0% found this document useful (0 votes)
29 views5 pages

Tds LT Cable Main

The document outlines the bill of materials for a grid-connected solar power plant at HDFC's regional head office in Kolkata, detailing specifications for aluminum and copper insulated armored power cables. It includes technical data such as voltage ratings, construction details, weight, dimensions, and electrical characteristics of the cables. The document is prepared by Engineering and Consultancy Services Pvt. Ltd. and requires approval from specified individuals.

Uploaded by

projects
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views5 pages

Tds LT Cable Main

The document outlines the bill of materials for a grid-connected solar power plant at HDFC's regional head office in Kolkata, detailing specifications for aluminum and copper insulated armored power cables. It includes technical data such as voltage ratings, construction details, weight, dimensions, and electrical characteristics of the cables. The document is prepared by Engineering and Consultancy Services Pvt. Ltd. and requires approval from specified individuals.

Uploaded by

projects
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

HDFC BANK LIMITED

(HDFC regional head office , kolkata)

SITC OF GRID CONNECTED SPV POWER PLANT AT THE ROOFTOP OF HDFC


PROJECT REGIONAL HEAD OFFICE , KOLKATA

TITLE BILL OF MATERIAL FOR SPV POWER PLANT(INVERTER TO LT ARM CABLE FOR MAIN BUILDING)

TPS PROJECT NO. TPS/24_002/E&C FY. 2023-24

SUPPLIER

ENGINEERING AND CONSULTANCY SERVICES PVT. LTD.


TPS DOCOMENT
E&C/24-P08
NO.
PURCHASE ORDER
CPC/25708-01/2023-24
NO.

STAMP:

PREPARED CHECKED APPROVED


REF. NO. DATE DESCRIPTION
(Int) (Int) (Int)
A 25/7/2024 FOR APPROVAL SAYAN RUPAM SUDIP

This document is the property of E&C. It should not be used,copied or reproduced without their written permission.
POLYCAB MC-3.5 ALUMINIUM CONDUCTOR XLPE INSULATED ARMORED
POWER CABLE (A2XFY) 650/1100V AC - IS 7098-Part 1

Stranded Aluminium Conductor

XLPE Insulation

Inner Sheath

Gal. Steel Flat Strip Armour

Extruded PVC Type ST2 Outer Sheath

Cross Section

APPLICATION

POLYCAB A2XFY MC-3.5,Stranded compacted aluminium conductor ,XLPE insulated, PVC inner sheathed,
Galvanised Steel Flat strip armour and PVC sheathed confirming to IS 7098-1 is suitable for AC single phase
or three phase (earthed or unearthed) systems with rated voltage up to and including 1100 V. This cable is also
suitable for DC systems with rated voltage up to and including 1500 V to earth.

VOLTAGE RATING STANDARD AND REFERENCES


650/1100 V IS 8130:2013
IS 5831:1984
IS 3975:1979
IS 7098-1:1988

OPERATION TEMPERATURE COMPLIANCE


Max.: 90˚C Conductor resistance - IS 8130:2013
Short circuit temperature 250˚C Insulation resistance - IS 7098-1:1988
Flammability test - IEC 60332-1:2015

CORE IDENTIFICATION BENDING RADIUS


Red, Yellow, Blue and Black Fixed installation | 12 x Overall diameter

CONSTRUCTION
Stranded plain compacted sector shaped Aluminium
conductor as per IS 8130, class 2
Insulated with Cross Linked Polyethylene (XLPE) to IS 7098-1
Extruded inner sheath with PVC Type ST2/FRLS/FR/LSZH
Armoured with Galvanised Flat Steel Strip to IS 3975
Sheathed with Extruded PVC Type ST2/FRLS/FR/LSZH

OUR CERTIFICATION
ISO ISO ISO NABL ABS IRS
9001 14001 45001 056
POLYCAB MC-3.5 ALUMINIUM CONDUCTOR XLPE INSULATED ARMORED
POWER CABLE (A2XFY) 650/1100V AC - IS 7098-Part 1

Weight & Dimension Data


Nominal Nominal
Nominal Minimum
Thickness dimension of Overall Weight
cross- sectional thickness
Product code of Insulation Armour flat Diameter (Approx.)
area of outer sheath
Main/Neutral wire
n x mm² mm mm mm mm kg/km

LVIS09AXSFYL3.5C025SA001S 3.5 x25 0.9/0.7 4x0.8 1.4 21.9 733


LVIS09AXSFYL3.5C035SA001S 3.5 x35 0.9/0.7 4x0.8 1.4 24.2 886
LVIS09AXSFYL3.5C050SA001S 3.5 x50 1/0.9 4x0.8 1.4 27.4 1113
LVIS09AXSFYL3.5C070SA001S 3.5 x70 1.1/0.9 4x0.8 1.56 31.5 1451
LVIS09AXSFYL3.5C095SA001S 3.5 x95 1.1/1 4x0.8 1.56 34.8 1796
LVIS09AXSFYL3.5C120SA001S 3.5 x120 1.2/1.1 4x0.8 1.72 38.5 2199
LVIS09AXSFYL3.5C150SA001S 3.5 x150 1.4/1.1 4x0.8 1.72 42 2579
LVIS09AXSFYL3.5C185SA001S 3.5 x185 1.6/1.1 4x0.8 1.88 47.2 3156
LVIS09AXSFYL3.5C240SA001S 3.5 x240 1.7/1.2 4x0.8 2.04 52.7 3913
LVIS09AXSFYL3.5C300SA001S 3.5 x300 1.8/1.4 4x0.8 2.2 57 4693
LVIS09AXSFYL3.5C400SA001S 3.5 x400 2/1.6 4x0.8 2.52 65 5890
LVIS09AXSFYL003C500SA001S 3.5 x500 2.2/1.7 4x0.8 2.68 73.5 7400

The above data is approximate & subject to manufacturing tolerance.

Electrical characteristics
Current carrying capacity and Maximum DC conductor resistance.

Nominal area Buried direct in In single Max. DC conductor


In air
of conductor the ground way Ducts resistance at 20˚C

mm² Amp. Amp. Amp. Ω/km

16 74 61 69 1.91
25 95 79 93 1.2
35 114 94 114 0.868
50 134 112 138 0.641
70 164 137 175 0.443
95 197 164 216 0.32
120 223 187 249 0.253
150 249 209 284 0.206
185 282 238 329 0.164
240 327 276 392 0.125
300 369 312 452 0.1
400 420 356 526 0.0778
500 478 412 612 0.0605

Air Ambient temperature: 40˚C,

Ground ambient temperature: 30˚C,

Conductor operating temperature: 90˚C

The above table is in accordance with IS 3961(part 6):2016

OUR CERTIFICATION
ISO ISO ISO NABL ABS IRS
9001 14001 45001 057
POLYCAB MC-3.5 COPPER CONDUCTOR XLPE INSULATED ARMORED
POWER CABLE (2XFY) 650/1100V AC - IS 7098-PART 1

Stranded Copper Conductor

XLPE Insulation

Inner Sheath

Gal. Steel Flat Strip Armour

Extruded PVC Type ST2 Outer Sheath

Cross Section

APPLICATION

POLYCAB 2XFY MC-3.5, Stranded compacted copper conductor, XLPE insulated, PVC inner sheathed, Galvanised
Steel Flat strip armour and PVC sheathed confirming to IS 7098-1 is suitable for AC single phase or three phase
(earthed or unearthed) systems with rated voltage up to and including 1100 V. This cable is also suitable for DC
systems with rated voltage up to and including 1500 V to earth.

STANDARD AND REFERENCES


VOLTAGE RATING
IS 8130:2013
650/1100 V
IS 5831:1984
IS 3975:1979
IS 7098-1:1988

OPERATION TEMPERATURE COMPLIANCE


Max.: 90˚C Conductor resistance - IS 8130:2013
Short circuit temperature 250˚C Insulation resistance - IS 7098-1:1988
Flammability test - IEC 60332-1:2015

CORE IDENTIFICATION BENDING RADIUS


Red, Yellow, Blue & Black Fixed installation | 12 x Overall diameter

CONSTRUCTION
Stranded plain compacted sector shaped copper conductor
as per IS 8130, class 2
Insulated with Cross Linked Polyethylene (XLPE) to IS 7098-1
Extruded inner sheath with PVC Type ST2/FRLS/FR/LSZH
Armoured with Galvanised Flat Steel Strip to IS 3975
Sheathed with Extruded PVC Type ST2/FRLS/FR/LSZH

OUR CERTIFICATION
ISO ISO ISO NABL ABS IRS
9001 14001 45001 052
POLYCAB MC-3.5 COPPER CONDUCTOR XLPE INSULATED ARMORED
POWER CABLE (2XFY) 650/1100V AC - IS 7098-PART 1

Weight & Dimension Data


Nominal Nominal
Nominal Minimum
Thickness dimension of Overall Weight
cross- sectional thickness
Product code of Insulation Armour flat Diameter (Approx.)
area of outer sheath
Main/Neutral wire
n x mm² mm mm mm mm kg/km

LVIS09CXSFY23.5C025SA001S 3.5 x25 0.9/0.7 4x0.8 1.4 21.9 1272


LVIS09CXSFY23.5C035SA001S 3.5 x35 0.9/0.7 4x0.8 1.4 24.2 1586
LVIS09CXSFY23.5C050SA001S 3.5 x50 1/0.9 4x0.8 1.4 27.4 2061
LVIS09CXSFY23.5C070SA001S 3.5 x70 1.1/0.9 4x0.8 1.56 31.5 2831
LVIS09CXSFY23.5C095SA001S 3.5 x95 1.1/1 4x0.8 1.56 34.8 3686
LVIS09CXSFY23.5C120SA001S 3.5 x120 1.2/1.1 4x0.8 1.72 38.5 4617
LVIS09CXSFY23.5C150SA001S 3.5 x150 1.4/1.1 4x0.8 1.72 42.7 5481
LVIS09CXSFY23.5C185SA001S 3.5 x185 1.6/1.1 4x0.8 1.88 47.2 6830
LVIS09CXSFY23.5C240SA001S 3.5 x240 1.7/1.2 4x0.8 2.04 52.7 8711
LVIS09CXSFY23.5C300SA001S 3.5 x300 1.8/1.4 4x0.8 2.2 57.9 10716
LVIS09CXSFY23.5C400SA001S 3.5 x400 2/1.6 4x0.8 2.52 65.5 13556

The above data is approximate & subject to manufacturing tolerance.

Electrical characteristics
Current carrying capacity and Maximum DC conductor resistance.

Nominal area Buried direct in In single Max. DC conductor


In air
of conductor the ground way Ducts resistance at 20˚C

mm² Amp. Amp. Amp. Ω/km

16 95 79 89 1.15
25 122 102 119 0.727
35 146 122 147 0.524
50 173 144 179 0.387
70 212 177 226 0.268
95 254 212 279 0.193
120 287 240 320 0.153
150 321 269 365 0.124
185 362 304 422 0.0991
240 418 352 500 0.0754
300 469 396 574 0.0601
400 528 447 662 0.047

Air Ambient temperature: 40˚C,

Ground ambient temperature: 30˚C,

Conductor operating temperature: 90˚C

The above table is in accordance with IS 3961(part 6):2016

OUR CERTIFICATION
ISO ISO ISO NABL ABS IRS
9001 14001 45001 053

You might also like