2001-Distribution System Neutral Grounding
2001-Distribution System Neutral Grounding
Distribution neutral grounding is probably one of the There are many ways to ground a distribution system
most confusing subjects faced by the utility distribution primary. This paper will deal primarily with the effects
engineer. In an industry where utilities are combining of grounding on a 4-wire multigrounded system since it
practices, complicated by the fact that European utilities predominates in this country. The following section,
are purchasing U.S. systems and vice versa, the confusion however, gives a brief overview of some of the
has been compounded. Questions being asked are: advantages and disadvantages of the various system
• Is good grounding really necessary? grounding practices in use today.
• Does poor grounding have advantages? Distribution systems are classified as either grounded
• What is the best grounding? or ungrounded. While there are advantages and
• When is grounding important? And when is it disadvantages of each type of grounding, it is impossible
not? to say which is the “best”. The following is a general
The purpose of this paper is to attempt to answer description of the major types:
some of these questions. It will be shown that while
good grounding is usually preferred, there are times A. Ungrounded Systems
when good grounds are not important and may even be Ungrounded system have the secondary windings of
detrimental. Some of the grounding areas covered are: the distribution substation transformer connected either
• Classes of distribution system grounding ungrounded delta or ungrounded wye, with the former
• Arrester application connection being more common. The distribution feeders
• European systems are three-wire, three-phase and two-wire single-phase
• Effect on swells circuits. The major advantage of an ungrounded system,
• High impedance faults like a delta system, is that a single line to ground fault
• Stray voltage will not result in high levels of fault current sufficient to
• Line protection disrupt service beyond the fault itself. This is also a
disadvantage in that overcurrent protection for this type
• Capacitor grounding
of fault is difficult if not impossible to detect. The delta
• Overcurrent protection
system also gives better phase balancing, lower energy
• Number of grounds per mile into a fault, and produces less EMF.
• Etc.
B. Grounded Systems
Grounded systems are usually derived from a
distribution substation transformer with wye-connected
secondary windings with a neutral point of the windings
solidly grounded or connected to ground through a non-
interrupting, current-limiting device such as a resistor or
reactor. A grounding transformer may be used to
establish a grounded system, as is common in Europe.
The circuits associated with grounded distribution
systems generally have a neutral conductor connected to
the supply grounding point. The neutral conductor of the
distribution circuits may be connected to earth at frequent
intervals (multigrounded), or it may be fully insulated and
have no other earth connection except at the source
(unigrounded). In three-wire unigrounded systems, a
neutral conductor is not run with each circuit, but the
Fig. 1. Typical 4-Wire Multigrounded System system is grounded through the connections of the
substation transformer or grounding transformer. The
neutral conductor associated with the primary feeders of
multi-grounded neutral distribution systems is connected
ID# 01TD089 to earth at intervals specified by national or local codes.
It is also common practice to bond this neutral conductor
1.4
stray voltages.
1.35
1.3
III. EFFECT OF GROUNDING 4 gpm
1.25 8gpm
percentage of poles without static grounds (>15%) DISTANCE IN MILES (FROM SUBSTATION)
REINFORCED
CONCRETE
the phase conductor either contacts the neutral wire or
that the arc to the neutral conductor has a very low 80
impedance. An EPRI study performed by one of the
authors over 15 years ago indicated that the maximum
DRY ASPHALT , CONCRETE OR DRY SAND
WET GRASS
40
impedance considerably decreases the level of fault
DRY SOD
WET SAND
current for close in faults but has little effect for faults
some distance away. The use of a fault impedance of 30, 20
40 and 50 ohms, used in many computer programs and by
many utilities is not justified on the basis of this
comprehensive study.
0 Type of Surface
V. CONCLUSIONS