CH14NB-Install-instructions-CP
CH14NB-Install-instructions-CP
Installation Instructions
NOTE: Read the entire instruction manual before starting the INSTALLATION RECOMMENDATIONS
installation.
NOTE: In some cases noise in the living area has been traced to
SAFETY CONSIDERATIONS
gas pulsations from improper installation of equipment.
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other 1. Locate unit away from windows, patios, decks, etc. where
conditions which may cause death, personal injury, or property unit operation sound may disturb customer.
damage. Consult a qualified installer, service agency, or your 2. Ensure that vapor and liquid tube diameters are appropriate
distributor or branch for information or assistance. The qualified for unit capacity.
installer or agency must use factory–authorized kits or accessories 3. Run refrigerant tubes as directly as possible by avoiding un-
when modifying this product. Refer to the individual instructions necessary turns and bends.
packaged with the kits or accessories when installing. 4. Leave some slack between structure and unit to absorb vi-
Follow all safety codes. Wear safety glasses, protective clothing, bration.
and work gloves. Use quenching cloth for brazing operations. 5. When passing refrigerant tubes through the wall, seal open-
Have fire extinguisher available. Read these instructions ing with RTV or other pliable silicon–based caulk (see Fig.
thoroughly and follow all warnings or cautions included in 1).
literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code (NEC) NFPA 70. 6. Avoid direct tubing contact with water pipes, duct work,
In Canada, refer to current editions of the Canadian electrical code floor joists, wall studs, floors, and walls.
CSA 22.1. 7. Do not suspend refrigerant tubing from joists and studs with
a rigid wire or strap which comes in direct contact with
Recognize safety information. This is the safety–alert symbol !! .
tubing (see Fig. 1).
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. 8. Ensure that tubing insulation is pliable and completely sur-
Understand these signal words; DANGER, WARNING, and rounds vapor tube.
CAUTION. These words are used with the safety–alert symbol. 9. When necessary, use hanger straps which are 1 in. wide and
DANGER identifies the most serious hazards which will result in conform to shape of tubing insulation (see Fig. 1).
severe personal injury or death. WARNING signifies hazards 10. Isolate hanger straps from insulation by using metal sleeves
which could result in personal injury or death. CAUTION is used bent to conform to shape of insulation.
to identify unsafe practices which may result in minor personal OUTDOOR WALL INDOOR WALL
WARNING
INSULATION
Failure to follow this warning could result in personal injury SUCTION TUBE
or death.
Before installing, modifying, or servicing system, main 1” (25.4 mm)
There may be more than 1 disconnect switch. Lock out and A07588
tag switch with a suitable warning label. Fig. 1 – Connecting Tubing Installation
WARNING
When outdoor unit is connected to factory–approved indoor unit,
! outdoor unit contains system refrigerant charge for operation with
AHRI rated indoor unit when connected by 15 ft. (4.57 m) of
EXPLOSION HAZARD field–supplied or factory accessory tubing. For proper unit
Failure to follow this warning could operation, check refrigerant charge using charging information
result in death, serious personal injury, located on control box cover and/or in the Check Charge section of
and/or property damage. this instruction.
Never use air or gases containing IMPORTANT: Maximum liquid–line size is 3/8–in. OD for all
oxygen for leak testing or operating residential applications including long line.
refrigerant compressors. Pressurized IMPORTANT: Always install the factory–supplied liquid–line
mixtures of air or gases containing filter drier. Obtain replacement filter driers from your distributor or
oxygen can lead to an explosion. branch.
CAUTION
Tiedown Knockouts in
! Basepan(2) Places
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when handling
parts.
If conditions or local codes require the unit be attached to pad, tie Operating Ambient
down bolts should be used and fastened through knockouts
The minimum outdoor operating ambient in cooling mode without
provided in unit base pan. Refer to unit mounting pattern in Fig. 2
to determine base pan size and knockout hole location. accessory is 55°F (12.78°C), and the maximum outdoor operating
ambient in cooling mode is 125°F (51.67°C). The maximum
For hurricane tie downs, contact distributor for details and PE outdoor operating ambient in heating mode is 66 °F (18.89°C).
Certification (Professional Engineer), if required.
On rooftop applications, mount on level platform or frame. Place
Check Defrost Thermostat
unit above a load–bearing wall and isolate unit and tubing set from Check defrost thermostat to ensure it is properly located and
structure. Arrange supporting members to adequately support unit securely attached. There is a liquid header with a distributor and
and minimize transmission of vibration to building. Consult local feeder tube going into outdoor coil. At the end of the one of the
codes governing rooftop applications. feeder tubes, there is a 3/8 in. O.D. stub tube approximately 2 in.
Roof mounted units exposed to winds above 5 mph may require (50.8 mm) long (see Fig. 3). The defrost thermostat should be
wind baffles. Consult the Service Manual – Residential Split located on stub tube. Note that there is only one stub tube used
System Air Conditioners and Heat Pumps for wind baffle with liquid header, and on most units it is the bottom circuit.
construction. FEEDER TUBE
NOTE: Unit must be level to within ±2° (3/8 in/ft,9.5 mm/m) STUB TUBE
per compressor manufacturer specifications.
Clearance Requirements
When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm)
clearance to service end of unit and 48 in. (1219.2 mm) (above
unit. For proper airflow, a 6–in. (152.4 mm) clearance on 1 side of
unit and 12–in. (304.8 mm) on all remaining sides must be DEFROST
maintained. Maintain a distance of 24 in. (609.6 mm) between THERMOSTAT
CAUTION
does not match, replace indoor piston with correct piston size
! which is listed on the rating plate.
NOTE: Heat pumps without piston indoor ratings may be
UNIT DAMAGE HAZARD installed as a replacement component in a piston system. When
Failure to follow this caution may result in equipment installing a non--piston rated heat pump with with a piston indoor
damage or improper operation. the correct indoor piston must be installed. When not listed on the
Service valves must be wrapped in a heat–sinking material rating plate the correct piston size is listed in the product data.
such as a wet cloth while brazing. Replacement pistons can be ordered from Replacement
Components.
Apply heat absorbing paste or heat sink product between service
valve and joint. Wrap service valves with a heat sinking material 13/16” BRASS HEX NUT
such as a wet cloth.
TEFLON® SEAL
After wrapping service valve with a wet cloth, tubing set can be
brazed to service valve using either silver bearing or non–silver TEFLON® 3/4” BRASS HEX BODY
RINGS
bearing brazing material. Do not use soft solder (materials which “H” DISTRIBUTOR
melt below 800°F/427°C). Consult local code requirements.
NOTE: Some outdoor units contain a mechanical fitting at the
liquid distributor. This connection is not field serviceable and
should not be disturbed.
NOTE: For Liquid Service Valve -- Braze lineset to adapter tube PISTON
BEFORE bolting adapter to valve. This helps prevent overheating PISTON RETAINER
and damage to plastic washer or o--ring.
A10342
For Vapor Service Valve -- remove valve core from schrader port Fig. 6 – Indoor Piston Installation
on Service Valve BEFORE brazing. This helps prevent
overheating and damage to valve seals (refer to Fig. 5). Replace
valve core when brazing is completed. Install Liquid Line Filter Drier Indoor
Refer to Fig. 7 and install filter drier as follows:
! WARNING 1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
FIRE HAZARD 3. Braze filter drier to 5 in. (127 mm) long liquid tube from
Failure to following this warning could result in personal step 1.
injury, death and/or property damage. 4. Connect and braze liquid refrigerant tube to the filter drier.
Refrigerant and oil mixture could ignite and burn as it escapes IMPORTANT: Installation of the filter drier in liquid line is
and contacts brazing torch. Make sure the refrigerant charge is required.
properly removed from both the high and low sides of the
system before brazing any component or lines.
Clean line set tube ends with emery cloth or steel brush. Remove
any grit or debris.
Insert line set tube ends into service valve tube stubs.
Apply heat absorbing paste or heat sink product between service
valve and joint. Wrap service valves with a heat sinking material
such as a wet cloth. A05227
Braze joints using a Sil--Fos or Phos--copper alloy. Fig. 7 – Liquid Line Filter Drier
! CAUTION NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch circuit disconnect of adequate size per NEC
UNIT DAMAGE HAZARD to handle unit starting current. Locate disconnect within sight from
Failure to follow this caution may result in equipment and readily accessible from unit, per Section 440–14 of NEC.
damage or improper operation. Route Ground and Power Wires
Never use the system compressor as a vacuum pump. Remove access panel to gain access to unit wiring. Extend wires
Refrigerant tubes and indoor coil should be evacuated using the from disconnect through power wiring hole provided and into unit
recommended deep vacuum method of 500 microns. The alternate control box.
triple evacuation method may be used (see triple evacuation Connect Ground and Power Wires
procedure in service manual). Always break a vacuum with dry
nitrogen.
Deep Vacuum Method
! WARNING
The deep vacuum method requires a vacuum pump capable of ELECTRICAL SHOCK HAZARD
pulling a vacuum of 500 microns and a vacuum gage capable of Failure to follow this warning could result in personal injury or
accurately measuring this vacuum depth. The deep vacuum method death.
is the most positive way of assuring a system is free of air and The unit cabinet must have an uninterrupted or unbroken
liquid water. A tight dry system will hold a vacuum of 1000 ground to minimize personal injury if an electrical fault should
microns after approximately 7 minutes. (See Fig. 8.) occur. The ground may consist of electrical wire or metal
5000 conduit when installed in accordance with existing electrical
4500 codes.
4000
LEAK IN Connect ground wire to ground connection in control box for
3500 SYSTEM safety. Connect power wiring to contactor as shown in Fig. 9.
MICRONS
3000
2500 DISCONNECT
PER N.E.C. AND/OR
2000 LOCAL CODES
VACUUM TIGHT
1500 TOO WET CONTACTOR
1000
TIGHT
500 DRY SYSTEM FIELD POWER
WIRING
A94025
Final Tubing Check
Fig. 9 – Line Connections
IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, makings sure wire ties on feeder tubes are
secure and tight.
Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of
improper voltage. See unit rating plate for recommended circuit
protection device.
NOTE: Operation of unit on improper line voltage constitutes
abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage may fluctuate above or below
permissible limits.
A00010
Fig. 10 – 3–Phase Monitor Control
(Applies to 3–Phase Units Only)
24 VAC COM C C C
HEAT STAGE 2 W2 W2 *
W2
! CAUTION
COOL/HEAT E * ENVIRONMENTAL HAZARD
STAGE 1 Y Y
W3 * Failure to follow this caution may result in environmental
INDOOR FAN G
G damage.
RVS COOLING O O Federal regulations require that you do not vent refrigerant to
the atmosphere. Recover during system repair or final unit
EMERGENCY E
* IF AVAILABLE disposal.
HEAT
LEGEND
24-V FACTORY WIRING
! CAUTION
24-V FIELD WIRING
UNIT OPERATION AND SAFETY HAZARD
FIELD SPLICE CONNECTION Failure to follow this caution may result in personal injury,
equipment damage or improper operation.
ODT
OUTDOOR THERMOSTAT
OUTDOOR FAN
RELAY
HK32EA001
DEFROST THERMOSTAT
MUST BE CLOSED BEFORE
DEFROST TIMER BEGINS
O - REVERSING VALVE
SPEEDUP
THERMOSTAT INPUTS
A05332
Fig. 12 – Defrost Control
Table 4 – Defrost Control Speedup–Timing Sequence
MINIMUM MAXIMUM SPEEDUP
PARAMETER
(MINUTES) (MINUTES) (NOMINAL)
30–minute cycle 27 33 7 sec
50–minute cycle 45 55 12 sec
90–minute cycle 81 99 21 sec
10–minute cycle 9 11 2 sec
5 minutes 4.5 5.5 1 sec
CAP**1814AL* --- CAP**2414AL* --- CAP**3014AL* --- CAP**3614AL* --- CAP**4221AL* --- CAP**4817AL* +5 CAP**6021AL* ---
CAP**2414AL* --- CAP**2417AL* --- CAP**3017AL* --- CAP**3617AL* --- CAP**4224AL* --- CAP**4821AL* +3 CAP**6024AL* ---
CAP**2417AL* --- CAP**2517AL* +5 CAP**3614AL* --- CAP**3621AL* --- CAP**4321AL* +5 CAP**4824AL* +3 CAP**6124AL* ---
CNPV*1814AL* --- CAP**3014AL* --- CAP**3617AL* --- CAP**4221AL* +3 CAP**4817AL* +5 CAP**6021AL* +5 CNPV*6024AL* ---
CNPV*2414AL* +3 CAP**3017AL* --- CAP**3621AL* --- CAP**4224AL* +3 CAP**4821AL* +3 CAP**6024AL* +5 CSPH*6012AL* ---
CNPV*2417AL* +3 CNPV*2414AL* --- CAP**3717AL* +5 CNPV*3617AL* --- CAP**4824AL* +3 CAP**6124AL* +5 FB4CNP060L ---
CSPH*2412AL* +3 CNPV*2417AL* --- CAP**3721AL* +5 CNPV*3621AL* --- CNPV*4217AL* --- CNPV*4821AL* --- FV4CNB006L ---
FB4CNF018L --- CNPV*3014AL* --- CNPV*3014AL* --- CNPV*4217AL* +3 CNPV*4221AL* --- CNPV*4824AL* --- FX4DN(B,F)061L ---
FB4CNF024L --- CNPV*3017AL* --- CNPV*3017AL* --- CNPV*4221AL* +3 CNPV*4821AL* --- CNPV*6024AL* +3
FB4CNP018L --- CSPH*2412AL* --- CNPV*3617AL* --- CSPH*3612AL* +3 CNPV*4824AL* --- CSPH*4812AL* ---
FB4CNP024L --- CSPH*3012AL* --- CNPV*3621AL* --- CSPH*4212AL* +5 CSPH*4212AL* --- CSPH*6012AL* +3
FFMANP018 --- FB4CNF030L --- CSPH*3012AL* --- FB4CNF036L --- CSPH*4812AL* --- FB4CNF048L ---
FFMANP019 --- FB4CNP030L --- CSPH*3612AL* +3 FB4CNF042L +5 FB4CNF042L --- FB4CNP048L ---
FFMANP024 --- FFMANP024 --- FB4CNF030L --- FB4CNP036L --- FB4CNF048L --- FB4CNP060L +3
FFMANP025 --- FFMANP025 --- FB4CNF036L --- FB4CNP042L +5 FB4CNP042L --- FV4CN(B,F)005L +3
FPMAN*018 --- FFMANP030 --- FB4CNP030L --- FFMANP036 --- FB4CNP048L --- FV4CNB006L +5
FPMAN*024 --- FFMANP031 --- FB4CNP036L --- FFMANP037 --- FV4CN(B,F)003L --- FX4DN(B,F)049L +3
FPMBN*018 --- FPMAN*024 --- FFMANP030 --- FPMAN*036 --- FV4CN(B,F)005L +3 FX4DN(B,F)061L +5
FV4CNF002L ---
FX4DN(B,F)031L ---
FX4DN(B,F)037L +5
FX4DN(B,F)043L +5
S Puron refrigerant operates at 50–70 percent higher pressures than R–22. Be sure that servicing equipment and replacement
components are designed to operate with Puron
S Puron refrigerant cylinders are rose colored.
S Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
S Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when
charging into suction line with compressor operating
S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low–side retard.
S Use hoses with 700 psig service pressure rating.
S Leak detectors should be designed to detect HFC refrigerant.
S Puron, as with other HFCs, is only compatible with POE oils.
S Vacuum pumps will not remove moisture from oil.
S Do not use liquid–line filter driers with rated working pressures less than 600 psig.
S Do not leave Puron suction line filter driers in line longer than 72 hours.
S Do not install a suction–line filter drier in liquid line.
S POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
S POE oils may cause damage to certain plastics and roofing materials.
S Wrap all filter driers and service valves with wet cloth when brazing.
S A factory approved liquid–line filter drier is required on every unit.
S Do NOT use an R–22 TXV or properly sized Puron piston metering device..
S If indoor unit is equipped with an R–22 TXV or piston metering device sized for R--22 application, it must be changed to a hard
shutoff Puron TXV.
S Never open system to atmosphere while it is under a vacuum.
S When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter
driers. Evacuate to 500 microns prior to recharging.
S Do not vent Puron into the atmosphere.
S Do not use capillary tube coils.
S Observe all warnings, cautions, and bold text.