405 Fire Alarm
405 Fire Alarm
NFPA
NFPA 72® contains requirements for
residential and commercial installation of fire alarm systems and equipment
NFPA 101® contains
requirements for life safety
Which NFPA standard deals with air conditioning and ventilating systems?
NFPA 90A
The simplest type of fire alarm system is the
conventional hardwired system
Most analog addressable systems operate on a
two-conductor circuit
Which of the following is one of the main components of a fire alarm system?
control panel
Which of the following pull stations require the user to lift a cover or open a door before operating the pull station?
Double-action
A fire alarm's secondary power can come from a battery or a(n)
generator
The standby time for operation of an alarm system on secondary power in a household system must be no less than
24 hours
The UL requires that system controls affecting fire alarm operation be protected by a(n)
a lock
According to the NFPA, under what conditions is it acceptable to reset a fire alarm remotely when it is alarming?
voice evacuation system
Alarm verification is commonly used in
hospitals
When two or more strobes are visible from a location, they must be
synchronized
A system that can be used to give instructions to building occupants in the event of an emergency is called a(n)
voice evacuation system
All residential alarm-sounding devices must have a minimum rating of
85dBA at 10'
According to code, a general evacuation signal should be
Temporal-Three
A digital device that sends fire alarm information over the public switched telephone network is called a
DACT
Cables in a fire alarm system must be supported by
the building structure
Anyoutdoor wiring for fire alarm circuits extending beyond one building is governed by
the NEC
The force required to operate a manual pull station must be no more than
5 foot-pounds (6.8 newton-meters)
Smoke detectors can malfunction if placed in temperatures above
120°F (49°C)
Which elevator recall method provides the highest probability of a safe evacuation?
Phase 1
When a fire alarm activates, stair enclosure doors must
unlock
If you cover a sensor during a troubleshooting procedure and it still malfunctions, the problem could be caused by
electromagnetic interference
The organization that establishes standardized testing for fire alarm designers and installers is the
NICET
NICET certifies professionals in fire alarm system design and installation.
Which NFPA standard deals with air conditioning and ventilating systems?
NFPA 90A
This covers fire safety in HVAC installations.
Which of the following is one of the main components of a fire alarm system?
control panel
Central unit that monitors and controls the system.
Which of the following pull stations require the user to lift a cover or open a door before operating the pull station?
Double-action
Prevents accidental activation by requiring two steps.
The standby time for operation of an alarm system on secondary power in a household system must be no less than
24 hours
Ensures alarm function for a full day without main power.
The UL requires that system controls affecting fire alarm operation be protected by a(n)
a lock
Prevents unauthorized access to critical controls.
According to the NFPA, under what conditions is it acceptable to reset a fire alarm remotely when it is alarming?
It is never acceptable to reset a fire alarm remotely if it is alarming.
This avoids silencing an alarm during an actual fire.
When two or more strobes are visible from a location, they must be
synchronized
Prevents disorienting flashing for those with photosensitivity.
A system that can be used to give instructions to building occupants in the event of an emergency is called a(n)
voice evacuation system
Broadcasts clear voice instructions during emergencies.
A digital device that sends fire alarm information over the public switched telephone network is called a
DACT
DACT transmits alarm signals to monitoring stations.
Any outdoor wiring for fire alarm circuits extending beyond one building is governed by
the NEC
Ensures safe wiring practices outside buildings.
The force required to operate a manual pull station must be no more than
5 foot-pounds (6.8 newton-meters)
Allows quick activation without excessive force.
If you cover a sensor during a troubleshooting procedure and it still malfunctions, the problem could be caused by
electromagnetic interference
External electrical noise may affect device operation.