Masibus' Model 1008S/1008S-XP is a high-performance flow indicator-totalizer designed for precise measurement and totalization of flow rates, featuring a 5-digit flow rate display and an 8-digit total display. The 1008S is panel-mounted while the 1008S-XP is wall-mounted with explosion-proof capabilities, offering various input options and programmable features. It includes optional relays, digital inputs, and communication interfaces for integration with PLC/DCS/SCADA systems.

Uploaded by

vipesh kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
17 views

1008S_1008S-XP_R6F_1119_Flow-Indicator-Totalizer

Masibus' Model 1008S/1008S-XP is a high-performance flow indicator-totalizer designed for precise measurement and totalization of flow rates, featuring a 5-digit flow rate display and an 8-digit total display. The 1008S is panel-mounted while the 1008S-XP is wall-mounted with explosion-proof capabilities, offering various input options and programmable features. It includes optional relays, digital inputs, and communication interfaces for integration with PLC/DCS/SCADA systems.

Uploaded by

vipesh kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

1008S

1008S-XP
Flow Indicator-Totalizer

1008S 1008S-XP

Features
Masibus' Model 1008S/ 1008S-XP has features and performance you
Input selectable from current, voltage & frequency
will find only in high end flow computers, like high accuracy, high Available in two options
resolution, PT compensation and fast sampling to measure and totalize 1008S: Panel mount
with precision even fast changing flow rates. The unit has a 5-digit flow 1008S-XP: Wall mount, Dual Compartment, Ex-proof
rate display and an 8-digit batch total/ integrated total display with (IP65, Gas Group, IIA/IIB) with touch sense keys
rollover counts. All Totalized data and configured parameters are Square root extractor
stored in non-volatile memory and retained during power off and 5 Digit Flow rate & 8 digit Batch/ Integrated Total with
rollover count
power disruptions. Model 1008S is available in Panel mount option, Programmable K factor for Freq Input
whereas 1008S-XP is available in Ex-proof, Wall mount Dual Programmable low/zero cutoff facility
Compartment enclosure having touch sensitive keys for operation. 8-digit totalizer with password protected resetting
Programmable time base Day/Hr/Min/Sec
Flow Totalizer has optional four relays, 2 for flow rate and 2 for batch Programmable zero flow rate
total, the flow rate relays can be setup for Hi/Lo Alarm and the batch Pulse output
total relays for Pre and Final batch total. 1008S also has optional four Mass flow measurement with additional Pressure and
Temperature I/P
digital inputs to operate the totalizing function remotely. RS485 and
Gas/ liquid flow measurement
flow rate Re-transmission option allows easy interface with Superheated steam flow measurement
PLC/DCS/SCADA systems. A selectable square root extractor Saturated steam flow measurement
function enables compatibility with DP transmitters without built-in Options:
square root extractor. DI inputs for remote operation
Mass Flow Measurement
Flow Totalizer is field selectable for mA/V DC or frequency flow rate 4 Configurable relays for Flow/Batch
input signal, for 4-20mA 2 wire transmitter it has a 24V DC Retransmission output (Isolated)
transmitter supply as a standard, the input signal can be scaled from RS485 serial communication (Isolated)
0 to 30000 engineering value and the time base is selectable from Applications
Sec/Min/Hour/Day, for frequency input the K factor is user Monitoring and controlling continuous and batch flow
programmable, the unit also has an option to accept 2 more dc processes like:
signals for pressure and temperature compensation for liquid/gas Mixing operation in chemical/Pharma
flow, saturated steam or super heated steam measurement. Fuel consumption
Custody Transfer
Energy management
Batch Filling
Receiver instrument for Turbine, PD & Magnetic pickup
flow elements
www.masibus.com [email protected]
TECHNICAL SPECIFICATIONS
Input Output
Input 1 Relay (Optional)
Current 0/4-20mA 2 Relays Programmable for Flow Rate or Batch Alarm
Voltage 0/1-5V DC 2 Relays Programmable for Flow Rate Alarm
4 Relays
ADC Resolution 16 bits & 2 Relays Programmable for Batch Alarm
Sampling Speed 10 Samples/Sec Contact Type C-NO-NC Single change over
Input impedance Rating 250V AC/30V DC@2A
Current Input 250 Ω Retransmission (Optional)
Voltage Input > 300K Ω Type Isolated 4-20 mA DC @ 500 Ω
NMRR > 50dB Accuracy 0.25% of FS +1 count
CMRR > 100dB Serial Communication (RS485) (Optional)
Time Base Accuracy 100 ppm Baud Rate (bps) 9600/19200, Programmable
Measurement Accuracy 0.025% FS [for Current / Voltage] Protocol Modbus-RTU
Polarity Protection Provided Data Pattern N, 8,1
Temp-co 100 ppm Transmitter Power Supply 24V DC ±5% @ 50 mA
0-10KHz Power Supply
Frequency Input*
*Max. Pulse level<=24V, Min. pulse level > 5.0V
85-265V AC @ 50Hz (Standard)
Input 2 (Optional) Power Supply
24V DC ±10% (Optional)
Current 0/4-20mA
Power Consumption <10 VA
Voltage 0/1-5V DC
Measurement Accuracy 0.025% FS [for Current / Voltage] Isolation (Withstanding voltage)
Pressure/Temperature Compensation Between primary terminals* and secondary terminals**: At least 1500 V AC for 1 minute
Purpose Between primary terminals* and grounding terminal: At least 1500 V AC for 1 minute
for Standard Vol. flow/Mass Flow
Between grounding terminal and secondary terminals**: At least 1500 V AC for 1 minute
Input 3 (Optional) Between secondary terminals**: At least 500 V AC for 1 minute
RTD 100.0 – 235.0 °C * Primary terminals indicate power terminals and relay output terminals.
Resolution 0.1 °C ** Secondary terminals indicate analog/digital I/O and Communication O/P.
Accuracy 0.25% Insulation resistance: 50MΩ or more @ 500V DC between power terminals and
Digital Input (Optional) grounding terminal.
No. of Channels 4 Nos. Physical
Input Type Dry Contact/Open Collector
1008S 1008S-XP
Exc. Voltage/Current 12V DC@10mA
Wall mount using 4 Nos
Stop batch, Integration total zero, Mounting type Panel
Input Function of M8 size bolts
Start batch, Batch total zero
Dimension (mm) 96(H)x96(W)x125(D) 340(H) X 186(W) X 110(D)
Display & Keys Panel Cut-out (mm) 92(H) X 92(W) NA
Process Value 0.56” 5 Digit, 7 Segment RED LED Weight 500 grams 6 Kgs
Total/Int. Value 0.4” 8 Digit, 7 Segment RED LED Ingress Protection IP20 IP65
Rate Indication Range Range programmable 0-30000 Zone 1 & 2,
Totalizing Range 0-99999999 Area Classification Safe
Gas Group: IIA & IIB
Decimal Point Adjustable Explosion Proof, Aluminum
Resolution 1 Count Enclosure Type ABS Plastic Alloy LM-6, Ex-d,
Keys Stop, Start, Escape & Enter Dual Compartment
Special Features Electrical Connection/ Cable
2.5mm² / Screwed 3/4” ET – 5 NOS
Batch/Integrated Total Reset Front Key (Password Protected) entry size
Time Base for Totalizer Programmable (Day / Hr /Min / Sec) Environmental
K Factor Function Yes (Frequency I/P) Operating Temperature 0 to 55 °C
Square Root Extraction For Differential Pressure Transmitter Storage Temperature 0 to 80 °C
NVRAM/EEPROM. Data will not be lost Operating Humidity 30 - 95%RH (non condensing)
Memory/Data storage
when power off, can hold for 10 years Warm-up time >10 min
With Two extra compensating I/P for
Mass Flow Measurement
Pressure and Temperature

ORDERING CODE
Retransmission Type of Flow No of extra Glands
Model Input Types Digital Input Power Supply Communication Relay
O/P Measurement (only for 1008S-XP)#
1008S X X XX X X X XX X
1008S-XP C 4-20mA N None A1 85-265V AC N None N None N None N None (with single I/P) N None
PT Compensated
D 0-20mA Y Yes A3 24V DC 2 RS485 2 2 Relays Y Yes PT 1 1 extra gland
liquid/ gas flow
E 1-5V DC 4 4 Relays SS Saturated Steam Flow 2 2 extra glands
F 0-5V DC SH Super heated Steam 3 3 extra glands
G 0-10V DC
N 0-10 KHz
S Special*

Standard Accessory
2 nos mounting clamps alongwith 1008S model
X – Specify from table 2 nos 3/4" ET Cable glands and 3 blind plugs alongwith 1008S-XP model

* Consult Factory

Head Office: Masibus Automation And Instrumentation Pvt. Ltd.


All specifications are subject to change without notice
B-30, GIDC Electronics Estate, Sector-25, Gandhinagar-382044, Gujarat, India.
due to continuous improvements.
Tel: +91 79 23287275-77, Fax: +91 79 23287281.
Doc. Ref.1008S/1008S-XP/R6/1119
E-mail: [email protected], Web: www.masibus.com