RP-C Specification Sheet
RP-C Specification Sheet
com/buildings | 1
RP-C
SmartX IP Controller
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 2
RP-C
SmartX IP Controller
Freely programmable
The freely programmable RP-C models provide
flexibility through support of both Script and Function
Block programming options. The RP-C promotes
efficiency and standardization through the use of
standard controller applications.
I/O Point Types RP-C-12A model RP-C-12B model RP-C-12C model RP-C-16A model
Universal I/O 8 8 4 8
Type Ub
Solid-state relay outputs 4 - 4 4
(MOSFET)
Relay outputs - 3 3 3
Form A
High power relay outputs - 1 1 1
Form C
Configurations Universal I/O Solid-state Relay Relay Outputs High Power Relay
Type Ub Outputs Form A Outputs
(MOSFET) Form C
Digital inputs yes - - -
Counter inputs yes - - -
Supervised inputs yes - - -
Voltage inputs yes - - -
(0 to 10 VDC)
Current inputs yes - - -
(0 to 20 mA)
Temperature inputs yes - - -
Resistive inputs yes - - -
2-wire RTD temperature yes - - -
inputs
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 3
RP-C
SmartX IP Controller
Continued
Configurations Universal I/O Solid-state Relay Relay Outputs High Power Relay
Type Ub Outputs Form A Outputs
(MOSFET) Form C
Voltage outputs yes - - -
(0 to 10 VDC)
Digital outputs - yes yes yes
Digital pulsed outputs - yes yes yes
PWM outputs - yes yes yes
Tristate outputs - yes yes -
Tristate pulsed outputs - yes yes -
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 4
RP-C
SmartX IP Controller
SmartX Sensors
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 5
RP-C
SmartX IP Controller
• WorkStation/WebStation interface
• Script and Function Block programming options
• Device discovery
• Engineering efficiency
WorkStation/WebStation interface
WorkStation and WebStation provide a consistent user
experience regardless of which EcoStruxure BMS
eCommission SmartX Controllers mobile app server the user is logged on to. The user can log on to
the parent EcoStruxure BMS server to engineer,
Using the eCommission SmartX Controllers mobile commission, supervise, and monitor the SmartX IP
application, you can connect to one or many RP-Cs. controller and its I/O as well as its attached SmartX
You can connect to a single RP-C using the controller's Sensors. For more information, see the WorkStation and
built-in Bluetooth connectivity or using the WebStation specification sheets.
eCommission Bluetooth Adapter connected to a
SmartX Sensor. You can connect to a network of RP-Cs Script and Function Block programming options
on the local IP network, using a wireless access point The freely programmable RP-C controller models have
or a network switch. both Script and Function Block programming options.
Existing programs can easily be reused between the
Device configuration EcoStruxure BMS server and the controller.
With the eCommission SmartX Controllers mobile
application, you can easily discover SmartX IP Device discovery
controllers on the IP network and change each The enhanced Device Discovery in WorkStation
controller's configuration, including the BACnet and IP enables you to easily identify SmartX IP controllers on a
network settings, location, and parent server. To save BACnet network and to associate the controllers with
engineering time, you can save common device their parent server.
settings and then reuse them for controllers of the same
model. Engineering efficiency
Field deployment and I/O checkout The engineering and maintenance of SmartX IP
controllers can be done very efficiently using the
The eCommission SmartX Controllers mobile EcoStruxure Building Operation reusability features.
application does not require an EcoStruxure BMS With these features, you can create library items
server or a network infrastructure to be in place. You (Custom Types) for a complete controller application
can use the mobile application to load the controller that contains programs and all necessary objects such
application directly into the local SmartX IP controller as trends, alarms, and schedules. The controller
and deploy the controller. The controller application application in the Custom Types library is reusable
can be created offline using Project Configuration Tool across all controllers of the same model. You can use
or WorkStation. You can use the mobile application to the controller application as a base for creating new
change the behavior of an installed standard controller controllers intended for similar applications. You can
application, such as configuring temperature setpoints. then edit the controller application, and the changes
You can also perform an I/O checkout to verify that the are automatically replicated to all controllers, while
controller's I/O points are configured, wired, and each controller keeps its local values.
operating correctly.
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 6
RP-C
SmartX IP Controller
WorkStation supports both online and offline tool also enables the quick creation of your own
engineering of SmartX IP controllers. You can make the templates based on SmartX IP controller applications
configuration changes online or use database mode to that you have developed. This facilitates a standard
make the changes offline. In database mode, the approach and drives the ability to easily reuse and
changes are saved to the EcoStruxure Building duplicate common controller applications. For more
Operation database so that you can apply the changes information, see the Automated Engineering Tool
to the controllers later. specification sheet.
Part Numbers
Specifications
AC input
RP-C-12A, -12B, and -12C models
Nominal voltage......................................................................................................................................................24 VAC
Operating voltage range........................................................................................................................................+/-15 %
Frequency ............................................................................................................................................................50/60 Hz
Maximum power consumption ..................................................................................................................................23 VA
Power input protection................................................................................................MOV suppression and internal fuse
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 7
RP-C
SmartX IP Controller
RP-C-16A model
Nominal voltage....................................................................................................................................................230 VAC
Operating voltage range........................................................................................................................................+/-10 %
Frequency ............................................................................................................................................................50/60 Hz
Maximum power consumption ..................................................................................................................................65 VA
Power input protection................................................................................................MOV suppression and internal fuse
...........................................................................Separate PTC thermistor used as a resettable fuse for 24 VAC Out only
DC input
RP-C-12A, -12B, and -12C models
Nominal voltage.............................................................................................................................................24 to 30 VDC
Operating voltage range ...............................................................................................................................21 to 33 VDC
Maximum power consumption................................................................................................................................... 14 W
Power input protection................................................................................................MOV suppression and internal fuse
AC output
RP-C-16A model
Nominal voltage......................................................................................................................................................24 VAC
Frequency ............................................................................................................................................................50/60 Hz
Power rating ..............................................................................................................................................................19 VA
Environment
RP-C-12A, -12B, and -12C models
Ambient temperature, operating ..................................................................0 to 50 °C (32 to 122 °F) at normal operation
............................................................-40 to +60 °C (-40 to +140 °F) for rooftop applications, horizontal installation only
Ambient temperature, storage ..............................................................................................-20 to +70 °C (-4 to +158 °F)
Maximum humidity.....................................................................................................................95 % RH non-condensing
RP-C-16A model
Ambient temperature, operating ..................................................................................................0 to 50 °C (32 to 122 °F)
Ambient temperature, storage ..............................................................................................-20 to +70 °C (-4 to +158 °F)
Maximum humidity.....................................................................................................................95 % RH non-condensing
Material
Plastic flame rating .............................................................................................................................................UL94-5VB
Ingress protection rating ............................................................................................................................................IP 20
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 8
RP-C
SmartX IP Controller
Mechanical
Dimensions...................................................................................... 180 W x 110 H x 64 D mm (7.1 W x 4.3 H x 2.5 D in.)
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 9
RP-C
SmartX IP Controller
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 10
RP-C
SmartX IP Controller
Counter inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ................................................................................................................................................20 ms
Maximum frequency..................................................................................................................................................25 Hz
Supervised inputs
5 V circuit, 1 or 2 resistors
Monitored switch combinations.............................................................Series only, parallel only, and series and parallel
Resistor range ................................................................................................................................................1 to 10 kohm
For a 2-resistor configuration, each resistor must have the same value +/- 5 %
Voltage inputs
Range ..............................................................................................................................................................0 to 10 VDC
Accuracy...............................................................................................................................+/-(7 mV + 0.2 % of reading)
Resolution................................................................................................................................................................1.0 mV
Impedance..........................................................................................................................................................100 kohm
Current inputs
Range ................................................................................................................................................................0 to 20 mA
Accuracy..........................................................................................................................+/-(0.01 mA + 0.4 % of reading)
Resolution....................................................................................................................................................................1 μA
Impedance .............................................................................................................................................................47 ohm
Resistive inputs
10 ohm to 10 kohm accuracy .......................................................................................................+/-(7 + 4 x 10-3 x R) ohm
R = Resistance in ohm
10 kohm to 60 kohm accuracy .....................................................................................+/-(4 x 10-3 x R + 7 x 10-8 x R2) ohm
R = Resistance in ohm
Temperature inputs (thermistors)
Range................................................................................................................................-50 to +150 °C (-58 to +302 °F)
Supported thermistors
Honeywell .............................................................................................................................................................20 kohm
Type I (Continuum) ...............................................................................................................................................10 kohm
Type II (I/NET) .......................................................................................................................................................10 kohm
Type III (Satchwell) ...............................................................................................................................................10 kohm
Type IV (FD) ......................................................................................................................................................... 10 kohm
Type V (FD w/ 11k shunt) ....................................................................................................................Linearized 10 kohm
Satchwell D?T......................................................................................................................................Linearized 10 kohm
Johnson Controls .................................................................................................................................................2.2 kohm
Xenta....................................................................................................................................................................1.8 kohm
Balco.......................................................................................................................................................................1 kohm
Measurement accuracy
20 kohm...................................................................................................-50 to -30 °C: +/-1.5 °C (-58 to -22 °F: +/-2.7 °F)
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 11
RP-C
SmartX IP Controller
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 12
RP-C
SmartX IP Controller
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 13
RP-C
SmartX IP Controller
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 14
RP-C
SmartX IP Controller
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 15
RP-C
SmartX IP Controller
a) For more information, see the Product Selection Guide (SmartX IP Controllers - Accessories). Abbreviations: UTP (Unshielded Twisted Pair), CMP (Plenum-rated
cable)
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 16
RP-C
SmartX IP Controller
a) For more information, see the Product Selection Guide (SmartX IP Controllers - Accessories). Abbreviations: UTP (Unshielded Twisted Pair), CMP (Plenum-rated
cable), LSZH (Low Smoke Zero Halogen)
a) For more information, see the Product Selection Guide (SmartX IP Controllers - Accessories). Abbreviations: UTP (Unshielded Twisted Pair), PVC (Polyvinyl
chloride)
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 17
RP-C
SmartX IP Controller
Regulatory Notices
Federal Communications Commission CE - Compliance to European Union (EU)
FCC Rules and Regulations CFR 47, Part 15, Class B 2014/53/EU Radio Equipment Directive (RED)
This device complies with part 15 of the FCC Rules. Operation is subject to the following two 2014/30/EU Electromagnetic Compatibility Directive
conditions: (1) This device may not cause harmful interference. (2) This device must accept 2014/35/EU Low Voltage Directive
any interference received, including interference that may cause undesired operation. 2011/65/EU Restriction of Hazardous Substances (RoHS) Directive
This equipment complies with the rules, of the Official Journal of the European Union, for
Industry Canada governing the Self Declaration of the CE Marking for the European Union as specified in the
This Class B digital apparatus complies with Canadian ICES-003. above directive(s) per the provisions of the following standards: EN 60730-1, EN 60730-2-
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada. 11, and EN 50491-3 Safety Standards.
UL 916 Listed products for the United States and Canada, Enclosed Energy
Management Equipment. UL file E80146.
eu.bac - European Building Automation and Controls Association. Certified
Product.
This product is certified by eu.bac and conforms to the quality and energy performance
criteria outlined by the following European product standard: EN 15500.
All eu.bac certified products are found on the eu.bac web site www.eubaccert.eu
www.schneider-electric.com
03-XX017-XX-en, DRAFT
© 2018 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.