01-04-2025 Vslc Wh4 Incom Cost Boq Rev0
01-04-2025 Vslc Wh4 Incom Cost Boq Rev0
S.NO DESCRIPTION
SUPPLY
1 CIVIL AND INTERIOR WORKS 31,380,950
2 FIRE HYDRANT SYSTEM 231,592
3 SPRINKLER SYSTEM 956,980
4 FIRE DETECTION AND ALARM SYSTEM AND PA 1,808,680
5 FIRE EXTINGUISHERS 108,300
6 SIGNAGES 12,600
7 COMPRESSED AIR SYSTEM 283,018
8 COMPRESSOR AND ACESSORIES WITH PIPING 1,500,000
9 GRIPPLE SUPPORTS FOR PIPING WORKS 500,000
10 PLUMBING WORKS 200,000
11 OPEX WORKS FOR FIRE AND MECH SYSTEM
12 TOTAL FOR11KV HT INFRASTRUCTURE WORKS 7,330,000
13 TOTAL FOR POWER WORKS 7,174,588
TOTAL FOR INTERNAL & EXTERNAL LIGHTING
14 962,638
WORKS
15 TOTAL FOR OPEX ELECTRICAL WORKS
16 IT WORKS ( PASSIVE COMPONENTS ONLY ) 1,122,843
17 CCTV WORKS 787,000
18 PRODUCTION BLOCK - HVAC SYSTEM AND ASSOCIA 5,521,436
19 OFFICE BLOCK - HVAC SYSTEM AND ASSOCIATED 1,323,275
20 DESIGN ENGINEERING SERVICES FEES
Remarks
INSTALLATION
61,342
278,850
151,019
2,900
260
51,220
150,000
50,000
50,000
500,000
2,762,450
1,129,315
84,578
140,125
197,451
184,900
724,970
178,500
1,950,000
8,647,880
1,556,618 GST AS APPLICABLE ON ITEM BASIS
10,204,498
82,425,100
AEDBM CONSULTANTS PRIVATE LIMITED
ESTIMATION SHEET
CLIENT : VALUE SPACES LOGISTICS PRIVATE LIMITED
PROJECT: PROPOSED VALUE SPACES LOGISTICS & INDUSTRIAL PARK POLIVAKKAM PVT LTD
CO-ORDINATOR :
ESTIMATOR :
TITLE / BUILDING NAME : WAREHOUSE 4
i From NGL to 1.5m in All kinds of soil including murrum, soft rock, weathered rock / highly
weathered rock, etc.. Cum 68 450 30,600.00
0
2 PLAIN CEMENT CONCRETE & PLUM CONCRETE 0
Providing and laying Plain Cement Concrete 1:3:6 (1 cement : 3 coarse sand :6 graded
stone aggregate 20mm nominal size) including necessary shuttering in leveling courses
under foundations, pipelines, pits, under floors etc., complete at all levels and locations as
Cum 5 5,800 29,000.00
directed by Engineer Incharge .
0
3 BRICK WORKS 0
Providing brick work using M-.35 grade bricks( with minimum compressive strength of 35kg/sq.
cm) in cement mortar 1:6 (1 cement : 6 coarse sand) in superstructure at all heights and locations Cum 21 8,500 178,500.00
including scaffolding, staging, curing etc., complete.
0
Providing brick work of half brick thickness using M - 35 grade bricks in Cement Mortar 1:4 (1
cement : 4 coarse sand) , proportions in walls at all heights as per specifications including
scaffolding, curing and providing RCC band of size 100 x 80mm with 2 Nos. of 6mm dia MS Bars Sqm 27 1,200 32,400.00
at every 1mtr interval etc., including the cost of MS reinforced steel. Complete at levels and
locations and as directed by engineer in charge
0
4 REINFORCED CEMENT CONCRETE 0
Providing and laying in position M-25 Grade Reinforced Cement Concrete machine
batched, machine mixed, and machine vibrated design mix cement concrete of specified
grade with Minimum Cement Content of 325 Kg Per Cum of concrete and water cement
ratio not more than 0.5 for reinforced cement concrete structural elements including the
cost of centering, shuttering finishing and excluding reinforcement, including adding
admixtures in recommended proportion ( as per IS 9103 ) to accelerate, retard setting of
concrete improve workability without impairing strength and durability, and necessary
curing etc.,complete all as directed at all levels and heights .
The designing of concrete mix for different grades of controlled concrete should be done
in accordance with latest IS 456 and SP-23 and other codes mentioned in the specs.
( Hand book on concrete mix design ) in an approved lab and the same should be got
approved by Consultant. ( Note 1 : The use of Fly Ash / GGBS are allowed in RMC. Notes
2 : Minimum cement content to be provided as per technical specifications OR as per IS :
456-2000. Note 3 : No separate measurement will be considered for Wastage and the
contractor has to include the same in his rates. )
M-25 grade Reinforced Cement Concrete. All works below and above plinth level.
i RCC for Footing, Raft Cum 15 8,500 127,500.00
ii RCC for Pedestal Cum 6 11,500 69,000.00
iii RCC for Wall Cum 13 12,500 162,500.00
0
5 REINFORCEMENT STEEL 0
Providing , fabricating & fixing in position reinforcement for RCC work with Thermo
mechanically Treated (TMT) bar of various diameters and grade of steel as specified
below conforming to IS specification including cutting, bending, hoisting, fabricating and
placing in position according to drawings and binding the reinforcement with MS binding
wire in two strands of 18 gauge and providing M25 Grade Cement cover blocks for
placing the reinforcements in position and for maintaining the cover specified and/or
according to relevant IS. Note : Unless noted otherwise the measurements in
accordance with IS 1200. However reinforcement shall be measured only in lengths of
bars as actually placed in position on standard weight basis, no allowance being made in
the weight for rolling margin. Authorised laps and splices, chairs of any shape & profile,
Spacer bar of any shape & profile only will be measured and paid seperately. Cover block,
wastage and binding wire shall be included in the quoted rate and to include lead, lift,
placing at all levels and as per the approved bar bending schedule,etc., complete all as
directed.
a a) TMT bars of grade Fe-500 conforming to IS - 1786/85 Mtn 5 90,000 450,000.00
0
6 SHUTTERING WORKS 0
Providing and erecting in position form work shuttering & boxing using steel / plywood /
props / bracing / scaffolding / ledges and other shuttering materials of approved quality for
concrete elements vertical, horizontal or inclined etc. in all shapes (except circular and
curvilinear) as per drawing including necessary scaffolding, bolts/nuts, fastener nails,
wires for keeping in position till concrete is laid and members have acquired required
strength, removal thereafter, applying shuttering oil, hacking etc. in line, level and plumb,
all complete as per specification or as directed. At all levels, heights & depths for all
concrete elements of linear shape, size & direction etc.
5.B
Supplying and Grouting of Pockets in-between the foundation top and Base Plate ,inside
the concrete structures using Conbextra GP2 of M/s Fosroc Chemicals or approved
equivalent including making arrangements to fix the MS framework , MS bolts , inserts,
etc to required line ,level and position & cleaning the pockets & surface using water to Cum 0.25 68,000 17,000.00
make it free from dirt and dust ,pouring the ready mixed grout in the locations as per
manufacturers detail specifications including curing at all levels and locations etc.,
complete all as directed.
5.C Removing of Existing P.C.C /RCC including disposing out debris as directed by Engineer
incharge
Cum 5 4,000 20,000.00
7 FALSE CEILING WORK 0
False Ceiling - Providing and Fixing Armstrong or approved equivalent ceiling in
600x600x15 mm silhouette suspension system (white) with acoustic mineral fibre board
perforated in true horizontal level suspended on inter locking metal grid of hot dipped
galvanized steel sections (galvanizing @ 120 grams per M2 including both side)
consisting of main 'T' runner suitably spaced at joints to get required length and of size 24
X 38mm made from 0.33 mm thick (minimum) sheet, spaced 1200mm centre to centre,
and cross "T" of size 24x28mm made out of 0.33mm (Minimum) sheet, 1200mm long
spaced between main 'T' at 600mm centre to centre to foMeter a grid of 1200 X 600mm
and secondary cross 'T' of length 600mm and size 24 X 28mm made of 0.33mm thick
(Minimum) sheet to be inter locked at middle of the 1200 X 600mm panel to from grid of
size 600 X 600mm, resting on periphery walls/ partitions on a Perimeter wall angle
deprecated steel of size of 24X 24X 3000 mm made of 0.40 mm thick (minimum) sheet Sqm 1980 2,150 4,257,000.00
with the help of raw plugs at 450mm centre to centre with 25mm long dry wall screws @
230mm interval and laying 18mm thick sheets of mineral fiber Dune max in the grid
including, cutting/ making opening for services like diffuser, grills, light fittings, fixtures,
smoke detectors etc., wherever required, Main 'T' runners to be suspended from ceiling
using G.I. slotted cleats of size 25X35X1.6mm fixed to ceiling with 12.5 mm dia and 50mm
long dash fasteners. Incuding drop as per requirement.
0
8 FLOORING WORKS 0
8.01 Providing and laying 1st quality Vitrified / Ceramic tile flooring of 10mm thickness,
conforming to IS:15622 of approved make, color and uniform shade of size , with water
absorption less than 0.08%, to required slope, set on 40mm thick cement mortar 1:4,
including fixing of tiles with cement slurry at 4.4kg/sqm and pointing the tile joints with
approved quality and colour pigmented cement to match the shade of tiles, oxalic acid
washing, , giving necessary slopes, etc., The rate shall include for cost of providing and
laying patterns, borders, inlays, cost of materials, wastages, labour, tools & plants, loading Sqm 255 1,950 497,250.00
and unloading charges, transportation, curing, protection of finished surface curing,
cleaning the area with water or water with mild acid, all other incidental charges, etc.,
complete with all leads and lifts as per specifications and drawings at all levels and as
per the instructions of Engineer in Charge.
0
8.02 Providing and laying 1st quality Anti-skid Vitrified / Ceramic tile flooring of 10mm
thickness, conforming to IS:15622 of approved make, color and uniform shade of size
600mm x 600mm , with water absorption less than 0.08%, to required slope, set on
40mm thick cement mortar 1:4, including fixing of tiles with cement slurry at 4.4kg/sqm
and pointing the tile joints with approved quality and colour pigmented cement to match
the shade of tiles, oxalic acid washing, , giving necessary slopes, etc., The rate shall
include for cost of providing and laying patterns, borders, inlays, cost of materials,
Sqm 45 1,850 83,250.00
wastages, labour, tools & plants, loading and unloading charges, transportation, curing,
protection of finished surface curing, cleaning the area with water or water with mild acid,
all other incidental charges, etc., complete with all leads and lifts as per specifications
and drawings at all levels and as per the instructions of Engineer in Charge.
0
8.03 Providing and fixing with 5 mm to 6 mm thick Glazed Ceramic Tiles of Size 300 x 450
mm of approved shade with border tile and make over and including 12 mm thick cement
plaster 1:3 (1 cement : 3 coarse sand) and jointed with grey cement slurry @ 3.30 Kg / Sqm 150 1,250 187,500.00
Sqm including pointing in white cement mixed with matching pigment in Dado etc., all
complete
0
8.04 PU FLOORING WORKS 0
Floor Treatment on Concrete surface - 6mm Thick -
Preparing & Cleaning the existing RCC Floor Surface by Diamond Grinding so as to
obtain a sound Surface. Preparation inludes groove cutting , scarification with scarifier and
cleaning the surface with Industrial vaccum to avoid dust accumulation in the room.
Applying High Build Solvent less Primer, on curing laying 2mm thick Stonclad GS / Pidilite
scratch coat, followed by Grinding and further topping with 3mm coat of High Build 100% sqm 1680 3,500 5,880,000.00
SolidS Stonkote HT4 / Pidilite final coat to provide non porous surface for better Abrasion
Resistance of approved shade . And the remaining 500 microns ( 0.5 mm) roller coat to be
done after positioning the machines to give proper finish. Colour code will be given by
client.
0
9 WATER-PROOFING WORK 0
9.01 Providing and laying Waterproofing for the Lift Pit,Surface preparation : Preparing the
surface to remove all loose matter, minor repair, honeycombed area and treat construction
joints with non-shrink fibre reinforced mortar with MasterBrace S 348. even out all
unevenness such as blowholes, pin holes and other surface defects with MasterBrace
ADH 2200.
Waterproof coating: Providing mixing and applying MasterSeal
551-IN of make MBS or equivavlent, a two component acrylic reinforced cementitious
waterproof coating, is supplied in premeasured units and should be mixed on site utilising
clean containers. Slowly add the powder to the liquid and mix, using a slow speed
(300rpm) drill fitted with a suitable paddle and applied on the prepared surface in two
coats at an interval of 4 to 8 hours between coats, depending on the climatic conditions,
applied at a total consumption of 3.6 kg / m² at 2 mm thickness(1.8kg/sq.m/mm) and
allowed to cure. The second coat shall be sprinkled / Broadcast with sand while in tacky
state to provide bond, all complete as per the instruction of manufacturer and as directed
by the engineer incharge.
0
10 STRUCTURAL STEEL WORKS 0
10.01 Supplying, fabricating, hoisting and erecting in position Mild steel structural steel works
(Make : Jindal / TATA) (for items mentioned below) at all elevations, levels and heights
including aligning, leveling, providing and fixing (Approved- TVS /Enbrako) HT bolts, nuts,
washers, comprising MS angles, channels, joists, rails, tees, plates, rounds, squares, etc.,
of 250 /310 Mpa Yield strength of various sizes and other structural steel sections
conforming to latest IS CODE Grade - A & B including straightening, cutting, welding
(6013-ESAB, ADORE ) bending to shape, bolting, cleaning the rust and scales to the
Mtn 58 125,000 7,250,000.00
satisfaction of Architect and inclusive of following finishes. Applying two coats of Synthetic
Enamel paint over two coats of Zinc Chromate primer of approved make and colour
before erection only touchup paint wherever needed to be done after erection . The rate to
include the cost of all materials, labours, tools, tackles, cranes, devices and plants as per
specifications and drawing complete.
13.02 Pedestal
Suppplying of 3 Drawer mobile pedestal: Material 18mm thick Prelaminated
particle board with 2mm PVC Edge banding on all exposed ares, with handles,
centralised lock, bottom mounting slides for drawer and 4 nos of heavy duty Each 24 8,000 192,000.00
castors. Size : 400 x 450 x 650 ht.
14 MISCELLANEOUS WORK
14.2 Providing and fixing of dock leveler HLS2 of 15T UDL (Uniformly distributed Each 1.00 600,000.00 600,000.00
load), as
Dock per EN:Dynamic load shall be 6T. Platform surface (S-235) of the dock
leveller 0.00 0.00
leveler shall
Operator & be minimum
Motor: 6mm
Electro-hydraulic operator with a Motor power 0.75 kW and 0.00 0.00
Connectingaccessories:
Standard voltage 3-phaseDock 400 V, pair
buffer 50 should
Hz. Protection category
be included IP 54.
to protect the Provide
leveller 0.00 0.00
Connecting
from theSteel
Finish: cable
hit of truck7.5 m
while
surfaces long.
backin2The
blasted control
coat, unit shall
PU-coated beofplaced
(layer 60 - 80next to the
micron) in dock
RAL 0.00 0.00
leveler-Ultramarine
5002 with membraneblue. push button integrated in housing. Press-andhold
14.3 Supply and installation of Hydro lift for G+1 stops - 250kgs /4 pax capacity Each 1.00 1,200,000.00 1,200,000.00
80mm nominal dia(gear operated Type) Nos 2 18,500.00 1,000.00 37,000.00 2,000.00
Supplying and fixing approved make 25mm dia. automatic Pressure release valve ,
6 Nos 2,500.00 1,000.00 - -
unions & other associated works & accessories etc. complete.
Supply, erection, testing & commissioning of electrical motor driven Booster gland
packing pump of Mono block type capable to deliver 450 LPM at 35mtrs
Head(1W+1S).The pump shall be coupled to TEFC motor of suitable HPand RPM and
complete set shall mounted on common base frame. The quoted rate shall includes
providing MS pipe heavy grade -interconnecting piping- suction from 5kl Fire tank to
11 outlet manifold with High & low Levelsensor 1 set, PN 16 Rating for matching flanges, Set 195,000.00 5,000.00 - -
Y'Strainer, NRV, suction & delivery side butterfly valves, pressure switch,pressure
guage ,outdoor type Controle panel locally remot controled,incoming , outgoing and
power Cabling,fromand to Panel to Booster pumps ,MCB,feeder,ON/OF control
switches,etc with associated works & accessories & ,The Size of pipes & Fittings as per
Pump GA Drawing .
Supplying fixinf testing and commissioning of Pressure switches assembly on header for
12 pressuring sencing, the cost shall be included with Approx 100mtrs length of cable for Nos 15,000.00 1,000.00 - -
making connection to Fire Panel.
Supplying, laying, testing & commissioning of XLPE , steel armored, aluminum/ copper
conductor, 1100v grade power cables with terminations (including double compression
brass glands & copper lugs at both ends) etc. The cables shall be laid in tray / on walls/ - -
13 floor etc. as required. The rate shall excludes tray. The minimum size of the cables shall
as mentioned below, asper IS 7098 code
4C x 10 Sqmm.A2XYFY Cable Mtr 600.00 50.00 - -
12 C x 2.5 Sqm YWY Cable Mtr 500.00 50.00 - -
2 C x 2.5 Sqmm. No 140.00 50.00 - -
CABLE TRAY - -
Supplying and fixing of perforated G.I.sheet cable tray as per IS with necessary angle
iron suspension supports, anchor fasteners etc. complete. Maximum height of
- -
14 suspension shall not exceed 500 mm.Size of the tray shall be suitable for laying the
above mentioned cables.
300x50 mm wide with 2runs of 25x6 mm GI strip and tray cover . Mtr 3,000.00 150.00 - -
50x50 mm wide with 2runs of 25x3 mm GI strip and tray cover . Mtr 700.00 100.00 - -
Supplying and fixing approved make 25mm dia. automatic air release valve , unions &
15 Nos 0 3,500.00 100.00 - -
other associated works & accessories etc. complete.
G.I. Earthing strips of 50mm x 6mm thick, strip shall be run on floor / ceiling / walls, from
the equipment to the nearest Earth pit with necessary accessories as required. ( Earth 300.00 100.00 - -
pit shall be executed by other agencies).
16
300mm long , 40x6 mm GI Flat on SMC/DMC insulator with M12 hole @ 50mm intervals
Mtr 300.00 100.00 - -
along with front acrylic cover protection .
1 Core x 16 Sqm YY Cable- green color . Mtr 400.00 100.00 - -
II SPRINKLER SYSTEM
Supply, fixing and commissioning of installation control valve / Sprinkler Alarm Valve
consisting of :-
a) 1 No. alarm valve.
b) 2 No. main stop valve.
1
c) 1 No. water meter with alarm gong.
d) Pressure gauge drain valve and drain piping etc., as per specification.
1)200 mm dia set 90000 4000 - -
2)150 mm dia set 75000 3000 - -
ABOVE GROUND PIPING WORKS
250 mm nominal dia (Header from Pump room To building ) Mtr 4620 1000 - -
250 mm nominal dia (Inside the Building) Mtr 4620 1000 - -
200 mm nominal dia (Inside the Building) Mtr 3688 800 - -
150 mm nominal dia (Inside the Building) Mtr 2460 600 - -
125 mm nominal dia (Inside the Building) Mtr 2068 500 - -
100 mm nominal dia (Inside the Building) Mtr 1776 400 - -
100 mm nominal dia (Outside the Building) Mtr 1776 400 - -
80 mm nominal dia (Inside the Building) Mtr 1148 300 - -
Excavating trenches of required width for pipes etc. in ordinary soil, hard/soft rock,
disintegrated rock which can be removed by wedging chiselling, controlled blasting for
pipes including excavation for sockets and dressing of sides, ramming of bottom depth
up to 1.0Mtr including getting out the excavated soil and then returning the soil as - -
required in layers not exceeding 20 cms in depth including consolidating each deposited
3 layer by ramming, watering, etc., and disposing of surplus excavated soil as directed
within a lead of 750 mtr (pipe dia. not exceeding 300mm).
a) 20 mm dia. (for sprinkler connection with branch pipe) Mtr 220 100 - -
b) 25 mm dia. (+ Test pipe) Mtr 230 344 100 79,120.00 23,000.00
c) 32 mm dia. Mtr 75 444 150 33,300.00 11,250.00
d) 40 mm dia. Mtr 124 510 100 63,240.00 12,400.00
g) 50 mm dia.(+ drain pipe) Mtr 126 770 100 97,020.00 12,600.00
h) 65mm dia Mtr 45 920 100 41,400.00 4,500.00
i) 80mm dia Mtr 15 1148 100 17,220.00 1,500.00
i) 100mm dia Mtr 30 1776 400 53,280.00 12,000.00
i) 150mm dia Mtr 24 2460 600 59,040.00 14,400.00
Supplying, Installing, testing and commissioning CI butterfly valves as per BS 5155 (PN
16) slim seal standard Gear valve type with required flanges, nuts, bolts etc. complete. - -
The quoted rate should be included with locking arrangement assembly.
5 250 mm nominal dia (lever operated Type) Nos 67000 2000 - -
200 mm nominal dia (lever operated Type) Nos 36650 1500 - -
150 mm nominal dia ( Lever operated Type) Nos 16610 1000 - -
80 mm nominal dia(lever operated Type) Nos - -
Supplying, Installing, testing and commissioning CI butterfly valves as per BS 5155 (PN
16) slim seal standard Gear valve type with required flanges, nuts, bolts etc. complete. - -
The quoted rate should be included with locking arrangement assembly.
250mm nominal dia(gear operated Type) Nos. 92265 2500 - -
6 200mm Nominal Dia(gear operate Type) Nos. 77000 2000 - -
150 mm nominal dia (lever operated Type) Nos. 1 45650 1500 45,650.00 1,500.00
100 mm nominal dia (lever operated Type) Nos. 18500 1000 - -
80 mm nominal dia (lever operated Type) Nos. 1 16610 1000 16,610.00 1,000.00
65 mm nominal dia (lever operated Type) Nos. 1 14500 1000 14,500.00 1,000.00
Supply and fix ball valve(PN16) of approved make with screwed end(inspector test
- -
7 connection) & connected associated works & accessories etc. Complete.
a) 25 mm dia. Nos. 1 9500 1000 9,500.00 1,000.00
Supply and fix ball valve(PN16) of approved make with screwed end(For Flushing
- -
8 connection) & connected associated works & accessories etc. Complete.
a) 50 mm dia. Nos. 1 15000 1000 15,000.00 1,000.00
Supply, Installation, Testing & commissioning of Sprinklers with connected associated
- -
works & accessories etc., complete.
K-80, Temp-68 Deg.C, Standard Response Pendent Type Sprinkler Nos. 124 650 50 80,600.00 6,200.00
9
K-115, Temp-68 Deg.C, Standard Response Upright Type Sprinkler Nos. 950 50 - -
K-115, Temp-68 Deg.C, Standard Response Pendent Type Sprinkler Nos. 950 50 - -
K-320, Temp-68 Deg.C, ESFR Upright Type Sprinkler Nos. 3950 50 - -
Supply, Installation, Testing & commissioning of Sprinklers with connected associated
- -
works & accessories etc., complete. For Spare
K-80, Temp-68 Deg.C, Standard Response Pendent Type Sprinkler Nos. 10 650 50 6,500.00 500.00
10
K-115, Temp-68 Deg.C, Standard Response Upright Type Sprinkler Nos. 950 50 - -
K-115, Temp-68 Deg.C, Standard Response Pendent Type Sprinkler Nos. 950 50 - -
K-320, Temp-68 Deg.C, ESFR Upright Type Sprinkler Nos. 3950 50 - -
Supply, install, testing & commissioning of FM approved -SS Flexible sprinkler braided
. hose assembly of 1” NPT x 3/4” x 1,000 mm length, straight outlet, braided , seal, ms Nos. 2500 50 - -
supports bracket & connected associated works & accessories etc. Complete.
Supplying and fixing approved make 25mm dia. automatic Pressure release valve ,
13 Nos. 4500 1000 - -
unions & other associated works & accessories etc. complete.
Supply, fabrication and fixing of Pipe Supports in GI Box type., as per
drawings/instructions at site. Rate quoted shall include for supply and providing
14 necessary welding, cutting "U" clamps, bolts, horse shoe supports, nuts, washers as per Kgs. 2500 130 70 325,000.00 175,000.00
specified for completing the job and also giving a two coat of primer and two coats of
approved epoxy paint.
Supply , Install, testing and commissioning of flow switch on the sprinklers line of
15 approved type and make capable of sending impulses to annunciation panel. Cost shall Nos. 8000 1000 - -
be included with approx. 300mtrs length of cable to connecting the panel.
Supplying, installing, testing and commissioning of flexible braided pipe supports which
17 Nos. - -
are UL approved
Excavation width-1m & depth-1m,Providing, Laying. Testing & Commissioning NP2
class RCC hume pipes conforming to IS: 458 with suitable collars filling the recess at
joints of pipes with hemp dipped in hot bitumen or other suitable compound for caulking - -
18 of joint by jack, setting up of loose space over the collar joints chaulked with CM 1:2,
finished both ends to a slope of 1:1 including curing, testing of pipes, etc., complete.
450 mm dia-Deleted Rmt. 2200 750 - -
300 mm dia-Deleted Rmt. 1200 500 - -
Supplying, installing, testing and commissioning Electronic Hooter cum strobe with
3 converter 230 AC to to 24V DC and dual tone type with control module and wiring Nos. 2 3294 313 6,588.00 626.00
circuit, with powder coated finish of approved color.( HONEY WELL MAKE)
Supplying, installing, testing and commissioning approved make Addressable
Multisensor (Smoke + Heat ) Detector. The detector shall have four sensing elements
4 viz. Photo electric smoke, Heat combined in a single detector. The detector shall have Nos. 174 2850 100 495,900.00 17,400.00
twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary
decimal switches with UL listed & & FM approved. ( NOTIFIRE MAKE) .
Supply, installing, testing & commissioning ofCONVENTIONAL TYPE Heat detector
rated at 8.3 deg C/min. The detector shall have twin bi-colour LED for 360 deg viewing.
5 Addressing shall be with user friendly rotary decimal switches. UL and FM approved Nos. 2 2950 200 5,900.00 400.00
with Junction box and other associated works & accessories etc. Complete. ( NOTIFIRE
MAKE)
Supply, installing, testing & commissioning of CONVENTIONAL TYPE PROBE TYPE
OF Heat detector rated at 8.3 deg C/min. The detector shall have twin bi-colour LED
5a for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. UL Nos. 3,478.00 420.00 - -
and FM approved with Junction box and other associated works & accessories etc.
Complete. ( NOTIFIRE MAKE)
Supply, installation, testing and commissioning of Fault Isolator Module .Isolator Base
can also be proposed, however in that case needs to be considered with each detector &
module. The device shall have an LED which shall blink in normal state & get steady on
8 Nos. 4945 200 - -
activation to monitor the heath status of the device. Module shall be supplied with
mounting plate from OEM for ease of installation & maintenance. Modukle should be
with UL and FM approved ( NOTIFIRE MAKE)
Supplying, installing, testing and commissioning approved make CONVENTIONAL TYPE
Loop Powered Autoaligned Beam Detector with reciver. The beam detector shall be
used for High Ceiling application with a detection range from 5 upto 100 mtrs and highly
resistant to building movement; tolerates +/- 1° movement, Resistant to solid object
9 Nos. 0 9373 1800 - -
intrusion, , Built-in imager heater, Resistant to strong light sources; does not alarm when
saturated by sunlight, Automatic sensitivity threshold level settings and drift
compensation. The detector shall be IP-55 compliant. UL Listed & FM approved. (HONEY
WELL MAKE)
Supply, Installation, Testing and Commissioning of 24V DC,3 AMPS SMPS for power
11 Nos. 7500 200 - -
supply to Devices.
Supply, Installation, Testing and Commissioning Control module with converter 230
AC to to 24V DC for activating the notification devices. Shall the supervisory facility
auxiliary power supply as well as the notification appliances circuit. The quoted rate
shall have the LED indication for normal working and active modes.The control module
12 shall provide supervised NAC output rated at 24v DC, 2A. The device shall have an LED Nos. 4945 200 - -
which shall blink in normal state & get steady on activation to monitor the heath status
of the device. Addressing shall be with user friendly rotary decimal switches. Module
shall be supplied with mounting plate from OEM for ease of installation & maintenance.
UL and FM approved (NOTIFIRE MAKE)
Supply, Installation, Testing and Commissioning of Relay Module with converter 230 AC
to to 24V DC for AHU, Access Control, Lifts, Fire Suppression & other Third Party
Outputs. The relay module shall provide contact rated at 24v DC, 2A. The device shall
13 have an LED which shall blink in normal state & get steady on activation to monitor the Nos. 4945 200 - -
heath status of the device. Addressing shall be with user friendly rotary decimal
switches. Module shall be supplied with mounting plate from OEM for ease of installation
& maintenance.UL and FM approved (NOTIFIRE MAKE)
Supplying, laying, testing and commissioning of communication loop cable 2CX 1.5
15 Rmt 1800 80 20 144,000.00 36,000.00
sq.mm copper armored cable with PVC insulated Cable shall be as per IS : 1554.
Supplying, laying, testing and commissioning of loop cable 3CX 1.5 sq.mm copper
16 armoured cable. Cable shall be as per IS : 1554. for Power supply for Hoter, Beam Rmt 600 80 20 48,000.00 12,000.00
detectors, manul call points, Siren etc
Supply, Installation, Testing and Commissioning of 2.5 Km range Siren with Weather
proof motor with 220V 50HZ AC Supply operation with required power contractor, MPCB
17 Nos. 6500 500 - -
for control all in a weather proof enclosure near motor including all installation materials
as required.
Supplying, laying, testing and commissioning of power cable for .2 runs of 1.5 sq.mm
18 cross section PVC insulated copper armoured cable, cable shall be as per IS : 1554. FOR Rmt 600 80 20 48,000.00 12,000.00
HOOTER laying, testing and commissioning of power cable for Hooter 3 runs of 2.5
Supplying,
19 sq.mm cross section PVC insulated copper armoured cable, cable shall be as per IS : Rmt 170 60 - -
1554. for Siren
Supplying, laying, testing and commissioning of communication cable 2CX 1.5 sq.mm
19A copper armored cable with PVC insulated Cable shall be as per IS : 1554. From FACP To Rmt 0 90 60 - -
RP
Supply and fixing of 16SWG SS conduit Inside the process area concealed/Surface in
20 wall/ceiling/above false ceiling including painting with 2 coats of Red color paint for - -
exposed part and all fixing accessories materials
a).32 mm dia, 16G SS conduit Rmt 320 60 - -
b).25 mm dia, 16G SS conduit Rmt 210 60 - -
c).20mm dia, 16G SS conduit Rmt - -
Supply and fixing of 16SWG GI conduit concealed/Surface in wall/ceiling/above false
21 ceiling including painting with 2 coats of Red color paint for exposed part and all fixing - -
accessories materials
a).32 mm dia, 16G GI conduit Rmt 80 320 60 25,600.00 4,800.00
b).25 mm dia, 16G GI conduit Rmt 210 60 - -
c).20mm dia, 16G GI conduit Rmt - -
Supply testing and commissioning of Linear Heat Sensing Cable with sensors which
consist of Effective monitoring at precise point of risk, Economical, reliable and durable
22 detection of temp Environmental -65oC to +88°C for cable tray As an integral part of a Nos. - -
fire protection system, Alarm line Digital cable may be used as a conventional detector
and operate by connecting to the fire alarm panel.
Repeater Control Panel ( RC ) - -
(Note: master slave/Master router controller concept not accepted to avoid single point
failure). No of controller to be quoted as per BOQ.
PAGING STATION
SITC of IP based 7 inch Networkable touch screen paging station for selection of zones,
supervision of system status, setting of scheduled broadcasts with the following
functions
25 Nos 1 135,865.00 10,000.00 135,865.00 10,000.00
Built-in monitoring loudspeaker
Detachable goose-neck microphone
LCD touchscreen display
Upto 2000 zones
DIGITAL AMPLIFIERS
SITC of 1X500W Class-D Amplifier with 2 speaker circuits with 1 channel and can provide
27 automatic re-settable overcurrent, overload, overheating, overvoltage, under-voltage Nos 1 75,000.00 3,125.00 75,000.00 3,125.00
and DC protection and High Efficiency Class D Power Amplifier, 2x500W, 100V/70
Output, with 100 - 240 VAC input and 24 VDC backup power Supply
Supply, laying, Testing and Commissioning 2C x 1.5 mm2, Stranded Copper conductor,
Type A ST1 PVC insulated,Armoured FRLS Cable 650 V as per IS 1554, with GI saddle
28 Rmt. 700 80.00 42.00 56,000.00 29,400.00
spacers every 0.3 mtr with Single compression Cable Glands, ABS Junction Boxes
(wherever required), terminals, Ferruling complete. (Make: Honeywell)
Supply, Installation, Testing and Commissioning of Volume controller for one speaker
29 Nos 1 2,760.00 188.00 2,760.00 188.00
(inside the BMS room & other specified areas)(Make: Honeywell)
Supply, installing, testing and commissioning of Rack Mounted DVD Player as per
30 Nos 1 12,546.00 625.00 12,546.00 625.00
specifications(Make: Honeywell)
Supply, Installation, Testing and Commissioning 2 mm thick CRCA Sheet Powder Coated
suitable size Rack to mount the above quantity DVD Player, Amplifiers, Controllers,
31 routers etc., Lot 60,221.00 3,000.00 - -
Rack shall be deep closed type with front glazed door with 6/13A horizontal power strip
(Make: Honeywell)
Supplying, installation, testing & commissioning of TWO WAY TALK BACK PANEL wih
33 320 character/ Touch screen LCD display with inbuilt Nos 1 24,465.00 3,125.00 24,465.00 3,125.00
reset, acknowledge and silence switches complete as required.
IV FIRE EXTINGUISHERS
Supplying, installing and commissioning Portable Fire extinguishers of following type &
capacity.
i).ABC powder stored pressure type fire extinguisher of 4.0 Kgs. Capacity, with initial
filling in brand new cylinder with powder coated finish, fitted with Gun metal union, high
pressure CO2 gas cartridge, discharge hose. quoted rate included pressure gauge, Shadow Nos. 6 2800 100 16,800.00 600.00
board, Sinage of the extinguisher,wall/coloum mounting bracket, floor stand etc complete,
confirming to As per IS 2190-2010.
ii).ABC powder stored pressure type fire extinguisher of 6.0 Kgs. Capacity, with
initial filling in brand new cylinder with powder coated finish, fitted with Gun metal
union, high pressure CO2 gas cartridge, discharge hose. quoted rate included pressure Nos. 16 4000 100 64,000.00 1,600.00
gauge, Shadow board, Sinage of the extinguisher,wall/coloum mounting bracket, floor
stand etc complete, confirming to As per IS 2190-2010.
iii). Dry powder extinguisher stored pressure type fire extinguisher of 6.0 Kgs.
Capacity, with initial filling in brand new cylinder with powder coated finish, fitted with
Gun metal union, high pressure CO2 gas cartridge, discharge hose. quoted rate Nos. 2 4000 100 8,000.00 200.00
included pressure gauge, Shadow board, Sinage of the extinguisher,wall/coloum
mounting bracket, floor stand etc complete, confirming to As per IS 2190-2010.
Supply and install in position approved make 5KG CO2 TYPE Fire Extinguisher , fitted
with discharge control valve( Sq. Grip type ) CE marked and pressure gauge, with
discharge hose and open nozzle and supplied complete with initial charge as peas per IS
1 Nos. 0 9500 100 - -
2190-2010. quoted rate included pressure gauge, Shadow board, Sinage of the
extinguisher,wall/coloum mounting bracket, floor stand etc complete, confirming to As
per IS 2190-2010.
v)Supply and install in position approved make Water Stored pressure type Fire
Extinguisher of 9lit capacity, fitted with discharge control valve( Sq. Grip type ) CE
marked and pressure gauge, with discharge hose and open nozzle.quoted rate included Nos. 9500 100 - -
pressure gauge, Shadow board, Sinage of the extinguisher,wall/coloum mounting
bracket, floor stand etc complete, confirming to As per IS 2190-2010.
vi).Supply and install in position approved make Foam stored pressure type Fire
Extinguisher of 6lit capacity, fitted with discharge control valve (squeeze grip type),
inside co2 gas cartridge of 60gms as per IS: 4947 with ISI mark and AFFF liquid of 540
ml as per IS: 4989 with ISI mark, with discharge hose and air induction nozzle and Nos. 2 4500 100 9,000.00 200.00
supplied complete with initial charge As per IS 2190-20103.quoted rate included
pressure gauge, Shadow board, Sinage of the extinguisher,wall/coloum mounting
bracket, floor stand etc complete, confirming to As per IS 2190-2010.
vii).Fire buckets 9ltrs capacity each round bottom type enamel painted, white inside
& Red out side and Letter "FIRE"in black out side and handle with mounting bracket, Nos. 0 200 100 - -
with shadow board and shelter
ix).Fire bucket stand fabricated by MS angles to install 2 Nos. of buckets. set 3 3500 100 10,500.00 300.00
IV SIGNAGES
Providing and installing in position the following type of sign boards made out of 3mm thick
"Opaque" PVC foam board with computer cut, PVC non-reflective self adhesive vinyle
painted foam board, complete with mirror fasteners.
a).Signage with printed "IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED
OTHERWISE" of 1.5cm height letters in red with white back ground. The size of the board
1 Nos 2 600 20 1,200.00 40.00
shall be 25cm x 30 cm and shall be fixed at the height of 2 mts. from finished floor near
Manual call points.
b).Floor identification signage ( ie, GROUND FLOOR …etc.) at each stair enclosure
on every floor, indicating the floor number in words, lettering size shall be 7.5 cm with Nos 2 600 20 1,200.00 40.00
contrasting colour from back ground. Size shall be 15cm x 60cm.
Providing and fixing in position the signages "FIRE ORDER" it should contain the following
matter on 3mm thick "Opaque" PVC foam board of computerised cut, PVC non-reflective - -
self adhesive vinyle painted foam board of 3' x 4'.
a) ALERT THE SECURITY AT SECURITY ROOM BY ACTUATING MANUAL CALL
- -
POINT LOCATED AT STRATEGIC LOCATIONS.
2 b) EVACUATE THE OCCUPANTS BY USING FIRE EXITS AND EMERGENCY EXITS
- -
ONLY AND ASSEMBLE AT VARIOUS ASSEMBLY POITS.
c) IF POSSIBLE TRY TO EXTINGUISH THE FIRE BY USING NEAREST / SUITABLE PORTABLE Lot
2 1500 20 3,000.00 40.00
EXTINGUISHER OR WATER FROM NEAREST WET RISER.
d) BE CALM AND DO NOT GIVE ANY ROOM FROM PANIC, WALK, DO NOT RUN. - -
e) IF YOU ENCOUNTER SERIOUS DIFFICULTY IN EVACUATION, FLAT AND TRY TO ATTRACT
- -
ATTENTION OF RESCUE TEAM.
ACTION BY SECURITY/RECEPTION UPON RECEIPT OF INFORMATION THROUGH
- -
FIRE ALARM OR FIRE DETECTORS SYSTEM.
a) ALERT THE OCCUPANTS BY USING FIRE ALARM SYSTEM. - -
b) INFORM FIRE CONTROL THROUGH ANY ONE OF THE FOLLOWING PHONE NUMBERS: 101
- -
/ ----- /----- / ------.
3 c) REFER EVACUATION PLAN FROM EVACUATING STANDARD PEOPLE. Lot 2 1500 20 3,000.00 40.00
d) GUIDE THE FIRE FORCE, ON THEIR ARRIVAL TO THE SEAT OF FIRE. - -
e) IN CASE OF THE CASUALTIES, CALL AMBULANCE BY DIALLING NUMBER…….. - -
f) FIRE FIGHTING AGNECY ------------------------------- - -
g) PHONE : ----------------------- - -
h) FAX : ---------------------------- - -
Providing and fixing in position the Rectungular type sign Board - "ASSEMBLY POINT" of
4 3mm thick PVC/FRP board of computerised cut, PVC non-reflective self adhesive vinyle Nos 1 600 20 600.00 20.00
painted foam board of Standard Size.
Providing and fixing in position the Rectungular type sign Board INDICATION OF DIRECTION
5 BOARD of 3mm thick PVC/FRP board of computerised cut, PVC non-reflective self adhesive vinyle Nos 2 1200 20 2,400.00 40.00
painted foam board of Standard Size.
Providing and fixing in position the Rectungular type sign Board INDICATION OF FIRE
6 DOOR of 3mm thick PVC/FRP board of computerised cut, PVC non-reflective self adhesive Nos 2 600 20 1,200.00 40.00
vinyle painted foam board of Standard Size.
TOTAL (Without TAX) 12,600.00 260.00
15 NB Rmt
20 NB Rmt
25 NB branch pipe at above false ceiling Rmt 160 344 100 55,040.00 16,000.00
26 NB branch pipe at below false ceiling Rmt 48 44 150 2,112.00 7,200.00
32 NB branch pipe at above false ceiling and compressor plant room piping Rmt 54 554 180 29,916.00 9,720.00
40 NB branch pipe at above false ceiling Rmt
50 NB Rmt
65 NB Rmt
100 NB Main Header from the Compressor Room Rmt
150 NB Rmt
Ball Valves -Ball Valves -Supply, Installation, Testing and Commissioning of Carbon
2 Steel full bore ball valves with Body ASTM A105 ,Trim ASTM A182 Gr.F304L, PTFE, Hand
Operated, Socket Weld Ends
15 NB Nos
25 NB Nos 6 5500 550 33,000.00 3,300.00
32 NB Nos 5 7500 550 37,500.00 2,750.00
40 NB Nos
Auto Drain Trap -Supply, Installation, Testing and Commissioning of Aluminum Body
3 Screwed Ends BSPT, internals hot dip galvanized with pair of nipples all complete for
installation and its function.
25 NB Rmt 5 5500 750 27,500.00 3,750.00
Filter Regulator -Supply, Installation, Testing and Commissioning of Aluminum Body
5 Screwed Ends BSPT, internals hot dip galvanized with pair of nipples all complete for
installation and its function.
25 NB Flow Rate : 25cum/hr @ 7.5bar Nos 6 5500 350 33,000.00 2,100.00
40 NB Flow Rate : 25cum/hr @ 10 bar Nos .
100 NB Flow Rate : 3500cum/hr @ 7 bar Nos
Air gun with spiral PU tube -Supply, Installation, Testing and Commissioning of air
6 gun with spiral PU tube (each expandable length 2 mtr) with Barrel Nipple which can be
suitably welded to pipe on one end and screwed to quick fix coupling on the other.
Ф8mm end connection with metal air gun Nos 3 1850 350 5,550.00 1,050.00
Pressure Gauges -Supply, Installation, Testing and Commissioning of Diaphragm Type
7 Pressure gauges (SS304). Pressure gauge shall be flanged type and having matching
flange, gasket & nut & bolt.
6 inch dial, 0-10 kg/cm2 Nos 11 4200 350 46,200.00 3,850.00
6 inch dial, 0-50 kg/cm2 (on header inlet side of the line for bottle busting) Nos
PU pipes -Supply, Installation, Testing and Commissioning of PU pipes with necessary
Quick Fix Coupling with an in-built check valve on the socket end and plug end feasible
8 to be connected to hose.
Barrel Nipple which can be suitably welded to pipe on one end and screwed to quick fix
coupling on the other.
Ф6mm x 30mtrs length including end connections to be fitted according to site
conditions.
Nos 6 2200 250 13,200.00 1,500.00
Ф8mm x 30mtrs length including end connections to be fitted according to site
Nos
conditions.
TOTAL (Without TAX) 283,018.00 51,220.00
Supply ,unloading at site ,Store , shift to location , erecting, testing and commissioning
of 11 kV, 3Phase, 50 Hz, 500 MVA, 630A, SINGLE VCB Panel with multi
function meter, Outdoor type, totally enclosed free standing MS sheet clad cubicle type,
Isolation type, HT Panel of siemens grey or of approved color with 1no.630A,26.3KA
for 3Sec motorised VCB as incomer &2no.s 630A ,26.3KA for 3sec motorised VCB as
3MODULE VCB PANEL
outgoing ,630A TP PVC sleeved copper bus bars suitable to receive 11KV, 1RX 3C x
300 Sqmm XLPE(E) HT incoming cable and outgoing cable. The VCB Panel shall
1 Each 1,500,000 1,500,000 3,000 3,000 FOR I/C+O/G-1:
INGEN+O/G-2 INCOM
comply to the requirements of TANGEDCO . The tripping mechanism shall be suitable
for 110V DC source in built power pack with 30 min backup & 230V AC source for
spring charge & heater circuit from external supply . AS PER TANGEDCO
STATUTORY NORMS AND REQUIREMENTS.
( Tender Dwg : VSLC -WH4-SLD-401,T0).
RCC Foundaiton for above 3Module HT panel with Supersture hieght of 1mtr from
FGL /NGL .
1 Each 100,000 100,000 15,000 15,000
3.0 NEW 11KV VCB PANEL- 1 MODULE OUTDOOR IP 54( EXTENSIBLE TYPE)
Supply ,unloading at site ,Store , shift to location , erecting, testing and commissioning
of 11kV, 3Phase, 50 Hz, 500 MVA,1no. 630A,26.3KA for 3Sec Motorised VCB Panel
with demand controller/manager and power monitor as incomer and 1no. 630A,
26.3KA for 3Sec Motorised VCB Panel with multi function meter as Outgoing, indoor
type, totally enclosed free standing MS sheet clad cubicle type, Isolation type, HT Panel
of siemens grey or of approved color with 630A TP PVC sleeved copper bus bars and 1MODULE VCB PANEL
suitable to receive 11KV 1R X 3C x 300 Sqmm XLPE(E) HT as incomer and outgoing 1 Each 500,000 500,000 10,000 10,000 FOR TRAFO- INCOM
cable. The VCB Panel shall comply to the requirements of TANGEDCO . The tripping
mechanism shall be suitable for 110V DC source in built power pack with 30 min
backup & 230V AC source for spring charge & heater circuit from external supply .
AS PER TANGEDCO STATUTORY NORMS AND REQUIREMENTS.
( Tender Dwg : VSLC -WH4-SLD-401,T0).
A
RCC Foundaiton for above 1Module HT panel with Supersture hieght of 1mtr from
FGL /NGL .
1 Each 50,000 50,000 5,000 5,000
HT CABLE FROM
3-Core x 240 Sqmm 11KV(E) A2XFY XLPE FLAT ARMOURED METER YARD NEAR
2,000 Mtrs 1,500 3,000,000 200 400,000 MAIN GATE TO INCOM
Cable
A TRAFO YARD .
3-Core x 240 Sqmm 11KV(E) A2XFY XLPE Cable STRAIGHT JOINT JOINT KIT FOR HT
B 4 Each 8,000 32,000 2,500 10,000 CABLE
KIT (OUTDOOR)
RCC Foundaiton for above transformer with Supersture hieght of 1mtr from FGL
/NGL .
1 Each 100,000 100,000 20,000 20,000 .
6.1 PIPES :
Supply and laying of pipes in existing excavated ground. Any collars and
bends and nipples etc as required shall be laid at a depth of 600 mm
below ground level or under paved areas/under floor as required.
A 100 mm dia Class 'B' GI pipe. 25 Mtr 1,000 25,000 100 2,500 HT CABLE PROTECT
B 300 mm outer dia Hume pipe NP2 class 50 Mtr 750 37,500 150 7,500 ROAD CROSS
C 150 mm outer dia Hume pipe. NP2 class 50 Mtr 350 17,500 100 5,000 ROAD CROSS
HT metalic cable Cast Iron Cable route marker with height atleast
300mm above ground level, angle/ GI pipe support and Concrete 50 Each 500 25,000 100 5,000 ROUTE MARKER
D foundation
LT CABLE EARTH
B Trench of width 600 mm & depth 750mm. 50 Mtr 300 15,000 850 42,500 EXCAVATION
C Trench of width 300mm & depth 450mm. 50 Mtr 300 15,000 750 37,500 EARTH STRIP WORKS
7 MISCELLANEOUS ITEMS :
SAFETY ITEM AS PER
A 4 Fire buckets of 9 Ltrs capacity with floor, stand, sand, painting, etc. 2 Each 5,000 10,000 500 1,000 CIEG
Rubber mats of 11KV grade 1.8 Mtrs x 0.9 Mtrs and of sufficient
thickness min 3mm & COLOUR as required by the Electrical SAFETY ITEM AS PER
5 Each 2,500 12,500 50 250 CIEG
Inspectorate and confirming to IS 15652. Electro mat with zone marking
B for safe operating distance .
Shock treatment chart with teak wood frame and glass cover as approved SAFETY ITEM AS PER
1 Each 1,000 1,000 100 100 CIEG
C by Electrical Inspectorate.
Electrical single line diagram A1 SHEET (As Built drawing/ SAFETY ITEM AS PER
1 Each 2,500 2,500 100 100 CIEG
D TANGEDCO APPROVED ) with teak wood frame and glass cover.
Danger boards mention voltage level in min three languages marked in SAFETY ITEM AS PER
6 Each 500 3,000 100 600 CIEG
red as per TNEB requirements. (In English, Hindi & Local Language)
F
providing one gate 2400 mm wide (min) in two (side hung) leaves to
B match the chain link fence including necessary hinges, locking 1.00 Each 9,000.00 9,000.00 1,500.00 1,500.00
arrangements, etc., complete.
providing one gate 1200 mm wide (min) in two (side hung) leaves to
C match the chain link fence including necessary hinges, locking 2.00 Each 6,000.00 12,000.00 1,000.00 2,000.00
arrangements, etc., complete.
The supply & fixing of steel supporting channels, grip bolts and all other
accessories as required shall be measured under separatly under heading
steel items.
TECHNICAL NOTES :
A) The MV Switchboards shall be confirming to the relevant latest
Indian standards, the technical specs forming part of this tender
documents and the Key Schematic Diagram attached with this tender
document and the BOQ. Main LT Panel shall be of Form 4A and other
Sub Panels shall be of Form 3B type of construction.
B) Total discrimination study shall be done by swicthgear OEM and
report to be sumitted with breaker and relay settings.
C) All Digital meters shall be with comm port for connecting to EMS
system.
Contractor / Vendor should quote all Panels as per following
minimum features / reqirements & for other detail requirements
refer relevent specification:
1) The all ACB feeders should have pad lock arrangement at its
TEST and ISOLATED Position.
2) All ACB's should have hinged and lockable cover to prevent the
accidental operation mechanical ON push button on ACB.
3) After any door opening panel should maintain minimum IP-20
protection against any electrical live parts with "Danger 415 V"
symbol in english, hindi and local language. All the terminals should
have proper cover to make them finger touch proof.
4) All fornt cubicles and back side should have large "Danger 415 V
" signage board in Hindi, Engilish and local language. This Danger
signage should be in red backgorund and the font should be in white
text. This signage board should be permanently fixed (not sticker
type) and should be indelible. The signage board should be of
5) All the front doors should have lock and it should be opneable
with dedicated key. It should also not be possible to open the front
door when the ACB is Racked IN.
6) All MP releases of ACBs should have with display and rotary
switches for protection setting.
7) Earth fault protection should be 3 ph, 4 wire in all TPN ACB'S &
MCCB'S. The earth fault protection should include neutral also for
all TPN ACB'S & MCCB'S feeder with required suitable materials
and it should be suitable of minimum setting at 10% of rated current
of breaker.
8) Busbar spreaders are required for feeder 125A and above.
9) All feeders should have Rotary operating handle (ROH)
10) All MCCB feeders should have extended rotary handle to putting
pad locks for LOTO
11) All panel feeders should have with LOTO provision.
A MAIN LT PANEL OUTDOOR TYPE IP54 1 Each 650,000 650,000 40,000 40,000 CPRI TESTED
( Tender Dwg :VSLC -WH4-SLD-401,T0)
RCC Foundaiton for above MV PANEL with Supersture hieght of 1mtr from FGL
A,1
/NGL .
1 Each 100,000 100,000 25,000 25,000
B PRODCUTION BLOCK MRLP INDOOR TYPE IP43 1 Each 1,000,000 1,000,000 15,000 15,000 CPRI TESTED
2.1 Vertical Type TPN MCCB DB's with Metal Door(Double Door)
12 Way VTPN MCCB DB with 1NO. 63A,4P MCCB Incomer and 12
no.s of 32A TP MCB's as outgoings. Scope includesMCCB & MCB
1 Each 35,000 35,000 5,000 5,000 M/C VTPN DB
supplies complete .
A ( Legrand or Approved Equivalent )
8 Way VTPN MCCB DB with 1NO. 63A,4P MCCB Incomer and 8 no.s
of 32A TP MCB's as outgoings.Scope includesMCCB & MCB supplies
1 Each 30,000 30,000 5,000 5,000 PDB-1
complete .
B ( Legrand or Approved Equivalent )
4 Way VTPN MCCB DB with 1NO. 63A,4P MCCB Incomer and 4 no.s
of 32A TP MCB's as outgoings. Scope includesMCCB & MCB supplies
1 Each 25,000 25,000 5,000 5,000 PDB-3 3PH
complete .
C ( Legrand or Approved Equivalent )
12 Way TPN MCB DB with 1NO. for 63A,4P MCB Incomer and 3NO.S
32A DP RCBO 30 mA RCBO as sub incomer and 36 no.s 10/16/20 SP
R.ONLY Each 25,000 0.00 5,000 0.00
MCB's as outgoings.Scope includes MCB supplies complete .
( Legrand or Approved Equivalent )
A
8 Way TPN MCB DB with 1NO. for 63A,4P MCB Incomer and 3NO.S
32A DP RCBO 30 mA RCBO as sub incomer and 24 no.s 10/16/20 SP
1 Each 20,000 20,000 4,000 4,000 UDB
MCB's as outgoings.Scope includes MCB supplies complete .
( Legrand or Approved Equivalent )
B
4 Way TPN MCB DB with 1NO. for 63A,4P MCB Incomer and 3NO.S
32A DP RCBO 30 mA RCBO as sub incomer and 12 no.s 10/16/20 SP
3 Each 15,000 45,000 3,000 9,000 PDB-2 ,ACDB,PDB-04
MCB's as outgoings.Scope includes MCB supplies complete .
( Legrand or Approved Equivalent )
C
A 3.5 Core x 300 Sqmm A2XFY Cable 250 Mtr 941 235,250 99 24,750
B 3.5 Core x 240 Sqmm A2XFY Cable R.ONLY Mtr 795 0.00 90 0.00
C 3.5 Core x 185 Sqmm A2XFY Cable R.ONLY Mtr 692 0.00 76 0.00
D 3.5 Core x 150 Sqmm A2XFY Cable R.ONLY Mtr 553 0.00 72 0.00
E 3.5 Core x 120 Sqmm A2XFY Cable R.ONLY Mtr 621 0.00 68 0.00
F 3.5 Core x 95 Sqmm A2XFY Cable R.ONLY Mtr 379 0.00 63 0.00
G 3.5 Core x 70 Sqmm A2XFY Cable 200 Mtr 297 59,400 54 10,800
H 3.5 Core x 50 Sqmm A2XFY Cable R.ONLY Mtr 226 0.00 45 0.00
I 3.5 Core x 35 Sqmm A2XFY Cable 250 Mtr 165 41,250 36 9,000
K 4 Core x16 Sqmm A2XFY Cable 200 Mtr 112 22,400 29 5,800
CONTROL CABLES
A 4Core x 10 Sqmm YFY Cable 100 Mtr 94 9,400 18 1,800
D 3 Core x 2.5 Sqmm YFY Cable 1,000 Mtr 101 101,000 22 22,000
Supply and providing the end terminations with Aluminium cable lugs,
Double compression brass cable glands, taping, crimping, gland and
armour earthing, etc. complete as required. Lugs shoulsd by bimattalic
type
4.10
A 3.5 Core x 300 Sqmm A2XFY Cable 12 Each 2,640 31,680 450 5,400
B 3.5 Core x 240 Sqmm A2XFY Cable R.ONLY Each 2,380 0.00 405 0.00
C 3.5 Core x 185 Sqmm A2XFY Cable R.ONLY Each 1,773 0.00 360 0.00
D 3.5 Core x 150 Sqmm A2XFY Cable R.ONLY Each 1,732 0.00 288 0.00
E 3.5 Core x 120 Sqmm A2XFY Cable R.ONLY Each 1,344 0.00 234 0.00
F 3.5 Core x 95 Sqmm A2XFY Cable R.ONLY Each 1,122 0.00 216 0.00
G 3.5 Core x 70 Sqmm A2XFY Cable 4 Each 946 3,784 162 648
H 3.5 Core x 50 Sqmm A2XFY Cable R.ONLY Each 796 0.00 144 0.00
I 3.5 Core x 35 Sqmm A2XFY Cable 6 Each 548 3,288 126 756
Supply and providing the end terminations with Copper cable lugs,
4.20
BRASS cable glands, taping, crimping,etc. complete as required.
CONTROL CABLES
A 4Core x 10 Sqmm YFY Cable 10 Each 237 2,370 90 900
B 32 mm dia, 2mm Thick FRLS PVC conduit with all accessories. 1,500 Mtr 222 333,000 45 67,500
C 25 mm dia, 2mm Thick FRLS PVC conduit with all accessories. 1,500 Mtr 182 273,000 45 67,500
D 20 mm dia, 12mm Thick FRLS PVC conduit with all accessories. 500 Mtr 160 80,000 35 17,500
Supply and running of 2RUNS X 2.5+ 1 RUN X 1.5 Sqmm FRLS PVC
insulated multistrand copper conductor wire in existing conduits-25mm 1,500 Mtr 78 117,000 14 21,000
H DIA
Supply and running of 2RUNS X 1.5+ 1 RUN X 1.0 Sqmm FRLS PVC
insulated multistrand copper conductor wire in existing conduits-20mm 500 Mtr 78 39,000 14 7,000
I DIA
63 Amps, 5-pin ,440V, three phase metal clad industrial socket with plug
top, controlled by 63 Amps, FP RCBO 30mA .
A R.ONLY Each 15,000 0.00 270 0.00
( Model : LEGRAND or Approved Equivalent )
32 Amps, 5-pin ,440V, three phase metal clad industrial socket with plug
top, controlled by 32 Amps, FP RCBO 30mA .
B 5 Each 7,500 37,500 216 1,080 PRODUCTION AREA
( Model : LEGRAND or Approved Equivalent )
16 Amps, 3-pin,230v, single phase metal clad industrial socket with plug
top, controlled by 20 Amps DP RCBO 30mA .
C 10 Each 5,000 50,000 180 1,800 SERVER RACK
( Model : LEGRAND or Approved Equivalent )
125 Amps, 5-pin ,440V, Three phase thermo plastic industrial socket
B controlled by 125 Amps, 4P MCB with plug top,. 1 Each 20,000.00 20,000.00 3,500.00 3,500.00 PROD ODU
( Model : LEGRAND or Approved Equivalent )
6/16 Amps, 5-pin ,230 Volts, single phase round pin socket with 16
B Amps single pole switch with indicating LAMP with GI metal box with 20 Each 575 11,500 63 1,260 OFFICE
press fit type PVC front plate complete with all accessories.
6 Amps, 3 pin ,230V, single phase round pin socket with 6 Amps SP
C switch along with indicating lamp with GI metal box with press fit type 15 Each 444 6,660 63 945 OFFICE
PVC front plate complete with all accessories.
7.0 EARTHING :
Providing the earth stations with necessary materials labour,civil works
7.10 such as construction of 600 x 600 chamber with CI cover, etc.,complete
as required and as per IS-3043.complete.
CI PIPE Earthing
Supply of CI pipe 100mm dia at a depth of 3000 mm. in an earth pit of
600 x 600 x 3000 mm. filled with 25Kg each salt and charcoal mixed
with sand in alternate layers 150 mm. each upto a height of 2000mm.
from bottom. Pipe shall have provision for watering through a funnel. It
shall also have provision for connecting 50 x 6 mm. GI Flat on two sides.
A. CI 100mm dia Pipe - 1no
A B. Funnel and clamping accessories of SS nuts&bolts - 1sets 10 set 11,872 118,720 7,200 72,000 TRAFO YARD
C. Salt -25 kg each -1 bag
D. Charcoal -25 kg each -1 bag
E. GI Flat – 50 x 6mm, 1 mtr
The Precast RCC chamber size shall be 600 x 600 mm with heavy duty
C.I. Cover plate. The identification number shall be provided both inside
and outside. As per IS 3043
.( Make - Indelec or Approved Equivalent)
GI strip should be rolled strip or slit strip with smooth edges with a single
length of 6Mtrs.Folded strip with uneven length should not be used.
Earth Flat should be tested and test report shall be submitted from third
party NABL accredited laboratory for below tests.
1. Electrical resistance test before and after salt mist
2. Tensile strength
3. Bend test
4. Adhestion test
5. Average mass of zinc coating as per DIN ISO 1461.
6. Salt spray test
Meets the requirement of VDE0185/305(IS-IEC 62305)
Should be tested and used exclusively for Earthing system, lightning
protection earthing system and ring equipotential bonding .
Tested as per IEC 62561(1-8).( Make - INDELEC or Approved
Equivalent )
A 50 x 10 mm Hot Dip Galvanised Iron Tape 100 Mtrs 426 42,600 126 12,600
B 50x 6 mm Hot Dip Galvanised Iron Tape 50 Mtrs 254 12,700 90 4,500
D 25 x 6 mm Hot Dip Galvanised Iron Tape 100 Mtrs 135 13,500 54 5,400
Copper strip shall be rolled type and minimum length of copper strip
should be 20mtrs.
Earth Flat should be tested and test report shall be submitted from third
party NABL accredited laboratory for below tests.
A 40 x 6 mm Copper Tape with 2mm thick Black PVC sleeves 20 Mtrs 2,261 45,220 72 1,440
B 25 x 6 mm Copper tape 2mm thick Black PVC sleeves 10 Mtr 1,459 14,590 54 540
A 1CX25 Sqmm PVC insulated flexible copper WIRE 200 Mtr 54 10,800 11 2,200
B 1CX16 Sqmm PVC insulated flexible copper WIRE 250 Mtr 54 13,500 11 2,750
C 1CX10 Sqmm PVC insulated flexible copper WIRE 200 Mtr 54 10,800 11 2,200
D 1CX4 Sqmm PVC insulated flexible copper WIRE 100 Mtr 54 5,400 11 1,100
7.2.4 Supply and installation of single compression PG gland with ring type /
pin type copper lugs suitable for earthing cables
D 1CX4 Sqmm PVC insulated flexible copper WIRE 20 Set 20 400 5 100
MS powder coated Adaptor Box houisng Auto / manual switch knob type
, 24 hours programmable digital mini timer and 32 A 4 Pole Mini
A R.ONLY Each 31,114 0.00 1,440 0.00
contactor logic with LED ON, OFF indication lamps.( Colour & width
shall be same of 7 seg LDB )
Note: The rates for the following items shall include supply and
installation of Modular type of switches, sockets, fan regulators, etc.,
along with all necessary fixing accessories like mounting screws,
concealed/surface mounted switch boxes suitable for modular type
switches, internal wiring, top plate, etc., all complete as required.
The modular type switches, sockets, regulators shall be of approved
make & shade.
F One light point controlled by two Nos. 6 Amps 2 way SP switch 2 Each 1,500 3,000 378 756
Ceiling fan point with fan hook box including 6 Amps single pole control
G 1 Each 1,500 1,500 374 374
switch including 100 Watts,5 Step, two module type electronic regulator.
Wall mounted fan point including 6 Amps single pole control switch as
per specification. (Note that wall mounted fans shall be mounted at
H suitable height in the range of 5-6 metres from FFL while regulator and 4 Each 1,500 6,000 266 1,064
switch to be mounted below the fan at the same height as that of other
switches).
Exhaust fan point with wall-mounted 6Amps, 3-pin socket near fan
location and 6 Amps single pole controlling switch located
I 6 Each 1,500 9,000 284 1,704
independently. The rate shall also include supply of 5 Amps, 3-pin plug
top .
NOTE:- The cost shall also include suitable threaded rods /MS down
rods / chains / ball & socket arrangements, etc., with all other
accessories complete as required for surface/ suspension/ Recessed of
lights, fans to the required level above FFL.
AVERFAGE LIFE L70B50 MIN 50,000 Burning Hours
40W LED High efficiency aluminium profile linear batten with
polycarbonate
diffuser for enhanced productivity. Ingress protection IP40.
A 20 Each 1,800 36,000 250 5,000 PROD.
( Philips :BN308C LED40S-6500 L120 PSU WH or approved
equivalent).
Lumen Output - 4000 lumens , CRI>80 , CCT = 5700 deg K
200W LED High efficiency High bay lights in Aluminium Die cast
housing and High quality Polycarbonate cover with integrated
B lens . Ingress protection IP40. 5 Each 7,500 37,500 250 1,250 PROD.
(Havells :Saucer genx DD P, 200W_ADV_ or approved equivalent).
Lumen Output - 29000 lumens , CRI>80 , CCT = 5700 deg K
150W LED Outdoor focus Type light fixture with Thermo plastic box
suitable for 8 terminal block ( loop in and loop out) , 10A SP MCB along
with 3C x 1.5Sqmm Copper cable above 6. 5 mtrs from FFL and all other
C 2 Each 7,000 14,000 250 500 PROD.
accessories complete.
(Wipro :LF20-192-060-57-BS or Approved equivalent)
Lumen output - 100 lm/watt, CCT -5700/6500K, CRI>80.
300 mm impeller dia, 1400 rpm exhaust fan with louvres(single phase) R.ONLY Each 4,501 0.00 405 0.00
A
150 mm impeller dia, 1400 rpm exhaust fan with louvres(single phase) 6 Each 1,369 8,214 405 2,430
B
3.00 TOTAL FOR INTERNAL & EXTERNAL LIGHTING WORKS 962,638 84,578
D
LT Cable from 120 sq mm to 185 sq mm 10.00 Each - 600 6,000
ABSTRACT
Sl. No. DESCRIPTION SUPPLY AMOUNT ERECTION AMOUNT BUA
26,663
1 TOTAL FOR INFRASTRUCTURE WORKS 7,330,000 2,762,450
4) Cable quantities indicated in this BOQ are tentative / indicative & contractor will be solely
responsible for calculating quantities as per site conditions, accordingly supply & erection of
materials at site. Payment will be made as per exact actual cable laid at site measurement.
Payment will not be made for procured cable by contractor but same was not used.
5) Before procurement of supply material contractor should take prior approval from client /
Consultant/ PMC and actual measurement at site. Contractor shall be fully responsible for supply
of material & its accessories based on actual site condition.
6) Before procurement of lighting fixtures contractor has to take approval from client regarding
type and color temperature of lighting fixture.
found, unit rates for the same should be submitted at the time of quoting. Later stage if any
material required as per relevant codes / standards / scope which is not covered in Tender BOQ
8)
but All testingforshall
required be in accordance
successful with
completion relevant
of job latest
will be IS care
taken standards and as per
by contractor international
(free of cost) at site
standards.
9) Submission of As built drawing , CEIG approved drawings in hard copies - 3sets (colour)and
soft copy- 2 sets with relevant O&M manual ,Inspection reports , test reports , comissioning
reports , warranty & guarantee certificates from OEM / Priniciple vendor complete .
10) Submission of Standard operating procedures for all Equippemnts , appartus for reliable
functioning.
11) Conduct Traning for authorized/ designated personnel for handling of equiipment and
operational funtionality etc .
12) Material supplied in excess at site but not used for project . Contractor has to take back
material at his own cost and perform all formalities with proper gate pass and credit note if any .
Sl Description Work
station Total
1 Total Data 1 30 0 30.00
2 Total Data for wifi, CCTV & ACS 5 0 5.00
3 Total Voice 1 30 0 30.00
4 Total 65.00
5 Dual Faceplate 30 0 30.00
6 Single Faceplate 10 0 10.00
7 Average length 80 5,200.00
EXCLUSIONS
1) ALL ACTIVE COMPONENTS LIKE ROUTERS , FIRE WALL , SERVERS, SOFTWARE .
2) ALL END USER HARDWARE LIKE COMPUTERS , WIFI ROUTER,EPABX AND IP TELEPHONE INSTRUMEN
DATE 3/29/2025
REVISON R0
1.35
250.00 - 16,250.00
1,122,843.00 197,451.00
202,111.74 35,541.18
1,324,954.74 232,992.18
1,557,946.92
FTWARE .
AND IP TELEPHONE INSTRUMENTS.
PROJECT: VSLC PH1 , INCOM TENANT ,POLLIVAKKAM , TAMIL NADU
SUBJECT:CCTV WORKS
SL.NO
6
7
10
11
12
13
II
III
PROJECT: VSLC PH1 , INCOM TENANT ,POLLIVAKKAM , TAMIL NADU
SUBJECT:CCTV WORKS
CCTV WORKS
DESCRIPTION OF WORK
Supply, Installtion & Commissioing of IP Fixed Dome Camera [2mp], 1/3" CMOS, 1080P
resolution, 1920 x 1080P pixel @ 25/30fps, motorised Vari-focal focal length 2-9mm Auto
Iris, , 0.1lux, Day night, PoE, SD card Tampering Detection , , UL Listed Celing Mounted
Type Power supply to be taken from Ethernet cable via POE switch. The camera shall be on
H.264 compression.
787,000.00
141,660.00
928,660.00
DATE 3/29/2025
REVISON R0
ERECTION ERECTION
RATE AMOUNT
500.00 4,000.00
500.00 500.00
250.00 750.00
500.00 500.00
500.00 3,000.00
1,500.00 1,500.00
5,000.00 5,000.00
150.00 150.00
500.00 1,500.00
100.00 1,500.00
100.00 1,500.00
100.00 150,000.00
10.00 15,000.00
184,900.00
33,282.00
218,182.00
1,146,842.00
HVAC BOQ-R0
PROJECT- VSLC (PRODUCTION)
Date : 29.03.2025
Supply Installation
SL No Description Unit Qty
Rate Amount Rate Amount
Fan: PLUG TYPE , Motor shall be suitable for Variable Frequency Drive along with spring Isolators and
415±10% volts, 3 phase AC supply, Frequency range shall be 10% to 100%. The harmonic levels in the
VFD shall not exceed the limits specified in IEEE 519 Standards(fan make:Ziehl-Abegg,Kruger)
Coil : DX cooling coil, 6 Row deep coils, Aluminum fins with Hydraufillic coating, coil size shall be
selected for a maximum face velocity of 500 feet/minute. Coils shall have automatic air vents, the vent
outlets beings piped to the drain pan with a copper pipe. drain cock with valve. Coil shall be Cu.header
and Ms adopter with end flange. 20% Cushion should be considered in coil selection.
Filter: Each unit shall be provided with a factory assembled filter section containing washable synthetic
type air filters media, class EU3 (MERV 8) mounted on Aluminum Frame. Filter bank framework shall be
fully sealed and constructed from GSS. The efficiency of the filters shall be 90%down to particle size of
20+10+5 microns as per IS 7613, and ASHRAE 52.1.AHU shall be supplied with one set of pre
commissioning filters
Fine filter section containing Synthetic or Glass fiber or FPCP media, class F8, equivalent to EU7
(MERV 13) of ASHRAE 52.2 1999 .The efficiency of the filters shall be 95% down to particle size of 5
microns as per IS 7613, and ASHRAE 52.1.
5 KW Finned Tubular / Strip Electrical Heater with thyristor controller, Sheathed in S.S. 304, with G.I fins
Filled with MGO as an insulating material & Kanthal-D as a resistance wire With Mounting Bracket
suitable for ahu installation inside AHU. Electrical should be IP-44 Indoor type Non-Compartmental Power
Supply Feeder Panel for Heaters for above KW rating.Humidistat for RH sensing,Electric Power, Control
Cable Copper 1x6sqmm cable for earthing strip nearest earthpit/strip.
Floor Mounted Air Handling unit complete with all sections as specified in technical specifications, 65
mmwg static, 6 row cooling coil, Fan motor with IE - 3 efficiency, filters with pre filter section & fine
filters, 1 set of spare pre-filters apart from 1 set of commissioning filters fixed in the units. ALL FANS
SHOULD BE AMCA CERTIFIED.
Static pressure and Motor Rating : The Indicated static pressure and motor rating is only provisional.
Contractor to calculate static pressure based on final approved construction drawing and pressure drop of
finalized Equipment / Items and submit for review / approval to the consultants. The procurement shall be
processed only after duly verification / approval of calculation and selection from the consultants.
Supply of VRF Outdoor Units Cooling only Model side discharge, with scroll inverter based compressors.
Refrigerant R-410A to be used. cooling mode, low noise inverter based condenser fans, microprocessor
panel as per requirement of sequential starting of VRF unit, coils, expansion valves, single phase
2 preventor, all vibration isolators, safeties etc. In the event of one compressor failure other compressor
shall provide its minimum rated capacity,.2mtrs Length of suitable copper cable is included in scope .
- Voltas,bluestar,daikin Make
(Note: Refrigeration Capacities indicated below are actual capacity. Selection to be done
considering derating at @ 41°+2C.), the refrigenrent topup for commissioning of
vrf units is included in the quote
a 18HP Top discharge QTY 3 655000 1965000 30000 90000
5 Supply and Installation of 4x4 Sqmm Copper control cable Rmt 85 410 34850 90 7650
6 MS Structure support for VRF ODU Nos 3 15000 45000 5000 15000
1 SHEET METAL DUCTING & ASSOCIATED WORKS - Make: Zeco / Rolastar / Veda
Supply, Installation, Testing & Commissioning of Galvanizing shall be Class VII – light
coating of zinc, nominal 120 gsm / sqm surface area and Lock Forming Quality prime
material alongwith mill test certificates. In addition, if deemed necessary, samples of raw
material, selected at random by owner’s site representative shall be subject to approval
and tested for thickness and zinc coating at contractor’s expense.All duct construction
and installation shall be in accordance with SMACNA standards. In addition ducts shall
be factory fabricated utilizing the following machines to provide the requisite quality of
ducts.All ducts shall be fabricated and installed in workman like manner, conforming to
relevant SMACNA codes.
1.1 24 G Ducting Sqm 530 1030 545,900 200.00 106,000.00
1.2 22 G Ducting Sqm 250 1130 282,500 200.00 50,000.00
1.3 20 G Ducting Sqm 30 1260 37,800 200.00 6,000.00
1.4 18 G Ducting Sqm 10 1610 16,100 210.00 2,100.00
1.5 Gripple wire support and necessary accessories for Duct installation Lot 1 500,000 75,000.00
throw of 8.0 Mt. Jet diffuser shall be complete with volume control damper .
a 315mm dia Rmt 0 6,740.00 - 350.00 -
b 250mm dia Rmt 60 4,590.00 275,400 350.00 21,000.00
c 200mm dia Rmt 0 4,400.00 - 350.00 -
Supply, Installation, Testing & Commissioning of Gear type Volume Control Dampers
4 made out of 100 x 40 x 1.55 mm thick galavanised steel frame and blades of 1.55 mm Sqm 1 6,800.00 6,800 1,500.00 1,500.00
galavanised sheet steel.
Supply, Installation, Testing & Commissioning of Belimo Actuators with Control Panel
6 Nos 2 10,500.00 21,000 2,500.00 5,000.00
forabove fire dampers- HIGH TORQUE TYPE
9 Suply and installation of the MS support for duct/pipe support KG R0 95.00 25.00
12 Strobe Hooter (Alarm acknowledgement required on Strobe Hooter.) Nos 1 1,200.00 1,200.00 500.00 500.00
13 Field Devices
Return Air Duct Temperature & RH transmitter
1. Humidity Sensor: Thermoset Polymer based capacitive
2. Temperature Sensor: 1000 Platinum
3. T & RH Accuracy: ± 0.2°C & ± 2 %
4. Output Signal : 4-20mA current loop, 0-5 V DC or 0-10 V DC Nos 1 9,500.00 9,500.00 800.00 800.00
5. Power Supply: 18 to 35 V DC, 15 to 26 V AC
6. Temperature Range : -10-50°C, RH range : 0-100 %
14 T Sensor in Non Flameproof construction-for supply air outlet monitoring Nos 1 1,100.00 1,100.00 500.00 500.00
Supply, Installation of Conventional Multi Sensor Smoke Detector with NO/NC Contact
15 Sensor shall be compatible to installed in room. Nos 1 1,500.00 1,500.00 550.00 550.00
(Duct mounted smoke detector is required)
Supply of VRF Outdoor Units Cooling only Model side discharge, with scroll inverter based compressors.
Refrigerant R-410A to be used. cooling mode, low noise inverter based condenser fans, microprocessor
panel as per requirement of sequential starting of VRF unit, coils, expansion valves, single phase
4 preventor, all vibration isolators, safeties etc. In the event of one compressor failure other compressor
shall provide its minimum rated capacity,.2mtrs Length of suitable copper cable is included in scope .
- Voltas,bluestar,daikin Make
(Note: Refrigeration Capacities indicated below are actual capacity. Selection to be done
considering derating at @ 41°+2C.), the refrigenrent topup for commissioning of
vrf units is included in the quote
a 10HP Side discharge QTY 1 235000 235000 15000 15000
5 Supply and Installation of 4x4 Sqmm Copper control cable Rmt 230 410 94300 90 20700
6 MS Structure support for VRF ODU Nos 1 15000 15000 5000 5000
Circular ducts for Decorative exhaust air fan out of 24 G GI Ducts shall be supported by
cable supports along with suitable rubber sleeves. Ducts to be painted as per architect
1
approved colour. Cost shall include supports,duct end connection with wire mesh to be
provided.
a 150mm dia Rmt 10 1,550.00 15,500 350.00 3,500.00
Auto sequence panel, Flexible, custom cable length, tracks,Switching time is 10 second with
an Operating Voltage 130V to 280V,Temper proof and maintenance free, powder coated
4 box.Microcontroller based technology with Pre Program interlocking to prevent short circuit Nos 2 18,000.00 36,000.00 3,000.00 6,000.00
shall be quoted cables . for dx hiwall units (Server room+ASRS room)