2
Contents
Introduction Heat pump project design example
The purpose of the eBook 4 Step 1 - Floor plan 41
You can trust us 5
Step 2 - Heat pump location 42
Step 3 - Recirculation pump location 42
Heat pump systems Step 4 - Domestic hot water
cylinder location 43
A brief history of heat pumps 7
Step 5 - Buffer tank location 44
Different types of heat pumps 7
Step 6 - Feed and return
The bene昀椀ts of heat pumps 9
pipe locations 45
The consequences of poor
Step 7 - Heat emitter locations 46
heat pump design 10
Step 8 - Diverter valve location 47
Step 9 - Calculate 48
Heat pump designs & calculations
Heat emitters 13
Feed and return pipes 14 Get started with the right software
Heat pump 14
Buffer tank (volumiser) 15 Apendix & Bibliography
Domestic hot water cylinder 16
Pipe Volume 53
Diverter valve 17
Velocity 57
Recirculation pumps 18
Pressure Drop 59
Heat loss 61
Heat pump system calculations
Design Checklist 64
Heat emitter 19
Bibliography 66
Feed and return pipes 25
Domestic hot water cylinder 31
Diverter valve 33
Heat pump 34
Buffer tank (volumiser) 35
Recirculation pumps 38
3
Everything you need
to know about heat pumps
Best Practices, Calculation
Methodologies and Example Designs
Almost every country in the world uses • US has introduced a bill to the
fossil fuels, which now account for senate to amend the Internal
around 80% of global energy.1 Revenue Code to establish a
However, a recent survey suggested refundable tax credit for the
most countries now see climate installation of air source heat
change as a major threat to their pumps.3
nation. 2
• EU have set the ambitious goal
of having 50 million heat pumps
This increased focus on the
installed by 2030, equating to annual
environment has resulted in new
growth of 16%.4
legislation that aims to combat the
impact of climate change. Whilst there • UK has introduced grants for heat
has been debate in recent years about pump installations as part of their
whether heat pumps or hydrogen gas legally binding net-zero targets.5
are the best way to proceed, studies
have concluded that heat pumps are
the better option.
As a result, we have seen the
introduction of new targets for heat
pump installations from governments
across the world, including:
4
Unfortunately, even with this
increased focus on heat pumps,
current installations are not
consistently meeting the required
standards. In fact, poor installations
based on poor designs appear to
be preventing the popularity of
heat pumps from spreading via
word of mouth.
As a result, engineers need to
ensure they are equipped with the
tools and knowledge required to
produce correct designs that lead to
successful installations.
The purpose of the eBook
In this eBook, we’re going to delve
into the world of heat pumps.
Our focus here is to provide the
knowledge and expertise engineers
need to produce high-quality
heat pump designs that result in
successful installations.
This will require:
• Looking at how heat pump
technology works
• The bene昀椀ts heat pumps can
provide
• Best practices for designing and
calculating each component in a
heat pump system
5
You can trust us
At H2X, we’re pioneers of software Our design software is already
that revolutionises traditional helping engineers improve outcomes.
design processes for engineers.
We understand that both the
complex calculations and the
traditional design process are
often inef昀椀cient and can lead to
errors.
7+ 5,000+
Before we look at how our solution Countries Projects
ensures accurate heat pump
designs, let’s start by going back
to the beginning and considering
what heat pumps are and how
the technology has evolved.
6
Heat pump systems
Heat pumps are devices designed to move heat from
one place to another. Whilst they are primarily used for
heating, they can also be deployed for ventilation and air
conditioning (HVAC).
The process of moving heat from
one place to the other is carried out
with the help of a compressor and
circulating a structure of liquid or gas
refrigerant, with heat extracted from
outside sources and pumped indoors.
This process is much more ef昀椀cient
than using a furnace, which generates
the hot temperature rather than
transferring it. As a result, heat pumps
can signi昀椀cantly reduce energy bills.
Did you know: Even in
below-freezing temperatures,
a heat pump can still heat a
property with more than twice
the ef昀椀ciency of gas or standard
electric heating systems.
7
A brief history of heat pumps
The history of the heat pump stretches Today, heat pumps are found in HVAC
back to the 18th century when Scottish units worldwide, but with more modern
scientist William Cullen developed system con昀椀gurations and more
the 昀椀rst crude version of the device.6 environmentally friendly refrigerants.
Cullen designed a refrigerating
machine that utilised a pump to
Heat Pumps in Operation (UK)
create a vacuum over diethyl ether,
300,000
causing the ether to boil and absorb
heat from the surrounding air.
250,000
200,000
Using this principle, Peter von Rittinger 150,000
developed the 昀椀rst heat pump 100,000
system in 1857. It wasn’t until 1948 that 50,000
American inventor Robert C. Webber
0
昀椀rst came up with the idea of a ground 2013 2014 2015 2016 2017 2018 2019
Annual amount of heat pumps in operation in the United Kingdom (UK) from 2013 to 2019 (Source Statista)
source heat pump.7
Different types of heat pumps
There are three primary types of That 昀氀uid is then circulated through
heat pumps deployed within a built a heat exchanger into the pump. This
environment, with each type classi昀椀ed then warms up the air or water needed
according to its primary source of for heating or cooling purposes inside
energy. Let’s take a look at these the property.
different types in detail.
Air-source heat pumps are the most
Air-source heat pumps prevalent type of domestic heat pump.
Air-source heat pumps absorb energy Between 2012-2022, approximately
from the surrounding air, compress it 47,000 air-source heat pumps have
and use it to heat a 昀氀uid. been installed in private and social
housing in the UK.8
8
Ground-source heat pumps Water-source heat pumps
Ground-source heat pumps use Water-source heat pumps work
the earth’s constant temperature to similarly to ground-source heat
provide heating for a building. The pumps, but instead of the ground, they
system consists of a ground loop, a utilise the water from lakes and rivers
pump, a compressor, and a control as the heat source.
system.
Like ground-source heat pumps,
The ground loop is a pipe that’s water-source heat pumps use a
buried in the ground. The pump then refrigerant to absorb heat from the
circulates a refrigerant — a mixture surrounding water. This is then turned
of water and antifreeze — through into useful heat by compressing the
the ground loop. The compressor working 昀氀uid so it can give the heat off
compresses the refrigerant and sends at a much higher temperature.
it to the control system. The control
system regulates the temperature of Water-source heat pumps need a
the building by sending the refrigerant considerable quantity of water in
to either the heating or cooling coil in order to function effectively, making
the air handler. them a more niche renewable energy
technology compared to air-source
Ground-source heat pumps are more and ground-source heat pumps.
ef昀椀cient than air-source heat pumps,
however, they are more expensive and
time-consuming to install.
9
The bene昀椀ts of heat pumps
Each of the different variations of heat
pump bring with them signi昀椀cant
bene昀椀ts following successful
installation. As a result, we are seeing
an increase in installations and
government targets across the globe.
The advantages associated with
effective heat pump installation
include, but are not limited to:
Carbon footprints: Ef昀椀cient energy use: Increased safety:
Although heat pumps Heat pumps are Heat pumps are
use electricity and are highly ef昀椀cient, so far generally a much
therefore not entirely less energy is used safer option than
carbon-free, they to produce hot water traditional heating
produce much less and heating for a systems which are
than gas boilers. property. based on combustion.
Maintenance: Improved reliability: Multi-purpose usage:
Heat pumps need Heat pumps are an During warm periods,
less maintenance incredibly reliable and heat pumps can
than traditional gas long-term source of reverse their primary
combustion heating heat, with a lifespan of purpose and switch to
systems. up to 25 years. cooling mode, acting
as an air conditioner.
Even with these bene昀椀ts in mind, it’s important to recognise that there are still
a number of design and installation challenges that will have to be overcome
before these bene昀椀ts can be realised.
10
The consequences of
poor heat pump design
Poor heat pump designs will inevitably
result in poor installations, leading to
unhappy and dissatis昀椀ed customers
in most instances. When this
happens, engineers will be required
to spend time investigating issues
and undertaking costly reworkings
of the system. This not only harms
pro昀椀t margins, but can also lead to
reputational damage that makes it
dif昀椀cult to win business moving forward.
Remember, nearly all the problems
associated with a heat pump
system can be linked back to errors
in the design, and issues often arise
when pumps are either oversized or
undersized.
An oversized heat pump will: An undersized heat pump will:
• Cycle on and off more • Not be capable of heating
frequently, which can cause the space to the desired
damage to the motor temperature
• Cycle between being too • Take longer to heat if it does
hot and too cold more often, succeed in heating the space
which makes maintaining a
• Increase the use of electricity,
comfortable temperature
defeating the purpose of
more dif昀椀cult
installation
• Use more electricity, cause
• Cause mechanical problems
higher energy bills and
as the pump has to work
make the heat pump more
harder than necessary
sustainable
• Have a shorter lifespan
• Be more expensive and noisier
11
In addition to this, if pipework that is Unfortunately, all these
too small is included within the design,
the velocity will be higher than 1m/s
design problems are often
— the maximum recommended by exacerbated by a massive
MCS and CIBSE. This will damage the skills shortage among
pipes and can result in a void warranty
from the pipe manufacturer.
engineers when it comes to
heat pumps.
High velocity causes more noise in the
system, which is obviously undesirable.
It will also create high amounts of
pressure loss, which means the
recirculation pump may not work
effectively.
12
Heat pump designs
& calculations
Before a successful heat pump installation can take place,
engineers need to undertake effective and accurate designs and
calculations for each component of the system.
Let’s take a closer look at each of the design considerations and
the calculation methodology for each component of a heat pump
system.
13
Heat emitters
A heat emitter is any component that is used to emit heat to a building space.
Heat emitters can take many different forms, the most common are:
Radiators
Radiators are traditionally common,
cheap and easy to install. However,
their operational costs can exceed
other heat emitters as they are less
ef昀椀cient at heating up spaces within
the building.
They are usually located in the coldest
part of the room i.e. below
the windows.
Radiators are not as effective with
Under昀氀oor heating
heat pump systems as they are with
traditional gas boiler systems. This is Although they are less common, more
because their surface area suits higher expensive and dif昀椀cult to install, they
water temperatures (~70°C) that have lower operational costs due to
traditional gas boilers operate at. With their higher ef昀椀ciency and provide
heat pump systems, because their better comfort for the occupants.
water circulates at lower temperatures
(~40°C), radiators often need to be The manifolds for under昀氀oor heating
signi昀椀cantly larger with larger pipework are generally located central to the
supplying them so their surface area zone they are supplying to ensure
can heat the space to the desired optimised performance. It also needs
temperature. to be accessible but in a location that
is out of view as it is not aesthetic.
Under昀氀oor heating is more suited to
heat pump systems than radiators
due to their large surface area which
is great for emitting and maintaining
temperatures that are within the heat
pump’s range.
14
Feed and return pipes
Hot water is supplied from the heat
source to each heating element
through a pipe network. This pipe
network comprises two separate
systems:
• Feed pipes that supply water from Heat pump
the heat source to the heat emitters
The heat pump is a critical piece of the
• Return pipes that circulate the
system as it is the heat source for the
water back to the heat source to be
building.
reheated
It is important to locate the heat pump
Feed and return generally run parallel,
in the best position possible. The
making them easy to install. They
main considerations for choosing the
should also be routed in the most
location are:
ef昀椀cient manner possible as this
helps to use less materials and avoids
• As close to the rest of the system
any extra heat loss and friction loss
as possible to prevent unnecessary
through the pipes.
pipe runs
• Keeping it out of view of entrances
and windows as they are not
aesthetic
• Avoiding areas where building
occupants will spend time as the
noise could be a nuisance - MCS
limit the noise to 42.0 dB(A)
• Locating it in a shady area to avoid
overheating during the summer
months
• Avoiding areas where there is the
possibility for it to be damaged by
objects like falling branches
• Locating it in an area that has good
air昀氀ow and room for maintenance
15
Buffer tank (volumiser)
A buffer tank (also known as a When deciding on the buffer tank’s
volumiser) stores water to increase the location, the main considerations are:
total system water volume and in turn
• As close to the rest of the system
reduce the cycling of a heat pump.
as possible to prevent unnecessary
pipe runs
The buffer tank is only required if
the heat pump is going to cycle too • Locating it in an area that has room
frequently. The additional hot water for maintenance
storage the buffer tank provides
reduces the heat pump’s on/off • Keeping it out of view of entrances
switching which in-turn reduces and windows as they are not
energy consumption of the heat aesthetic
pump.
• Locating it in an area where a leak
would not be catastrophic
These are generally located in the
garage, basement or attic.
They can also be located outside if
they have suf昀椀cient insulation.
16
Domestic
hot water cylinder
A domestic hot water cylinder is used
to store hot water for domestic use
such as showers and sinks.
The hot water generated by the heat
pump should not be used for domestic
purposes; however, the hot water can
be used to increase the temperature
of the cylinder’s incoming domestic
cold water. This is often supplemented
with an electrical immersion heater to
increase the temperature to 60°C+.
The cylinder is generally located in the
garage, basement or attic. They can
also be located outside if they have
suf昀椀cient insulation.
When deciding on the cylinder’s
location, the main considerations are:
• As close to the rest of the system
as possible to prevent unnecessary
pipe runs
• Locating it in an area where
electricity is relatively easy to
connect
• Keeping it out of view of entrances
and windows as they are not
aesthetic
• Locating it in an area that has room
for maintenance
• Locating it in an area where a leak
would not be catastrophic
17
Diverter valve
Diverter valves are located on the Without the diverter valve, the
tee where the system splits off to the heat pump would be sized for the
domestic hot water cylinder and the combined load of the heating system
heat emitters. and the domestic hot water cylinder
which would be overkill.
The diverter valve works by opening
and closing to direct heated water It is important to ensure there are
to either the heating system or the no heat emitters between the heat
domestic hot water cylinder. pump and diverter valve so it
The valve chooses the domestic performs correctly.
hot water cylinder as the priority.
18
Recirculation pumps
Recirculation pumps are required to do two things:
1 Circulate the water through 2 Provide enough pressure for the
the pipes fast enough to ensure water to circulate at the
the temperature of the water required 昀氀ow rate
does not fall below the
chosen Delta T
The smaller the Delta T, the higher the
昀氀ow rate. This is because the pump
needs to move the water faster so
it isn’t exposed to the cold surfaces
of the pipes and heat emitters for
as long, thus not losing as much
temperature as it would if it moved
slower.
Generally, the faster the water is
昀氀owing, the higher velocity and
pressure drop there will be too.
The recirculation pump is best located
adjacent to the actual heat pump.
They are commonly installed on the
heat pump’s feed or return side.
As the temperature is cooler on the
return side, some industry experts
argue that it’s the better location as it
extends its life.
19
Heat pump
system calculations
In this section, we’re going to look at the calculations
required to accurately size each component so the
system operates ef昀椀ciently.
Disclaimer: Not ALL design considerations are included within this eBook as requirements for
each building vary. Please contact [email protected] for any further questions or queries.
Heat emitter
To size the heat emitter, you need to
determine the heat loss through each
part of the building. To do this, you
need to know:
• The dimensions of each wall, 昀氀oor,
ceiling, door, and window
• The U-values of each wall, 昀氀oor,
ceiling, door, and window
• The desired internal temperature
and the average lowest external
temperature
• How many hourly air changes
there will be
Refer to Appendix (52pg) for reference
material relating to heat loss
calculations.
20
1. Temperature Differential (Delta T)
The difference between the desired internal temperature
and the average lowest external temperature.
Desired internal temperature (21°C) - Average lowest external temperature
(-1.8°C) = Delta T of 22.8°C
2. Surface Areas
The area of each wall, 昀氀oor, ceiling,
Floor
door, and window in the room.
5m x 6m = 30m²
Ceiling
5m x 6m = 30m²
Doors
2m x 0.8m = 1.6m²
2m x 0.8m = 1.6m²
Windows
1.6m x 0.5m = 0.8m²
1.6m x 0.5m = 0.8m²
1.6m x 0.5m = 0.8m²
1.6m x 0.5m = 0.8m²
Walls
5m x 3m = 13.4m² (minus 1 door)
5m x 3m = 13.4m² (minus 1 door)
6m x 3m = 16.4m² (minus 2 windows)
6m x 3m = 16.4m² (minus 2 windows)
21
3. U-Values
The thermal resistance of each
building element.
Floor
Concrete = 1.35 W/m²K
Ceiling
Clay Tiles = 1.00 W/m²K
Doors
Solid Wood Door = 3.00 W/m²K
Windows
Metal Double Glazed = 3.40 W/m²K
Walls
Cavity Wall (Mineral Wool)
= 0.56 W/m²K
22
4. Surface Heat Loss
Surface Heat Loss = Area (m²) x U-Value (W/m²K) x Delta T (°C)
Floor
30m² x 1.35 W/m²K x 22.8°C = 923W
Ceiling
30m² x 1.00 W/m²K x 22.8°C = 684W
Doors
1.6m² x 3.00 W/m²K x 22.8°C = 109W
1.6m² x 3.00 W/m²K x 22.8°C = 109W
Windows
0.8m² x 3.40 W/m²K x 22.8°C = 62W
0.8m² x 3.40 W/m²K x 22.8°C = 62W
0.8m² x 3.40 W/m²K x 22.8°C = 62W
0.8m² x 3.40 W/m²K x 22.8°C = 62W
Walls
13.4m² x 0.56 W/m²K x 22.8°C = 171W
13.4m² x 0.56 W/m²K x 22.8°C = 171W
16.4m² x 0.56 W/m²K x 22.8°C = 209W
16.4m² x 0.56 W/m²K x 22.8°C = 209W
Total Surface Heat Loss = 2833W / 2.833kW
23
5. Air Change Heat Loss
Air Change Heat Loss =
Room Volume (m³) x Hourly Air Changes x Delta T (°C) x 0.33
Room Volume Delta T
90m³ (30m² x 3m Height) 22.8°C
Hourly Air Changes Total Air Change Heat Loss =
677W / 0.677kW
1
24
6. Total Heat Loss
Total Heat Loss =
Surface Heat Loss + Air Change Heat Loss
Total Surface Heat Loss
2833W / 2.833kW
Total Air Change Heat Loss
677W / 0.677kW
Total Heat Loss = 3510W / 3.51kW
7. Heat Emitter Size
The heat emitter(s) in that
space needs to be able to
generate 3510W / 3.51kW.
25
Feed and return pipes
It is commonly stated throughout
the industry that heat pumps require
28mm pipes. This is a myth, is
misleading, and should be avoided.
The “28mm pipe” emerges from the
understanding that heat pumps
require larger 昀氀ow rates than gas
boilers. So where a gas boiler system
would typically need a 15mm or 22mm
pipe, people are using rule of thumb
to ‘guesstimate’ that 28mm should be
appropriate for heat pumps.
For a pipe to be 28mm, it needs to be
accurately sized as described below.
Firstly, you need to know:
• The load of the heat emitters
connected to each pipe
• The Delta T of the feed and return
temperatures
• The pipe material and its technical
properties
• The maximum design velocity
• The maximum allowable pressure
drop per metre
Refer to Appendix 52 for reference
material relating to heat loss
calculations.
26
Example:
1. Heat Emitters
Connected to the Pipe
Heat Emitter 1
3kW
Heat Emitter 2
2kW
Total Load = 5kW
2. Delta T
The difference between the
temperature on the feed and
return pipes.
Heat pumps are recommended to
operate around 40°C with a Delta T of
around 5°C.
Feed temperature (40°C)
- Return temperature (35°C)
= Delta T of 5°C
27
3. Pipe Flow Rate
Convert the heat load to a 昀氀ow rate.
Flow Rate (L/s) = Heat Load (kW) /
(Delta T (°C) * Speci昀椀c Heat
Capacity of Water (kJ))
Heat Load
5kW
Delta T
5°C
Speci昀椀c Heat Capacity of Water
4.18kJ
Flow Rate
5kW / (5°C x 4.18kJ)
0.24L/s
The 昀氀ow rate should also consider
the heat lost through the pipes. This is
very dif昀椀cult to calculate and could be
an ebook in itself, so for simplicity, we
are adding a factor of 10% to the heat
emitter load.
Flow Rate
0.24 L/s + 10%
0.264 L/s
28
4. Pipe Properties
For the pipe material, the main piece
of technical information you need to
know is the internal diameter.
It is important you use the internal
diameter rather than the nominal or
external diameter otherwise the results
will be incorrect.
For example, the internal diameter of
copper pipes is:
15mm
13.6mm internal diameter
22mm
20.2mm internal diameter
28mm
26.2mm internal diameter
35mm
32.6mm internal diameter
42mm
39.6mm internal diameter
54mm
51.6mm internal diameter
67mm
64.3mm internal diameter
29
5. Pipe Sizing
Based on Velocity
A common method for pipe sizing
is to ensure your 昀氀ow rate is below
a maximum velocity. The maximum
velocity is generally limited to 1m/s.
Velocity (m/s) =
(Flow Rate (L/s) / 1000) / ((3.14 *
(Internal Pipe Diameter (mm)/2)
^2) / 100000
The results for 0.264L/s going through each copper pipe are shown below:
15mm = 13.6mm internal diameter = 1.82m/s
22mm = 20.2mm internal diameter = 0.82m/s
28mm = 26.2mm internal diameter = 0.49m/s
35mm = 32.6mm internal diameter = 0.32m/s
42mm = 39.6mm internal diameter = 0.21m/s
54mm = 51.6mm internal diameter = 0.13m/s
67mm = 64.3mm internal diameter = 0.08m/s
Based on a 昀氀ow rate of 0.264L/s, the 22mm pipe (and larger pipes) have a
velocity below 1m/s.
30
6. Pipe Sizing Based
on Pressure Drop
CIBSE recommends a maximum
pressure drop of 350Pa/m.
So although the pipe velocity is below
1m/s, the velocity could still cause
pressure drops that are too high for
the recirculation pump to overcome.
Therefore it is important to know the
pressure drop through the pipe by
doing the pressure drop calculation.
(Friction Factor x (Pipe Length (m)
/ Pipe Diameter (m)) x (Velocity
(m/s)^2 / 19.62)) x 9084
Pressure drop in 22mm pipe 0.264L/s in a 22mm pipe has a
pressure drop of 426Pa/m
0.0274 x (1m / 0.0202m) x (0.82m/s / which exceeds CIBSE’s
19.62) x 9084 recommendation of 350Pa/m.
426Pa/m
Whereas in a 28mm pipe, the pressure
drop is 124Pa/metre.
Pressure drop in 28mm
0.0292 x (1m / 0.0262m) x (0.49m/s /
19.62) x 9084
124Pa/m
Therefore, based on the system design,
velocity considerations, and pressure
drop considerations, this pipe needs to
be 28mm.
31
Domestic hot
water cylinder
As this ebook is not going into
the details of sizing domestic
water systems, we shall use the
MCS guidance that the domestic
hot water cylinder should store
45L per building occupant.
Example:
1. Domestic Hot
Water Cylinder Size
Storage (L)
Number of Occupants * 45L
2 x 45L
Storage
90L
32
2. Domestic Hot Water
Cylinder Heat Load
Heat Load (kW) = (Speci昀椀c Heat
Capacity (kJ) * Storage (L) * Delta
T (°C)) / 3600
Speci昀椀c Heat Capacity
4.18kJ
Storage
90L
Delta T
34°C (Cold Water = 4°C, Heating
Water = ~38°C)
Heat Load
(4.18kJ * 90L * 34°C) / 3600
3.55kW
33
Diverter valve
The diverter valve is sized based on the
three pipes that connect to it.
Domestic Hot Water Outlet
The pipe is sized based on the total
domestic hot water heat load
Domestic hot water heat load
= 3.55kW / 0.17L/s
Heating System Outlet
The pipe is sized based on the total
heating system heat load.
Heating system heat load = 11kW /
0.53L/s
Inlet from Heat Pump
The pipe coming from the heat
pump is sized for only the larger of
the two outlet heat loads.
As the heating system has a higher
heat load than the domestic hot
water system, the inlet pipe size to
the diverter valve is sized at
11kW / 0.53L/s.
34
Heat pump
The heat pump needs to be sized to
match, as closely as possible, the heat
load through the system.
Example:
1. Heat Emitter Heat Load
Heat Emitter 1 = 3kW
Heat Emitter 2 = 1kW
Heat Emitter 3 = 2.5kW
Heat Emitter 4 = 1.5kW
Heat Emitter 5 = 2kW
Total Heat Emitter Heat Load = 10kW
2. Pipe Heat Load
Total Pipe Heat Load = 1kW
3. Heat Pump Size
The heat pump(s) for the building
needs to be able to generate 11kW.
35
Buffer tank (volumiser)
To determine whether you need a
buffer tank, you need to know the
following:
• The heat pump load = 11kW
• The maximum heat pump starts
recommended per hour = 6
• The speci昀椀c heat capacity of the
water = 4.18kJ
• The Delta T = 5°C
Example
1. Heat Energy Required
Heat Energy (kJ) = Heat Pump Load (kW) x (60 (minutes) / number of hourly
starts) x 60 seconds
Heat Energy (kJ) = 11 kW x (60/6) x 60 seconds
Heat Energy = 6,600kJ
2. Mass of Water Required
Mass of Water (kg) = Heat Energy (kJ) / (Speci昀椀c Heat Capacity (kJ) x Delta T
(°C))
Mass of Water (kg) = 6,600 kJ / (4.18 kJ x 5°C)
Mass of Water = 315.8 kg
3. Minimum System Volume Required
1kg of water is approximately equal to 1L of water.
Therefore, the system needs to have a total volume of 315.8L to avoid
a buffer tank.
36
4. Calculating the System Volume
The following components of your system contribute to the system volume:
• Heat Emitters
• Pipes
• Domestic Hot Water Cylinder Coil
Heat Emitters
It is best to check the technical data from the manufacturer to get the exact
volume.
However, for this example we will use:
Radiators = 11L / kW
Under昀氀oor Heating = 23L / kW
Therefore, the system volume in this example is:
Radiators = 44L (4 kW x 11L)
Under昀氀oor Heating = 138L (6 kW x 23L)
Total Heat Emitter Volume = 182L
Pipes
Using the area of the pipe, we will calculate the volume across its length.
Pipe Volume (L) = Pipe Length (m) x (Pipe Radius² (mm) / 1000) x 3.14
To calculate this, we will need to know the length of each pipe size.
25m x 0.266 (35mm pipe) x 3.14 = 20.88L
22m x 0.172 (28mm pipe) x 3.14 = 11.88L
38m x 0.102 (22mm pipe) x 3.14 = 12.17L
62m x 0.046 (15mm pipe) x 3.14 = 9L
Total Pipe Volume = 53.93L
37
4. (Continuation)
Domestic Hot Water Cylinder Coil
Again, it is best to check the technical data from the manufacturer.
However, for this example we will assume there is 10m of 22mm pipe in the
domestic hot water cylinder coil.
10m x 0.102 (22mm pipe) x 3.14 = 3.20L
Total System Volume
Heat Emitters = 182L
Pipes = 53.93L
Domestic Hot Water Cylinder Coil = 3.20L
Total System Volume = 239.13L
5. System Volume
The heat pump required a minimum system volume of 315.8L to prevent it from
cycling on/off too frequently.
The total system volume is 239.13L.
Therefore, we need to add a buffer tank to the system,
The buffer tank shall be a minimum of 76.67L (315.8L - 239.13L).
38
Recirculation pumps
There are two parts to de昀椀ning the
recirculation pump duty:
1. The 昀氀ow rate of the system
2. The pressure drop through the index
circuit, generally the furthest circuit
from the heat pump*
*It is important that you do not
cumulate the pressure drop
through every part of the heating
system. The pressure only needs
to overcome the circuit with the
most pressure drop (the index
circuit) and that will ensure there
is enough pressure to overcome
all of the other circuits.
Example
1. Pump Flow Rate
This matches the 昀氀ow rate
that you size the heat pump
for = 11 kW / 0.53 L/sec
39
2. Pump Pressure Drop
The index circuit has pressure drop
through the following:
Pipes:
The pressure drop through pipes is
calculated using the below formula:
Pressure Drop (bar) = (Friction
Factor x (Pipe Length (m) / Pipe
Diameter (m)) x (Velocity (m/s)^2 Valves and Fittings:
/ 19.62)) x 9084 The pressure drop through valves and
昀椀ttings are calculated using their K
(also known as Zeta) values. Again,
25m x 35mm pipe = 3345Pa
it is best to check the technical data
22m x 28mm pipe = 4455Pa from the manufacturer for the valve/
昀椀tting K value.
18m x 22mm pipe = 4716Pa
15m x 15mm pipe = 2322Pa The pressure drop is then calculated
using the below formula:
Total Pipe Pressure Loss
= 14838Pa / 0.149bar
Pressure Drop (bar) = (K Value x
(Velocity (m/s)^2 / 19.62)) x 9084
Heat Emitters:
It is best to check the technical
data from the manufacturer for 1 x 15mm TRV = 0.74 K Value = 55Pa
the pressure drop through the heat
2 x 35mm Isolation Valve = 0.06 K
emitter.
Value = 9Pa
In this example, we will use 1000Pa per
4 x 35mm Elbow = 0.63 K Value = 184Pa
radiator.
2 x 28mm Elbow = 0.66 K Value = 98Pa
1x Radiator = 1000Pa
1 x 22mm Elbow = 0.69 K Value = 52Pa
There is also pressure drop through
the lockshield valve, this is usually 6 x 15mm Elbow = 0.75 K Value = 224Pa
10000Pa / 0.1bar on the index circuit.
Total Valve and Fitting Pressure Loss
Total Heat Emitter Pressure Loss = 622Pa / 0.00622bar
= 11000Pa / 0.11bar
40
Total Pressure Drop
The total pressure drop through the
whole system is:
Pipes = 14838Pa
Heat Emitters = 11000Pa
Valves and Fittings = 622Pa
Total Pressure Drop
= 26460Pa / 0.26bar
Pump Duty
The recirculation pump duty is
0.53L/s @ 0.26bar.
41
Heat pump
project design example
The ongoing engineering skills That’s why below we’re going to run
shortage has the potential to scupper through a detailed, step-by-step
ambitious government targets. As a example of how to put together a
result, engineers need solutions that design for a heat pump system using
help them to design heating systems H2X’s design software.
easily, quickly and accurately.
Let’s dive straight into step 1.
Step 1
Floor plan
At the very outset of the design
process, engineers need to obtain the
PDF 昀氀oor plan for the building which
they are designing the heat pump
system for.
The example we will be working
through is shown on the right:
42
Step 2
Heat pump location
The next step is choosing where to • Locating it in a shady area to avoid
locate the heat pump. overheating during the summer
months
As described earlier, the main
considerations for choosing the • Avoiding areas where there is the
location are: possibility for it to be damaged by
objects like falling branches
• As close to the rest of the system
as possible to prevent unnecessary • Locating it in an area that has good
pipe runs air昀氀ow and room for maintenance
• Keeping it out of view of entrances In the example, we have located the
and windows as they are not heat pump towards the back of the
aesthetic house where it meets all of the above
criteria.
• Avoiding areas where building
occupants will spend time as the
noise could be a nuisance - MCS
limits the noise to 42.0 dB(A).
Step 3
Recirculation pump
location
As described earlier, the best
location for the recirculation pump
is adjacent to the heat pump.
In the example, we will locate it on
the return side of the heat pump.
43
Step 4
Domestic hot water
cylinder location
The next step is choosing where to • Keeping it out of view of entrances
locate the domestic hot water cylinder and windows as they are not
aesthetic
As described earlier, the main
• Locating it in an area that has room
considerations for choosing the
for maintenance
location are:
• Locating it in an area where a leak
• As close to the rest of the system
would not be catastrophic
as possible to prevent unnecessary
pipe runs In this example, we have chosen the
location to be within the store room
• Locating it in an area where
adjacent to the air source heat pump.
electricity is relatively easy to
connect
44
Step 5
Buffer tank location
The next step is choosing where to • Keeping it out of view of entrances
locate the buffer tank. and windows as they are not
aesthetic
As described earlier, the main
considerations for choosing the • Locating it in an area where a leak
location are: would not be catastrophic
• As close to the rest of the system In this example, we do not know if
as possible to prevent unnecessary we need one until we have done
pipe runs the calculations, so we will allow
provisional space for it adjacent to the
• Locating it in an area that has room
domestic hot water cylinder.
for maintenance
45
Step 6
Feed and return
pipe locations
As described earlier, the feed and
return pipes should run in parallel and
in the most ef昀椀cient manner possible.
This will use less materials in the
design and avoid any extra heat loss
and friction loss through the pipes.
In this example, the heat emitters
will be located around the perimeter,
so that’s where the pipes will be
located too.
46
Step 7
Heat emitter locations
The heat emitters within this building
will be a mix of radiators (in small
spaces) and under昀氀oor heating
manifolds (in large spaces).
In this example, the radiators are
located around the perimeter of
the building (below windows where
possible) and the under昀氀oor heating
manifolds are located central to the
zone they are supplying.
47
Step 8
Diverter valve location
The diverter valve is located on the
tee where the system splits off to the
domestic hot water cylinder and the
heat emitters.
Remember, it is important to ensure
there are no heat emitters between
the air source heat pump and diverter
valve to ensure correct performance.
48
Step 9
Calculate
As you click ‘Results’, using your design
parameters (pipe material, kW ratings,
maximum velocity, Delta T, etc.), H2X
will automate all of the complex
calculations involved in heat pump
systems. This includes but is not limited
to:
Feed &
return pipes
49
Heat pump size
Heat load: 22.06kw
Recirculation pump size
Recirculation Pump Duty:
0.57L/s @ 0.63bar
50
Get started with
the right software
To ensure consistently excellent heat pump
installations, engineering teams need to identify
solutions that allow them to produce heat pump
system designs that provide:
Accuracy
Simplicity
Quality
Ef昀椀ciency
At H2X, that’s exactly what we created our
cutting-edge software to do.
51
How h2x can help
Founded by engineers frustrated with inef昀椀cient
design processes, at its core H2X is an innovative tool
that can reduce design time by as much as 72%.
Automated Calculations: With H2X, engineers
can simply set calculation parameters, draw
the layout of their design and all of the required
calculations are automated in seconds.
In addition to that, by using H2X to undertake their
heat pump designs, engineers can bene昀椀t from:
PDF exports: Export your system layout and
results to a professional PDF set that comes
with a cover sheet and title block.
An automated bill of materials: Download
an accurate bill of materials that includes all
of the pipes, valves, 昀椀ttings, and equipment
that have been designed and calculated.
Keep track of cost changes from evolving
architectural designs, including estimated
costs and bills of material split up by level
and by the system.
If you’re ready to see for yourself how H2X can help
you and your team produce high-quality heat pump
designs, book a demo with us today before starting
a free trial.
52
Appendix & Bibliograpy
Pipe Volume 53 Heat loss 61
Velocity 57 Design Checklist 64
Pressure Drop 59 Bibliography 66
53
Pipe Volume
54
Copper Pipe
Nominal Diameter (mm) Internal Diameter (mm) Volume (L) Per Metre
15 13.6 0.145
22 20.2 0.321
28 26.2 0.539
35 32.6 0.835
42 39.6 1.232
54 51.6 2.091
67 64.3 3.248
76 73 4.186
108 105 8.660
133 130 13.275
159 134 14.104
PEX Pipe
Nominal Diameter (mm) Internal Diameter (mm) Volume (L) Per Metre
16 12 0.113
20 15.5 0.189
25 20 0.314
32 26 0.531
40 32 0.804
50 41 1.320
63 51 2.043
Stainless Steel Pipe
Nominal Diameter (mm) Internal Diameter (mm) Volume (L) Per Metre
15 16.1v 0.204
20 21.7 0.370
25 27.3 0.585
32 36 1.018
40 41.9 1.379
50 53.1 2.215
65 68.9 3.729
80 80.9 5.141
100 114.9 10.370
MLCP Pipe
Nominal Diameter (mm) Internal Diameter (mm) Volume (L) Per Metre
16 12 0.113
20 15.5 0.189
25 20 0.314
32 26 0.531
40 32 0.804
50 41 1.320
63 51 2.043
55
Pipe Area
56
Copper Pipe
Nominal Diameter (mm) Internal Diameter (mm) Area (mm²)
15 13.6 145.3
22 20.2 320.5
28 26.2 539.2
35 32.6 834.8
42 39.6 1231.8
54 51.6 2091.4
67 64.3 3247.6
76 73 4185.9
108 105 8660.1
133 130 13275.0
159 134 14104.4
PEX Pipe
Nominal Diameter (mm) Internal Diameter (mm) Area (mm²)
16 12 113.1
20 15.5 188.7
25 20 314.2
32 26 531.0
40 32 804.4
50 41 1320.4
63 51 2043.1
Stainless Steel Pipe
Nominal Diameter (mm) Internal Diameter (mm) Area (mm²)
15 16.1 203.6
20 21.7 369.9
25 27.3 585.4
32 36 1018.0
40 41.9 1379.0
50 53.1 2214.8
65 68.9 3728.9
80 80.9 5140.9
100 114.9 10370.2
MLCP Pipe
Nominal Diameter (mm) Internal Diameter (mm) Area (mm²)
16 12 113.1
20 15.5 188.7
25 20 314.2
32 26 531.0
40 32 804.4
50 41 1320.4
63 51 2043.1
57
Velocity
58
Copper Pipe
Nominal Internal Velocity (m/s) Velocity (m/s) Velocity (m/s) Velocity (m/s) Velocity (m/s) Velocity (m/s)
Diameter Diameter @ 0.25L/s @ 0.5L/s @ 0.75L/s @ 1L/s @ 1.25L/s @ 1.5L/s
(mm) (mm)
15 13.6 1.72 3.44 5.16 6.88 8.61 10.33
22 20.2 0.78 1.56 2.34 3.12 3.90 4.68
28 26.2 0.46 0.93 1.39 1.85 2.32 2.78
35 32.6 0.30 0.60 0.90 1.20 1.50 1.80
42 39.6 0.20 0.41 0.61 0.81 1.01 1.22
54 51.6 0.12 0.24 0.36 0.48 0.60 0.72
67 64.3 0.08 0.15 0.23 0.31 0.38 0.46
76 73 0.06 0.12 0.18 0.24 0.30 0.36
108 105 0.03 0.06 0.09 0.12 0.14 0.17
133 130 0.02 0.04 0.06 0.08 0.09 0.11
159 134 0.02 0.04 0.05 0.07 0.09 0.11
PEX Pipe
Nominal Internal Velocity (m/s) Velocity (m/s) Velocity (m/s) Velocity (m/s) Velocity (m/s) Velocity (m/s)
Diameter Diameter @ 0.25L/s @ 0.5L/s @ 0.75L/s @ 1L/s @ 1.25L/s @ 1.5L/s
(mm) (mm)
16 12 2.21 4.42 6.63 8.84 11.05 13.26
20 15.5 1.32 2.65 3.97 5.30 6.62 7.95
25 20 0.80 1.59 2.39 3.18 3.98 4.77
32 26 0.47 0.94 1.41 1.88 2.35 2.83
40 32 0.31 0.62 0.93 1.24 1.55 1.87
50 41 0.19 0.38 0.57 0.76 0.95 1.14
63 51 0.12 0.24 0.37 0.49 0.61 0.73
Stainless Steel Pipe
Nominal Internal Velocity (m/s) Velocity (m/s) Velocity (m/s) Velocity (m/s) Velocity (m/s) Velocity (m/s)
Diameter Diameter @ 0.25L/s @ 0.5L/s @ 0.75L/s @ 1L/s @ 1.25L/s @ 1.5L/s
(mm) (mm)
15 16.1 1.23 2.46 3.68 4.91 6.14 7.37
20 21.7 0.68 1.35 2.03 2.70 3.38 4.06
25 27.3 0.43 0.85 1.28 1.71 2.14 2.56
32 36 0.25 0.49 0.74 0.98 1.23 1.47
40 41.9 0.18 0.36 0.54 0.73 0.91 1.09
50 53.1 0.11 0.23 0.34 0.45 0.56 0.68
65 68.9 0.07 0.13 0.20 0.27 0.34 0.40
80 80.9 0.05 0.10 0.15 0.19 0.24 0.29
100 114.9 0.02 0.05 0.07 0.10 0.12 0.14
MLCP Pipe
Nominal Internal Velocity (m/s) Velocity (m/s) Velocity (m/s) Velocity (m/s) Velocity (m/s) Velocity (m/s)
Diameter Diameter @ 0.25L/s @ 0.5L/s @ 0.75L/s @ 1L/s @ 1.25L/s @ 1.5L/s
(mm) (mm)
16 12 2.21 4.42 6.63 8.84 11.05 13.26
20 15.5 1.32 2.65 3.97 5.30 6.62 7.95
25 20 0.80 1.59 2.39 3.18 3.98 4.77
32 26 0.47 0.94 1.41 1.88 2.35 2.83
40 32 0.31 0.62 0.93 1.24 1.55 1.87
50 41 0.19 0.38 0.57 0.76 0.95 1.14
63 51 0.12 0.24 0.37 0.49 0.61 0.73
59
Pressure drop
60
Copper Pipe
Nominal Internal Pressure Pressure Pressure Pressure Pressure Pressure
Diameter Diameter Drop (pa/m) Drop (pa/m) Drop (pa/m) Drop (pa/m) Drop (pa/m) Drop (pa/m)
(mm) (mm) @ 0.25 m/s @ 0.5 m/s @ 0.75 m/s @ 1 m/s @ 1.25 m/s @ 1.5 m/s
15 13.6 50 174 365 620 938 1317
22 20.2 31 107 226 384 581 817
28 26.2 22 78 165 281 425 598
35 32.6 17 61 127 216 327 460
42 39.6 14 48 101 171 260 365
54 51.6 10 35 74 125 190 267
67 64.3 8 27 57 96 146 205
76 73 7 23 49 83 126 177
108 105 5 15 32 54 82 115
133 130 4 12 25 42 64 90
159 134 3 12 24 41 62 87
Stainless Steel Pipe
Nominal Internal Pressure Pressure Pressure Pressure Pressure Pressure
Diameter Diameter Drop (pa/m) Drop (pa/m) Drop (pa/m) Drop (pa/m) Drop (pa/m) Drop (pa/m)
(mm) (mm) @ 0.25 m/s @ 0.5 m/s @ 0.75 m/s @ 1 m/s @ 1.25 m/s @ 1.5 m/s
15 16.1 41 142 298 506 765 1075
20 21.7 29 99 207 353 534 750
25 27.3 22 75 157 267 405 569
32 36 16 54 113 192 291 409
40 41.9 13 45 94 160 243 341
50 53.1 10 34 71 121 183 258
65 68.9 7 35 52 89 134 189
80 80.9 6 21 43 74 111 157
100 114.9 4 14 29 49 74 104
MLCP Pipe
Nominal Internal Pressure Pressure Pressure Pressure Pressure Pressure
Diameter Diameter Drop (pa/m) Drop (pa/m) Drop (pa/m) Drop (pa/m) Drop (pa/m) Drop (pa/m)
(mm) (mm) @ 0.25 m/s @ 0.5 m/s @ 0.75 m/s @ 1 m/s @ 1.25 m/s @ 1.5 m/s
16 12 59 204 426 723 1093 1535
20 15.5 42 149 312 529 801 1125
25 20 31 109 229 389 589 827
32 26 23 80 167 284 429 604
40 32 18 62 130 221 335 471
50 41 13 46 97 165 249 350
63 51 10 36 75 127 192 270
61
Heat loss
62
Design Temperatures
Location External Temperature (degC)
Belfast -1.2
Birmingham -3.4
Caridff -1.6
Edinburgh -3.4
Glasgow -3.9
London -1.8
Manchester -2.2
Plymouth -1.2
Room Temperature (degC)
Lounge 21
Dining 21
Kitchen 18
Hall / Landing 18
Utility 18
Study 21
Bedroom 18
Bed & Ensuite 21
Bathroom 22
WC 18
Store 16
Ventilation Rates
Room Pre 2000 Build ACH Post 2000 Build ACH Post 2006 Build ACH
Lounge 1.5 1 0.5
Dining 1.5 1 0.5
Kitchen 2 1.5 1.5
Hall / Landing 2 1 0.5
Utility 3 2 0.5
Study 1.5 1.5 0.5
Bedroom 1 1 0.5
Bed & Ensuite 2 1.5 1
Bathroom 3 1.5 1.5
WC 2 1.5 1.5
Store 1 0.5 0.5
Room with Chimney/Flue ACH
40m3 - Without Throat Restrictor 5
40m3 - With Throat Restrictor 3
70m3 - Without Throat Restrictor 4
70m3 - With Throat Restrictor 2
63
U Values
Element W/m²K
Roof
Aerated Concrete 0.16
Asphalt 0.5
Felt/Bitumen 0.3
Screed 0.41
Stone Chippings 0.96
Clay Tiles 1
Concrete Tiles 1.5
Wood / Wool 0.1
Floors
Concrete 1.35
Steel 50
Screed 1.2
Softwood 0.13
Hardwood 0.18
Wood Blocks 0.14
Windows
Metal Single Glazed 5.7
Metal Double Glazed 3.4
Metal Triple Glazed 2.6
Wood Single Glazed 4.8
Wood Double Glazed 2.8
Wood Triple Glazed 2.1
PVC Single Glazed 4.8
PVC Double Glazed 2.8
PVC Triple Glazed 2.1
Doors
Solid Wood Door 3
Glazed Wood Single 5.7
Glazed Wood Double 3.4
Glazed Wood Triple 2.6
Metal Single 5.7
Metal Double 3.4
Metal Triple 2.6
Walls
Solid Brick 2.1
Solid Brick Insulated 0.28
Solid Stone 2.25
Solid Stone Insulated 0.32
Solid Concrete 3
Solid Concrete Insulated 0.31
Cavity Wall Uninsulated 1.3
Cavity Wall Insulated 0.55
Hardwood 0.18
Softwood 0.13
Plasterboard 0.16
64
Design Checklist
Design
Component Requirement
Heat Pump Located close to the rest of the system
Located away from the entrance and any windows
Located away from rooms where noise will be a nuisance
Located in a shady area
Located in an area that has no risk of damage from falling
objects
Located in an area with good air昀氀ow and access for
maintenance
Recirculation Pump Located on the design adjacent to the heat pump
Cylinder Located close to the rest of the system
Located away from the entrance and any windows
Located in an area with access for maintenance
Located in an area where a leak would not be catastrophic
Located in an area where electricity is relatively easy to
connect
Buffer Tank Located close to the rest of the system
Located away from the entrance and any windows
Located in an area where a leak would not be catastrophic
Pipes Pipe routes are the most ef昀椀cient possible
Heat Emitters Location of radiators con昀椀rmed
Location of the under昀氀oor heating manifold con昀椀rmed
Diverter Valve Located on the design between the heat pump and cylinder
No heat emitters between the heat pump and diverter valve
65
Calculations
Component Requirement
Heat Emitters Find the Delta T
Calculate the surface areas
Find the U-Value of surfaces
Calculate the surface heat loss
Calculate the air change heat loss
Size the heat emitters
Pipes Calculate the heat load connected to each pipe
Choose the Delta T of the system
Calculate the 昀氀ow rate through each pipe
Find the properties of the chosen pipe material
Size the pipe based on the velocity at the calculated
昀氀ow rate
Check the pressure drop through each pipe and
adjust sizes accordingly
Cylinder Calculate the cylinder capacity
Calculate the cylinder heat load on the heating
system
Diverter Valve Calculate the 昀氀ow rate on each of the two diverter
valve outlets
Size the pipe on the inlet to the diverter valve for the
largest of the two out昀氀ows only
Heat Pump Calculate the heat load of all of the heat emitters that
are connected to the heat pump
Calculate the heat load of all of the pipes that are
connected to the heat pump
Determine the heat pump size for the combination of
all the heat loads
Buffer Tank Calculate the system volume required to avoid a
buffer tank
Calculate the volume in the designed system
Con昀椀rm if/what size buffer tank is required
Recirculation Pump Calculate the 昀氀ow rate of the system
Calculate the pressure drop through the index circuit
66
Bibliography
1 Percentage of Fossil Fuels Used in the World.
2 A look at how people around the world view climate change.
3 King, Collins Introduce Legislation Incentivizing Americans To Use Cheaper,
Cleaner Home Heating and Cooling Units.
4 EU Heat Pumps: warnings against “one size 昀椀ts all” policies.
5 Households in England and Wales to be offered new £5,000 Government
grant from April 2022 to help replace gas boilers with heat pumps.
6 William Cullen: Scottish physician and professor.
7 Heat Pump Technology: A Brief History.
8 Heat pump installations in the UK – where and why?