue * black
Nickel-Chromium
+ brown + yellow + red + yellow
( Ni-Cr )
K blue red green purple
Nickel-Aluminum
* red * yellow * green * yellow
( Ni-Al )

+ white + black + red + yellow


R Pt-13%Rh,Pt
blue red white green
S Pt-10%Rh,Pt
* green * green * white * green

+grey +red
Pt-30%Rh Use Use
B red grey
Pt-6%Rh Copper Wire Copper Wire
* grey * grey

* Color of overall sheath


47
UM4300-August-2024
A 1 Menu Existance Conditions

Menu Existance Conditions Table

Parameter
Menu Existence Conditions
Notation

SP1 Exists unconditionally

TIME Exists if A1FN selects TIMR or A2FN selects TIMR

A1SP Exists if A1FN selects PV1H, PV1L, PV2H, PV2L, P12H, P12L, D12H or D12L

A1DV Exists if A1FN selects DEHI, DELO, DBHI, or DBLO

A2SP Exists if A2FN selects PV1H, PV1L, PV2H, PV2L, P12H, P12L, D12H or D12L

A2DV Exists if A2FN selects DEHI, DELO, DBHI, or DBLO

RAMP Exists if SPMD selects MINR or HRR

Exists if TI1 is used for control (depends on Event input and EIFN selection) but TI1= 0 and
OFST PB1=0 or if TI2 is used for control (depends on Event input and EIFN selection) but TI2= 0
and PB2=0

REFC Exists if SPMD selects PUMP

SHIF
Exists unconditionally
PB1
User
TI1
Menu Exists if PB1= 0
TD1

CPB, DB Exists if OUT2 select COOL

SP2 Exists if EIFN selects SP2 or SPP2, or if SPMD selects PUMP

PB2 Exists if EIFN selects PID2 or SPP2

TI2
Exists if EIFN selects PID2 or SPP2 provided that PB2= 0
TD2

If PID2 or SPP2 is selected for EIFN, then O1HY exists if PB1= 0 or PB2 = 0. If PID2 or SPP2
O1HY
is not selected for EIFN, then O1HY exists if PB1= 0

A1HY Exists if A1FN selects DEHI, DELO, PV1H, PV1L, PV2H, PV2L, P12H, P12L, D12H, or D12L

A2HY Exists if A2FN selects DEHI, DELO, PV1H, PV1L, PV2H, PV2L, P12H, P12L, D12H, or D12L

If PID2 or SPP2 is selected for EIFN, then PL1 exists if PB1= 0 or PB2 = 0. If PID2 or SPP2
PL1
is not selected for EIFN, then PL1 exists if PB1= 0

PL2 Exists if OUT2 selects COOL

48 UM4300-August-2024
Menu Existance Conditions Table ( continued 2/3 )
Parameter
Menu Existance Conditions
Notation

FUNC Exists unconditionally

COMM Exists if FUNC selects FULL

PROT

ADDR

BAUD
Exists if COMM selects 485 or 232
DATA

PARI

STOP

AOFN Exists if COMM selects 4-20, 0-20, 0-1V, 0-5V, 1-5V, or 0-10

AOLO
Exists if COMM selects 4-20, 0-20, 0-1V, 0-5V, 1-5V, or 0-10 and AOFN is not MV1 and MV2
AOHI

IN1

IN1U Exists unconditionally

Setup DP1
Menu
IN1L
Exists if IN1selects 4-20, 0-20, 0-1V, 0-5V, 1-5V, or 0-10
IN1H

IN2 Exists if FUNC selects FULL

IN2U

DP2
Exists if IN2 selects 4-20, 0-20, 0-1V, 0-5V, 1-5V, or 0-10
IN2L

IN2H

OUT1

O1TY

CYC1 Exists unconditionally

O1FT

OUT2

O2TY

CYC2 Exists if OUT2 selects COOL

O2FT

UM4300-August-2024 49
Menu Existance Conditions Table ( continued 3/3 )
Parameter
Menu Existance Conditions
Notation

A1FN Exists unconditionally

Exists if A1FN selects DEHI, DELO, DBHI, DBLO, PV1H, PV1L, PV2H, PV2L, P12H, P12L,
A1MD
D12H, D12L, LB or SENB

A1FT Exists if A1FN is not NONE

A2FN Exists unconditionally

Exists if A2FN selects DEHI, DELO, DBHI, DBLO, PV1H, PV1L, PV2H, PV2L, P12H, P12L,
A2MD
D12H, D12L, LB or SENB

A2FT Exists if A2FN is not NONE

EIFN

PVMD Exists if FUNC selects FULL


Setup
FILT
Menu
SELF Exists unconditionally

SLEP
Exists if FUNC selects FULL
SPMD

SP1L
Exists unconditionally
SP1H

SP2F Exists if EIFN selects SP2 or SPP2, or if SPMD selects PUMP

SEL1

SEL2

SEL3 Exists unconditionally

SEL4

SEL5

50 UM4300-August-2024
PAGE INTENTIONALLY LEFT BLANK
PAGE INTENTIONALLY LEFT BLANK
PAGE INTENTIONALLY LEFT BLANK
State of California Proposition 65 Warning

Cancer and Reproductive Harm: This warning is intended to address certain Prop 65 chemicals that
may be found in Future Design Controls products. These products can expose you to chemicals
including lead and lead compounds which are known to the State of California to cause cancer, birth
defects or other reproductive harm.

What is the state of California Proposition 65?

Proposition 65 requires businesses to provide warnings to Californians about significant exposures to chemicals
that cause cancer, birth defects or other reproductive harm. These chemicals can be in the products that
Californians purchase, in their homes or workplaces, or that are released into the environment. By requiring
that this information be provided, Proposition 65 enables Californians to make informed decisions about their
exposures to these chemicals.

For more information go to: www.P65Warnings.ca.gov

The most recent list of chemicals known to the State of California can be seen at:

https://oehha.ca.gov/media/downloads/proposition-65//p65list102618.pdf

Affected Products: This applies to all existing and future products offered by Future Design Controls.
A 2 Warranty

Future Design Controls products described in this manual are warranted to be free from functional
defects in materials and workmanship at the time the products leave Future Design Controls
Facilities and to conform at that time to the specifications set forth in the relevant Future Design
Controls manual, sheet or sheets for a period of 3 years after delivery to the first purchaser for use.
There are no expressed or implied Warranties extending beyond the Warranties herein and
above set forth.
Limitations:
Future Design Controls provides no warranty or representations of any sort regarding the fitness of
use or application of its products by the purchaser. Users are responsible for the selection,
suitability of the products for their application or use of Future Design Controls products.

Future Design Controls shall not be liable for any damages or losses, whether direct, indirect,
incidental, special, consequential or any damages, costs or expenses excepting only the cost or
expense of repair or replacement of Future Design Controls products as described below.

Future Design Controls sole responsibility under the warranty, at Future Design Controls option, is
limited to replacement or repair, free of charge or refund of purchase price within the warranty
period specified. The warranty does not apply to damage resulting from transportation, alteration,
misuse or abuse.

Future Design Controls reserves the right to make changes without notification to purchaser to
materials or processing that does not effect the compliance with any applicable specifications.

Return Material Authorization:


Contact Future Design Controls for a Return Authorization Number prior to returning any product
to our facility.
Future Design Controls
7524 West 98th Place, P.O. Box 1196
Bridgeview, IL. 60455 USA
888.751.5444 - Office
888.307.8014 - Fax
866.342.5332 - Technical Support
E-mail: [email protected]
Website: http://futuredesigncontrols.com

UM4300-August-2024 51
User's Manual
FDC4300 Process / Temperature Controller

7524 West 98th Place


Bridgeview, IL 60455
Phone - 888-751-5444
Fax 888-307-8014
UM4300-August-2024

You might also like