FInal Relay Settings

The document outlines protective device settings for various relays and low voltage circuit breakers, detailing their designated buses, relay IDs, and specific settings for overcurrent and overload functions. Each entry includes parameters such as pickup values, time delays, and trip elements, categorized by manufacturer and model. The settings adhere to IEC standards and are critical for ensuring the safety and reliability of electrical systems.

Uploaded by

kerim.gurbuz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4 views

FInal Relay Settings

The document outlines protective device settings for various relays and low voltage circuit breakers, detailing their designated buses, relay IDs, and specific settings for overcurrent and overload functions. Each entry includes parameters such as pickup values, time delays, and trip elements, categorized by manufacturer and model. The settings adhere to IEC standards and are critical for ensuring the safety and reliability of electrical systems.

Uploaded by

kerim.gurbuz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Protective Device Settings - Relay

PT / OCR (51, 51V), OLR (49, Acc.) OCR (50), OLR (50, Jam)
Manufacturer
Level
DESIGNATION DESCRIPTION Designated Bus Relay ID & Settings Group Device Function Trip Element Curve
/Stage Prim. Prim. Block TOC by
Model CT Ratio Pickup Time Delay Pickup Time Delay
Amps Amps IOC

BUS SECTION ALSTOM IEC - Standard


Relay28 400:1 Overcurrent Phase OC1 1.000 400.000 0.550
GTG - 1 P122 Inverse
32-MSW-05 CABLE

BUS SECTION ALSTOM IEC - Standard


Relay28 400:1 Overcurrent Ground OC1 0.100 40.000 0.100
GTG - 1 P122 Inverse

GE Multilin
Bus53 Relay48 300:5 Overload Phase Overload Curve 1.010 314.929 5.000
MM300

GE Multilin
Bus53 Relay48 300:5 Overload Jam 1.010 314.93 0,5 s
MM300
21-MSW-01 MOTOR

GE Multilin
Bus53 Relay48 300:5 Overload Ground/Neutral 0.500 0.50 0,1 s
MM300

GE Multilin Acceleration
Bus53 Relay48 300:5 Overload Acceleration 1.000 311.811 0.500
MM300 Protection

BUS SECTION ALSTOM IEC - Standard


Relay34 400:1 Overcurrent Phase OC1 1.000 400.000 0.550
GTG - 2 P122 Inverse
32-MSW-09 CABLE

BUS SECTION ALSTOM IEC - Standard


Relay34 400:1 Overcurrent Ground OC1 0.100 40.000 0.100
GTG - 2 P122 Inverse

GE Multilin
Bus58 Relay49 300:5 Overload Phase Overload Curve 1.010 314.929 5.000
MM300

GE Multilin
Bus58 Relay49 300:5 Overload Jam 1.010 314.93 0,5 s
MM300
21-MSW-02 MOTOR

GE Multilin
Bus58 Relay49 300:5 Overload Ground/Neutral 0.500 0.50 0,1 s
MM300

GE Multilin Acceleration
Bus58 Relay49 300:5 Overload Acceleration 1.000 311.811 0.500
MM300 Protection

BUS SECTION ALSTOM IEC - Standard


Relay38 400:1 Overcurrent Phase OC1 1.000 400.000 0.550
GTG - 3 P122 Inverse
32-MSW-15 CABLE

BUS SECTION ALSTOM IEC - Standard


Relay38 400:1 Overcurrent Ground OC1 0.100 40.000 0.100
GTG - 3 P122 Inverse
GE Multilin
Bus66 Relay50 300:5 Overload Phase Overload Curve 1.010 314.929 5.000
MM300

GE Multilin
Bus66 Relay50 300:5 Overload Jam 1.010 314.93 0,5 s
MM300
21-MSW-03 MOTOR

GE Multilin
Bus66 Relay50 300:5 Overload Ground/Neutral 0.500 0.50 0,1 s
MM300

GE Multilin Acceleration
Bus66 Relay50 300:5 Overload Acceleration 1.000 311.811 0.500
MM300 Protection

BUS SECTION ALSTOM IEC - Standard


Relay29 150:1 Overcurrent Phase OC1 1.000 150.000 0.080 19.000 2850.00 0,05 s
GTG - 1 P122 Inverse
32-MSW-06

BUS SECTION ALSTOM IEC - Standard


Relay29 150:1 Overcurrent Ground OC1 0.100 15.000 0.100
GTG - 1 P122 Inverse

BUS SECTION ALSTOM IEC - Standard


Relay35 150:1 Overcurrent Phase OC1 1.000 150.000 0.080 19.000 2850.00 0,05 s
GTG - 2 P122 Inverse
32-MSW-11

BUS SECTION ALSTOM IEC - Standard


Relay35 150:1 Overcurrent Ground OC1 0.100 15.000 0.100
GTG - 2 P122 Inverse

BUS SECTION ALSTOM IEC - Standard


Relay39 150:1 Overcurrent Phase OC1 1.000 150.000 0.080 19.000 2850.00 0,05 s
GTG - 3 P122 Inverse
32-MSW-17

BUS SECTION ALSTOM IEC - Standard


Relay39 150:1 Overcurrent Ground OC1 0.100 15.000 0.100
GTG - 3 P123 Inverse

BUS SECTION ALSTOM IEC - Standard


Relay25 150:1 Overcurrent Phase OC1 1.000 150.000 0.080 18.000 2700.00 0,05 s
GTG - 1 P122 Inverse
32-MSW-02

BUS SECTION ALSTOM IEC - Standard


Relay25 150:1 Overcurrent Ground OC1 0.100 15.000 0.100
GTG - 1 P122 Inverse

BUS SECTION ALSTOM IEC - Standard


Relay20 150:1 Overcurrent Phase OC1 1.000 150.000 0.080 18.000 2700.00 0,05 s
GTG - 2 P122 Inverse
32-MSW-08

BUS SECTION ALSTOM IEC - Standard


Relay20 150:1 Overcurrent Ground OC1 0.100 15.000 0.100
GTG - 2 P122 Inverse

BUS SECTION ALSTOM IEC - Standard


Relay37 150:1 Overcurrent Phase OC1 1.000 150.000 0.080 18.000 2700.00 0,05 s
GTG - 3 P122 Inverse
32-MSW-14

BUS SECTION ALSTOM IEC - Standard


Relay37 150:1 Overcurrent Ground OC1 0.100 15.000 0.100
GTG - 3 P122 Inverse
ALSTOM IEC - Standard
Bus2 Relay42 500:1 Overcurrent Phase OC1 0.660 330.000 0.800 9.000 4500.00 0,5 s Enabled
P122 Inverse

ALSTOM IEC - Standard


Bus2 Relay42 500:1 Overcurrent Ground OC1 0.060 30.000 0.100
P122 Inverse

31-MVUAT-01 ALSTOM IEC - Standard


Bus3 Relay21 400:1 Overcurrent Phase OC1 0.100 40.000 0.025 40.000 16000.00 0,01 s
P122 Inverse

ALSTOM IEC - Standard


Bus3 Relay21 400:1 Overcurrent Ground OC1 0.002 0.800 0.025 1.000 400.00 0,01 s
P122 Inverse

ALSTOM
Bus50 Relay8 1200:1 Group 1 Overcurrent Phase OC1 0.250 300.00 0,25 s
P642

ALSTOM IEC - Standard


Bus50 Relay26 1200:1 Overcurrent Phase OC1 1.000 1200.000 1.500
P122 Inverse
32-MSW-03

ALSTOM IEC - Standard


Bus50 Relay26 1200:1 Overcurrent Ground OC1 0.100 120.000 0.150
P122 Inverse

ALSTOM IEC - Standard


Bus16 Relay43 500:1 Overcurrent Phase OC1 0.660 330.000 0.800 9.000 4500.00 0,5 s Enabled
P122 Inverse

ALSTOM IEC - Standard


Bus16 Relay43 500:1 Overcurrent Ground OC1 0.060 30.000 0.100
P122 Inverse

31-MVUAT-02 ALSTOM IEC - Standard


Bus17 Relay22 400:1 Overcurrent Phase OC1 0.100 40.000 0.025 40.000 16000.00 0,01 s
P122 Inverse

ALSTOM IEC - Standard


Bus17 Relay22 400:1 Overcurrent Ground OC1 0.002 0.800 0.025 1.000 400.00 0,01 s
P122 Inverse

ALSTOM
Bus23 Relay12 1200:1 Group 1 Overcurrent Phase OC1 0.250 300.00 0,25 s
P642

ALSTOM IEC - Standard


Bus23 Relay30 1200:1 Overcurrent Phase OC1 1.000 1200.000 1.500
P122 Inverse
32-MSW-10

ALSTOM IEC - Standard


Bus23 Relay30 1200:1 Overcurrent Ground OC1 0.100 120.000 0.150
P122 Inverse
ALSTOM IEC - Standard
Bus25 Relay44 500:1 Overcurrent Phase OC1 0.660 330.000 0.800 9.000 4500.00 0,5 s Enabled
P122 Inverse

ALSTOM IEC - Standard


Bus25 Relay44 500:1 Overcurrent Ground OC1 0.060 30.000 0.100
P122 Inverse

31-MVUAT-03 ALSTOM IEC - Standard


Bus28 Relay23 400:1 Overcurrent Phase OC1 0.100 40.000 0.025 40.000 16000.00 0,01 s
P122 Inverse

ALSTOM IEC - Standard


Bus28 Relay23 400:1 Overcurrent Ground OC1 0.002 0.800 0.025 1.000 400.00 0,01 s
P122 Inverse

ALSTOM
Bus37 Relay18 1200:1 Group 1 Overcurrent Phase OC1 0.250 300.00 0,25 s
P642

ALSTOM IEC - Standard


Bus37 Relay19 1200:1 Overcurrent Phase OC1 1.000 1200.000 1.500
P122 Inverse
32-MSW-16

ALSTOM IEC - Standard


Bus37 Relay19 1200:1 Overcurrent Ground OC1 0.100 120.000 0.150
P122 Inverse

BUS SECTION ALSTOM IEC - Standard


Relay36 250:1 Overcurrent Phase OC1 1.000 250.000 0.025 10.000 2500.00 0,05 s
GTG - 2 P122 Inverse

32-MSW-12 BUS SECTION ALSTOM IEC - Standard


Relay36 250:1 Overcurrent Ground OC1 0.100 25.000 0.100
GTG - 2 P122 Inverse

BUS SECTION ALSTOM Thermal


Relay36 250:1 Overload Phase 0.100 25.000 1.000
GTG - 2 P122 Overload Curve

BUS SECTION ALSTOM IEC - Very


Relay27 200:1 Overcurrent Phase OC1 1.200 240.000 1.025
GTG - 1 P122 Inverse
32-MSW-04

BUS SECTION ALSTOM IEC - Standard


Relay27 200:1 Overcurrent Ground OC1 0.100 20.000 0.100
GTG - 1 P122 Inverse

BUS SECTION ALSTOM IEC - Very


Relay40 200:1 Overcurrent Phase OC1 1.200 240.000 1.025
GTG - 3 P122 Inverse
32-MSW-18

BUS SECTION ALSTOM IEC - Standard


Relay40 200:1 Overcurrent Ground OC1 0.100 20.000 0.100
GTG - 3 P122 Inverse
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device
Long Time Short-Time / Ground Inst. / Maintenance

Breaker Pickup Delay Pickup Delay Pickup


Manufacturer
Trip Device Sensor/ Rating Trip Trip Trip
Designated Bus LVCB ID & Function Setting Curve Band Setting Curve Band Ixt Setting
Model Frame Plug (Amps) (Amps) (Amps)
Model

RMS 520
Bus86 33-LSW-01 Cutler-Hammer 1600 Phase 1 1600 4 3 4800 0.5 OUT 4 6400
Series

RMS 520
Bus85 21-LSW-01 Cutler-Hammer 630 Phase 1 630 4 6 3780 0.5 OUT 10 6300
Series

RMS 520
Bus61 21-LSW-02 Cutler-Hammer 630 Phase 1 630 4 6 3780 0.5 OUT 10 6300
Series

RMS 520
Bus69 21-LSW-03 Cutler-Hammer 630 Phase 1 630 4 6 3780 0.5 OUT 10 6300
Series

RMS 520
Bus94 33-LSW-03 Cutler-Hammer 1600 Phase 1 1600 4 3 4800 0.5 OUT 4 6400
Series

RMS 520
LV SECTION -1 33-LSW-10 Cutler-Hammer 1000 Phase 1 1000 4 6 6000 0.5 OUT 10 10000
Series

RMS 520
LV SECTION - 2 33-LSW-12 Cutler-Hammer 1000 Phase 1 1000 4 6 6000 0.5 OUT 10 10000
Series

RMS 520
BOP LV BOARD 53-LSW-01 Cutler-Hammer 1000 Phase 1 1000 4 6 6000 0.5 OUT 10 10000
Series

RMS 520
BOP LV BOARD 2 53-LSW-03 Cutler-Hammer 1000 Phase 1 1000 4 6 6000 0.5 OUT 10 10000
Series

RMS 520
BOP LV BOARD 2 53-LSW-02 Cutler-Hammer 1000 Phase 0.4 400 4 6 2400 0.5 OUT 10 10000
Series

RMS 520
BOP LV BOARD 53-LSW-13 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 53-LSW-12 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 53-LSW-11 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 53-LSW-10 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 53-LSW-09 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 53-LSW-08 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 53-LSW-07 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

Page 1 of 4
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device
Long Time Short-Time / Ground Inst. / Maintenance

Breaker Pickup Delay Pickup Delay Pickup


Manufacturer
Trip Device Sensor/ Rating Trip Trip Trip
Designated Bus LVCB ID & Function Setting Curve Band Setting Curve Band Ixt Setting
Model Frame Plug (Amps) (Amps) (Amps)
Model

RMS 520
BOP LV BOARD 53-LSW-06 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 53-LSW-05 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 53-LSW-04 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-51 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-52 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-50 Cutler-Hammer 250 Phase 1 250 4 6 1500 0.5 OUT 10 2500
Series

RMS 520
BOP LV BOARD 2 53-LSW-49 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-48 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-47 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-46 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-45 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-44 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-43 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-42 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-41 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-40 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-39 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

Page 2 of 4
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device
Long Time Short-Time / Ground Inst. / Maintenance

Breaker Pickup Delay Pickup Delay Pickup


Manufacturer
Trip Device Sensor/ Rating Trip Trip Trip
Designated Bus LVCB ID & Function Setting Curve Band Setting Curve Band Ixt Setting
Model Frame Plug (Amps) (Amps) (Amps)
Model

RMS 520
BOP LV BOARD 2 53-LSW-38 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-37 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-36 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
BOP LV BOARD 2 53-LSW-35 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
Bus7 GTG1-SW-01 Cutler-Hammer 1250 Phase 0.4 500 2 2 1000 0.1 OUT 3 3750
Series

RMS 520
Bus7 GTG1-SW-01 Cutler-Hammer 1250 Ground 0.25 312.5 0.1 OUT
Series

RMS 520 Maintenance


Bus7 GTG1-SW-01 Cutler-Hammer 1250 5 3125
Series Phase

RMS 520
Bus7 GTG1-SW-02 Cutler-Hammer 1250 Phase 0.5 625 2 2 1250 0.2 OUT 2 2500
Series

RMS 520
Bus7 GTG1-SW-02 Cutler-Hammer 1250 Ground 0.25 312.5 0.1 OUT
Series

RMS 520 Maintenance


Bus7 GTG1-SW-02 Cutler-Hammer 1250 1 12500
Series Phase

RMS 520
Bus21 GTG2-SW-01 Cutler-Hammer 1250 Phase 0.4 500 2 2 1000 0.1 OUT 2 2500
Series

RMS 520
Bus21 GTG2-SW-01 Cutler-Hammer 1250 Ground 0.25 312.5 0.1 OUT
Series

RMS 520 Maintenance


Bus21 GTG2-SW-01 Cutler-Hammer 1250 5 3125
Series Phase

RMS 520
Bus21 GTG2-SW-02 Cutler-Hammer 1250 Phase 1 1250 20 10 12500 0.4 OUT M1(14) 17500
Series

RMS 520
Bus21 GTG2-SW-02 Cutler-Hammer 1250 Ground 0.25 312.5 0.1 OUT
Series

RMS 520 Maintenance


Bus21 GTG2-SW-02 Cutler-Hammer 1250 1 12500
Series Phase

RMS 520
Bus36 GTG3-SW-01 Cutler-Hammer 1250 Phase 1 1250 4 2 2500 0.1 OUT 3 3750
Series

Page 3 of 4
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device
Long Time Short-Time / Ground Inst. / Maintenance

Breaker Pickup Delay Pickup Delay Pickup


Manufacturer
Trip Device Sensor/ Rating Trip Trip Trip
Designated Bus LVCB ID & Function Setting Curve Band Setting Curve Band Ixt Setting
Model Frame Plug (Amps) (Amps) (Amps)
Model

RMS 520
Bus36 GTG3-SW-01 Cutler-Hammer 1250 Ground 0.25 312.5 0.1 OUT
Series

RMS 520 Maintenance


Bus36 GTG3-SW-01 Cutler-Hammer 1250 5 3125
Series Phase

RMS 520
Bus36 GTG3-SW-02 Cutler-Hammer 1250 Phase 1 1250 2 2 2500 0.1 OUT 3 3750
Series

RMS 520
Bus36 GTG3-SW-02 Cutler-Hammer 1250 Ground 0.25 312.5 0.1 OUT
Series

RMS 520 Maintenance


Bus36 GTG3-SW-02 Cutler-Hammer 1250 3 7500
Series Phase

RMS 520
LV SECTION - 2 CB11 Cutler-Hammer 100 Phase 1 100 4 6 600 0.5 OUT 10 1000
Series

RMS 520
LV SECTION - 2 CB12 Cutler-Hammer 300 Phase 1 300 4 6 1800 0.5 OUT 10 3000
Series

* Library settings have been modified.