Output data IG 15 IG 20 IG 30 IG 40 IG 60 HV
AC nominal output (Pac,r) 1,300 W 1,800 W 2,500 W 3,500 W 4,600 W
Max. output power 1,500 W 2,000 W 2,650 W 4,100 W 5,000 W
Max. output current (Iac max) 6.5 A 8.7 A 11.5 A 17.8 A 21.7 A
Grid connection (Uac,r) 1~NPE 230 V
Min. output voltage (Uac min) 180 V
Max. output voltage (Uac max) 270 V
Frequency (fr) 50 Hz / 60 Hz
Frequency range (fmin – fmax) 47 Hz – 65 Hz
Distortion factor <3 %
Power factor (cos φac,r) 1
General data IG 15 IG 20 IG 30 IG 40 IG 60 HV
Dimensions (height x width x depth) 366 x 344 x 220 mm / 500 x 435 x 225 mm1) 610 x 344 x 220 mm / 733 x 435 x 225 mm1)
Weight 9 kg / 12 kg1) 16 kg / 20 kg1)
Degree of protection IP 21 / IP 451)
Protection class 1
Overvoltage category (DC / AC) 2/3
Night-time consumption <1W
Inverter concept HF transformer
Cooling Regulated air cooling
Installation Indoor and outdoor installation1)
Ambient temperature range from -20°C to +50°C
Permitted humidity 0 % to 95 %
DC connection technology Fronius Indoor Screw terminal connection 1.5 – 10 mm²; DC plug optional2)
DC connection technology Fronius Outdoor DC plug2)
AC connection technology Fronius Indoor Screw terminal connection 1.5 – 10 mm²; plug optional
AC connection technology Fronius Outdoor Screw terminal connection 1.5 – 10 mm²
DIN V VDE V 0126-1-1, ÖVE/ÖNORM E 8001-4-712, UTE C15-712-1, EN 50438, G83, G59, C 10 / 11, CER 06-190,
Certificates and compliance with standards
AS 4777-1, AS 4777-2, AS 4777-3
This applies to Fronius IG Outdoor 2) MC3, MC4 or Tyco
1)
Further information regarding the availability of the inverters in your country can be found at www.fronius.com.
Fronius IG 60 HV efficiency curve Fronius IG temperature derating
96 6.000
94 Fronius IG 60 HV
5.000
92
90 4.000
88
3.000 Fronius IG 30
86
2.000
84
82 1.000
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 20 25 30 35 40 45 50
STANDARDISED OUTPUT POWER PAC /PAC,R ■ 150 V ■ 280 V ■ 400 V AMBIENT TEMPERATURE [°C] ■ 150 V ■ 280 V ■ 400 V
Efficiency IG 15 IG 20 IG 30 IG 40 IG 60 HV
Max. efficiency 94.2 % 94.3 % 94.3 % 94.3 % 94.3 %
European efficiency (ηEU) 91.4 % 92.3 % 92.9 % 93.2 % 93.5 %
η at 5% Pac,r1) 75.0 / 76.9 / 71.1 % 77.4 / 80.6 / 71.1 % 81.6 / 83.1 / 81.4 % 82.7 / 83.3 / 80.2 % 85.6 / 85.8 / 83.3 %
η at 10% Pac,r1) 81.6 / 83.1 / 81.4 % 84.9 / 86.2 / 83.4 % 87.4 / 88.6 / 85.9 % 88.5 / 89.3 / 85.0 % 90.0 / 90.3 / 87.5 %
η at 20% Pac,r1) 87.8 / 89.2 / 85.9 % 89.7 / 90.5 / 87.3 % 91.2 / 91.8 / 89.1 % 91.5 / 92.3 / 89.6 % 92.2 / 93.0 / 90.8 %
η at 25% Pac,r1) 89.3 / 89.9 / 86.8 % 90.8 / 91.3 / 88.5 % 91.8 / 92.7 / 90.2 % 92.1 / 92.9 / 90.6 % 92.4 / 93.5 / 91.6 %
η at 30% Pac,r1) 90.1 / 90.7 / 87.9 % 91.5 / 92.3 / 89.8 % 92.3 / 93.2 / 90.9 % 92.4 / 93.3 / 91.1 % 92.5 / 93.6 / 92.1 %
All information is without guarantee in spite of careful editing - liability excluded. Copyright © 2011 Fronius™. All rights reserved.
η at 50% Pac,r1) 92.0 / 92.9 / 90.3 % 92.6 / 93.7 / 91.4 % 92.8 / 94.0 / 92.4 % 92.7 / 93.9 / 91.5 % 92.9 / 94.3 / 92.3 %
η at 75% Pac,r1) 92.7 / 93.8 / 91.7 % 92.8 / 94.3 / 92.6 % 92.4 / 94.3 / 92.8 % 92.9 / 94.1 / 92.6 % 92.5 / 94.1 / 92.9 %
η at 100% Pac,r1) 92.8 / 94.2 / 92.5 % 92.4 / 94.0 / 92.9 % 92.0 / 93.4 / 92.6 % 92.5 / 94.3 / 92.9 % 92.0 / 93.7 / 92.7 %
MPP adaptation efficiency > 99.9 %
Text and images correspond to the current state of technology at the time of printing. Subject to modifications.
Protective equipment IG 15 IG 20 IG 30 IG 40 IG 60 HV
DC insulation measurement Warning/shutdown (depending on country setup) at R ISO < 500 kOhm
Overload behaviour Operating point shift. power limitation
Reverse polarity protection Integrated
INTERFACES IG 15 IG 20 IG 30 IG 40 IG 60 HV
Optional with Fronius Datamanager WLAN, Ethernet, Modbus TCP, 6 digital inputs, 4 digital inputs/outputs, Datalogger, Webserver
and at Umpp min / Udc,r / Umpp max.
1)
Further information regarding the availability of the inverters in your country can be found at www.fronius.com.
Further information about all Fronius products and our global sales partners and representatives can be found at www.fronius.com
v01 2013 EN
M,06,0009,EN v01 Sep 2013 as14