nfpa-72 smoke detection
nfpa-72 smoke detection
ENHANCED CONTENT
Collapse
17.7.1 General.
17.7.1.1*
The smoke detection design documentation shall state the required
performance objective of the system.
ENHANCED CONTENT
Collapse
The designer has two routes in the design of a fire detection system
using smoke detectors. One route is to use prescriptive requirements,
in which the designer follows the prescribed spacing and location
criteria in the Code. The second route is the use of the performance-
based design methods outlined in Annex B. Also see the commentary
following Section 17.3. In either case, the performance objective of the
system must be stated in the smoke detection design documentation.
Smoke detectors are required by the relevant building code where a life
safety objective is to be achieved. Smoke detectors are also used
where a property conservation objective justifies early warning. The
term early warning is not defined and can be interpreted in many ways.
In general, it implies that detection is achieved during the incipient
stage of a fire, which typically produces more smoke than heat when
ordinary combustibles are involved. Thus, smoke detection is
considered to provide an earlier warning than heat detection when
installed in a normal building environment.
FAQ What types of fire are assumed in the methods in Annex B for
predicting the actuation of smoke detectors?
The designer must understand the behaviors of the fire plume and the
ceiling jet to understand how the building structure can affect the flow
of smoke through the compartment and from one compartment to
others. The site evaluation includes an audit of all combustibles within
the compartment, as well as all ignition sources, including transient
ones. The designer models the fires to obtain an estimate of the rate
of fire growth for each combustible and ignition source scenario and
then compares the fire scenarios to the performance objectives for the
compartment. This procedure leads to a basis for design.
17.7.1.2*
Designs not in accordance with 17.7.1.3 shall be deemed prescriptive
designs and shall be designed in accordance with the prescriptive
requirements of this chapter.
17.7.1.3*
Performance-based designs shall be executed in accordance with
Section 17.3.
17.7.1.4
The prescriptive requirements in this section shall be applied only
where detectors are installed in ordinary indoor locations.
ENHANCED CONTENT
Collapse
Where the application falls outside the conditions assumed for the
prescriptive requirements of Section 17.7, the designer must consider
the impact of those conditions on the operability and reliability of the
detector. In evaluating the reasons why the conditions are not
appropriate, the designer might identify an alternative design approach
that solves the problem. Some authorities having jurisdiction establish
additional requirements for specific types of occupancies that go
above and beyond the requirements of Section 17.7. To protect
extremely valuable assets, the designer might also reduce the smoke
detector spacing in certain areas, such as in a data center or where the
owner’s fire protection goals demand a faster response. In some
cases, the situation might warrant the use of a more fully developed
performance-based approach or the use of a different type of fire
detection than smoke-sensing fire detection.
17.7.1.5
Where smoke detectors are being installed to control the spread of
smoke, they shall be installed in accordance with the requirements
of 17.7.6.
ENHANCED CONTENT
Collapse
17.7.1.6
Smoke detectors shall be installed in all areas where required by other
governing laws, codes, or standards or by other parts of this Code.
ENHANCED CONTENT
Collapse
17.7.1.7
The selection and placement of smoke detectors shall take into
account both the performance characteristics of the detector and the
areas into which the detectors are to be installed to prevent nuisance
and unintentional alarms or improper operation after installation.
ENHANCED CONTENT
Collapse
The process of detector selection and how the design addresses the
criteria outlined in A.17.7.1.8 and A.17.7.1.10 should be documented
as part of the project file. See 17.7.1.1.
17.7.1.8*
Unless specifically designed and listed for the expected conditions,
smoke detectors shall not be installed if any of the following ambient
conditions exist:
• (1)
• (2)
• (4)
The cited temperature, humidity, and airflow criteria reflect the test
criteria in the test standards used by the listing agency in the process
of the listing evaluation. Different detection technologies are affected
differently by these environmental extremes. Although the
identification of these effects is beyond the scope of this handbook,
the designer must recognize that some detector designs are inherently
more forgiving than others.
17.7.1.9*
Smoke detectors installed in ducts and other locations with air
velocities greater than 300 ft/min (1.5 m/sec) shall be listed for the
velocity conditions anticipated and installed in accordance with the
manufacturer’s published instructions.
ENHANCED CONTENT
Collapse
17.7.1.10*
The location of smoke detectors shall be based on an evaluation of
potential ambient sources of smoke, moisture, dust, or fumes, and
electrical or mechanical influences, to minimize nuisance alarms.
17.7.1.11*
The effect of stratification below the ceiling shall be taken into
account. The guidelines in Annex B shall be permitted to be used.
ENHANCED CONTENT
Collapse
A ceiling jet is formed when the plume hits the ceiling with sufficient
momentum. The radial flow of the ceiling jet from the plume centerline
is the result of the residual momentum of the upward flowing plume
gases. This momentum conveys smoke to the detector location.
Without a ceiling jet, the smoke and heat from the fire will not move
horizontally beneath the ceiling. Most of the spacing criteria for smoke
and heat detectors are based on the assumption that a ceiling jet
exists and that it is moving the smoke and heat horizontally in a layer
immediately beneath the ceiling. Stratification affects the performance
of the detection system because the smoke forms a layer too far
below the ceiling-mounted smoke detectors.
17.7.2.2
Where detectors are installed but not operational during construction,
they shall be protected from construction debris, dust, dirt, and
damage in accordance with the manufacturer’s recommendations and
verified to be operating in accordance with the listed sensitivity, or they
shall be replaced prior to the final acceptance test of the system.
ENHANCED CONTENT
Collapse
Many smoke detectors are shipped with a thin plastic cover that fits
over the sensing portion of the detector, similar to the one shown in
Exhibit 17.31. These covers are widely assumed to be suitable for
protecting the detector from construction dust, dirt, and debris.
However, most of these covers are merely for protection during
shipping and are not intended to be used in lieu of the manufacturer’s
recommended protection. Therefore, cleaning detectors after all
construction trades have finished work is often still necessary.
EXHIBIT 17.31 Smoke Detector with Protective Plastic Cover.
(Courtesy of Hochiki America Corp., Buena Park, CA)
It should be recognized that any means of keeping dust and debris out
of a smoke detector sensing chamber would also impede the entry of
smoke. To ensure operability of the system, the contractor must have
a means of verifying that all protective measures are removed from the
detectors when the construction trades have completed their work.
17.7.3* Sensitivity.
ENHANCED CONTENT
Collapse
Full-scale room fire tests are also conducted during the listing
evaluation of a smoke detector. The fire test room has a ceiling height
of 10 ft (3.0 m). In accordance with UL 268, Smoke Detectors for Fire
Alarm Systems, smoke detectors are required to render an alarm when
subjected to fires that ultimately produce smoke obscurations of 37
percent per foot for a paper fire, 17 percent per foot for a wood fire, 5
percent per foot for a flaming polyurethane foam fire, 12 percent per
foot for a smoldering polyurethane foam fire, and 10 percent per foot
for a smoldering wood fire. Additionally, smoke detectors are required
not to render an alarm before a smoke obscuration of 1.5 percent per
foot is produced in the cooking nuisance smoke test. These pass/fail
tests also do not provide a meaningful basis for predicting smoke
detector performance.
17.7.3.1*
Smoke detectors shall be marked with their nominal production
sensitivity and tolerance in percent per foot (percent per meter)
obscuration, as required by the listing.
17.7.3.2
Spot-type smoke detectors that have provision for field adjustment of
sensitivity via a mechanical means shall have an adjustment range of
not less than 0.6 percent per foot (1.95 percent per meter)
obscuration.
ENHANCED CONTENT
Collapse
17.7.3.3
If the means of adjustment of sensitivity is on the detector, a method
shall be provided to restore the detector to its factory calibration.
ENHANCED CONTENT
Collapse
17.7.3.4
Detectors that have provision for program-controlled adjustment of
sensitivity shall be permitted to be marked with their programmable
sensitivity range only.
ENHANCED CONTENT
Collapse
17.7.4.1* General.
17.7.4.1.1
The location and spacing of smoke detectors shall be based upon the
anticipated smoke flows due to the plume and ceiling jet produced by
the anticipated fire, as well as any pre-existing ambient airflows that
could exist in the protected compartment.
ENHANCED CONTENT
Collapse
17.7.4.1.2
The design shall account for the contribution of the following factors in
predicting detector response to the anticipated fires to which the
system is intended to respond:
• (1)
• (2)
Ceiling height
• (3)
• (4)
• (5)
Compartment ventilation
• (6)
These general criteria are far less specific than those established for
heat detectors. The reasoning can be understood by a review of the
importance of fire plume dynamics in the location and spacing of heat
detectors versus smoke detectors.
Heat detectors depend on the fire plume and ceiling jet to carry hot
gaseous combustion products and entrained air to the detector where
heat can flow from the ceiling jet into the detector, resulting in an
alarm. Although not explicitly stated in the Code, heat detectors are
generally used where response is needed once the fire has achieved an
energy output of at least 1.2 MW, which is the size of fire used in
determining the listed spacing for a heat detector. This size of fire
discharges a significant quantity of energy, which serves as the engine
that creates its own air currents. The energy from the fire propels the
hot air and smoke mixture across the ceiling. As a result, the fire is the
dominant air mover in the compartment.
Modeling the flow of the fire plume and ceiling jet is possible with
computer programs such as FDS that apply the rules of fluid flow
physics and thermodynamics to the plume from a fire. If explicit
modeling is not used, the designer must determine the location and
spacing of smoke detectors based on how the site-specific
environmental features will affect the flow of smoke from early-stage,
low-energy-output fires.
17.7.4.1.3
If the intent is to protect against a specific hazard, the detector(s) shall
be permitted to be installed closer to the hazard in a position where the
detector can intercept the smoke.
ENHANCED CONTENT
Collapse
17.7.4.2.1*
Spot-type smoke detectors shall be located on the ceiling or, if on a
sidewall, between the ceiling and 12 in. (300 mm) down from the
ceiling to the top of the detector.
17.7.4.2.2*
To minimize dust contamination, smoke detectors, where installed
under raised floors, shall be mounted only in an orientation for which
they have been listed.
17.7.4.2.3
On smooth ceilings, spacing for spot-type smoke detectors shall be in
accordance with 17.7.4.2.3.1 through 17.7.4.2.3.4.
17.7.4.2.3.1*
In the absence of specific performance-based design criteria, one of
the following requirements shall apply:
• (1)
• (2)*
17.7.4.2.3.3
Other spacing shall be permitted to be used depending on ceiling
height, different conditions, or response requirements.
ENHANCED CONTENT
Collapse
17.7.4.2.3.4
For the detection of flaming fires, the guidelines in Annex B shall be
permitted to be used.
ENHANCED CONTENT
Collapse
17.7.4.2.4*
For solid joist and beam construction, spacing for spot-type smoke
detectors shall be in accordance
with 17.7.4.2.4.1 through 17.7.4.2.4.6.
17.7.4.2.4.1
Solid joists shall be considered equivalent to beams for smoke
detector spacing guidelines.
ENHANCED CONTENT
Collapse
17.7.4.2.4.2
For level ceilings, the following shall apply:
• (1)
o (a)
o (b)
• (2)
o (a)
o (b)
i.
Smooth ceiling spacing in the direction parallel to
the beams and at one-half smooth ceiling spacing in
the direction perpendicular to the beams
ii.
• (3)*
o (a)
o (b)
• (4)*
o (a)
o (b)
• (5)
For rooms of 900 ft2 (84 m2) or less, the following shall apply:
o (a)
o (b)
(1) The designer is permitted to use smooth ceiling spacing under level
ceilings where beams and joists extend down from the ceiling surface
less than 10 percent of the floor-to-ceiling height, regardless of the
beam or joist spacing. Since the thickness of the ceiling jet is generally
taken to be equal to the upper 10 percent of the floor-to-ceiling height,
beams and joists extending down a depth of less than this thickness
are not expected to have a significant effect on the response time of
the smoke detector. The farthest a detector should be from the fire is
0.7 times the 30 ft (9.1 m) spacing. Therefore, detectors can be
located on either the ceiling or the bottom of the beam. See Exhibit
17.32.
EXHIBIT 17.32 Smoke Detector Locations with Beams Less than 0.1H.
(2) (b) The speed with which smoke enters the sensing chamber of a
detector is controlled by the velocity of the ceiling jet as it flows past
the detector. Where beams or joists extend down from a level ceiling
more than 10 percent of the floor-to-ceiling height, they obstruct the
ceiling jet flow and cause it to flow more slowly. This could increase
the time needed for smoke to enter the detection chamber after the
ceiling jet arrives at the detector location.
FAQ What spacing should be used when beam spacing is greater than
40 percent of the floor-to-ceiling height (0.4H)?
Since it is generally accepted that the smoke plume from a fire will
diverge at a nominal 22 degrees (see Exhibit 17.29), the width of the
plume is assumed to be about 40 percent of the floor-to-ceiling height
(0.4H). Where the beam spacing exceeds 40 percent of the floor-to-
ceiling height, the entire plume can fit within a single beam pocket. If a
smoke detector is not in that pocket, the entire bay must fill with
smoke before there is fill-and-spill propagation to an adjacent bay
where a smoke detector might be. This phenomenon can result in a
delayed response. In the case where the beams are both equal to or
more than 10 percent of the floor-to-ceiling height in depth and spaced
equal to or more than 40 percent of the floor-to-ceiling height, a
detector must be installed in each beam pocket, as shown in Exhibit
17.33.
(5) Where smoke detectors are installed in a room of only 900 ft2 (84
m2), the small ceiling area constrains the ceiling jet such that even
when beams are present, the fire can be detected sufficiently early to
achieve the objective. Where other objectives demand more rapid
response, performance-based design methods should be employed.
It is not the intent of 17.7.4.2.4.2(5) that the 900 ft2 (84 m2) be applied
to 5 ft (1.5 m) wide passage-ways 180 ft (54.9 m) in length, 10 ft (3.1
m) wide corridors 90 ft (27.4 m) in length, or other compartments
where the fire hazard and risk are nominally equivalent to the rest of
the normally occupied portion of the building. List item
17.7.4.2.4.2(5)(a) requires the use of smooth spacing;
see 17.7.4.2.3.1.
17.7.4.2.4.3*
For sloping ceilings with beams running parallel up slope, the following
shall apply:
• (1)
• (2)
• (3)
• (4)
• (5)
• (6)
o (a)
For beam spacing greater than or equal to 40 percent of
the ceiling height (0.4 H), spot-type detectors shall be
located in each beam pocket.
o (b)
17.7.4.2.4.4*
For sloping ceilings with beams running perpendicular across slope,
the following shall apply:
• (1)
• (3)
• (4)
• (5)
• (6)
Beams that are perpendicular to the slope are parallel to the ridge
beam. These beams form dams that prevent the smoke from flowing
up the ceiling slope toward the ridge beam. When the smoke
encounters a beam running across the slope, the ceiling jet will begin
forming a smoke layer. Smoke will flow laterally as the depth of the
smoke layer increases. Eventually the smoke layer will become deep
enough to spill over the beam and begin filling the next bay. This
process is a much slower propagation than when the beams run up the
slope. However, the damming effect of the beams will tend to channel
smoke across the roof, parallel to the beams. The spacing adjustments
in this section are the result of a detailed analysis of the computational
fluid dynamics modeling research that was conducted to investigate
this issue.
17.7.4.2.4.5*
For sloped ceilings with beam pockets formed by intersecting beams,
the following shall apply:
• (1)
• (2)
• (3)
• (4)
• (5)
17.7.4.3* Peaked.
17.7.4.3.1
Detectors shall first be spaced and located within 36 in. (910 mm) of
the peak, measured horizontally.
17.7.4.3.2
The number and spacing of additional detectors, if any, shall be based
on the horizontal projection of the ceiling.
ENHANCED CONTENT
Collapse
17.7.4.4* Shed.
17.7.4.4.1
Detectors shall first be spaced and located within 36 in. (910 mm) of
the high side of the ceiling, measured horizontally.
17.7.4.4.2
The number and spacing of additional detectors, if any, shall be based
on the horizontal projection of the ceiling.
ENHANCED CONTENT
Collapse
17.7.4.5.1
Spaces beneath raised floors and above suspended ceilings shall be
treated as separate rooms for smoke detector spacing purposes.
17.7.4.5.2
Detectors installed beneath raised floors or above suspended ceilings,
or both, including raised floors and suspended ceilings used for
environmental air, shall not be used in lieu of providing detection within
the room.
17.7.4.5.3
For raised floors, the following shall apply:
• (1)
• (2)
Where the area beneath the raised floor is also used for
environmental air, detector spacing shall also conform
to 17.7.5.1 and 17.7.5.2.
17.7.4.5.4
For suspended ceilings, the following shall apply:
• (1)
Detector spacing above suspended ceilings shall conform to the
requirements of 17.7.4 for the ceiling configuration.
• (2)
17.7.4.6.1.2
Air sampling–type smoke detectors shall produce trouble signals if the
airflow is outside the manufacturer’s specified range.
ENHANCED CONTENT
Collapse
17.7.4.6.1.3
If provided, atmospheric contaminant filtration shall be listed for use
with the detector and installed and maintained in accordance with the
air sampling–type smoke detector manufacturer’s published
instructions.
ENHANCED CONTENT
Collapse
FAQ What effect does limiting the transport time have on the system
design?
The air transport time criterion places an effective limit on the design
of the fan and the maximum distance from the detector to the farthest
sampling port, as well as the size and layout of the sampling pipes.
The manufacturer’s listing and instructions provide the details on how
to comply with this limitation when using a specific product. As part of
the system design process, the air transport time must be calculated in
accordance with 17.7.4.6.2.2 and 17.7.4.6.2.3.
17.7.4.6.2.2
Sampling pipe networks shall be designed on the basis of, and shall be
supported by, computer-based fluid dynamics design calculations to
ensure required performance.
ENHANCED CONTENT
Collapse
17.7.4.6.2.3
The sampling pipe network design calculations shall include pressure,
volumetric flow, and alarm sensitivity at each sampling port.
ENHANCED CONTENT
Collapse
17.7.4.6.2.4
Software applications for the design of pipe networks shall be listed
for use with the manufacturer’s equipment.
ENHANCED CONTENT
Collapse
17.7.4.6.2.5
Sampling system piping shall be conspicuously identified as “SMOKE
DETECTOR SAMPLING TUBE — DO NOT DISTURB,” as follows:
• (1)
• (2)
• (3)
17.7.4.6.2.6*
Sampling ports shall be identified as such.
17.7.4.6.2.7*
If provided, test ports at the end (most remote location) of a pipe run
installed in the pipe network solely for the purpose of validating
consistency in performance (also referred to as benchmark test
points) shall be included in the design calculations and allowed, but
not required, to comply with the requirements of 17.7.4.6.2.
ENHANCED CONTENT
Collapse
17.7.4.6.2.8
If the piping and fittings are painted, the painting shall be performed in
accordance with the air sampling–type smoke detector manufacturer’s
published instructions.
17.7.4.6.2.9*
Pipe network materials, sizing, and installation shall be in accordance
with the manufacturer’s published requirements and suitable for use in
the environment in which they are installed.
ENHANCED CONTENT
Collapse
17.7.4.6.2.10
Where used, capillary tubing shall be sized and affixed in accordance
with the manufacturer’s published instructions and computer-based
design calculations.
17.7.4.6.3 Installation and Spacing.
17.7.4.6.3.1*
Air sampling pipe network fittings shall be installed air-tight and
permanently affixed.
17.7.4.6.3.2
Sampled air shall be exhausted to a lessor or equal pressure zone. The
pressure differential between the sampled air and detector exhaust
shall not exceed the manufacturer’s published instructions.
ENHANCED CONTENT
Collapse
Because pressure gradients are not often a concern, most air sampling
detection systems are designed to exhaust directly from the detector.
However, if a pressure gradient exists between the sampling location
and the detector location, an exhaust pipe can be used to return the
exhausted air to the room of origin.
17.7.4.6.3.3*
Supports for sampling pipe shall be in accordance with the air
sampling–type smoke detector manufacturer’s published instructions.
17.7.4.6.4 Special Applications.
17.7.4.6.4.1 Air Duct Applications.
(A)
The air sampling system shall be listed for air duct applications and
shall be installed in accordance with the manufacturer’s published
instructions.
(B)
The inlet and exhaust sections of pipe that are installed inside the air
duct shall be air-tight and shall exhaust the sampled air in accordance
with the manufacturer’s published instructions.
17.7.4.6.4.2* Electrical Cabinet Applications.
For protection of cabinets containing electrical equipment, the air
sampling ports shall be located in the main airflow at the exhaust
vents, downstream of the airflow distribution path, or in accordance
with the manufacturer’s published instructions.
17.7.4.7* Projected Beam–Type Smoke Detectors.
17.7.4.7.1
Projected beam–type smoke detectors shall be located in accordance
with the manufacturer’s published instructions.
ENHANCED CONTENT
Collapse
17.7.4.7.2*
The effects of stratification shall be evaluated when locating the
detectors.
ENHANCED CONTENT
Collapse
17.7.4.7.3
The beam length shall not exceed the maximum permitted by the
equipment listing.
ENHANCED CONTENT
Collapse
17.7.4.7.4
If reflectors are used with projected beams, the reflectors shall be
installed in accordance with the manufacturer’s published instructions.
ENHANCED CONTENT
Collapse
17.7.4.7.5
A projected beam-type smoke detector shall be considered equivalent
to a row of spot-type smoke detectors for level and sloping ceiling
applications.
ENHANCED CONTENT
Collapse
17.7.4.7.6
Projected beam-type detectors and reflectors shall be mounted on
stable surfaces to prevent false or erratic operation due to movement.
ENHANCED CONTENT
Collapse
Note that the term mirror, formerly used in the Code, was replaced by
the term reflector for the 2022 edition. A mirror is a type of reflector.
17.7.4.7.7
The beam shall be designed so that small angular movements of the
light source or receiver do not prevent operation due to smoke and do
not cause nuisance or unintentional alarms.
ENHANCED CONTENT
Collapse
17.7.4.7.8*
Unless otherwise permitted by 17.4.2.2, the design and installation of
projected beam-type detectors shall address the potential for the
obstruction of the light path.
ENHANCED CONTENT
Collapse
Projected beam–type detectors use obscuration algorithms in their
software that can distinguish the progressive obscuration that occurs
during a fire with the step-wise obscuration that usually indicates
interference in the path of the beam by an opaque object. However,
despite the most sophisticated software, seasonal decorations, party
balloons, and hanging plants have been known to cause problems.
Obstructions that can gradually grow and block a beam detector, such
as trees in an atrium, should also be considered a potential problem.
This paragraph applies to both air supply and air return. In research
conducted under the International Fire Detection Research Project,
computer modeling identified situations where areas of nonactuation
extended almost 11 ft (3.4 m) from some supply diffusers. In addition,
the research showed that a smoke dilution effect occurred near air
returns. An air return pulls air up from levels in the room that are
beneath the ceiling jet, which has the effect of diluting smoke
concentration near the air return grille. The designer should arrange
detectors such that they are not adjacent to either air supplies or air
returns.
Situations could exist where even a 36 in. (910 mm) separation is not
adequate. This situation could depend on the air velocity (i.e., supply
air and return air), the throw characteristics of the supply diffuser, and
the diffuser size. Because the research did not address wide variations
in HVAC flow rates, the minimum distance between a detector and the
HVAC system supply or return recommended in A.17.7.5.1 might not
be valid in all cases. Where in doubt, airflow in the vicinity of the
detector should be mapped with a velometer or anemometer. Certainly,
the ambient airflow at the detector location should be only a fraction of
that used in the UL 268 smoke box of 30 ft/min (0.152 m/sec).
17.7.5.2
In under-floor spaces and above-ceiling spaces that are used as HVAC
plenums, detectors shall be listed for the anticipated environment as
required by 17.7.1.8.
ENHANCED CONTENT
Collapse
17.7.5.3
Detector spacings and locations shall be selected on the basis of
anticipated airflow patterns and fire type.
17.7.5.4*
Detectors placed in environmental air ducts or plenums shall not be
used as a substitute for open area detectors.
ENHANCED CONTENT
Collapse
In most buildings, there are periods when the HVAC system is not
moving significant quantities of air from the compartments it serves.
As a result, the fire detection system cannot be designed to rely on the
HVAC system operation for the transport of smoke to detectors in the
duct or plenum.
17.7.5.4.1
Where detectors are used for the control of smoke spread, the
requirements of 17.7.6 shall apply.
17.7.5.4.2
Where open area protection is required, 17.7.4 shall apply.
17.7.5.5
Detectors placed in environmental air ducts or plenums shall be
permitted to be either supervisory or alarm initiating devices.
17.7.6* Smoke Detectors for Control of Smoke Spread.
ENHANCED CONTENT
Collapse
FAQ Does 17.7.6 require the installation of smoke detectors for smoke
control?
17.7.6.1* Classifications.
Smoke detectors installed and used to prevent smoke spread by
initiating control of fans, dampers, doors, and other equipment shall be
classified in the following manner:
• (1)
• (2)
• (3)
17.7.6.2* Limitations.
17.7.6.2.1
Detectors that are installed in the air duct system in accordance
with 17.7.6.1(2) shall not be used as a substitute for open area
protection.
ENHANCED CONTENT
Collapse
17.7.6.2.2
Where open area protection is required, 17.7.4 shall apply.
17.7.6.3* Purposes.
17.7.6.3.1
To minimize the recirculation of smoke, a detector approved for air
duct use shall be installed as required by NFPA 90A and 17.7.6.4.2.
17.7.6.3.2
If smoke detectors are used to initiate selectively the operation of
equipment to control smoke spread, the requirements
of 17.7.6.4.2.2 shall apply.
17.7.6.3.3
If detectors are used to initiate the operation of smoke doors, the
requirements of 17.7.6.6 shall apply.
17.7.6.3.4
If duct detectors are used to initiate the operation of smoke dampers
within ducts, the requirements of 17.7.6.5 shall apply.
17.7.6.4 Application.
17.7.6.4.1 Area Smoke Detectors Within Smoke Compartments.
Area smoke detectors within smoke compartments shall be permitted
to be used to control the spread of smoke by initiating operation of
doors, dampers, and other equipment.
ENHANCED CONTENT
Collapse
Complete area coverage may be used for the control of smoke spread.
In this case, when a compartment detector actuates in the smoke
compartment, it signals the FACU, which in turn signals the HVAC
control system or smoke door release system. The HVAC controller
operates or controls fans and dampers to prevent the introduction of
smoke into other smoke compartments and to vent the smoke from
the fire compartment, facilitating occupant egress. The smoke door
release system closes either all doors in the building or all doors in the
smoke zone.
The relevant NFPA standards are NFPA 90A, NFPA 92, and NFPA 101.
The purpose of supply-side smoke detection is the sensing of smoke
that might be contaminating the area served by the duct but not as a
result of a fire in that area. The smoke might be coming from another
area via return air ducts, from outside via fresh air mixing ducts, or
from a fire in the duct (e.g., in a filter or fan belt). If the source of the
smoke is from outside or from in the duct, a fire alarm response for
area detection in the space would not normally be expected to produce
the most appropriate set of responses.
The exception is based on the fire resistance of HVAC ducts and the
unlikelihood of smoke escaping from the HVAC duct into a
compartment not served by the duct. Refer to the following excerpt
from NFPA 90A for supply and return air smoke detection
requirements:
6.4.2* Location.
6.4.2.1 Smoke detectors listed for use in air distribution systems shall
be located as follows:
6.4.2.2 Return system smoke detectors shall not be required where the
entire space served by the air distribution system is protected by a
system of area smoke detectors.
6.4.2.3 Smoke detectors shall not be required for fan units whose sole
function is to remove air from the inside of the building to the outside
of the building.
(A)
Where the detection of smoke in the supply air system is required by
other NFPA standards, a detector(s) listed for the air velocity present
shall be installed in the supply air duct downstream of both the fan and
the filters.
(B)
Where the air duct system passes through other smoke compartments
not served by the duct, additional smoke detectors shall not be
required to be installed.
17.7.6.4.2.2* Return Air System.
Unless otherwise modified by 17.7.6.4.2.2(A) or 17.7.6.4.2.2(B), if the
detection of smoke in the return air system is required by other NFPA
standards, a detector(s) listed for the air velocity present shall be
located where the air leaves each smoke compartment, or in the duct
system before the air enters the return air system common to more
than one smoke compartment.
ENHANCED CONTENT
Collapse
(A)
Additional smoke detectors shall not be required to be installed in
ducts where the air duct system passes through other smoke
compartments not served by the duct.
ENHANCED CONTENT
Collapse
This is based on the fire resistance of HVAC ducts and the unlikelihood
of smoke escaping from the HVAC duct into a compartment not
served by the duct. As shown in Figure A.17.7.6.4.2.2(c), the top duct
does not need additional detectors and/or dampers where it passes
through either the center compartment or the right compartment.
(B)
Where total coverage smoke detection is installed in accordance
with 17.5.3.1 in all areas of the smoke compartment served by the
return air system, installation of additional detector(s) listed for the air
velocity present where the air leaves each smoke compartment, or in
the duct system before the air enters in the return air system shall not
be required, provided that their function is accomplished by the design
of the total coverage smoke detection system.
ENHANCED CONTENT
Collapse
17.7.6.5.1
Detectors shall be listed for the purpose for which they are being used.
ENHANCED CONTENT
Collapse
Not all smoke detectors are suitable for use as duct detectors. The
manufacturer’s listing should identify whether a detector can be used
in a duct. See also 17.7.6.5.7.
17.7.6.5.2*
Air duct detectors shall be installed in such a way as to obtain a
representative sample of the airstream.
17.7.6.5.3
This installation shall be permitted to be achieved by any of the
following methods:
• (1)
• (2)
Rigid mounting to the wall of the duct with the sensing element
protruding into the duct
• (3)
• (4)
17.7.6.5.5
The location of all detectors in air duct systems shall be permanently
and clearly identified and recorded.
ENHANCED CONTENT
Collapse
17.7.6.5.6
Detectors mounted outside of a duct that employs sampling tubes for
transporting smoke from inside the duct to the detector shall be
designed and installed to allow verification of airflow from the duct to
the detector.
17.7.6.5.7
Detectors shall be listed for operation over the complete range of air
velocities, temperature, and humidity expected at the detector when
the air-handling system is operating.
ENHANCED CONTENT
Collapse
The listing of the detector stipulates the range of air velocities over
which it can operate, as well as the temperature and the relative
humidity range. These last two criteria are particularly important where
a general purpose detector is being installed in a duct detector
housing. Given that HVAC system fans and ducts are often located in
areas where comfort heating and cooling are not provided, the
environment of the detector might exceed the limits observed in the
listing investigation. In addition, when warm moist air is circulated
through a cold duct smoke detector housing, condensation can occur
in that housing. These conditions can seriously degrade detector
performance and stability. Where these extremes are likely, the
operating environment of the detector must be maintained within its
operating range.
17.7.6.5.8
All penetrations of a return air duct in the vicinity of detectors installed
on or in an air duct shall be sealed to prevent entrance of outside air
and possible dilution or redirection of smoke within the duct.
17.7.6.6 Smoke Detectors for Door Release Service.
ENHANCED CONTENT
Collapse
Building and fire codes including NFPA 101 provide requirements for
means of egress. The means of egress is the way of travel from any
point in a building or structure to a public way; it consists of the exit
access, the exit, and the exit discharge. At times, exits might be
required to be separated from other parts of the building. Corridors
used as exit access may need to be separated from other parts of the
building by walls having a prescriptive fire resistance rating. Doors in
corridors might also be required to create smoke barriers to separate
smoke compartments.
Two general methods for controlling doors with smoke detectors are
available. The first involves using area smoke detectors to control the
doors for that area. Either smoke detectors served by a selected circuit
of an FACU or specific addressable detectors are programmed to
operate magnetic door release devices via the FACU. When one of the
area smoke detectors renders an alarm, the control unit transfers to
the alarm state and energizes the output circuit that controls the door
holders (see Exhibit 17.44). These detectors are located and spaced as
required by 17.7.4 and do not need to be installed within 5 ft (1.52 m)
of the door. The requirements for such a system are addressed in
Section 21.9.
EXHIBIT 17.44 Method for Controlling Door Holders with Area Smoke
Detector(s).
The second column graphically depicts the ceiling and the depth of
the wall section above the door for each scenario. The detector is
illustrated by an X in a rectangle and is a smoke detector specifically
listed for door frame mounting or as part of a listed combination or
integral detector–door closer assembly. A single integral detector–
door closer assembly is provided for a single door, or a matched set is
provided for a double door [one door is provided with a detector and
closer and the second door is provided with an identical (reversed
matching) housing but with a closer only]. The single detector controls
the door set (see Exhibit 17.46). When applicable, the integral
detector–door closer assembly is installed on the higher side (i.e., the
side with the greater dimension from the ceiling to the door opening) in
accordance with Part C of Figure 17.7.6.6.4.1(A).
The third column depicts detectors installed on both sides of the door,
on the wall section above the door, and on the ceiling. Again, the
detector is illustrated by an X in a rectangle. In Part B of Figure
17.7.6.6.4.1(A), one detector is depicted above the door on the left
side of the door and two detectors are depicted on the right side, one
above the door and one on the ceiling; note the word or between these
two detectors. One ceiling-mounted detector must be installed on
either side of the door or two wall-mounted detectors must be installed
with one above the door on each side of the door. The ceiling-mounted
detector is required to be installed within 5 ft (1.5 m) of the door. Part
D of Figure 17.7.6.6.4.1(A) is similar but if one chooses to install a
single ceiling-mounted detector, it must be installed on the side of the
door with the greater measurement from the ceiling to the clear
opening of the door. The ceiling-mounted detector is required to be
installed within 5 ft (1.5 m) of the door. If the installation chooses to
use wall-mounted detectors, one detector must be installed above the
door on each side of the door. In Part F of Figure 17.7.6.6.4.1(A),
because of the greater dimension from the ceiling to the clear opening
of the door, two detectors must always be used. Two wall-mounted
detectors would be installed above the door on each side of the door
or two ceiling-mounted detectors would be installed on the ceiling,
each within 5 ft (1.5 m) of the door.
17.7.6.6.1
Smoke detectors that are part of an open area protection system
covering the room, corridor, or enclosed space on each side of the
smoke door and that are located and spaced as required
by 17.7.4 shall be permitted to accomplish smoke door release
service.
ENHANCED CONTENT
Collapse
FAQ What location and spacing requirements apply when open area
smoke protection is used?
17.7.6.6.2
Smoke detectors that are used exclusively for smoke door release
service shall be located and spaced as required by 17.7.6.6.
ENHANCED CONTENT
Collapse
17.7.6.6.3
Where smoke door release is accomplished directly from the smoke
detector(s), the detector(s) shall be listed for releasing service.
17.7.6.6.4
The number of detectors required shall be determined in accordance
with 17.7.6.6.4.1 through 17.7.6.6.4.4.
ENHANCED CONTENT
Collapse
17.7.6.6.4.1
If doors are to be closed in response to smoke flowing in either
direction, the requirements
of 17.7.6.6.4.1(A) through 17.7.6.6.4.1(D) shall apply.
ENHANCED CONTENT
Collapse
(A)
If the depth of wall section above the door is 24 in. (610 mm) or less,
one ceiling-mounted smoke detector shall be required on one side of
the doorway only, or two wall-mounted detectors shall be required, one
on each side of the doorway. Figure 17.7.6.6.4.1(A), part A or B, shall
apply.
Figure 17.7.6.6.4.1(A) Detector Location Requirements for Wall
Sections.
ENHANCED CONTENT
Collapse
The depth of the wall section 24 in. (610 mm) or less above the door is
analogous to a deep beam (see 17.7.4.2.4) impeding the flow of
smoke across a ceiling. Smoke detectors used for door release are
permitted to be near the ceiling. Previously, these detectors would
have to be installed at a distance of 4 in. to 12 in. (100 mm to 300 mm)
below the ceiling to avoid placement in a dead air space. The 4 in. to
12 in. (100 mm to 300 mm) requirement was removed in the 2016
edition of the Code to be consistent with current smoke behavior
testing and knowledge and to correlate with 17.7.4.2.1.
(B)
If the depth of wall section above the door is greater than 24 in.
(610 mm) on one side only, one ceiling-mounted smoke detector shall
be required on the higher side of the doorway only, or one wall-
mounted detector shall be required on both sides of the
doorway. Figure 17.7.6.6.4.1(A), part D, shall apply.
ENHANCED CONTENT
Collapse
(C)*
If the depth of wall section above the door is greater than 24 in.
(610 mm) on both sides, two ceiling-mounted or wall-mounted
detectors shall be required, one on each side of the doorway. Figure
17.7.6.6.4.1(A), part F, shall apply.
ENHANCED CONTENT
Collapse
Since the average door height is a nominal 84 in. to 96 in. (2.1 m to 2.4
m), the addition of 60 in. (1.52 m) above the door results in a ceiling
height as high as 13 ft (3.9 m). The data in Annex B suggest that when
the ceiling height exceeds 10 ft (3 m), reduced spacing for heat
detectors is required if there is to be no reduction in performance due
to the higher ceilings. In the modeling of smoke detectors, a similar
logic is accepted. Thus, when the height above the door exceeds 60 in.
(1.52 m) on either side of the door opening, an engineering evaluation
might be warranted to determine if reduced smoke detector spacing is
appropriate for the specific application under consideration. The
engineering evaluation would be most appropriate where the door
closing is initiated only by detectors within 5 ft (1.52 m) of the door
openings. In cases where multiple devices are used for door closing
operation, as with systems with full corridor detection or closing
initiated by sprinkler waterflow in fully sprinklered buildings, the need
for such an engineering evaluation is generally not warranted.
(D)
If a detector is specifically listed for door frame mounting, or if a listed
combination or integral detector–door closer assembly is used, only
one detector shall be required if installed in the manner recommended
by the manufacturer's published instructions. Figure 17.7.6.6.4.1(A),
parts A, C, and E, shall apply.
17.7.6.6.4.2
If door release is intended to prevent smoke transmission from one
space to another in one direction only, detectors located in the space
to which smoke is to be confined, regardless of the depth of wall
section above the door, shall be in accordance with 17.7.6.6.5.
Alternatively, a smoke detector conforming with 17.7.6.6.4.1(D) shall
be permitted to be used.
ENHANCED CONTENT
Collapse
17.7.6.6.4.3
If there are multiple doorways, additional ceiling-mounted detectors
shall be required as specified
in 17.7.6.6.4.3(A) through 17.7.6.6.4.3(C).
(A)
If the separation between doorways exceeds 24 in. (610 mm), each
doorway shall be treated separately. Figure 17.7.6.6.4.3(A), part E,
shall apply.
Figure 17.7.6.6.4.3(A) Detector Location Requirements for Single and
Double Doors.
(B)
Each group of three or more doorway openings shall be treated
separately. Figure 17.7.6.6.4.3(B) shall apply.
Figure 17.7.6.6.4.3(B) Detector(s) Location ±24 in.(610 mm)
Requirements for Group Doorways.
ENHANCED CONTENT
Collapse
(C)
Each group of doorway openings that exceeds 20 ft (6.1 m) in width,
measured at its overall extremes, shall be treated separately. Figure
17.7.6.6.4.3(C) shall apply.
17.7.6.6.4.4
If there are multiple doorways and listed door frame–mounted
detectors, or if listed combination or integral detector–door closer
assemblies are used, there shall be one detector for each single or
double doorway.
17.7.6.6.5
The locations of detectors shall be determined in accordance
with 17.7.6.6.5.1 and 17.7.6.6.5.2.
17.7.6.6.5.1
If ceiling-mounted smoke detectors are to be installed on a smooth
ceiling for a single or double doorway, they shall be located as
follows [Figure 17.7.6.6.4.3(A) shall apply]:
• (1)
• (3)
17.7.7.1.2*
Holes in the back of a detector shall be covered by a gasket, sealant, or
equivalent means, and the detector shall be mounted so that airflow
from inside or around the housing does not prevent the entry of smoke
during a fire or test condition.
ENHANCED CONTENT
Collapse
The designer should be aware of any factor in the protected area that
could contribute to unwanted alarms or prevent the successful
conveyance of smoke to the detector, and then take steps consistent
with the manufacturer’s installation instructions to address those
factors.
The orientation of the fuel also creates vertical flues between the
combustibles that produce ideal conditions for the propagation of fire
and the worst possible conditions for extinguishment. Likewise, the
presence of solid shelving can create horizontal flues that materially
aid in horizontal fire spread. The shelves also tend to shield the fire
from water discharged by the automatic fire suppression sprinkler
system and hose streams intended to extinguish the fire. These
factors make early detection highly desirable so that rapid
extinguishment of the fire in the incipient stages is possible. It is
virtually impossible to extinguish the fire once it becomes well
established, as demonstrated by the catastrophic total losses that
have occurred in high-rack storage facilities.
ENHANCED CONTENT
Collapse
Usually, high air movement areas are characterized by six or more air
changes per hour. The most regularly encountered example of a high
air movement area is the data center (i.e., computer room). Because of
the very high concentration of value in a data center, reducing the
spacing of spot-type smoke detectors is common. This spacing can be
derived from Table 17.7.7.3.3.2 and Figure 17.7.7.3.3.2. In some cases,
an authority having jurisdiction, such as an insurance carrier, will
establish a spacing criterion for such locations.
FAQ What are the requirements that apply to smoke detection in under-
floor or above-ceiling spaces used for environmental air?
Closer Look
High air movement areas might not necessarily mean high air velocity
at the detector or detection location. Airflow patterns at the detector
locations should be measured and recorded in the system
documentation.
The velocity of the air stream from supply registers supplying high air
movement areas is likely to exceed 300 ft/min (1.5 m/sec), which is
the maximum for which most detectors are listed.
(See 17.7.1.8 and 17.7.1.9.) When detectors are tested for a listing
that includes high airflow environments, they are tested to ensure they
do not render a false alarm in high airflow conditions. No test verifies
that they will detect fires as quickly as they would in a non–high
airflow condition. The designer should take into consideration any
potential effects of high air velocity at the detector location on the
ability of the detector to sense smoke from the fires it is intended to
detect, as well as the effect the air velocity might have on the detector
stability and maintenance needs.
17.7.7.3.3.3
Air sampling or projected beam smoke detectors shall be installed in
accordance with the manufacturer’s published instructions.
17.7.7.3.4 HVAC Mechanical Rooms.
Where HVAC mechanical rooms are used as an air plenum for return
air, the spacings of smoke detectors shall not be required to be
reduced based on the number of air changes.
ENHANCED CONTENT
Collapse
17.7.8.2
Video image smoke detection systems shall comply with all of the
applicable requirements of Chapters 1, 10, 14, 17, and 23 of this Code.
ENHANCED CONTENT
Collapse
17.7.8.2.1
Systems shall be designed in accordance with the performance-based
design requirements of Section 17.3.
ENHANCED CONTENT
Collapse
Because prescriptive design criteria have not been developed for video
image smoke detection, each video image smoke detection system
should be designed with complete documentation — including the
basis of the design, calculations demonstrating the capability of
detecting the design fire over the entire volume covered by the system,
and reliability calculations demonstrating that the system will be
adequately reliable over the maintenance interval for the system.
Section B.2 provides guidance on the performance-based design
method. Also see the commentary following Section 17.3.
17.7.8.2.2
The location and spacing of video image smoke detectors shall
comply with the requirements of 17.11.5.
ENHANCED CONTENT
Collapse
17.7.8.3*
Video signals generated by cameras that are components of video
image smoke detection systems shall be permitted to be transmitted
to other systems for other uses only through output connections
provided specifically for that purpose by the video system
manufacturer.
ENHANCED CONTENT
Collapse
FAQ What types of applications are suitable for video image detection
systems?
Video image smoke detection systems are best suited for large open
spaces with high-value assets that warrant such protection. In many
cases, the facility security system includes cameras to monitor the
space during unoccupied periods to maintain surveillance. There is
little basis for two sets of cameras, one for smoke detection and a
second for surveillance. The video signal may be shared if the
equipment and the software that allow the sharing are listed for the
purpose and the security system does not interfere with the fire safety
use of the signal.
17.7.8.4*
All component controls and software shall be protected from
unauthorized changes.
ENHANCED CONTENT
Collapse