0% found this document useful (0 votes)
30 views

CH14NB-Install-instructions-CP

The document provides installation instructions for a split-system heat pump using R-410A refrigerant, emphasizing safety considerations and proper installation techniques. It outlines necessary precautions, equipment checks, and specific requirements for various applications, including low-ambient cooling and sea coast installations. Additionally, it includes guidelines for piping connections, refrigerant charge, and clearance requirements to ensure optimal operation and compliance with regional efficiency standards.

Uploaded by

bartfuentes111
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views

CH14NB-Install-instructions-CP

The document provides installation instructions for a split-system heat pump using R-410A refrigerant, emphasizing safety considerations and proper installation techniques. It outlines necessary precautions, equipment checks, and specific requirements for various applications, including low-ambient cooling and sea coast installations. Additionally, it includes guidelines for piping connections, refrigerant charge, and clearance requirements to ensure optimal operation and compliance with regional efficiency standards.

Uploaded by

bartfuentes111
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

CH14NB

SPLIT–SYSTEM HEAT PUMP


WITH R–410A REFRIGERANT
1--1/2 TO 5 TONS

Installation Instructions
NOTE: Read the entire instruction manual before starting the INSTALLATION RECOMMENDATIONS
installation.
NOTE: In some cases noise in the living area has been traced to
SAFETY CONSIDERATIONS
gas pulsations from improper installation of equipment.
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other 1. Locate unit away from windows, patios, decks, etc. where
conditions which may cause death, personal injury, or property unit operation sound may disturb customer.
damage. Consult a qualified installer, service agency, or your 2. Ensure that vapor and liquid tube diameters are appropriate
distributor or branch for information or assistance. The qualified for unit capacity.
installer or agency must use factory–authorized kits or accessories 3. Run refrigerant tubes as directly as possible by avoiding un-
when modifying this product. Refer to the individual instructions necessary turns and bends.
packaged with the kits or accessories when installing. 4. Leave some slack between structure and unit to absorb vi-
Follow all safety codes. Wear safety glasses, protective clothing, bration.
and work gloves. Use quenching cloth for brazing operations. 5. When passing refrigerant tubes through the wall, seal open-
Have fire extinguisher available. Read these instructions ing with RTV or other pliable silicon–based caulk (see Fig.
thoroughly and follow all warnings or cautions included in 1).
literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code (NEC) NFPA 70. 6. Avoid direct tubing contact with water pipes, duct work,
In Canada, refer to current editions of the Canadian electrical code floor joists, wall studs, floors, and walls.
CSA 22.1. 7. Do not suspend refrigerant tubing from joists and studs with
a rigid wire or strap which comes in direct contact with
Recognize safety information. This is the safety–alert symbol !! .
tubing (see Fig. 1).
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. 8. Ensure that tubing insulation is pliable and completely sur-
Understand these signal words; DANGER, WARNING, and rounds vapor tube.
CAUTION. These words are used with the safety–alert symbol. 9. When necessary, use hanger straps which are 1 in. wide and
DANGER identifies the most serious hazards which will result in conform to shape of tubing insulation (see Fig. 1).
severe personal injury or death. WARNING signifies hazards 10. Isolate hanger straps from insulation by using metal sleeves
which could result in personal injury or death. CAUTION is used bent to conform to shape of insulation.
to identify unsafe practices which may result in minor personal OUTDOOR WALL INDOOR WALL

injury or product and property damage. NOTE is used to highlight CAULK


LIQUID TUBE

suggestions which will result in enhanced installation, reliability, or


operation.
SUCTION TUBE

WARNING
INSULATION

! THROUGH THE WALL

ELECTRICAL SHOCK HAZARD


JOIST
HANGER STRAP
(AROUND SUCTION
TUBE ONLY) INSULATION

Failure to follow this warning could result in personal injury SUCTION TUBE

or death.
Before installing, modifying, or servicing system, main 1” (25.4 mm)

electrical disconnect switch must be in the OFF position. MIN


SUSPENSION
LIQUID TUBE

There may be more than 1 disconnect switch. Lock out and A07588
tag switch with a suitable warning label. Fig. 1 – Connecting Tubing Installation

WARNING
When outdoor unit is connected to factory–approved indoor unit,
! outdoor unit contains system refrigerant charge for operation with
AHRI rated indoor unit when connected by 15 ft. (4.57 m) of
EXPLOSION HAZARD field–supplied or factory accessory tubing. For proper unit
Failure to follow this warning could operation, check refrigerant charge using charging information
result in death, serious personal injury, located on control box cover and/or in the Check Charge section of
and/or property damage. this instruction.
Never use air or gases containing IMPORTANT: Maximum liquid–line size is 3/8–in. OD for all
oxygen for leak testing or operating residential applications including long line.
refrigerant compressors. Pressurized IMPORTANT: Always install the factory–supplied liquid–line
mixtures of air or gases containing filter drier. Obtain replacement filter driers from your distributor or
oxygen can lead to an explosion. branch.

Catalog No: CH14NB--- 01SI


Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New
INSTALLATION NOTE: 18” (457.2 mm) clearance option described above is
approved for outdoor units with wire grille coil guard only.
IMPORTANT: Effective January 1, 2015, all split system air
Units with louver panels require 24” (609.6 mm) between units.
conditioners and heat pumps must be installed pursuant to the
regional efficiency standards issued by the Department of On rooftop applications, locate unit at least 6 in. above roof
Energy. surface.
3/8–in. (9.53 mm) Dia.

CAUTION
Tiedown Knockouts in
! Basepan(2) Places

CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when handling
parts.

Check Equipment and Job Site


View From Top
Unpack Unit
UNIT BASE PAN TIEDOWN KNOCKOUT LOCATIONS in. (mm)
Move to final location. Remove carton taking care not to damage Dimension in. (mm) A B C
unit. 23 X 23
(585 X 585) 7–3/4 (196.8) 4–13/32 (111.9) 18–1/32 (457.9)
Inspect Equipment
26 X 26
9–1/8 (231.8) 4–7/16 (112.7) 21–1/4 (539.8)
File claim with shipping company prior to installation if shipment (660 X 660)
is damaged or incomplete. Locate unit rating plate on unit corner 31–1/2 X 31–1/2
(800 X 800) 9–1/8 (231.8) 6–9/16 (166.7) 24–11/16 (627.1)
panel. It contains information needed to properly install unit.
35 X 35
Check rating plate to be sure unit matches job specifications. (889 X 889) 9–1/8 (231.8) 6–9/16 (166.7) 28–7/16 (722.3)

Install on a Solid, Level Mounting Pad Fig. 2 – Tiedown Knockout Locations


A05177

If conditions or local codes require the unit be attached to pad, tie Operating Ambient
down bolts should be used and fastened through knockouts
The minimum outdoor operating ambient in cooling mode without
provided in unit base pan. Refer to unit mounting pattern in Fig. 2
to determine base pan size and knockout hole location. accessory is 55°F (12.78°C), and the maximum outdoor operating
ambient in cooling mode is 125°F (51.67°C). The maximum
For hurricane tie downs, contact distributor for details and PE outdoor operating ambient in heating mode is 66 °F (18.89°C).
Certification (Professional Engineer), if required.
On rooftop applications, mount on level platform or frame. Place
Check Defrost Thermostat
unit above a load–bearing wall and isolate unit and tubing set from Check defrost thermostat to ensure it is properly located and
structure. Arrange supporting members to adequately support unit securely attached. There is a liquid header with a distributor and
and minimize transmission of vibration to building. Consult local feeder tube going into outdoor coil. At the end of the one of the
codes governing rooftop applications. feeder tubes, there is a 3/8 in. O.D. stub tube approximately 2 in.
Roof mounted units exposed to winds above 5 mph may require (50.8 mm) long (see Fig. 3). The defrost thermostat should be
wind baffles. Consult the Service Manual – Residential Split located on stub tube. Note that there is only one stub tube used
System Air Conditioners and Heat Pumps for wind baffle with liquid header, and on most units it is the bottom circuit.
construction. FEEDER TUBE

NOTE: Unit must be level to within ±2° (3/8 in/ft,9.5 mm/m) STUB TUBE
per compressor manufacturer specifications.
Clearance Requirements
When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm)
clearance to service end of unit and 48 in. (1219.2 mm) (above
unit. For proper airflow, a 6–in. (152.4 mm) clearance on 1 side of
unit and 12–in. (304.8 mm) on all remaining sides must be DEFROST
maintained. Maintain a distance of 24 in. (609.6 mm) between THERMOSTAT

units or 18 in. (457.2 mm) if no overhang within 12 ft. (3.66 m).


Position so water, snow, or ice from roof or eaves cannot fall A97517
directly on unit. Fig. 3 – Defrost Thermostat Location

Catalog No: CH14NB--- 01SI


Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New
2
Table 1 – Accessory Usage
REQUIRED FOR LOW–AMBIENT REQUIRED FOR
REQUIRED FOR
Accessory COOLING APPLICATIONS SEA COAST APPLICATIONS
LONG LINE APPLICATIONS*
(Below 55F / 12.8C) (Within 2 miles / 3.22 km)
Accumulator Standard Standard Standard
Ball Bearing Fan Motor Yes{ No No
Compressor Start Assist Capacitor and
Yes Yes No
Relay
Crankcase Heater Yes Yes No
Evaporator Freeze Thermostat Yes No No
Hard Shutoff TXV Yes Yes No
Isolation Relay Yes No No
Liquid Line Solenoid Valve No See Long–Line Application Guideline No
Motor Master Control or
Yes No No
Low Ambient Switch
Support Feet Recommended No Recommended
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Piping and Longline Guideline. .
{ Additional requirement for Low–Ambient Controller (full modulation feature) MotorMasterr Control. Always Ask For

Make Piping Connections Service Valves


Service valves are closed and plugged from the factory. Outdoor
! WARNING units are shipped with a refrigerant charge sealed in the unit. Leave
the service valves closed until all other refrigerant system work is
PERSONAL INJURY AND ENVIRONMENTAL complete or the charge will be lost. Leave the plugs in place until
HAZARD line set tubing is ready to be inserted.
Failure to follow this warning could result in personal injury Heat pumps require a piston metering device in the liquid service
or death. valve for proper heating operation. Piston is shipped in the piston
Relieve pressure and recover all refrigerant before system body of the liquid service valve, temporarily held in place with a
repair or final unit disposal. plastic cap. Do not remove the plastic cap until line set tubing is
Use all service ports and open all flow–control devices, ready to be installed.
including solenoid valves. Refer to Fig. 4 and follow these steps for piston installation:
1. Remove plastic cap holding piston in piston body of liquid

! CAUTION service valve.


2. Check that piston size (stamped on side of piston) matches
with number listed on unit rating plate. Return piston to
UNIT DAMAGE HAZARD
piston body of liquid service valve (either direction).
Failure to follow this caution may result in equipment damage 3. Find plastic bag taped to unit containing copper adapter
or improper operation.
tube, brass nut, and plastic washer.
If ANY refrigerant tubing is buried, provide a 6–in (152.4 4. Install plastic washer in the seat inside piston body.
mm). vertical rise at service valve. Refrigerant tubing lengths
up to 36–in (914.4 mm). may be buried without further special 5. Fit brass nut onto adapter tube and install tube onto liquid
consideration. Do not bury lines longer than 36 in (914.4 mm). service valve. Tighten nut finger tight, then wrench
additional ½ turn only [15--ft lbs (20.3 N--m)]. Over
Outdoor units may be connected to indoor section using accessory tightening may damage the plastic washer and service
tubing package or field–supplied refrigerant grade tubing of correct valve’s piston body.
size and condition. For tubing requirements beyond 80 ft, BRASS NUT
substantial capacity and performance losses can occur. Following
the recommendations in the Residential Piping and Long Line ADAPTER TUBE
Guideline will reduce these losses. Refer to Table 1 for accessory PLASTIC WASHER
requirements. Refer to Table 2 for field tubing diameters.
There are no buried–line applications greater than 36 in. (914.4
mm)
If refrigerant tubes or indoor coil are exposed to atmosphere, they PISTON
must be evacuated to 500 microns to eliminate contamination and
PISTON BODY
moisture in the system.
Outdoor Unit Connected To Factory Approved Indoor
Unit LIQUID SERVICE VALVE
Outdoor unit contains approximate system refrigerant charge for
A14235
operation with approved AHRI rated indoor unit when connected
Fig. 4 – Liquid Service Valve with Heating Piston and
by 15 ft (4.57 m) of field–supplied or factory–accessory tubing,
and factory supplied filter drier. Some indoor units require Adapter Tube
additional subcooling to achieve optimal heating performance.
Using Table 5 – Additional Subcooling Required, check refrigerant
charge for maximum efficiency

Catalog No: CH14NB--- 01SI


Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New
3
Table 2 – Refrigerant Connections and Recommended Liquid
and Vapor Tube Diameters (In.)
LIQUID RATED VAPOR
SERVICE VALVE UNIT SIZE Connection Tube Connection Tube
Diameter Diameter Diameter Diameter
VALVE CORE
18, 24 3/8 3/8 5/8 5/8
30, 36 3/8 3/8 3/4 3/4
42, 48 3/8 3/8 7/8 7/8
60 3/8 3/8 7/8 1–1/8
* Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance
data when using different size and length linesets.
Notes:
1. Do not apply capillary tube indoor coils to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or
A14236 20 ft. (6.09 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length, refer to
Fig. 5 – Vapor Service Valve the Residential Piping and Longline Guideline – Air Conditioners and Heat Pumps
using Puron refrigerant.

Brazing Connections Installing with Indoor Piston


Connect vapor tube to fitting on outdoor unit vapor service valves Heat pumps with piston indoor ratings are shipped with the correct
(see Table 2). Connect liquid tubing to adapter tube on liquid piston size in the accessory bag. Check piston size shipped with
service valve. Use refrigerant grade tubing. indoor unit to see if it matches required indoor piston size. If it

CAUTION
does not match, replace indoor piston with correct piston size
! which is listed on the rating plate.
NOTE: Heat pumps without piston indoor ratings may be
UNIT DAMAGE HAZARD installed as a replacement component in a piston system. When
Failure to follow this caution may result in equipment installing a non--piston rated heat pump with with a piston indoor
damage or improper operation. the correct indoor piston must be installed. When not listed on the
Service valves must be wrapped in a heat–sinking material rating plate the correct piston size is listed in the product data.
such as a wet cloth while brazing. Replacement pistons can be ordered from Replacement
Components.
Apply heat absorbing paste or heat sink product between service
valve and joint. Wrap service valves with a heat sinking material 13/16” BRASS HEX NUT
such as a wet cloth.
TEFLON® SEAL
After wrapping service valve with a wet cloth, tubing set can be
brazed to service valve using either silver bearing or non–silver TEFLON® 3/4” BRASS HEX BODY
RINGS
bearing brazing material. Do not use soft solder (materials which “H” DISTRIBUTOR
melt below 800°F/427°C). Consult local code requirements.
NOTE: Some outdoor units contain a mechanical fitting at the
liquid distributor. This connection is not field serviceable and
should not be disturbed.
NOTE: For Liquid Service Valve -- Braze lineset to adapter tube PISTON
BEFORE bolting adapter to valve. This helps prevent overheating PISTON RETAINER
and damage to plastic washer or o--ring.
A10342
For Vapor Service Valve -- remove valve core from schrader port Fig. 6 – Indoor Piston Installation
on Service Valve BEFORE brazing. This helps prevent
overheating and damage to valve seals (refer to Fig. 5). Replace
valve core when brazing is completed. Install Liquid Line Filter Drier Indoor
Refer to Fig. 7 and install filter drier as follows:
! WARNING 1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
FIRE HAZARD 3. Braze filter drier to 5 in. (127 mm) long liquid tube from
Failure to following this warning could result in personal step 1.
injury, death and/or property damage. 4. Connect and braze liquid refrigerant tube to the filter drier.
Refrigerant and oil mixture could ignite and burn as it escapes IMPORTANT: Installation of the filter drier in liquid line is
and contacts brazing torch. Make sure the refrigerant charge is required.
properly removed from both the high and low sides of the
system before brazing any component or lines.

Clean line set tube ends with emery cloth or steel brush. Remove
any grit or debris.
Insert line set tube ends into service valve tube stubs.
Apply heat absorbing paste or heat sink product between service
valve and joint. Wrap service valves with a heat sinking material
such as a wet cloth. A05227
Braze joints using a Sil--Fos or Phos--copper alloy. Fig. 7 – Liquid Line Filter Drier

Catalog No: CH14NB--- 01SI


Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New
4
Make Electrical Connections
! CAUTION
UNIT DAMAGE HAZARD ! WARNING
Failure to follow this caution may result in equipment damage ELECTRICAL SHOCK HAZARD
or improper operation.
Failure to follow this warning could result in personal injury or
Installation of filter drier in liquid line is required. death.
Evacuate Refrigerant Tubing and Indoor Coil Do not supply power to unit with compressor terminal box
cover removed.

! CAUTION NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch circuit disconnect of adequate size per NEC
UNIT DAMAGE HAZARD to handle unit starting current. Locate disconnect within sight from
Failure to follow this caution may result in equipment and readily accessible from unit, per Section 440–14 of NEC.
damage or improper operation. Route Ground and Power Wires
Never use the system compressor as a vacuum pump. Remove access panel to gain access to unit wiring. Extend wires
Refrigerant tubes and indoor coil should be evacuated using the from disconnect through power wiring hole provided and into unit
recommended deep vacuum method of 500 microns. The alternate control box.
triple evacuation method may be used (see triple evacuation Connect Ground and Power Wires
procedure in service manual). Always break a vacuum with dry
nitrogen.
Deep Vacuum Method
! WARNING
The deep vacuum method requires a vacuum pump capable of ELECTRICAL SHOCK HAZARD
pulling a vacuum of 500 microns and a vacuum gage capable of Failure to follow this warning could result in personal injury or
accurately measuring this vacuum depth. The deep vacuum method death.
is the most positive way of assuring a system is free of air and The unit cabinet must have an uninterrupted or unbroken
liquid water. A tight dry system will hold a vacuum of 1000 ground to minimize personal injury if an electrical fault should
microns after approximately 7 minutes. (See Fig. 8.) occur. The ground may consist of electrical wire or metal
5000 conduit when installed in accordance with existing electrical
4500 codes.
4000
LEAK IN Connect ground wire to ground connection in control box for
3500 SYSTEM safety. Connect power wiring to contactor as shown in Fig. 9.
MICRONS

3000
2500 DISCONNECT
PER N.E.C. AND/OR
2000 LOCAL CODES
VACUUM TIGHT
1500 TOO WET CONTACTOR

1000
TIGHT
500 DRY SYSTEM FIELD POWER
WIRING

A95424 3 PHASE ONLY BLUE


0 1 2 3 4 5 6 7
MINUTES FIELD GROUND
A95424 WIRING
GROUND
Fig. 8 – Deep Vacuum Graph LUG

A94025
Final Tubing Check
Fig. 9 – Line Connections
IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, makings sure wire ties on feeder tubes are
secure and tight.
Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of
improper voltage. See unit rating plate for recommended circuit
protection device.
NOTE: Operation of unit on improper line voltage constitutes
abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage may fluctuate above or below
permissible limits.

A00010
Fig. 10 – 3–Phase Monitor Control
(Applies to 3–Phase Units Only)

Catalog No: CH14NB--- 01SI


Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New
5
Table 3 – 3–Phase Monitor LED Indicators Final Wiring Check
LED STATUS IMPORTANT: Check factory wiring and field wire connections
OFF No call for compressor operation
FLASHING Reversed phase
to ensure terminations are secured properly. Check wire routing to
ON Normal ensure wires are not in contact with tubing, sheet metal, etc.
Compressor Crankcase Heater
Connect Control Wiring When equipped with a crankcase heater, furnish power to heater a
Route 24v control wires through control wiring grommet and minimum of 24 hr before starting unit. To furnish power to heater
connect leads to control wiring. See Thermostat Installation only, set thermostat to OFF and close electrical disconnect to
Instructions for wiring specific unit combinations. (See Fig. 11.) outdoor unit.
Use No. 18 AWG color–coded, insulated (35°C minimum) wire. If A crankcase heater is required if refrigerant tubing is longer than
thermostat is located more than 100 ft (30.5 m) from unit, as 80 ft (23.4 m), or when outdoor unit is 20 ft (6.09 m) below indoor
measured along the control voltage wires, use No. 16 AWG unit. Refer to the Residential Piping and Long Line Guideline.
color–coded wire to avoid excessive voltage drop.
Install Electrical Accessories
All wiring must be NEC Class 2 and must be separated from
incoming power leads. Refer to the individual instructions packaged with kits or
accessories when installing.
Use furnace transformer, fan coil transformer, or accessory
transformer for control power, 24v/40va minimum. Start–Up
NOTE: Use of available 24v accessories may exceed the
minimum 40va power requirement. Determine total transformer ! CAUTION
loading and increase the transformer capacity or split the load with
an accessory transformer as required. PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
TYPICAL HEAT
HP THERMOSTAT FAN COIL PUMP Wear safety glasses, protective clothing, and gloves when
handling refrigerant and observe the following:
24 VAC HOT R R R S Front seating service valves are equipped with Schrader valves.

24 VAC COM C C C

HEAT STAGE 2 W2 W2 *
W2
! CAUTION
COOL/HEAT E * ENVIRONMENTAL HAZARD
STAGE 1 Y Y
W3 * Failure to follow this caution may result in environmental
INDOOR FAN G
G damage.
RVS COOLING O O Federal regulations require that you do not vent refrigerant to
the atmosphere. Recover during system repair or final unit
EMERGENCY E
* IF AVAILABLE disposal.
HEAT

LEGEND
24-V FACTORY WIRING
! CAUTION
24-V FIELD WIRING
UNIT OPERATION AND SAFETY HAZARD
FIELD SPLICE CONNECTION Failure to follow this caution may result in personal injury,
equipment damage or improper operation.
ODT

OUTDOOR THERMOSTAT

EHR EMERGENCY HEAT RELAY S Do not overcharge system with refrigerant.


SHR SUPPLEMENTAL HEAT RELAY S Do not operate unit in a vacuum or at negative pressure.
S Do not disable low pressure switch in scroll compressor
applications.
A02325 / A97413
Fig. 11 – Generic Wiring Diagrams S Compressor dome temperatures may be hot.
(See thermostat Installation Instructions
Follow these steps to properly start up system:
for specific unit combinations)
1. After system is evacuated, fully open liquid and vapor ser-
vice valves.
2. Unit is shipped with valve stem(s) front seated (closed) and
caps installed. Replace stem caps after system is opened to
refrigerant flow (back seated). Replace caps finger–tight and
tighten with wrench an additional 1/12 turn.
3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Be sure set
point is below indoor ambient temperature.
5. Set room thermostat to HEAT or COOL and fan control to
ON or AUTO mode, as desired. Operate unit for 15
minutes. Check system refrigerant charge.

Catalog No: CH14NB--- 01SI


Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New
6
Sequence of Operation The electronic defrost timer sequence is enabled when the T1 input
Turn on power to indoor and outdoor units. Transformer is on the board is energized. The timer starts only when the defrost
energized. thermostat is closed and the contactor is energized.
Cooling Defrost mode is identical to cooling mode except that outdoor fan
motor stops and second–stage heat is turned on to continue
On a call for cooling, thermostat makes circuits R–O and R–Y, and warming conditioned spaces.
R–G. Circuit R–O energizes reversing valve, switching it to
cooling position. Circuit R–Y energizes contactor, starting outdoor To initiate defrost, the defrost thermostat must be closed. This can
fan motor and compressor circuit. R–G energizes indoor unit be accomplished as follows:
blower relay, starting indoor blower motor on high speed. 1. Turn off power to outdoor unit.
When thermostat is satisfied, its contacts open, de–energizing 2. Disconnect outdoor fan motor lead from OF2 on control
contactor and blower relay. Compressor and motors should stop. board (see Fig. 12). Tape lead to prevent grounding.
NOTE: If indoor unit is equipped with a time–delay relay circuit, 3. Restart unit in heating mode, allowing frost to accumulate
the indoor blower will run an additional 90 seconds to increase on outdoor coil.
system efficiency. 4. After a few minutes in heating mode, liquid line temperat-
Heating ure should drop below closing point of defrost thermostat
(approximately 30°F/–1.11°C).
On a call for heating, thermostat makes circuits R–Y and R–G.
5. Short between speedup terminals with a flat–blade screw-
Circuit R–Y energizes contactor, starting outdoor fan motor and
driver. This reduces the timing sequence to 1/25th of origin-
compressor. Circuit R–G energizes indoor blower relay, starting
al time. (See Table 4.)
blower motor on high speed.
6. When you hear reversing valve change position, remove
Should temperature continue to fall, R–W2 is made through
screwdriver immediately; otherwise, control will terminate
second–stage room thermostat. Circuit R–W2 energizes a relay,
normal 10–minute defrost cycle in approximately 2
bringing on first bank of supplemental electric heat and providing
seconds.
electrical potential to second heater relay (if used). If outdoor
temperature falls below setting of outdoor thermostat (field NOTE: Length of defrost cycle is dependent upon length of time
installed option), contacts close to complete circuit and bring on it takes to remove screwdriver from test pins after reversing valve
second bank of supplemental electric heat. has shifted.
When thermostat is satisfied, its contacts open, de–energizing 7. Unit will remain in defrost for remainder of defrost cycle
contactor and relay. All heaters and motors should stop. time or until defrost thermostat reopens at approximately
Defrost 65°F (18.33°C) coil temperature of liquid line.
The defrost control is a time/temperature control which includes a 8. Turn off power to outdoor unit and reconnect fan motor
field selectable (quick–connects located at board edge) time period lead to OF2 on control board.
between defrost cycles (30, 60, or 90 minutes), factory set to either
60 or 90 minutes.

OUTDOOR FAN
RELAY
HK32EA001

DEFROST THERMOSTAT
MUST BE CLOSED BEFORE
DEFROST TIMER BEGINS

T1 - ENABLES DEFROST Y OUTPUT TO PRESSURE


TIMER.MUST BE SWITCHES AND CONTACTOR
ENERGIZED FOR
DEFROST TIMER
TO START
C - COMMON

O - REVERSING VALVE

SPEEDUP

THERMOSTAT INPUTS
A05332
Fig. 12 – Defrost Control
Table 4 – Defrost Control Speedup–Timing Sequence
MINIMUM MAXIMUM SPEEDUP
PARAMETER
(MINUTES) (MINUTES) (NOMINAL)
30–minute cycle 27 33 7 sec
50–minute cycle 45 55 12 sec
90–minute cycle 81 99 21 sec
10–minute cycle 9 11 2 sec
5 minutes 4.5 5.5 1 sec

Catalog No: CH14NB--- 01SI


Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New
7
Check Charge
Factory charge amount and desired subcooling are shown on unit Units with Indoor Pistons
rating plate. Additional subcooling may be required to achieve Units installed with indoor pistons require charging by the
optimal heating performance based on the installed indoor unit. superheat method.
(see Table 5).
The following procedure is valid when indoor airflow is within
Charging method is shown on information plate inside unit. For
TXV, use subcooling method. For piston, use superheat method. 21 percent of its rated CFM.
To properly check or adjust charge, conditions must be favorable 1. Operate unit a minimum of 10 minutes before checking
for subcooling or superheat charging. Favorable conditions exist charge.
when the outdoor temperature is between 70_F and 100_F 2. Measure suction pressure by attaching an accurate gage to
(21.11_C and 37.78_C), and the indoor temperature is between suction valve service port.
70_F and 80_F (21.11_C and 26.67_C). Follow the procedure 3. Measure suction temperature by attaching an accurate ther-
below: mistor type or electronic thermometer to suction line at ser-
Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge vice valve.
by adding or removing 0.6 oz/ft (.018 kg/m) of 3/8 liquid line 4. Measure outdoor air dry–bulb temperature with thermomet-
above or below 15ft (4.57 m) respectively. er.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow 5. Measure indoor air (entering indoor coil) wet–bulb temper-
system to operate in cooling mode at least 15 minutes. If conditions ature with a sling psychrometer.
are favorable, check system charge by super heat method for fixed
metering device and subcooling method for TXV. If any 6. Refer to Table 7. Find outdoor temperature and evaporator
adjustment is necessary, adjust charge slowly and allow system to entering air wet–bulb temperature. At this intersection, note
operate for 15 minutes to stabilize before declaring a properly superheat. Where a dash (––) appears on the table, do not
charged system. Refer to Table 5 for additional subcooling attempt to charge system under these conditions or refriger-
required. ant slugging may occur. Charge must be weighted in,
adding or removing 0.6 oz/ft of 3/8 liquid line above or be-
If the indoor temperature is above 80_F (26.67_C), and the low 15 ft (4.57 m) respectively.
outdoor temperature is in the favorable range, adjust system charge
by weight based on line length and allow the indoor temperature to 7. Refer to Table 8. Find superheat temperature located in item
drop to 80_F (26.67_C) before attempting to check system charge 6 and suction pressure. At this intersection, note suction line
by subcooling method as described above. temperature.
If the indoor temperature is below 70_F (21.11_C), or the outdoor 8. If unit has a higher suction line temperature than charted
temperature is not in the favorable range, adjust charge for line set temperature, add refrigerant until charted temperature is
length above or below 15ft (4.57 m) only. Charge level should then reached.
be appropriate for the system to achieve rated capacity. The charge 9. If unit has a lower suction line temperature than charted
level could then be checked at another time when the both indoor temperature, reclaim refrigerant until charted temperature is
and outdoor temperatures are in a more favorable range. reached.
NOTE: If line length is beyond 80 ft (24.38 m) or greater than 20 10. When adding refrigerant, charge in liquid form into suction
ft (6.10 m) vertical separation, See Residential Piping and Long service port using a flow–restricting device.
Line Guideline for special charging requirements. 11. If outdoor air temperature or pressure at suction valve
Units with Cooling Mode TXV changes, charge to new suction line temperature indicated
on chart.
Units installed with cooling mode TXV require charging by the
subcooling method. 12. Optimum performance will be achieved when the operating
1. Operate unit a minimum of 10 minutes before checking charge produces 5_ to 6_F suction superheat at suction
charge. service valve with 82_F outdoor ambient and 80_F
2. Measure liquid service valve pressure by attaching an accur- (26.7_C) dry bulb (67_F / 19.4_C) wet bulb) indoor
ate gage to service port. temperature (DOE “B” test conditions) at rated airflow.
3. Measure liquid line temperature by attaching an accurate Heating Check Chart Procedure
thermistor type or electronic thermometer to liquid line near To check system operation during heating cycle, refer to the
outdoor coil. Heating Check Chart on outdoor unit. This chart indicates whether
4. Refer to unit rating plate for required subcooling temperat- a correct relationship exists between system operating pressure and
ure. air temperature entering indoor and outdoor units. If pressure and
5. Refer to Table 6. Find the point where required subcooling temperature do not match on chart, system refrigerant charge may
temperature intersects measured liquid service valve pres- not be correct. Do not use chart to adjust refrigerant charge.
sure.
6. To obtain required subcooling temperature at a specific li-
quid line pressure, add refrigerant if liquid line temperature
is higher than indicated or reclaim refrigerant if temperature
is lower. Allow a tolerance of 3_F.

Catalog No: CH14NB--- 01SI


Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New
8
Table 5 – Additional Subcooling Required
Subcooling Delta from Rating Plate Value

Outdoor Unit Tonnage


Indoor Unit | Additional Subcooling Required
18 24 30 36 42 48 60

CAP**1814AL* --- CAP**2414AL* --- CAP**3014AL* --- CAP**3614AL* --- CAP**4221AL* --- CAP**4817AL* +5 CAP**6021AL* ---

CAP**2414AL* --- CAP**2417AL* --- CAP**3017AL* --- CAP**3617AL* --- CAP**4224AL* --- CAP**4821AL* +3 CAP**6024AL* ---

CAP**2417AL* --- CAP**2517AL* +5 CAP**3614AL* --- CAP**3621AL* --- CAP**4321AL* +5 CAP**4824AL* +3 CAP**6124AL* ---

CNPV*1814AL* --- CAP**3014AL* --- CAP**3617AL* --- CAP**4221AL* +3 CAP**4817AL* +5 CAP**6021AL* +5 CNPV*6024AL* ---

CNPV*2414AL* +3 CAP**3017AL* --- CAP**3621AL* --- CAP**4224AL* +3 CAP**4821AL* +3 CAP**6024AL* +5 CSPH*6012AL* ---

CNPV*2417AL* +3 CNPV*2414AL* --- CAP**3717AL* +5 CNPV*3617AL* --- CAP**4824AL* +3 CAP**6124AL* +5 FB4CNP060L ---

CSPH*2412AL* +3 CNPV*2417AL* --- CAP**3721AL* +5 CNPV*3621AL* --- CNPV*4217AL* --- CNPV*4821AL* --- FV4CNB006L ---

FB4CNF018L --- CNPV*3014AL* --- CNPV*3014AL* --- CNPV*4217AL* +3 CNPV*4221AL* --- CNPV*4824AL* --- FX4DN(B,F)061L ---

FB4CNF024L --- CNPV*3017AL* --- CNPV*3017AL* --- CNPV*4221AL* +3 CNPV*4821AL* --- CNPV*6024AL* +3

FB4CNP018L --- CSPH*2412AL* --- CNPV*3617AL* --- CSPH*3612AL* +3 CNPV*4824AL* --- CSPH*4812AL* ---

FB4CNP024L --- CSPH*3012AL* --- CNPV*3621AL* --- CSPH*4212AL* +5 CSPH*4212AL* --- CSPH*6012AL* +3

FFMANP018 --- FB4CNF030L --- CSPH*3012AL* --- FB4CNF036L --- CSPH*4812AL* --- FB4CNF048L ---

FFMANP019 --- FB4CNP030L --- CSPH*3612AL* +3 FB4CNF042L +5 FB4CNF042L --- FB4CNP048L ---

FFMANP024 --- FFMANP024 --- FB4CNF030L --- FB4CNP036L --- FB4CNF048L --- FB4CNP060L +3

FFMANP025 --- FFMANP025 --- FB4CNF036L --- FB4CNP042L +5 FB4CNP042L --- FV4CN(B,F)005L +3

FPMAN*018 --- FFMANP030 --- FB4CNP030L --- FFMANP036 --- FB4CNP048L --- FV4CNB006L +5

FPMAN*024 --- FFMANP031 --- FB4CNP036L --- FFMANP037 --- FV4CN(B,F)003L --- FX4DN(B,F)049L +3

FPMBN*018 --- FPMAN*024 --- FFMANP030 --- FPMAN*036 --- FV4CN(B,F)005L +3 FX4DN(B,F)061L +5

FPMBN*024 --- FPMAN*030 --- FFMANP031 --- FV4CN(B,F)003L --- FV4CNB006L +5

FV4CN(B,F)003L +5 FPMBN*024 --- FFMANP036 --- FV4CN(B,F)005L +5 FX4DN(B,F)043L ---

FV4CNF002L +5 FPMBN*030 --- FFMANP037 --- FV4CNB006L +5 FX4DN(B,F)049L +3

FX4DNF019L +3 FV4CN(B,F)003L --- FPMAN*030 --- FV4CNF002L --- FX4DN(B,F)061L +5

FX4DNF025L +3 FV4CNF002L --- FPMAN*036 --- FX4DN(B,F)037L +5

FX4DN(B,F)031L --- FPMBN*030 --- FX4DN(B,F)043L +5

FX4DN(B,F)037L +5 FV4CN(B,F)003L --- FX4DN(B,F)049L +5

FX4DNF025L --- FV4CN(B,F)005L +5

FV4CNF002L ---

FX4DN(B,F)031L ---

FX4DN(B,F)037L +5

FX4DN(B,F)043L +5

Catalog No: CH14NB--- 01SI


Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New
9
Table 6 – Required Liquid Line Temperatures _F
LIQUID PRESSURE AT REQUIRED SUBCOOLING TEMPERATURE (° F)
SERVICE VALVE (PSIG) 8 10 12 14 16 18
251 76 74 72 70 68 66
259 78 76 74 72 70 68
266 80 78 76 74 72 70
274 82 80 78 76 74 72
283 84 82 80 78 76 74
291 86 84 82 80 78 76
299 88 86 84 82 80 78
308 90 88 86 84 82 80
317 92 90 88 86 84 82
326 94 92 90 88 86 84
335 96 94 92 90 88 86
345 98 96 94 92 90 88
354 100 98 96 94 92 90
364 102 100 98 96 94 92
374 104 102 100 98 96 94
384 106 104 102 100 98 96
395 108 106 104 102 100 98
406 110 108 106 104 102 100
416 112 110 108 106 104 102
427 114 112 110 108 106 104
439 116 114 112 110 108 106
450 118 116 114 112 110 108
462 120 118 116 114 112 110
474 122 120 118 116 114 112
486 124 122 120 118 116 114
499 126 124 122 120 118 116
511 128 126 124 122 120 118

Table 7 – Superheat Charging (Heat Pump Only)


EVAPORATOR ENTERING AIR TEMPERATURE (° F WB)
OUTDOOR TEMP (° F)
50 52 54 56 58 60 62 64 67 68 70 72 74 76
55 11 11 12 12 12 13 17 20 24 24 25 25 25 25
60 6 6 7 7 7 7 12 16 21 22 23 23 23 23
65 – – – – – 3 7 12 18 19 21 21 22 22
70 – – – – – – – 7 14 16 18 20 20 20
75 – – – – – – – 3 11 13 16 18 18 19
82 – – – – – – – – *6 8 12 15 16 17
85 – – – – – – – – 4 7 11 14 15 16
90 – – – – – – – – – 4 8 12 14 15
95 – – – – – – – – – – 6 10 12 14
100 – – – – – – – – – – 4 8 11 12
105 – – – – – – – – – – 3 6 9 11
110 – – – – – – – – – – – 5 7 10
115 – – – – – – – – – – – 3 6 8
*Optimum performance point, 82° F outdoor ambient and (80° F dry bulb),( 67° F wet bulb) indoor conditions. (DOE B Test Conditions)
Where a dash (––) appears do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in.
Note: Superheat ° F is at low–side service port, Allow a tolerance of ± 3° F
Note: Indoor dry bulb between 70° F and 80° F

Table 8 – Required Suction–Line Temperature


SUCTION PRESSURE AT SERVICE PORT (PSIG)
SUPERHEAT TEMP (° F)
107.8 112.2 116.8 121.2 126 130.8 138.8 140.8 145.8
0 35 37 39 41 43 45 47 49 51
2 37 39 41 43 45 47 49 51 53
4 39 41 43 45 47 49 51 53 55
6 41 43 45 47 49 51 53 55 57
8 43 45 47 49 51 53 55 57 59
10 45 47 49 51 53 55 57 59 61
12 47 49 51 53 55 57 59 61 63
14 49 51 53 55 57 59 61 63 65
16 51 53 55 57 59 61 63 65 67
18 53 55 57 59 61 63 65 67 69
20 55 57 59 61 63 65 67 69 71
22 57 59 61 63 65 67 69 71 73
24 59 61 63 65 67 69 71 73 75
26 61 63 65 67 69 71 73 75 77
28 63 65 67 69 71 73 75 77 79
30 65 67 69 71 73 75 77 79 81

Catalog No: CH14NB--- 01SI


Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New
10
FINAL CHECKS CARE AND MAINTENANCE
IMPORTANT: Before leaving job, be sure to do the following: For continuing high performance and to minimize possible
1. Ensure that all wiring is routed away from tubing and sheet equipment failure, periodic maintenance must be performed on this
metal edges to prevent rub–through or wire pinching. equipment.
2. Ensure that all wiring and tubing is secure in unit before Frequency of maintenance may vary depending upon geographic
adding panels and covers. Securely fasten all panels and areas, such as coastal applications. See Users Manual for
covers. information.
3. Tighten service valve stem caps to 1/12–turn past finger
tight.
4. Leave Owner’s Manual with owner. Explain system opera-
tion and periodic maintenance requirements outlined in
manual.
5. Fill out Dealer Installation Checklist and place in customer
file.

PURONR (R–410A) QUICK REFERENCE GUIDE

S Puron refrigerant operates at 50–70 percent higher pressures than R–22. Be sure that servicing equipment and replacement
components are designed to operate with Puron
S Puron refrigerant cylinders are rose colored.
S Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
S Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when
charging into suction line with compressor operating
S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low–side retard.
S Use hoses with 700 psig service pressure rating.
S Leak detectors should be designed to detect HFC refrigerant.
S Puron, as with other HFCs, is only compatible with POE oils.
S Vacuum pumps will not remove moisture from oil.
S Do not use liquid–line filter driers with rated working pressures less than 600 psig.
S Do not leave Puron suction line filter driers in line longer than 72 hours.
S Do not install a suction–line filter drier in liquid line.
S POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
S POE oils may cause damage to certain plastics and roofing materials.
S Wrap all filter driers and service valves with wet cloth when brazing.
S A factory approved liquid–line filter drier is required on every unit.
S Do NOT use an R–22 TXV or properly sized Puron piston metering device..
S If indoor unit is equipped with an R–22 TXV or piston metering device sized for R--22 application, it must be changed to a hard
shutoff Puron TXV.
S Never open system to atmosphere while it is under a vacuum.
S When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter
driers. Evacuate to 500 microns prior to recharging.
S Do not vent Puron into the atmosphere.
S Do not use capillary tube coils.
S Observe all warnings, cautions, and bold text.

Catalog No: CH14NB--- 01SI


Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New
11
ECAC/BDP S 7310 W. Morris St. S Indianapolis, IN 46231 Edition Date: 11/14
Catalog No: CH14NB--- 01SI
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New
12

You might also like